B&B RT12-2222-ZP-12, RT12-0044-ZP-12, RT12-4444-9T-W20 User Manual

series
Wireless Modbus I/O Modules
Models: RT12-0044-ZP-12 RT12-2222-ZP-12
RT12-4444-9T-W20
Documentation Number: RT-12 series-4006m (pn#7331)
This product designed and manufactured in Ottawa, Illinois USA
of domestic and imported parts by
707 Dayton Road -- P.O. Box 1040 -- Ottawa, IL 61350 USA
Phone (815) 433-5100 -- General Fax (815) 433-5105
Phone (815) 433-5100 -- General Fax (815) 433-5105
Website: www.bb-elec.com
Sales e-mail: orders@bb-elec.com
Technical Support e-mail: support@bb.elec.com
European Headquarters
Westlink Commercial Park -- Oranmore, Co. Galway, Ireland
Phone +353 91-792444 -- Fax +353 91-792445
Website: www.bb-europe.com
Sales e-mail: sales@bb-europe.com
Technical Support e-mail: support@bb-europe.com
B&B Electronics Mfg. Co. Inc. -- October 2006
-- Fax (815) 433-5109
-- Fax (815) 433-5104
B&B Electronics
DO NOT OPERATE ANY EQUIPMENT UNTIL THIS MANUAL
IS READ IN ITS ENTIRETY
2006 B&B Electronics. No part of this publication may be reproduced or transmitted in any form or by any
©
means, electronic or mechanical, including photography, recording, or any information storage and retrieval system without written consent. Information in this manual is subject to change without notice, and does not represent a commitme n t on the part of B&B Electroni c s .
B&B Electronics shall not be liable for incidental or consequential damages resulting from the furnishing, performance, or use of this manual.
All brand names used in this manual are the registered trademarks of their respective owners. The use of trademarks or other designations in this publication is f or reference purposes only and does not constitute an endorsement by the trademark holder.
This document contains information that is proprietary and confidential to B&B Electronics Mfg. Co. Inc. The methods described herein are for the exclusive use of B&B Electronics authorized per sonnel. Any unauthorized use or dissemination of the information contained in the document is strictly forbidden.
B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104 – www.bb-elec.com
B&B Electronics – Westlink Commercial Park – Oranmore, Galway, Ireland – Ph +353 91-792444 – Fax +353 91-792445 – www.bb-europe.com
Manual Documentation Number: RT-12 series-4006m
B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104 – www.bb-elec.com
B&B Electronics – Westlink Commercial Park – Oranmore, Galway, Ireland – Ph +353 91-792444 – Fax +353 91-792445 – www.bb-europe.com
Manual Documentation Number: RT-12 series-4006m
Wireless I/O Modules – from B&B Electronics
We value our customers. If you have any suggestion to improve o ur system please contact us at: support@bb-elec.com
RT12-4444-9T-W20
RT12-0044-ZP-S12
B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104 – www.bb-elec.com
B&B Electronics – Westlink Commercial Park – Oranmore, Galway, Ireland – Ph +353 91-792444 – Fax +353 91-792445 – www.bb-europe.com
Manual Documentation Number: RT-12 series-4006m
RT12-2222-ZP-S12
B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104 – www.bb-elec.com
B&B Electronics – Westlink Commercial Park – Oranmore, Galway, Ireland – Ph +353 91-792444 – Fax +353 91-792445 – www.bb-europe.com
Manual Documentation Number: RT-12 series-4006m
Table of Contents
Chapter 1 – Introduction............................................................................................1
THEORY OF OPERATION..............................................................................................1
MODBUS OVERVIEW...................................................................................................3
MODBUS FUNCTIONS SUPPORTED...............................................................................5
MODBUS REGISTER MAPS ..........................................................................................6
PEER TO PEER OVERVIEW...........................................................................................8
Chapter 2 – System Identification...........................................................................10
RT12-4444-9T-W20 FRONT PANEL IDENTIFICATION............................................10
RT12-4444-9T-W20 EXTERNAL BATTERY BACK-UP............................................13
RT12-2222-ZP-S12 FRONT PANEL IDENTIFICATION .............................................14
RT12-2222-ZP-S12 EXTERNAL BATTERY BACK-UP.............................................17
RT12-0044-ZP-S12 FRONT PANEL IDENTIFICATION .............................................18
RT12-0044-ZP-S12 EXTERNAL BATTERY BACK-UP.............................................21
HARDWARE SET-UP ..................................................................................................22
Typical Application: Peer-to-Peer......................................................................22
