B&B Electronics EKI-1222 User Manual

Page 1
User Manual

ADAM-4572, EKI-1221,EKI-1222, EKI-1224, EKI-1221D, EKI-1222D

1/2/4-port Modbus Gateway
Page 2
Copyright
Acknowledgements
Intel and Pentium are trademarks of Intel Corporation. Microsoft Windows and MS-DOS are registered trademarks of Microsoft Corp. All other product names or trademarks are properties of their respective owners.
Product Warranty (2 years)
Advantech warrants to you, the original purchaser, that each of its products will be free from defects in materials and workmanship for two years from the date of pur­chase.
This warranty does not apply to any products which have been repaired or altered by persons other than repair personnel authorized by Advantech, or which have been subject to misuse, abuse, accident or improper installation. Advantech assumes no liability under the terms of this warranty as a consequence of such events.
Because of Advantech’s high quality-control standards and rigorous testing, most of our customers never need to use our repair service. If an Advantech product is defec­tive, it will be repaired or replaced at no charge during the warranty period. For out­of-warranty repairs, you will be billed according to the cost of replacement materials, service time and freight. Please consult your dealer for more details.
If you think you have a defective product, follow these steps:
1. Collect all the information about the problem encountered. (For example, CPU
speed, Advantech products used, other hardware and software used, etc.) Note anything abnormal and list any onscreen messages you get when the problem occurs.
2. Call your dealer and describe the problem. Please have your manual, product,
and any helpful information readily available.
3. If your product is diagnosed as defective, obtain an RMA (return merchandize
authorization) number from your dealer. This allows us to process your return more quickly.
4. Carefully pack the defective product, a fully-completed Repair and Replacement
Order Card and a photocopy proof of purchase date (such as your sales receipt) in a shippable container. A product returned without proof of the purchase date is not eligible for warranty service.
5. Write the RMA number visibly on the outside of the package and ship it prepaid
to your dealer.
Part No. 2003122102 Edition 3 Printed in Taiwan July 2010
ADAM-4572 & EKI-122X Series User Manual ii
Page 3
Declaration of Conformity
CE
This product has passed the CE test for environmental specifications when shielded cables are used for external wiring. We recommend the use of shielded cables. This kind of cable is available from Advantech. Please contact your local supplier for ordering information.
CE
This product has passed the CE test for environmental specifications. Test conditions for passing included the equipment being operated within an industrial enclosure. In order to protect the product from being damaged by ESD (Electrostatic Discharge) and EMI leakage, we strongly recommend the use of CE-compliant industrial enclo­sure products.
FCC Class A
Note: This equipment has been tested and found to comply with the limit s for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Opera­tion of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Technical Support and Assistance
1. Visit the Advantech web site at www .ad vantech.com/support where you can find
the latest information about the product.
2. Contact your distributor, sales representative, or Advantech's customer service
center for technical support if you need additional assistance. Please have the following information ready before you call:
Product name and serial numberDescription of your peripheral attachmentsDescription of your software (operating system, version, applicatio n software,
etc.)
A complete description of the problemThe exact wording of any error messages
iii ADAM-4572 & EKI-122X Series User Manual
Page 4
Safety Instructions
1. Read these safety instructions carefully.
2. Keep this User Manual for later reference.
3. Disconnect this equipment from any AC outlet before cleaning. Use a damp
cloth. Do not use liquid or spray detergents for cleaning.
4. For plug-in equipment, the power outlet socket must be located near the equip-
ment and must be easily accessible.
5. Keep this equipment away from humidity.
6. Put this equipment on a reliable surface during installation. Dropping it or letting
it fall may cause damage.
7. The openings on the enclosure are for air convection. Protect the equipment
from overheating. DO NOT COVER THE OPENINGS.
8. Make sure the voltage of the power source is correct before connecting the
equipment to the power outlet.
9. Position the power cord so that people cannot step on it. Do not place anything
over the power cord.
10. All cautions and warnings on the equipment should be noted.
11. If the equipment is not used for a long time, disconnect it from the power source
to avoid damage by transient overvoltage.
12. Never pour any liquid into an opening. This may cause fire or electrical shock.
13. Never open the equipment. For safety reasons, the equipment should be
opened only by qualified service personnel.
14. If one of the following situations arises, get the equipment checked by service
personnel:
The power cord or plug is damaged.Liquid has penetrated into the equipment.The equipment has been exposed to moisture.The equipment does not work well, or you cannot get it to work according to
the user's manual.
The equipment has been dropped and damaged.The equipment has obvious signs of breakage.
15. DO NOT LEAVE THIS EQUIPMENT IN AN ENVIRONMENT WHERE THE
STORAGE TEMPERATURE MAY GO BELOW -20° C (-4° F) OR ABOVE 60° C (140° F). THIS COULD DAMAGE THE EQUIPMENT. THE EQUIPMENT SHOULD BE IN A CONTROLLED ENVIRONMENT.
16. CAUTION: DANGER OF EXPLOSION IF BATTERY IS INCORRECTLY
REPLACED. REPLACE ONLY WITH THE SAME OR EQUIVALENT TYPE RECOMMENDED BY THE MANUFACTURER, DISCARD USED BATTERIES ACCORDING TO THE MANUFACTURER'S INSTRUCTIONS.
17. The sound pressure level at the operator's position according to IEC 704-1:1982
is no more than 70 dB (A).
DISCLAIMER: This set of instructions is given according to IEC 704-1. Advantech disclaims all responsibility for the accuracy of any statements contained herein.
ADAM-4572 & EKI-122X Series User Manual iv
Page 5

