Documentation Number – p/n 8931r002 485DRCI-PH-3512qsg
©2011 B&B Electronics Manufacturing Company
22.. IInnffoorrmmaattiioonn
–
–
UULL CCllaassss 22 DDiivv 22
1. Refer to the Nonincendive Field Wiring Apparatus
Control Drawing for important information.
2. Power, Input / output (I/O) wiring for the end use
enclosure must be in accordance with Class 1
Division 2 wiring methods (Article 501.10(B) of the
National Electric Code, NFPA 70) and in
accordance with the local authority having
jurisdiction.
3. Maximum ambient air temperature 85°C.
4. Temperature rating of field installed conductors
105°C. Use Copper Wire Only.
5. These devices must be installed in end use
enclosure suitable for the location.
6. WARNING – EXPLOSION HAZARD
SUBSTITUTION OF COMPONENTS MAY IMPAIR
SUITABILITY FOR CLASS 1, DIVISION 2.
7. WARNING – EXPLOSION HAZARD: DO NOT
DISCONNECT EQUIPMENT UNLESS POWER
HAS BEEN SWITCHED OFF OR THE AREA IS
KNOWN TO BE NON-HAZARDOUS.
8. WARNING – THIS APPARATUS IS SUITABLE
FOR USE IN CLASS 1 DIVISION 2, GROUPS A,
B, C, AND D OR NONHAZARDOUS LOCATIONS
ONLY.
11.. CChheecckk ffoorr RReeqquuiirreedd HHaarrddwwaarree
ILinx 485DRCI-PH Serial Converter
This Quick Start Guide
Additional Items Required but not included
o A 10 to 48 VDC Power Supply (Converter
draws 1.9W Max).
Quick Start Guide
ILinx 485DRCI-PH
Triple Isolated RS-232 to
RS-422/485 Converter
44.. CCoonnffiigguurraattiioonn DDIIPP SSwwiittcchh
SWITCH POSITION 8 IS NOT USED
Highlighted settings indicate factory default.
RS-485
2-Wire
Half Duplex
RS-485
4-Wire
Full Duplex
Built-in Termination Resistor
Use the 120Ω Built-in Termination
Use External or No Termination
Built-in Transmit Bias Resistor
6 Use External or No Bias Resistor
Use the 1.2K Ω Transmit Bias Resistor
Built-in Receive Bias Resistor
7 Use External or No Bias Resistor
Use the 1.2K Ω Receive Bias Resistor
For an explanation of RS-485 termination and biasing
requirements, refer to B&B Electronics’ RS-485
application note. This publication can be downloaded
at: www.bb-elec.com
33.. FFrroonntt && BBaacckk PPaanneell,, DDBB99 PPiinn--oouutt
Front Panel
Back Panel
Front and Back Panel
Red, ON When Power Applied
Green. LEDs Flash When Data is on
Chassis Ground to Earth Ground

Documentation Number – p/n 8931r002 485DRCI-PH-3512qsg
©2011 B&B Electronics Manufacturing Company
66.. PPoowweerr CCoonnnneeccttiioonn
1. Connect Power. Power Requirements: 10 to 48 VDC,
1.9W Maximum.
2. The terminal block will accept 28 to 12 AWG Wire.
77.. RRSS--442222//448855 TTeerrmmiinnaall BBlloocckk
See cable recommendation in section one.
88.. WWiirriinngg EExxaammpplleess
RS-485 2-wire
99.. LLoooopp BBaacckk TTeesstt // TTrroouubblleesshhoooottiinngg
Configure for RS-485 Four wire.
Jumper terminals A to C and B to D
Connect a PC to the RS-232 port (see Step 3).
Using hyper terminal or similar program, connect to
the appropriate COM port. Turn off hyper terminal
local echo
Transmit data. The same data should be returned.
When data is sent and looped back, the TD and RD
LED’s will blink on both ports.
55.. GGrroouunndd CCoonnnneeccttiioonn
1. It is recommended that the chassis be grounded.
2. Connect a grounding wire from the ground lug to a good
source of Earth Ground.