Typical Application: Modbus..............................................................................24
Typical Application: Well Monitor and Control (Peer-to-Peer)........................25
Typical Application: Well Monitor and Control (Mo dbus) ...............................26
Typical Application: 4-20 mA to Voltage Conversion........................................27
Configuration Cable Description........................................................................28
Chapter 3 – Configuration & Programming..........................................................29
CONFIGURATION/MONITORING SOFTWARE SYSTEM MAP........................................29
CONFIGURATION/MONITORING SOFTWARE MAIN PAGE...........................................30
CONTROLLER CONFIGURATION ................................................................................31
CURRENT CONTROLLER SETTINGS ...........................................................................32
CONNECTING / DISCONNECTING...............................................................................35
Master, Slave, Modbus, Peer-to-Peer.................................................................36
MODBUS CONFIGURATION........................................................................................37
DIGITAL INPUT TYPES ..............................................................................................38
RTU ALARMS...........................................................................................................39
ANALOG OUTPUTS RESTING VOLTAGE.....................................................................42
UPDATING/SENDING CONFIGURATION TO RTU........................................................45
THIRD PARTY COMMUNICATIONS PROTOCOL SUPPORT ...........................................46
STATUS BAR.............................................................................................................47
DIGITAL OUTPUTS ....................................................................................................48
Manual Documentation Number: RT-12 series-4006m Table of Contents i
B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104 – www.bb-elec.com
B&B Electronics – Westlink Commercial Park – Oranmore, Galway, Ireland – Ph +353 91-792444 – Fax +353 91-792445 – www.bb-europe.com
ii Table of Contents Manual Documentation Number: RT-12 series-4006m
B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104 – www.bb-elec.com
B&B Electronics – Westlink Commercial Park – Oranmore, Galway, Ireland – Ph +353 91-792444 – Fax +353 91-792445 – www.bb-europe.com
Chapter 1 – Introduction
Theory of Operation
This manual will refer to two types of SCADA communications to pologies, Peer to Peer (P2P) and Modbus.
The Peer to Peer topology and digital I/O is communicated between the Master and Slave.
The Modbus topology Modbus slaves. The Modbus master is responsible for requesting data from a respective Modbus slave.
The ‘RT’ serie s RTU’s have se veral unique functions and features and has been designed to replicate a wired sensor system. Transmission distances of up to 40 miles (64 km), (depending on the radio type and with modified antennas), user programmable sample/polling rates from 10 sam ples/sec to one sample every 20 seconds, programmable transmission retries, user programmable “full scale” engineering units allow users to enter full scale for a respective sensor, just to name a few.
The hardware architecture for RT series RTU’s are identical. Number of analog or digital I/O depends on the type of RTU. Each respective RTU has Bi-directional analog signal flow.
Other features include:
-Battery backup and in -circuit charging sys tem,
-MODBUS-RTU-Slave Enhancements,
-Programmable main voltage failure alarm,
-Low and high input voltage alarm,
-Communications failure alarm,
-Programmable resting voltages on communication failure,
-Programmable Output to Active High or Low during Communications Failure,
-Report by exception if a respective input changes by a +/- percentage,
-Configurable Inputs to Digital, Frequency or Accumulato r/Total.
An enhanced monitoring and configuration windows based program, allows you to configure each controller as well as monitor data.
consists of one “Master” and one “Slave” RTU. Analog
consists of one Modbus Master, and as many as 255
Your system may consist of two RT type wireless analo g bridges or RTU. In Peer to Peer mode, one controller must be programmed as the master and the other as the slave. It is critical that your system be programmed properly. Confi rm your system configuration before using your system.
All configuration parameters may be retrieved by connecting to the respective device’s serial configuration port. The wireless type and other parameters may be adjusted or viewed.
