4-Slot Distributed DA&C System
ADAM-5000/485
for RS-485 Networks
8-Slot Distributed DA&C System
ADAM-5000E
for RS-485 Networks
Features
RS-485 Communication for easy installation and networking
4 or 8 slots for up to 128 points data monitoning card control in one
module
Extensive Software support, inclucles windows DLL drivers, OCX drivers,
OPC server and popular HMI/SCADA software drivers.
Seamlessly inteqrated with easy-to-use ADAMView data acquisition
software.
Introduction
The ADAM-5000/485 and ADAM-5000E systems use the EIA RS-485 communication protocol. This is the industry's most widely used, balanced, bidirectional transmission line
standard. RS-485 was specifically developed for industrial applications to transmit and receive data at high rates over long distances.
Specifications
Control System
CPU 16-bit 80188 microprocessor
I/O Slots ADAM-5000/485: 4
ADAM-5000E: 8
LED Indicators Power, CPU, communications
Watchdog Timer 1.6 sec. (System)
Communications
Command Format ASCII command/response protocol, Modbus/RTU
Communication RS-485: 1.2 km (4000 feet)
Distance
Data Format Asynchronous. 1 start bit, 8 data bits, 1 stop bit, no
parity
Network Protocols Programming link: RS-232 (3-wire: TX, RX, GND)
Communication: RS-485 (2-wire)
Reliability Check Communication error checking with checksum
Max. Nodes 256 (in RS-485 daisy-chain network)
Speeds (kbps) 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, and 115.2
Power
Power Consumption 1.0 W (ADAM-5000/485) (not including I/O modules)
4.0 W (ADAM-5000E) (not including I/O modules)
Power Input Unregulated 10 ~ 30 VDC
Software
Driver Support Windows DLL, OPC server, Wonderware® InTouch®,
Intellution®, iFIX®, Citect.
Protection
Communication Line 2500 VDC (ADAM-5000/485)
Isolation 3000 VDC (ADAM-5000E)
Communication Power 3000 V
Isolation
I/O Module Isolation 3000 V
Transient Protection RS-485 communication lines, power input
Power Reversal Yes
Protection
General
Certifications CE, FM
Connectors 1 x DB9-M/DB9-F/screw terminal for RS-485
Dimensions (WxHxD) 4-slot: 231 x 110 x 75 mm
Enclosure ABS+PC
Mounting DIN 35 rail, wall, rack (with mounting kit)
Environment
Humidity 5 ~ 95%, non-condensing
Operating Temperature -10 ~ 70° C (14 ~ 158° F)
Storing Temperature -25 ~ 85° C (-13 ~ 185° F)
DC
DC
(communication)
1 x DB9-F for RS-232 (configuration)
1 x Screw-terminal for power input
8-slot: 355 x 110 x 75 mm
Ordering Information
ADAM-5000/485 Distributed DA&C System Based on RS-485 (4 slot)
ADAM-5000E Distributed DA&C System Based on RS-485 (8 slot)
PCLS-OPC/ADM OPC Server for ADAM-4000/5000 Series (RS-485)
PCLS-OCX ActiveX Control for Data Acquisition and Control
PCLS-ADAMVIEW32 ADAMView Data Acquisition Software
Distributed DA&C Systems
All product specifications are subject to change without notice Last updated : 20-Jan-2006
ADAM-5000/485
ADAM-5000E
Wall mounting
hole
DB9-F with RS-232
for configuration
DB9-M for
RS-485
Screw-terminal for
RS-485
Diagnostic LEDs
Power terminal
Industrial connector
DB9-F for
RS-485
Node ID switch
Wall mounting
hole
Snap-lock
Plugged in I/O
module
Feature Details
Two-wire Communication
ADAM-5000/485 and ADAM-5000E systems use a single twisted pair of wires to transmit
and receive data. Special circuitry ensures reliable communications and suppresses
line noise on communication lines. This reduces overall network cost by simplifying
installation and minimizing the number of cables, connectors, communication repeaters
and filters required.
Transient Protection
High-speed transient suppressors protect the system from dangerous voltage surges or
power spikes from both the power supply input and the communication ports.
Network Expansion
By using the ADAM-4510 repeater to amplify or boost existing signals, your networks
can be stretched beyond 1.2 km.
Each ADAM-4510 repeater enables you to add up to 32 ADAM-5000 units to your network,
extending the network by another 4000 feet (1.2 km). Up to 256 ADAM-5000/485, ADAM5000E units can be connected to a single RS-485 network.
RS-232 to RS-485 Conversion
RS-232 serial ports are standard with most industrial computer systems. Though widely
accepted, RS-232 has limited transmission speed, range and networking capabilities.
The RS-485 standard overcomes these limitations by using differential voltage lines for
data and control signals.
ADAM-4520 is an isolated converter that lets you take advantage of RS-485 on an RS-232
system by converting RS-232 signals to RS-485 signals. Software written for half-duplex
RS-232 may also be used without modification. ADAM-4520 helps you build an industrial
grade, long distance communication system with standard PC hardware.
Intelligent RS-485 Data Flow Control
The RS-485 communication protocol will support half-duplex communication. Only two
wires are needed for transmitting and receiving data. Handshaking signals such as RTS
(Request to Send) normally control the direction of the data flow. A special I/O circuit in
the ADAM-4510 and ADAM-4520 modules sense the data flow direction and automatically
switches the transmission direction, making handshaking signals unnecessary. This makes
the RS-485 bus control completely transparent to the user.
Built-in RS-232 Communication
The RS-232 port is used to connect to a host PC for programming, control and monitoring
of applications. This aids troubleshooting, and allows a PC to be linked with all the I/O
points of the I/O modules.
ASCII-based Protocol and Modbus/RTU Protocol
ADAM-5000 commands are in ASCII format. ADAM applications can be written in any highlevel language that supports ASCII string functions, such as C, Pascal or BASIC. ASCII
support means you can use virtually any computer to manage your ADAM network.
Furthermore, the Modbus/RTU protocol is supported for connecting to 3rd party
controllers.
Online Download