Contents

Chapter 1 Introduction..........................................1
1.1 Overview................................................................................................... 2
1.2 Features....................................................................................................2
1.3 Package Check List ..................................................................................3
Chapter 2 Getting Started.....................................5
2.1 Understanding Modbus Gateways............................................................6
2.1.1 Protocol Overview.........................................................................6
Figure 2.1 Modbus System Architecture 1................................... 7
Figure 2.2 Modbus System Architecture 2................................... 7
2.1.2 Modbus RTU....................................... ... ... ... ... .............................. 8
2.1.3 Modbus ASCII................................. .... ... ... ... ... .... .......................... 8
Table 2.1: Comparison of Modbus RTU and ASCII Modes.........8
2.1.4 Modbus TCP... ... ... .... ... .......................................... ... ....................8
2.2 Specifications............................................................................................9
2.2.1 EKI-1221/1222/1224..................................................................... 9
2.2.2 EKI-1221D/1222D.......................................................................10
2.2.3 ADAM-4572 ................................................................................11
2.3 Hardware.................................................................................................12
2.3.1 LED Indicators ............................................................................12
Table 2.2: EKI-1221/1222/1224, EKI-1221D/1222D LED Indica-
tors............................................................................12
Table 2.3: ADA M-4572 LED Indicat ors ..................................... 12
2.3.2 Dimensions (Units: mm)..............................................................13
Figure 2.3 Front View of EKI-1221 ............................................13
Figure 2.4 Side View of EKI-1221.............................................. 13
Figure 2.5 Back View of EKI-1221.............................................14
Figure 2.6 Top View of EKI-1221............................................... 14
Figure 2.7 Front View of EKI-1222 ............................................15
Figure 2.8 Side View of EKI-1222.............................................. 15
Figure 2.9 Back View of EKI-1222.............................................16
Figure 2.10Top View of EKI-1222...............................................16
Figure 2.11Front View of EKI-1224 ............................................17
Figure 2.12Side View of EKI-1224..............................................17
Figure 2.13Back View of EKI-1224.............................................18
Figure 2.14Top View of EKI-1224...............................................18
Figure 2.15Front View of EKI-1221D.......................................... 19
Figure 2.16Side View of EKI-1221D........................................... 19
Figure 2.17Back View of EKI-1221D..........................................20
Figure 2.18Top View of EKI-1221D............................................ 20
Figure 2.19Front View of EKI-1222D.......................................... 21
Figure 2.20Side View of EKI-1222D........................................... 21
Figure 2.21Back View of EKI-1222D..........................................22
Figure 2.22Top View of EKI-1222D............................................ 22
Figure 2.23Front View of ADAM-4572........................................ 23
Figure 2.24Back View of ADAM-4572........................................23
Figure 2.25Bottom View of ADAM-4572.....................................24
Figure 2.26Side View of ADAM-4572......................................... 24
2.4 Connecting Hardware .... ... .... ... ... .......................................... ... .... ... ... ... .. 25
2.4.1 Choosing the Location................................................................ 25
Figure 2.27Combine the Metal Mounting Kit .............................. 25
Figure 2.28ADAM-4572 Panel Mounting Bracket Dimensions... 26
Figure 2.29ADAM-4572 Panel Mounting....................................26
v ADAM-4572 & EKI-122X Series User Manual
Page 6
Figure 2.30DIN-rail Step 1.......................................................... 27
Figure 2.31DIN-rail Step 2.......................................................... 27
Figure 2.32DIN-rail Adapter .. .... ... ... ... ... .... ... ... ... .... ... ... ... ... .... ... .. 28
Figure 2.33DIN-rail Mounting ...... ... ... ... .... ...... ... .... ... ... ... ... .... ... .. 28
2.4.2 Connecting Power ...................................................................... 29
Figure 2.34Power Connector.......................................... ... .... ... .. 29
2.4.3 Connecting Serial Devices.......................................................... 29
Figure 2.35EKI-122X series Serial Port Pin Assignments.......... 29
2.4.4 Connecting to a Host or the Network.......................................... 30
2.4.5 ADAM-4572 Serial Port Wiring.............................. ... ... ... ... .... ... .. 30
Figure 2.36Wiring RS-232 Connection........ ... ... .... ... ... ... ....... ... .. 30
Figure 2.37Wiring RS-485 Connection........ ... ... .... ... ... ... ....... ... .. 31
Figure 2.38Wiring RS-422 Connection........ ... ... .... ... ... ... ....... ... .. 31
Chapter 3 Configuration ....................................33
3.1 Installing the Configuration Utility................................................... .... ... .. 34
3.2 Starting the Configuration Utility ............................................................. 37
3.3 Discovering Modbus Gateways ..... ... .... ... ... ... ... .... ... ... ... .... ... ... ... ... .... ... .. 38
3.3.1 Auto Searching........................................................................... 38
3.3.2 Clear Device List and Search Again........................................... 41
3.3.3 Manual Appending... .... ... ... ... .... ... ... ... ... .... ... ... ... .... ... ... ............... 41
3.4 Setting Ethernet Parameters................................................................... 42
3.5 Setting Serial Communication Parameters............................................. 43
3.5.1 Basic Configuration...................................... ... ... .... ..................... 44
3.5.2 Operation Configuration.............................................................. 46
3.6 Function Accessible Setting.................................................................... 49
3.7 Monitoring Modbus Status...................................................................... 50
3.8 Administrator Setting............................................. ... ... ... .... ... ... ... ... .... ... .. 50
3.8.1 Import/Export Serial Port Setting................................................ 51
3.8.2 Locate the Modbus Data Gateway ............................................. 51
3.8.3 Lock Device................................................................................ 52
3.8.4 Restore to Factory Default Settings ... ... .... ... ... ... .... ... ... ... ... .... ... .. 53
3.8.5 Update Firmware.................................. .... ... ... ... .... ... ... ... ... .... ... .. 54
ADAM-4572 & EKI-122X Series User Manual vi
Page 7
Chapter 1