For Peer-to-Peer mode, check and confirm the following:
___ Your system consists of one MASTER and one SLAVE. Do not allow two masters or two slaves to communicate with each other. The devices may communicate but a systems failure will occur.
___ Make sure the system ID’s and RF-Network ID’s match.
WARNING: ID numbers for the Master and Slave must match and must not be repeat ed with any other Master/Slave pairs with the same RF-Network ID within the radio range of each respective wireless pair. Doing so will cause cross talk between master/slave pairs.
___ Make sure both Master and Slave have an antenna attached and installed correctly.
___ Make sure that the input power supply doe s NOT exceed 28 Vdc.
___ Make sure that the input power supply does N OT fall below 8.5 Vdc.
___ When power is applied to both the master and slave both units will communicate with each other.
For Modbus Slave RTU mode, check and confirm the following:
___ Your system does not consist of two RT RTU/devices with the same Slave ID numbers.
___ Each RTU/device has the same Radio ID and RF-Network ID numbers. Your Modbus Master device will need to be connected to our Packaged Modbus Modem (PMM) and will need to be configured with the same Radio ID and RF-Network ID numbers as the Modbus Slave devices. The PMM may be configured to allow for an RS-232 or RS-485 communications port.
Manual Documentation Number: RT-12 series-4006m 1
B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104 – www.bb-elec.com
B&B Electronics – Westlink Commercial Park – Oranmore, Galway, Ireland – Ph +353 91-792444 – Fax +353 91-792445 – www.bb-europe.com
2 Manual Documentation Number: RT-12 series-4006m
B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104 – www.bb-elec.com
B&B Electronics – Westlink Commercial Park – Oranmore, Galway, Ireland – Ph +353 91-792444 – Fax +353 91-792445 – www.bb-europe.com
Modbus Overview
This section is written for the person who will use the RT series RTU’s with Modicon Modbus protocols for communication in Modicon programmable controller applications. It describes the different types of Modbus registers supported. The RT Series RTU’s support Modbus, Slave RTU mode.
The Modbus protocol provides the internal standard that the Modicon controllers use for parsing messages. During communications on a Modbus network, the protocol determines how each controller will know its device address, recognize a message addressed to it, determine the kind of action to be taken, and extract any data or other information contained in the message.
All of the RT series RTU’s use a common Modbus communications protocol. All data is sent and received raw units.
Engineering Note: It may be necessary to force your PLC or Modbus master device to delay between Modbus packet transmissions. Some devices transmit without a break in data packets. Because of the nature of half-duplex radio you may need to configure or program your device with a 30-50 mS delay between packets and a 1.5-
2.0 second timeout.
Modbus Data: Some Modbus devices send data differently than others. This example shows Slave address 9, using fu n ction 3 and 16. It also shows he full data address of
40001. The RT series RTU’s do not send the full address. The Modbus protocol allows a system to assume the data address based on the function type. This is true of all Modbus functions for the RT series RTU’s.
09 03 9C 40 00 01 91 7E 09 10 9C 40 00 01 02 00 00 9E 54
09 = Slave 9 03 = Read Holding Registers 9C = Starting Address High -\ 40 = Starting Address Low -/ 40001 00 = Number of Points High-\ 01 = Number of Points Low -/ Read 1 Point 91 = Check Sum 7e = Check Sum
This is an example showing what data would look like for the RT series RTUs. 09 = Slave 9 03 = Read Holding Registers 00 = Starting Address High -\ 00 = Starting Address Low -/ 40001 00 = Number of Points High-\ 01 = Number of Points Low -/ Read 1 Point 91 = Check Sum 7e = Check Sum
Manual Documentation Number: RT-12 series-4006m 3
B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104 – www.bb-elec.com
B&B Electronics – Westlink Commercial Park – Oranmore, Galway, Ireland – Ph +353 91-792444 – Fax +353 91-792445 – www.bb-europe.com
4 Manual Documentation Number: RT-12 series-4006m
B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104 – www.bb-elec.com
B&B Electronics – Westlink Commercial Park – Oranmore, Galway, Ireland – Ph +353 91-792444 – Fax +353 91-792445 – www.bb-europe.com
Modbus Functions Supported
01 Read Coil Status: Reads the ON/OFF status of discrete outputs (0X references, coils) in the slave. Broadcast is not supported.
