Introduction
ADAM-4521 is an intelligent RS-485 to RS-232
converter specifically designed to connect RS-232
devices to an RS-485 network with other RS-485
devices. RS-232 is the most common transmission
standard. Although widely available on most computer
systems, measurement equipment, PLCs, and
industrial devices, its transmission speed, communication distance, and especially networking capability
are limited due to unbalanced transmission. The
ADAM-4521 addressable converter solves this
problem and lets you easily build up an RS-485
network with your RS-232 devices by assigning each
one an address for easier communication.
Built-in Intelligence
ADAM-4521 is equipped with a built-in microprocessor, which uses two UAR Ts and automatically
processes data before transmitting it to the RS-232
device. This makes ADAM-4521 able to allow different
baud rates between RS-232 devices and the RS-485
network. The microprocessor also verifies whether the
data is transmitted with the appropriate address,
which enables each device on the RS-485 network to
communicate with your PC over long distances.
RS-485 Network with Automatic Data
Flow Control
The RS-485 standard supports half-duplex
communication, meaning a single pair of wires is used
to both transmit and receive data. Handshaking
signals such as RTS (Request To Send) are normally
used to control the direction of the data flow, but a
special I/O circuit in the ADAM-4521 automatically
senses the direction of the data flow and switches the
transmission direction. No handshaking signals are
necessary.
Features
• Built-in microprocessor
• Transmission speeds of up to 115.2 kbps
• 1000 V
• Surge protection on RS-485 line
• RS-232 and RS-485 can be set to different baud
rates
• Automatic RS-485 data flow control
• Watchdog timer function included
• Power and data flow indicator for troubleshooting
• Reserved space for termination resistor
• Software configurable to either addressable or non
addressable mode
• Easily mounted on DIN rail, panel or piggyback
• All communication setups stored in EEPROM
isolation
DC
Specifications
• Transmission speed (bps): 300, 600, 1200, 2400,
4800, 9600, 19.2K, 38.4K, 57.6K, 115.2K (software
configurable)
Power requirement: Unregulated +10 to +30 V
•
with protection from power reversals
Case: ABS with captive mounting hardware
•
Accessories (included): Nylon DIN-rail mounting
•
adapter, SECC panel mounting bracket
RS-232 interface connector: Female DB-9
•
•
RS-422/RS-485 interface connector: plug-in
screw terminal (accepts AWG 1-#12 or 2-#14~#22
(0.5 to 2.5mm
Operating temperature: -10 to 70°C
•
Dimension: 2.36" x 4.41" (60mm x 120mm)
•
•
Power consumption: 1 W
2
) wires)
DC
ADAM and the ADAM logo are trademarks of Advantech.
Part No. 2003452100 3nd Edition Printed in Taiwan Aug. 2007
Installation
Power Supply
Initial
Inspection
We carefully inspect the ADAM-4521 both m echanic cally and electrically before w e ship it. It shou ld be
free of marks and scratches and in perfec t ord er on
receipt.
As you unpack the module, check it for si gns of
shipping damage (damaged box, scratc hes, de nts,
etc.). If it is damaged or fai ls to meet o ur spe cifica tions, notify our service departmen t o r you r local sale
representative immediately. Al so, ca ll the carr ier
immediately and retain the ship ping c arton a nd
packing material for inspectio n by t he carrie r. We will
then make arrangements to repair o r repl ace th e unit .
Before you begin installation, please make su re you
have the following items:
□
1 ADAM-4521 module
□
1 Bracket
□
1 Utility disk
Basic
Configuration
Before installing the ADAM-4521 in an existing
network, it should be configured. Though all modules
are initially configured at the factory, it is recommended that you check the baud rate settings.
Factory Default Settings:
Protocol: RS-485
Buad Rate: 9600 bps
Delimiter: {
Addressable
Mode:
Add cr: Yes
Address: 01
For the ease of use in industrial environments the
DAM modules are designed to accept industry
standard +24 V
guaranteed when using any power supply between
+10 and +30 V
peak to peak while the voltage in all cases must be
maintained between +10 and +30 V
supply specifications are referenced at module
connector.
The power cables should be selected according to the
number of modules connected and the length of the
power lines. When using a network with long cables,
we advise the use of thicker wire to limit the line
voltage drop. In addition to serious voltage drops,
long voltage lines can also cause interference with
communication wires.
We advise that the following standard colors (as
indicated on the modules) be used for power lines:
+Vs
(R) Red
GND (B) Black
Communication Wiring
We recommend that shielded-twisted- pair cable s that
comply with the EIA RS-485 standard be use d with
the ADAM network to reduce interfere nce. On ly one
set of twisted-pair cables is required to transmit both
Data and RTS signals. We advise that the f ollow ing
standard colors (as indicated on the modules ) be
used for the communication lines:
DATA +
DATA -
unregulated power. Operation is
DC
. Power ripples must be limited to 5V
DC
. All power
DC
(Y)
Yello w
Green
ADAM-4521 User's
Manual
Software Configuration
The ADAM-4521 comes with a utility disk containing
software with the following capabilities:
• Baud rate configuration
• Address configuration
• Addressable or non-addressable mode selection
• RS-485 or RS-422 mode
NOTE: Before configuring the ADAM-
The main screen consists of a menu bar at the top
and a status field which displays information about the
connected modules. When you first start the program,
it will automatically scan for any connected modules
and display their data. The status field lists module
characteristics and configuration parameters.
4521, make
host
RS-485
Figure 1 Main Screen
NOTE: An asterix sign “*” after the
sure
through an RS-422 or
line.
module's address indicates that
the module is in the INIT* state.
COMport
To configure your communication port, press
COMport icon. A menu will appear allowing you to
change which port you are using, the baud rate, and
the timeout.
Search
To scan the network for connected devices, click the
right button on the COM port to search the existed
com port. A window will appear and prompt you for
a value from 0 to 255. It will then scan all the
addresses from 0 to that number.
selection
it is connected to your
Setup
When you enter the setup screen, look at the
below frame of screen. You can see the RS-232
setting and the RS-485 setting. Please check the
setting of the interface. You can choose a proper
item to fit your owned setting. After you finish the
setting, please remember to press the Apply button
on the right side.
Figure 2 Setup Options
To change the basic settings, select the item the
1.
press <Enter>. Choose the parameter you wish to
change, and press <Enter>. A small popup windo
will appear with the configuration options for that
parameter. Choose the proper value, and press
<Enter>.
To change the RS-232/RS-485(RS-422) baud rate
2.
settings, select RS-232 Frame or RS-422/485
Frame and press <Enter>. Choose the parameter
you wish to change and press <Enter>. A window
will appear with the configuration options for that
parameter. Choose the proper value and press
<Enter>. In addition, you can assign the module
with proper ID via the Identification option.
The Mode (addressable or non-addressable) and
3.
Baud Rate options need special attention because
they can only be changed when ADAM-4521 is in
the INIT* state. To alter the Mode and Baud Rate,
do the following:
• Power all components on except ADAM-4521.
• Power ADAM-4521 on while shorting the INIT*
and GND terminals.
• Configure the Mode and/or Baud Rate.
• Power ADAM-4521 off.
• Remove the grounding of the INIT* terminal,
and power ADA M-4521 on.
• Check the settings.
INIT* state default settings:
Baud Rate:
Protocol:
Address:
9600
RS-485
00h
bps
ADAM-4521 User's