1 Introduction

Page 8

1.1 Overview

Advantech’s ADAM-4572 and EKI-1221/1222/1224/1221D/1222D series of Modbus Gateways (the following manual will use EKI-122X series instead of complete model name) are a robust, feature-rich, and cost effective way to integrate of Ethernet and Serial Modbus devices. The ADAM-4572 and EKI-122X series provides one, two or four serial ports, one or two Ethernet ports, a wide range of power inputs, and a compact slim design, making them an ideal solution for connecting multiple Modbus/ RTU and Modbus/ASCII serial devices to Modbus TCP (Ethernet).
Originally developed for PLCs in industrial automation and manufacturing control applications, Modbus is one of the most popular open standard protocols in use today. The communication mode can be Modbus R TU/ASCII (Serial) or Mo dbus TCP (Ethernet). Many industrial devices use Modbus as their communication standard. However, the Ethernet-based Modbus protocol is different from the original serial­based protocols that a Modbus Gateway is needed to be a bridge for integration.
The two Ethernet ports allow the EKI-122X series to establish two separated Ethernet connections to two Ethernet domains or two Ethernet switches in the same domain. Through a dual Ethernet connection, the EKI-122X series greatly improves the device connectivity reliability, increase system stability, and simplify the redundant configuration.
The Modbus/RTU and Modbus/ASCII protocols define how a “master” device polls one or more “slave” devices and write real-time data over RS-232, RS-422, or RS­485 serial data communication. The ADAM-4572 and EKI-122X series provides a feature that can allow users to select master or slave operation for each serial port. The ADAM-4572 and EKI-122X series not only allows Ethernet master can control serial slaves, but also allow serial masters to control Ethernet or serial slaves. Furthermore, the EKI-122X series can allow both Ethernet and serial slaves to be controlled by both Ethernet and serial masters.
The ADAM-4572 and EKI-122X series supports various operating modes: RTU Master, RTU Slave, ASCII Master, and ASCII Slave.

1.2 Features

Provides dual 10/100 Mbps auto-sensing Ethernet ports (EKI-122X series only) Integration of Modbus TCP and Modbus RTU/ASCII networks Supports COM port's baud rate up to 921.6 kbps Supports up to 16 TCP connections and 32 requests simultaneously Supports 31 slaves (RS-485) per serial port Supports auto-bypass function (EKI-1221D/1222D only) Software selectable RS-232/422/485 communication Auto searching slave ID over configuration utility Mounts on DIN-rail, wall, or panel Class I, Division 2 certificate for EKI-122X series
ADAM-4572 & EKI-122X Series User Manual 2
Page 9

1.3 Package Check List

ADAM-4572
1 x ADAM-4572 Modbus Gateway 1 x Document and software CD 1 x DIN-rail kit 1 x 30 cm 3P to DB9 cable for RS-232 connection
EKI-1221/1222/1224
1 x EKI-1221 or EKI-1222 or EKI-1224 Modbus Gateway 1 x 6P power connector 1 x Document and software CD 1 x DIN-rail kit 2 x Wall/panel mount kit
EKI-1221D/1222D
1 x EKI-1221D or EKI-1222D Modbus Gateway 1 x 6P power connector 1 x Documents and software CD 1 x OPT1-DB9-AE (DB9 to terminal connector) 1 x DIN-rail kit 2 x Wall/panel mount kit
Chapter 1 Introduction
Note! Please check above items, if any one of them is missing or damaged,
contact your sales representative.
3 ADAM-4572 & EKI-122X Series User Manual
Page 10
ADAM-4572 & EKI-122X Series User Manual 4
Page 11
Chapter 2

2 Getting Started

Page 12

2.1 Understanding Modbus Gateways

Networks have become increasingly vital for industrial automation applications. Many control devices today do not have a network port and can only communicate with a dedicated local PC or control panel. Advantech’s revolutionary network-enabling technology is now allowing control devices with serial ports to connect to the Ethernet and share networks quickly and cost-effectively. The ADAM-4572 and EKI-122X series are network-based, Modbus gateways for integrating new and existing Modbus/RTU and Modbus/ASCII serial devices to newer TCP/IP networked-based devices. Manufacturers, system integrators, and end users can now take advantage of Modbus gateways to create networked applications for remote managing and accessing data for their control devices that wasn’t possible before.
2.1.1 Protocol Overview
Originally developed for PLCs in industrial automation and manufacturing control application, Modbus has become one of the most popular open standard protocols in use today. When it comes to planning data communication for open, multi-vendor industrial control systems, Modbus is the first choice of end-users and integrators. Although it’s not the most powerful protocol available, its rare simplicity allows not only rapid implementation, but also remains flexible enough to be applied in virtually all industrial situations. The communication mode of Modbus can be ASCII, RTU, or TCP/IP. Modbus gateways are used to support applications such as protocol conver­sion between serial (Modbus/ASCII or Modbus/RTU) and networked (Modbus/TCP) Modbus devices or it can be used to bridge Modbus serial devices over TCP/IP net­work.
The Modbus/RTU and Modbus/ASCII protocols define how a “master” device polls one or more “slave” devices to read and write real-time data over RS-232, RS-422, or RS-485 serial data communication. The simplicity of Modbus/RTU not only allows rapid implementation, but can also remain flexible enough to be applied in virtually all industrial situations.
During Modbus network communication, the protocol determines how each controller will know its device address, recognize a message addressed to it, determine the kind of action to be taken, and extract any data or other information contained in the message. If a reply is required, the controller will construct the reply message and send it back using Modbus protocol.
The way controllers communicate with each other is by using a master-slave tech­nique, in which only one device (the master) can initiate queries. The other devices (the slaves) respond by supplying the requested data to the master, or by taking the action requested in the query. Typical master devices include host processors and programming panels. Typical slaves include programmable controllers.
It is the master that can address individual slaves and initiate a broadcast message to all slaves. On the other hand, slaves return a response to queries that are addressed to them individually. Responses are not returned to broadcast queries from the master.
The Modbus protocol has a definite format for the master’s query , which incorporates the device (or broadcast) address, a function code defining the requested action, any
ADAM-4572 & EKI-122X Series User Manual 6
Page 13
data to be sent, and an error-checking field. The slave’s response message, which is also constructed using Modbus protocol, contains fields confirming the action taken, any data to be returned, and an error-checking field. If an error occurred in receipt of the message, or if the slave is unable to perform the requested action, the slave will construct an error message and send it as its response.
The basic system architecture is as below:
Chapter 2 Getting Started
Figure 2.1 Modbus System Architecture 1
Figure 2.2 Modbus System Architecture 2
7 ADAM-4572 & EKI-122X Series User Manual
Page 14
2.1.2 Modbus RTU
The Modbus/RTU protocol defines how a “master” device polls one or more “slave” devices to read and write data in real-time over RS-232, RS-422, or RS-485 serial data communication.
When using RTU mode, each 8-bit byte in a message contains two 4-bit hexadecimal characters. The main advantage of this mode is that its greater character density allows better data throughput than ASCII mode for the same baud rate. Neverthe­less, each message must be transmitted in continuous stream.
2.1.3 Modbus ASCII
When using ASCII mode, each 8-bit byte in a message is sent as two ACSII charac­ters. The primary advantage of this ASCII mode is that it allows time intervals of up to one second to occur between characters without causing an error.
Table 2.1: Comparison of Modbus RTU and ASCII Modes
Mode RTU ASCII
Coding System 8-bit binary.
Bits per Byte 1 start bit,
Error Check CRC LRC
Two hexadecimal character contained in each ASCII character of the message
8 data bits, 1 bit for even/odd parity; no bit for parity 1 stop bit if parity is used; 2 bits if no parity
Hexadecimal. One hexadecimal character contained in each ASCII character of the message
1 start bit , 7 data bits, 1 bit for even/odd parity; no bit for parity 1 stop bit if parity is used; 2 bits if no parity
2.1.4 Modbus TCP
As a new extension of Modbus/RTU, the Modbus/TCP protocol defines how Modbus/ RTU messages are encoded within and transported over TCP/IP-based networks. Modbus/TCP is just as simple to implement and flexible to apply as the original Mod­bus/RTU. The Modbus/TCP protocol is defined by its form of encapsulation for a Modbus request or response. That means the Modbus request or response data is encapsulated in TCP frame that has a six-byte header in Modbus/TCP protocol.
Modbus/TCP enables the use of Modbus messaging in an Intranet running the TCP/ IP protocols. Modbus/TCP is most commonly used for Ethernet attachment of PLC’s or I/O modules to other simple field buses or I/O networks.
ADAM-4572 & EKI-122X Series User Manual 8
Page 15