02 Read Input Status: Reads the ON/OFF status of discrete inputs (1X references) in the slave. Broadcast is not supported.
03 Read Holding Registers: Reads the binary contents of holding registers (4X references) in the slave. Broadcast is not supported.
04 Read Input Registers: Reads the binary contents of input registers (3X references) in the slave. Broadcast is not supported.
05 Force Single Coil: Forces a single coil (0X reference) to either ON or OFF.
06 Preset Single Register: Presets a value into a single holding registe r (4X
reference).
15 (0F Hex) Force Multiple Coils: Forces each coil (0X reference) in a sequence of coils to either ON or OFF.
16 (10 Hex) Preset Multiple Registers: Presets values into a sequence of holding registers (4X references).
Modbus Register Maps
RT12-4444 Modbus Map
Function 1
00001 Digital Input 1 00002 Digital Input 2 00003 Digital Input 3 00004 Digital Input 4
Function 2 10001 Digital Input 1 10002 Digital Input 2 10003 Digital Input 3 10004 Digital Input 4
Function 3 (Holding Reg) 40001 AO 1 40002 AO 2 40003 AO 3 40004 AO 4 40005 Freq Input 1 40006 Freq Input 2 40007 Totalize 1 Low 40008 Totalize 1 High 40009 Totalize 2 Low 40010 Totalize 2 High 40011 Time to Save Counter
Function 4 (Inputs) 30001 AI 1 12bit 30002 AI 2 12bit 30003 AI 3 12bit 30004 AI 4 12bit 30005 Vin 10bit
RT12-0044 Modbus Map
Function 1
00001 Digital Input 1 00002 Digital Input 2 00003 Digital Input 3 00004 Digital Input 4
Function 2 10001 Digital Input 1 10002 Digital Input 2 10003 Digital Input 3 10004 Digital Input 4
Function 3 (Holding Reg) 40001 FQ1 (Input-1) 40002 FQ2 (Input-2) 40003 Totalize 1 Low 40004 Totalize 1 High 40005 Totalize 2 Low 40006 Totalize 2 High 40007 Time To Save Counter
Function 4 (Inputs) 30001 Main Vin 10Bit 30002 Batt Vin 10Bit
Manual Documentation Number: RT-12 series-4006m 5
B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104 – www.bb-elec.com
B&B Electronics – Westlink Commercial Park – Oranmore, Galway, Ireland – Ph +353 91-792444 – Fax +353 91-792445 – www.bb-europe.com
6 Manual Documentation Number: RT-12 series-4006m
B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104 – www.bb-elec.com
B&B Electronics – Westlink Commercial Park – Oranmore, Galway, Ireland – Ph +353 91-792444 – Fax +353 91-792445 – www.bb-europe.com
RT12-2222 Modbus Map
Function 1
00001 Digital Input 1 00002 Digital Input 2
Function 2
10001 Digital Input 1 10002 Digital Input 2
Function 3 (Holding Reg) 40001 AO 1 40002 AO 2 40003 Freq Input 40004 Freq-2/Input 1 40005 Freq-3/Input 2 40006 Total Count 1_Low 40007 Total Count 1_High 40008 Total Count 2_Low 40009 Total Count 2_High 40010 Time To Next Save
Function 4
30001 AI 1 30002 AI 2 30003 Battery Input 30004 Main Input
Manual Documentation Number: RT-12 series-4006m 7
B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104 – www.bb-elec.com
B&B Electronics – Westlink Commercial Park – Oranmore, Galway, Ireland – Ph +353 91-792444 – Fax +353 91-792445 – www.bb-europe.com
Peer to Peer Overview
Peer to Peer mode can be described as a Wireless Signal Re plicator. The product line of RT series RTU’s can be configured as a Peer to Peer device. Two of the same type RTU’s are required to create a peer to peer system, one Master and one Slave.