2.2 Specifications

2.2.1 EKI-1221/1222/1224
LAN
Ethernet 10/100 Mbps, RJ45 No. of Ports 2 Protection Built-in 1.5 KV magnetic isolation
Serial Interface
Interface RS-232/422/485 No. of Ports 1, 2 or 4 Connector Type D-Sub 9 male Parity None, Even, Odd, Space, Mark Data bits 7, 8 Stop bits 1, 2 Flow Control RTS/CTS, XON/XOFF Speed 50 bps to 921.6 kbps
Chapter 2 Getting Started
Signals
RS-232 TxD, RxD, RTS, CTS, DTR, DSR, DCD, RI, GND RS-422 Tx+, Tx-, Rx+, Rx-, GND RS-485 Data+, Data-, GND Protection 15 KV ESD for all signals
Software Features
Operation Mode Modbus RTU master/slave, Modbus ASCII master/slave Utility Serial Device Server Configuration Utility
Power Requirements
Power Input 12 to 48 VDC No. of Power Inputs 2 Power Connector Terminal block Power Consumption 300 mA (max.)
Environment
Operating Temperature 0 to 60 °C (32 to 140 °F) Storage Temperature -20 to 85 °C (-4 to 185 °F)
9 ADAM-4572 & EKI-122X Series User Manual
Page 16
2.2.2 EKI-1221D/1222D
LAN
Ethernet 10/100Mbps, RJ45 No. of Ports 2 Protection Built-in 1.5 KV magnetic isolation
Serial Interface
Interface RS-232/422/485 No. of Ports EKI-1221D: 1
EKI-1222D: 2 Connector Type D-Sub 9 male Parity None, Even, Odd, Space, Mark Data bits 7, 8 Stop bits 1, 2 Flow Control RTS/CTS, XON/XOFF Speed 50 bps to 921.6 kbps
Signals
RS-232 TxD, RxD, RTS, CTS, DTR, DSR, DCD, RI, GND RS-422 Tx+, Tx-, Rx+, Rx-, GND RS-485 Data+, Data-, GND Protection 15 KV ESD for all signals
Software Features Operation Mode Modbus RTU master/slave, Modbus ASCII master/slave Configuration Serial Device Server Configuration Utility
Power Requirements
Power Input 12 to 48 VDC Power Connector Terminal block Power Consumption 300 mA (max.)
Environment Operating Temperature 0 to 60 °C (32 to 140 °F) Storage Temperature -20 to 80 °C (-4 to 176 °F)
ADAM-4572 & EKI-122X Series User Manual 10
Page 17
2.2.3 ADAM-4572
LAN
Ethernet 10/100 Mbps, RJ45 Protection Built-in 1.5 KV magnetic isolation
Serial Interface
Interface RS-232/422/485 No. of Ports 1 Connector Type Terminal block Parity None, Even, Odd, Space, Mark Data bits 7, 8 Stop bits 1, 2 Flow Control RTS/CTS, XON/XOFF Speed 50 bps to 921.6 kbps
Signals
RS-232 TxD, RxD, GND RS-422 Tx+, Tx-, Rx+, Rx-, GND RS-485 Data+, Data-, GND Protection 15 KV ESD for all signals
Chapter 2 Getting Started
Software Features
Operation Mode Modbus RTU master/slave, Modbus ASCII master/slave Utility Serial Device Server Configuration Utility
Power Requirements
Power Input 10 to 30 VDC Power Connector Terminal block Power Consumption 150 mA (max.)
Environment
Operating Temperature 0 to 60 °C (32 to 140 °F) Storage Temperature -20 to 80 °C (-4 to 176 °F)
11 ADAM-4572 & EKI-122X Series User Manual
Page 18

2.3 Hardware

The following instructions will give the overview of ADAM-4572 and EKI-122X series hardware and its installation.
2.3.1 LED Indicators
There are LEDs display the two sets of power status, system status, dual networks status, and serial communication status on the front panel of ADAM-4572 and .EKI­122X series. Each of them has its own specific meaning as below table.
Table 2.2: EKI-1221/1222/1224, EKI-1221D/1222D LED Indicators
LED Name LED Color LED Description
P1
P2
Status
Ethernet
Serial
Green Power 1 is on. Off Power 1 is off, or power error condition exists. Green Power 2 is on. Off Power 2 is off, or power error condition exists.
Orange
Off System is not working.
Orange
Green Orange Serial port is transmitting data.
Green Serial port is receiving data. Off No data is transmitted or received through the serial port.
Blinking: System is ready. Steady on: The device server has been located by utility’s locating the device function.
Blinking: Ethernet port is transmitting or receiving data. Steady on: Ethernet has the good link for 10Mbps or 100Mbps operations.
On: 100Mbps Ethernet connection. Off: 10Mbps Ethernet connection.
Table 2.3: ADAM-4572 LED Indicators
LED Name LED Color Status LED Description
RED
Status/Power
GREEN
RED
Speed/Link
GREEN
RED
Serial
GREEN
ADAM-4572 & EKI-122X Series User Manual 12
ON Heartbeat (1 time/sec), system is ready OFF System is not working ON Power is on OFF Power is off ON 100 Mbps speed OFF 10 Mbps speed ON Valid network link OFF Invalid network link ON Data being transmitted OFF No data being transmitted ON Data being received OFF No data being received
Page 19
2.3.2 Dimensions (Units: mm)
EKI-1221:
Chapter 2 Getting Started
Figure 2.3 Front View of EKI-1221
Figure 2.4 Side View of EKI-1221
13 ADAM-4572 & EKI-122X Series User Manual
Page 20
Figure 2.5 Back View of EKI-1221
Figure 2.6 Top View of EKI-1221
ADAM-4572 & EKI-122X Series User Manual 14
Page 21
EKI-1222:
Chapter 2 Getting Started
Figure 2.7 Front View of EKI-1222
Figure 2.8 Side View of EKI-1222
15 ADAM-4572 & EKI-122X Series User Manual
Page 22
Figure 2.9 Back View of EKI-1222
Figure 2.10 Top View of EKI-1222
ADAM-4572 & EKI-122X Series User Manual 16
Page 23
EKI-1224:
Chapter 2 Getting Started
Figure 2.11 Front View of EKI-1224
Figure 2.12 Side View of EKI-1224
17 ADAM-4572 & EKI-122X Series User Manual
Page 24
Figure 2.13 Back View of EKI-1224
Figure 2.14 Top View of EKI-1224
ADAM-4572 & EKI-122X Series User Manual 18
Page 25
EKI-1221D:
Chapter 2 Getting Started
Figure 2.15 Front View of EKI-1221D
Figure 2.16 Side View of EKI-1221D
19 ADAM-4572 & EKI-122X Series User Manual
Page 26
Figure 2.17 Back View of EKI-1221D
Figure 2.18 Top View of EKI-1221D
ADAM-4572 & EKI-122X Series User Manual 20
Page 27
EKI-1222D:
Chapter 2 Getting Started
Figure 2.19 Front View of EKI-1222D
Figure 2.20 Side View of EKI-1222D
21 ADAM-4572 & EKI-122X Series User Manual
Page 28
Figure 2.21 Back View of EKI-1222D
Figure 2.22 Top View of EKI-1222D
ADAM-4572 & EKI-122X Series User Manual 22
Page 29
ADAM-4572
Chapter 2 Getting Started
Figure 2.23 Front View of ADAM-4572
Figure 2.24 Back View of ADAM-4572
23 ADAM-4572 & EKI-122X Series User Manual
Page 30
Figure 2.25 Bottom View of ADAM-4572
Figure 2.26 Side View of ADAM-4572
ADAM-4572 & EKI-122X Series User Manual 24
Page 31