The master or slave is determined by the way It is configured. The only difference between a master and slave is, the master is responsible for starting the communication process.
Both the master and slave must contain the same Radio ID and Subnet Value. Only the respective peer-to-peer systems may have the same Radio ID and RF-Network numbers. Failure to do so will cause erratic output voltages, AO’s or Digital Outputs, DO’s.
Each respective “RT” RTU device has the same number of Analog Inputs (AI’s),
Analog Outputs (AO’s), Digital Inputs (DI’s) and Digital Outputs (DO’s).
The number and type of I/O will depend on the type of RTU. Each RTU, including I/O, is described in this manual.
Peer to Peer mode will allow you to transmit a 0-5 Vdc analog input, or a Digital Input, from a Master device to a Slave device and vice-versa. A master’s analog or digital inputs, become a slave’s analog or digital outputs, and vice-versa. This allows for a full-duplex, looped system.
An application example would be a remote PLC with the RT12-2222’s analog and digital I/O connected to it, this RTU will be conf igured as a Master. The Slave device would monitor and control a water well system and would be connected to several sensors, pump status indicators, current sensor, etc.
The PLC will view the analog and digital signals from the slave device as if the PLC was connected directly to the several sensors, pump status indicators, current sensor, etc. See “Typical Application – Well Monitor and Control, Peer-to-Peer” in this manual.
8 Manual Documentation Number: RT-12 series-4006m
B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104 – www.bb-elec.com
B&B Electronics – Westlink C ommercial Park – Oranmore, Ga lway, Ireland – Ph +353 91-792444 – Fax +353 91-792445 – www.bb-europe.com
Note: This section assumes that your computer is equipped with a serial port and you have installed the RT series configuration software.
To Connect to a Controller:
1) Install the configuration software (setup.exe).
2) Apply Power to the controller. The heartbeat/sanity LED will begin to FLASH.
3) Connect the programming cable to your PC’s serial Port.
4) Launch the “Configuration” software.
5) You must select a communications port. Select “Comm”, “Serial” then the desired serial port.
6) The “Connect” box will be Red.
7) Press the “Connect” Button. The “Asserting” check box will become checked.
8) If the software successfully connects to the controller,
9) The “Connect” check box will become checked and the “Connect” butt on will turn Green.
10) The software will begin retrieving configuration data from the controller you are connected to. If all data boxes are not filled in refer back to step #6 in this section.
11) The software will indicate the type of device, Master or Slave.
12) For further programming features see, “Configuration/Programming Software Setup.”
Chapter 2 – System Identification
RT12-4444-9T-W20 – Front Panel Identification
All analog voltage inputs and outputs are 12-bit, 0- 5 Vdc. All digital inputs are from 0 to 12 Vdc. Digital inputs must fall to 0 Vdc as a LOW. Digital o utputs are Open Drain.
Connection Screw Terminal Description
PIN NAME DESCRIPTION
1 AO 1 Analog Output-1 2 AO 2 Analog Output-2 3 AO 3 Analog Output-3 4 AO 4 Analog Output-4 5 DO 1 Digital Output-1 6 DO 1 Digital Output-2 7 DO 1 Digital Output-3 8 DO 1 Digital Output-4 9 GND (-) Power Input. Ground. 10 PWR (+) Power Input. 10-28 Vdc. 11 AI 1 Analog Input-1 12 AI 2 Analog Input-2 13 AI 3 Analog Input-3 14 AI 4 Analog Input-4 15 DI 1 Digital Input-1 16 DI 2 Digital Input-2 17 DI 3 Digital Input-3 18 DI 4 Digital Input-4 19 BAT (+) Battery I/O. 10.5-28 Vdc. 20 GND (-) Battery.