2.4 Connecting Hardware

In this instruction, it will explain how to find a proper location for your Modbus Gateways, and how to connect to the network, hock up the power cable, and connect to the ADAM-4572 and EKI-122X series.
2.4.1 Choosing the Location
Due to thier innovative design, ADAM-4572 and EKI-122X series can be:
Fixed to a panel mount Fixed to a DIN-rail
Panel/Wall Mounting
The ADAM-4572 and EKI-122X serie can be attached to a wall using the included metal brackets. Each bracket comes with four screws. You can install the Modbus Gateways firmly via the components, please see the figures below.
Chapter 2 Getting Started
Figure 2.27 Combine the Metal Mounting Kit
25 ADAM-4572 & EKI-122X Series User Manual
Page 32
Figure 2.28 ADAM-4572 Panel Mounting Bracket Dimensions
Figure 2.29 ADAM-4572 Panel Mounting
ADAM-4572 & EKI-122X Series User Manual 26
Page 33
DIN-rail Mounting
The ADAM-4572, EKI-122X series can be mounted on a standard DIN-rail. The DIN­rail kit is screwed on the Modbus data gateway when out of factory. If the DIN-rail kit is not screwed on the ADAM-4572, EKI-122X series, please screw the DIN-rail kit on the Modbus data gateway first.
First, hang the Modbus Gateways to the DIN-rail with angle of inclination. See below figure.
Chapter 2 Getting Started
Figure 2.30 DIN-rail Step 1
Then, let the Modbus Gateways down straight to slide over the rail smoothly.
Figure 2.31 DIN-rail Step 2
27 ADAM-4572 & EKI-122X Series User Manual
Page 34
Figure 2.32 DIN-rail Adapter
Figure 2.33 DIN-rail Mounting
ADAM-4572 & EKI-122X Series User Manual 28
Page 35
2.4.2 Connecting Power
The EKI-122X series supports dual +12 to 48 VDC power inputs and a power-fail relay output. Following figure is the power terminal block pin assignments. Please refer it to connect to the proper power requirements and polarity.
Chapter 2 Getting Started
Figure 2.34 Power Connector
You can connect an alarm indicator, buzzer or other signaling equipment through the power-fail relay output. The relay opens if power input V1 or V2 fails. (“Open” means if you connect relay output with an LED, the light will be shut off)
2.4.3 Connecting Serial Devices
The EKI-122X series provides one, two or four standard serial ports DB9 (male) connectors. RS-232/422/485 pin assignments are as below.
Figure 2.35 EKI-122X series Serial Port Pin Assignments
Pin123456789
RS-232 DCD RX TX DTR GND DSR RTS CTS RI RS-422 TX- - - TX+ GND - RX+ - RX­RS-485Data---Data+GND----
29 ADAM-4572 & EKI-122X Series User Manual
Page 36
2.4.4 Connecting to a Host or the Network
The EKI-122X series provides two RJ45 connectors with dual independent Ethernet networks, and supports 10/100 Mbps transmission speed. The ADAM-4572 and EKI­122X Series will auto detect current transmission speed on the network and configure itself accordingly. For normal operation, the ADAM-4572 and EKI-122X Series can be connected to other hubs or switches through a twisted-pair straight through the Ethernet cable. For configuration or troubleshooting purposes, user may need to connect the ADAM-4572 and EKI-122X Series directly to the host PC. In this operation mode, user can use a crossover Ethernet cable to connect the ADAM-4572 and EKI-122X Series to the host PC’s Ethernet connector.
For advanced model, EKI-1221D and EKI-1222D, provide two Ethernet ports with one IP address. One port can be used to connect to the network, and the other port can be used to connect to another Ethernet device (or another EKI-1221D/1222D, like Daisy-Chain structure).
2.4.5 ADAM-4572 Serial Port Wiring
We recommend that shielded-twisted-pair cables that comply with the EIA RS-485 standard be used with the ADAM network to reduce interference. Only one set of twisted-pair cables is required to transmit both Data and R TS signals. W e advise that the following standard colors (as indicated on the modules) be used for the communi­cation lines:
Data+ (Y) -> Yellow Data- (G) -> Green
Wiring for RS-232 Connection
Figure 2.36 Wiring RS-232 Connection
ADAM-4572 & EKI-122X Series User Manual 30
Page 37
Wiring for RS-485 Connection
Figure 2.37 Wiring RS-485 Connection
Chapter 2 Getting Started
Wiring for RS-422 Connection
Figure 2.38 Wiring RS-422 Connection
31 ADAM-4572 & EKI-122X Series User Manual
Page 38
ADAM-4572 & EKI-122X Series User Manual 32
Page 39
Chapter 3

3 Configuration

Page 40

3.1 Installing the Configuration Utility

The following section will show you how to install Advantech Serial Device Server Configuration Utility, a tool to set up and monitor the Modbus Gateways.
Note Be sure the Microsoft .NET Framework on your host PC is
greater than version 2.0 .
1. Insert the Advantech IEDG Series Driver Utility CD-ROM into the CD-ROM drive (e.g. E:\) on the host PC.
2. Use Windows explorer or the Windows Run command to execute the setup program, the path for the setup program on the CD-ROM should be:
E:\Utility&Driver\SerialDeviceServerConfigurationUtility\Serial_Device_ Server_Configuration_Utility_[Version]_Release_[date].exe
3. If there is an existed COM port mapping utility on the host PC, you have to remove it and reboot, then go on installing.
4. Once the InstallShield Wizard starts running, click “Next” when the welcome window opens to proceed with the installation.
ADAM-4572 & EKI-122X Series User Manual 34
Page 41
5. Carefully read the Software License Agreement, and press "I Agree" to continue.
Chapter 3 Configuration
6. The InstallShield will specify a default installation path, C:\Program Files\Advantech eAutomation\Serial Device Server Configuration Utility.
35 ADAM-4572 & EKI-122X Series User Manual
Page 42
7. After few minutes, a message will indicate that Configuration Utility is suc­cessfully installed, click “Finish” to exit the InstallShield.
ADAM-4572 & EKI-122X Series User Manual 36
Page 43

3.2 Starting the Configuration Utility

Advantech provides an easy-to-use configuration utility to configure your Modbus Gateways through an Ethernet connection. For secure administration, it can also restrict the access rights for configuration to only one host PC to enhance network security. With this secure function enabled, other PCs will not have permission for configuration. After the installation program on the Advantech IEDG Series Driver Utility CD-ROM is finished, the serial device servers will be ready for use and config­ure.
You may open the Serial Device Server Configuration Utility from the Windows Start Menu by clicking Start Æ All Programs Æ Advantech eAutomation Æ Serial Device Server Configuration Utility. The Serial Device Server Configuration Utility will appear as below figure.
There are four major areas in the new Serial Device Server Configuration Utility.
1. Serial Device Servers List Area: All devices will be searched and listed in this area. You can arrange different favorite group and virtual COM ports.
2. Serial Device Servers Information Area: Click on the devices or move cursor to the devices, the related information will be shown in this area.
3. Configuration Area: Click on the items on the Serial Device Sever List Area, the configuration page will be displayed in this area.
4. Quick Tool Bar: Useful management functions’ shortcuts.
Chapter 3 Configuration
37 ADAM-4572 & EKI-122X Series User Manual
Page 44