Manual Documentation Number: RT-12 series-4006m 9
B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104 – www.bb-elec.com
B&B Electronics – Westlink Commercial Park – Oranmore, Galway, Ireland – Ph +353 91-792444 – Fax +353 91-792445 – www.bb-europe.com
10 Manual Documentation Number: RT-12 series-4006m
B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104 – www.bb-elec.com
B&B Electronics – Westlink C ommercial Park – Oranmore, Ga lway, Ireland – Ph +353 91-792444 – Fax +353 91-792445 – www.bb-europe.com
Power: 10.5~28 Vdc
Most DC power supplies rated from 10.5 to 28 Vdc @ 1000mA, will work with the RT12-4444-9T-W20. Do not use a power supply rated less than 1000mA. Doing so may cause the RT12-4444-9T-W20 to continuously reset. Make sure that the power supply voltage is maintained between the programmable HIGH and LOW supply voltage limits or an alarm may occur. If a rechargeable battery is used or if you ar e supplying voltage to a sensor using the same power used to power the RT12-4444-9T­W20, then the input volt age will need to be adjusted to th e proper voltage to mainta i n respective equipment. Never exceed 28 Vdc. Damage by overheating to the controller will occur causing the system to malfunction.
Data Activity LED Indicators
The RT12-4444-9T-W20 RTU is equipment with four LED indicators. The RED/GREEN pair labeled “SERIAL”, indicate data transmit and data received. The RED LED will blink when data is being transmitted The GREEN LED will blink any time data is received, this is true for the MASTER and SLAVE.
Link/Sanity LED Indicators
The yellow LED indicator labeled “Status” indicates proper system operation. The second yellow LED indicator, labeled “Error”, will flash any time an alarm is programmed and the respective alarm is active.
Serial RS-232 Interface
Used to configure the RTU. See “Software Setup”.
The RT12-4444-9T-W20 has two rows of 10, screw type, connections. Using a common type screwdriver, loosen the respective te rminal screw, insert the respective wire and tighten.
The front panel is stenciled with each Connection number. Listed below are the respective Connection numbers and Connection description.
Connection Screw Terminals Description
Pin 1: “AO 1” (+) Analog Output - 1, 0-5 Vdc Pin 2: “AO 2” (+) Analog Output - 2, 0-5 Vdc Pin 3: “AO 3” (+) Analog Output - 3, 0-5 Vdc Pin 4: “AO 4” (+) Analog Output - 4, 0-5 Vdc Pin 5: “DO 1” (+) Digital Output - 1, Open Drain, Act ive Low, Output Pin 6: “DO 2” (+) Digital Output - 2, Open Drain, Act ive Low, Output Pin 7: “DO 3” (+) Digital Output - 3, Open Drain, Act ive Low, Output Pin 8: “DO 4” (+) Digital Output - 4, Open Drain, Act ive Low, Output Pin 9: “GND” (-) Main Supply GROUND Pin 10: “VIN+” (+) Main Supply 10.5 to 28.0, Must be > 13.0 to Charge External Battery. Do Not Exceed 28 Vdc Pin 11: “AI 1” (+) Analog Input - 1, 0-5 Vdc Pin 12: “AI 2” (+) Analog Input - 2, 0-5 Vdc Pin 13: “AI 3” (+) Analog Input - 3, 0-5 Vdc Pin 14: “AI 4” (+) Analog Input - 4, 0-5 Vdc Pin 15: “DI 1” (+) Digital Input - 1, Active Low, 0~12 Vdc Pin 15: “DI 2” (+) Digital Input - 2, Active Low, 0~12 Vdc Pin 15: “DI 3” (+) Digital Input - 3, Active Low, 0~12 Vdc Pin 15: “DI 4” (+) Digital Input - 4, Active Low, 0~12 Vdc Pin 19: “Batt” (+) Battery Charge During Normal Main Power Input. Battery Backup during Main Power Fa ils. Pin 20: “GND” (-) Battery Ground
Manual Documentation Number: RT-12 series-4006m 11
B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104 – www.bb-elec.com
B&B Electronics – Westlink Commercial Park – Oranmore, Galway, Ireland – Ph +353 91-792444 – Fax +353 91-792445 – www.bb-europe.com
12 Manual Documentation Number: RT-12 series-4006m
B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104 – www.bb-elec.com
B&B Electronics – Westlink C ommercial Park – Oranmore, Ga lway, Ireland – Ph +353 91-792444 – Fax +353 91-792445 – www.bb-europe.com
Loading...
+ 18 hidden pages