3.3 Discovering Modbus Gateways

3.3.1 Auto Searching
Advantech Serial Device Server Configuration Utility will automatically search all the EKI, ADAM and EDG series device servers on the network and show them on the Serial Device Server List Area of the utility. The Utility provides an auto-searching function to show your device(s) by simply executing the configuration utility program from the Start Menu.
From here all devices on the same network domain will be searched and display on the Serial Device Server List Area. You can click on the device name to show the fea­tures of the specific device. Click on the "+" before the model name (e.g. EKI-1224), and the utility will expand the tree structure to show the individual device name. Click on the “-“ before the model name (e.g. EKI-1224), and the utility will collapse the tree structure.
For example, EKI-1224 in this figure is shown “EKI-1224-A6A1D4” after expending the tree structure.
Note When you configure the device for the first time, the default device name is
“MAC ID”. In this case, the device name “EKI-1224-A6A1D4” means the device’s Mac ID is “00 D0 C9 A6 A1 D4”. You can change the device name in System Tab of Device Property.
ADAM-4572 & EKI-122X Series User Manual 38
Page 45
Select the device in this sub-tree. The first tab on the “Configuration Area” shows the summary of “Basic Information” included device type, firmware version, and device name, “Ethernet Information”, and “Serial Port Information”. In the serial port informa­tion frame, it displays the operation mode, status and connected host IP.
Chapter 3 Configuration
Click on the “+” before the device name, and the utility will expand the communication interfaces on this Modbus data gateway.
Click on each interface item, you will entry the configuration page to modify the set­ting. The configuration will be introduced on following sections.
39 ADAM-4572 & EKI-122X Series User Manual
Page 46
ADAM-4572 & EKI-122X Series User Manual 40
Page 47
3.3.2 Clear Device List and Search Again
You can click the “Clear Device List and Search Again” button on the Quick Tool Bar and the utility will clear all list device servers in the Serial Device Server List
Area and re-search again. Don’t use this function frequently, or the warning message will be pop-up.
You also can click the “Search Again” button on the Quick Tool Bar and the util­ity will search serial device servers on the local LAN.
3.3.3 Manual Appending
Using “Add IP address to Favorite” or “Search a Range of IP addresses” functions, you are allowed to add one device or group of devices to “Favorites”. These devices can locate on local network domain or other network domain.
Chapter 3 Configuration
41 ADAM-4572 & EKI-122X Series User Manual
Page 48

3.4 Setting Ethernet Parameters

Click on the “+” before the model name (e.g. EKI-1224), and the utility will exp and the tree structure to show the individual device name. And clink on the “+” before the device name, and utility will expand the communication interfaces on this Modbus data gateway. Select the Ethernet interface (Eth1 or Eth2, these are two individual Ethernet ports).
ADAM-4572 & EKI-122X Series User Manual 42
Page 49
MAC Address: The MAC address is for the local system to identify and locate each serial device
servers. This MAC address is already set before delivery from factory, hence no need for further configuration.
IP Address, Subnet Mask, Default Gateway: The IP address identifies your Modbus data gateway on the global network. Each
ADAM-4572, EKI-122X series has the same default IP address 10.0.0.1 and 10.0.0.2 for dual Ethernet ports. Obtain these specific IP addresses from your network admin­istrator and then configure each Advantech Modbus gateway with individual IP addresses, related Subnet Mask and Gateway Setting.
Note When you have finished the configuration of these settings for each cate-
gory, please press the “Apply” button in order to make these settings effec­tive on the Modbus data gateway. (Will reboot your Modbus gateway immediately)

3.5 Setting Serial Communication Parameters

Chapter 3 Configuration
Click on the "+" before the model name (e.g. EKI-1224), and the utility will exp and the tree structure to show the individual device name. And click on the “+” before the device name, and the utility will expand the interfaces on this device server. Select the serial interface. (Port1 to Port4 on e.g. EKI-1224)
43 ADAM-4572 & EKI-122X Series User Manual
Page 50
3.5.1 Basic Configuration
Description:
You can give a more detailed description on the function of the port for easier man­agement and maintenance. Descriptions have a limit of 128 characters.
Type: The EKI-122X series offers 3 kinds of serial interfaces, RS-232, RS-485 and RS-422.
You can use any one of these serial interfaces according to your requirements. You must also pay special attention to the wiring scheme of the EKI-122X series serial connection to make sure it conforms to the serial type you select.
Baud Rate: The EKI-122X series supports baud rate from 50 bps to 921.6 Kbps. While setting the
baud rate, please note that the value should conform to the current transmission speeds of connected devices.
ADAM-4572 & EKI-122X Series User Manual 44
Page 51
Parity, Data bits, Stop bits: The settings for these parameters depend on the protocol that is running on the con-
nected Modbus device (i.e. Modbus/ASCII or Modbus/RTU).
Parity None Even or Odd Data bits Stop bits
77 21
Modbus/ASCII
Parity None Even or Odd
Chapter 3 Configuration
Data bits Stop bits
88 21
Modbus/RTU
Flow Control:
The EKI-122X series provides four options: None, XOn/XOff, RTS/CTS, and DTR/ DSR.
45 ADAM-4572 & EKI-122X Series User Manual
Page 52
3.5.2 Operation Configuration
The Operation tab is for each serial port’s operation mode configuration. The opera­tion mode determines whether the devices that are connected to the serial port will operate as a master or a slave, and whether the Modbus RTU or Modbus ASCII pro­tocol will be used.
Modbus Slave Mode:
Type:
This option specifies whether the Modbus RTU or Modbus ASCII slave devices are connected to the serial port.
Modbus Timeouts (ms): This option specifies the time duration in milliseconds for the EKI-122X series to wait
for a response after it has issued a command while using Modbus/RTU or Modbus ASCII. After the timeout is expired and no response is received, the EKI-122X series will regard the command as failed. Note that the timeout for the host PC must be greater than the timeout setting here specified, otherwise an error will occur.
ASCII Character Timeouts (ms): This option specifies the time interval in milliseconds between characters within the
Modbus/ASCII message. If a greater interval occurs, the receiving device assumes an error has occurred.
ADAM-4572 & EKI-122X Series User Manual 46
Page 53
Slave ID Information (EKI-122X Series Only):: The EKI-122X series features an excellent function that the utility will scan slave ID
automatically. Click “Scan Slave ID” button, and the utility will start to issue the requests to the devices connected to this serial port and wait the reply about slave ID information. Alternative option, the utility allows to manual add or delete slave ID information.
Chapter 3 Configuration
Modbus/TCP Listen Port (ADAM-4572 Only):
The default port number of Modbus/TCP is 502. If you want to select the port number yourself, you can set it within the range of 512 to 50000. Note that a port number below 512 is already reserved in each situation for other specific uses and unavail­able for your selection.
47 ADAM-4572 & EKI-122X Series User Manual
Page 54
MAP Slave ID (EKI-122X Series Only)
The EKI-122X Series features another excellent function that you can map the real slave device ID to be the virtual slave device ID. Just key in the slave ID you want to map in the column "Map ID".
Modbus Master Mode:
Type:
This option specifies whether the Modbus RTU or Modbus ASCII master device is connected to the serial port.
Modbus Timeouts (ms): This option specifies the time duration in milliseconds for the EKI-122X series to wait
for a response after it has issued a command while using Modbus/RTU or Modbus ASCII. After the timeout is expired and no response is received, the EKI-122X series will regard the command as failed.
ADAM-4572 & EKI-122X Series User Manual 48
Page 55
ASCII Character Timeouts (ms): This option specifies the time interval in milliseconds between characters within the
Modbus/ASCII message. If a greater interval occurs, the receiving device assumes an error has occurred.
Slave IP Information: This option specifies the slave IP address and slave ID of the Modbus TCP slave
device or another EKI-122X series acts the Modbus slave device. Type the IP address in the column and its slave ID range, then click “Add” or “Delete” button to add or remove the slave IP list.

3.6 Function Accessible Setting

The EKI-122X series provides a security function that the utility allows to set up an accessible IP list for Modbus TCP devices which can access data from Modbus data gateway.
Chapter 3 Configuration
Allow any IP access: The default option, any Modbus TCP device can communicate with this Modb us data
gateway.
Specified IP which can access: Type the IP address in the column and click “Add” or “Delete” button to make the
accessible IP address list. The limit of this list is 32 IP addresses.
49 ADAM-4572 & EKI-122X Series User Manual
Page 56

3.7 Monitoring Modbus Status

Configuration utility provides an excellent function that allows monitoring the serial ports’ status. It will present each serial port’s operation mode and status. The IP address of the Modbus TCP device which is communicating with serial port will be list on the right window. Click “Refresh” button, the status will be refresh once. It will be auto refresh after click “Auto Refresh” and the time duration is depending on the set­ting (the default value is 1000ms).

3.8 Administrator Setting

The configuration utility provides several administrator settings for easy management and configuration. Right click the mouse on the device name in the sub-tree of Serial Device Sever List Area, and select these administrator settings.
ADAM-4572 & EKI-122X Series User Manual 50
Page 57
3.8.1 Import/Export Serial Port Setting
The utility allows importing or exporting the serial port setting including “Basic Set­ting” and “Operation Setting” via “.sps” file format.
Chapter 3 Configuration
3.8.2 Locate the Modbus Data Gateway
If there are many Modbus data gateways need your management, you may need to identify which unit is correct to configuration on utility. Click “Locate” to make that unit’s “Status” LED be steady on until you click “Stop Locate”.
51 ADAM-4572 & EKI-122X Series User Manual
Page 58
3.8.3 Lock Device
The configuration utility provides the “Lock Device” function to make it more confiden­tial. You need to set up a passwo rd while the first time clicking “Lock Device”. Be sure to click “Reset Device” to restart the Modbus gateway and store your setting pass­word into the memory.
Click “Unlock Device” to unlock the Modbus data gateway, and you need to fill in the password you have set up before. If you forgot the password, the only way to solve this problem is to restore the setting of the Modbus data gateway to the factory default which will be introduced next section.
ADAM-4572 & EKI-122X Series User Manual 52
Page 59
Chapter 3 Configuration
If you want to disable this function or change the password, click “Change Password” to change the password to default “None” (leave the new password and confirm new password columns blank) to disable this function or other password you want to change. Be sure to click “Reset Device” to restart the Modbus gateway and store the new password into the memory.
3.8.4 Restore to Factory Default Settings
The configuration utility provides this function to let you can restore the Modbus data gateway to factory default settings. The confirm message will be pop-up while click­ing “Restore to Factory Default Settings”. If you really want to restore the Modbus data gateway to factory default settings, please click “Yes” button to continue.
Then, please power off the Modbus data gateway within ten seconds, after recon­necting the power back, the all setting will be reset to the factory default. If the power remains more than ten seconds, the Modbus data gateway will not have any changes.
53 ADAM-4572 & EKI-122X Series User Manual
Page 60
3.8.5 Update Firmware
Advantech continually upgrades its firmware to keep up with the ever-expending world of computing. You can use the update firmware function in the utility to carry out the upgrade procedure. Please access Advantech’s website:
http://www.advantech.com to download the latest version of the firmware.
1. Right click on the device name and select “Update Firmware” function.
ADAM-4572 & EKI-122X Series User Manual 54
Page 61
2. Select the firmware file you want to update.
Chapter 3 Configuration
3. After downloading the firmware completely, click “OK” button, and the Modbus
data gateway will restart automatically.
55 ADAM-4572 & EKI-122X Series User Manual
Page 62
www.advantech.com
Please verify specifications before quoting. This guide is intended for reference purposes only. All product specifications are subject to change without notice. No part of this publication may be reproduced in any form or by any means, electronic, photocopying, recording or otherwise, without prior written permis­sion of the publisher. All brand and product names are trademarks or registered trademarks of their respective companies. © Advantech Co., Ltd. 2010