http://www.del ta.c om .tw /ind ustr ialau toma tion /
DELTA Temperature Controller
DTB Series
User Manual
B Series Temperature Controller
User Manual
1 Precaution
DANGER!Caution! Electric Shock!
1. Do not touch the AC terminals while the power is supplied to the controller to prevent an electric shock.
2. Make sure power is disconnected while checking the unit inside.
3. The symbol indicates that this Delta B Series Temperature Controller is protected throughout by DOUBLE INSULATION or REINFORCED
INSULATION (equivalent to Class II of IEC 536).
WARNING!
This controller is an open-type temperature controller. Make sure to evaluate any dangerous application in which a serious human injury or serious
property damage may occur.
1. Always use recommended solder-less terminals: Fork terminal with isolation (M3 screw, width is 7.0mm (6.0mm for DTB 4824), hole diameter 3.2mm).
Screw size: M3 x 6.5 (With 6.8 x 6.8 square washer). Screw size for DTB4824: M3 x 4.5 (With 6.0 x 6.0 square washer). Recommended tightening
torque: 0.4 N.m (4kgf.cm). Applicable wire: Solid/twisted wire of 2 mm2, 12AWG to 24AWG. Please be sure to tighten them properly.
2. Do not allow dust or foreign objects to fall inside the controller to prevent it from malfunctioning.
3. Never modify or disassemble the controller.
4. Do not connect anything to the “No used” terminals.
5. Make sure all wires are connected to the correct polarity of terminals.
6. Do not install and/or use the controller in place s su bje ct to: (a ) Du st or c orr osive gases and liquid. (b) High humidity and high radiation. (c) Vibration and
shock. (d) High voltage and high frequency.
7. Must turn power off when wiring and changin g a temp era tur e sensor.
8. Be sure to use compensating wires that match the thermocouple types when extending or connecting the thermocouple wires.
9. Please use wires with resistance when extending or connecting a platinum resistance thermometer (RTD).
10. Please keep the wire as short as possible when wiring a platinum resistance thermometer (RTD) to the controller and please route power wires as far as
possible from load wires to prevent interference and induced noise.
11. This controller is an open-type unit and must be placed in an enclosure away from high temperature, humidity, dripping water, corrosive materials,
airborne dust and electric shock or vibrati on.
12. Make sure power cables and signals from instruments are all installed properly before energizing the controller, otherwise serious damage may occur.
13. Please do not touch the terminals in the controller or try to repair the controller when power is applied to prevent an electric shock.
14. Wait at least one minute after power is disconnected to allow capacitors to discharge, and please do not touch any internal circuit within this period.
15. Do not use acid or alkaline liquids for cleaning. Please use a soft, dry cloth to clean the controller.
16. This instrument is not furnished with a power sw itch or fuse. Therefore, if a fuse or power switch is required , i nstall the protection close to the instrument.
Recommended fuse rating: Rated voltage 250 V, Rated current 1 A. Fuse type: Time-lag fuse
17. Note: This controller doe s n ot p rovide overcurrent protection. Use of this product requires that suitable overcurrent protection device(s) m us t be a dded to
ensure compliance with all relevant electrical standards and codes. (Rated 250 V, 15 Amps max). A suitable disconnecting device should be provided
near the controller in th e end-use installation.
2 Display, LED and Pushbuttons
PV D i spl ay
SV D i spl ay
manipulated variable or set value of the parameter.
AT
: flas hes whe n the A ut o-tuning operation is ON.
OUT1/OUT2
: . Press this key to select the desired function mode and
confirm a setting value.
: . Press this key to set parameters within function mode.
O
OOO
C, F : .
ALM1 ~ A LM 3 : Al ar m output LED, li ghts when AL M 1/ALM2/ALM3 is ON.
: . Press this key to decrease values displayed on the SV
display. Hold down this key to speed up the decrements.
:
Hold down this key to speed up the increme ntal action.
3 Ordering Information
DTB
DTB Series DTB : Delta B Series Temperature Controller
1 2 3 4
5
1st Output Group Selection
6
2nd Output Group Selection
7
EVENT Inputs /
CT function (Optional)
Note 1: DTB4824 series: no optional function provided and no extra alarm output supported, but user can set 2nd output as alarm mode.
Note 2: DTB4848 series: only one alarm output when optional function supported, but user can set 2nd output as 2nd alarm output.
Note 3: “Valve control” with feedback selection is only available for DTB9696RRV.
1 2 3 45 67
Panel Size (W×H)
4824: 1/32 DIN W48 x H24mm; 4848: 1/16 DIN W48 x H48mm;
4896: 1/8 DIN W48 x H96mm; 9696: 1/4 DIN W96 x H96mm
R: Relay output, SPDT (SPST: 1/16 DIN and 1/32 DIN size), 250VAC, 5A
V: Voltage pulse output, 14V +10%~ -20% (Max. 40mA)
C: DC current output, 4 ~ 20m A; L: Linear voltage output, 0~5V, 0~10Vdc
R: Relay output, SPDT (SPST: 1/16 DIN and 1/32 DIN size), 250VAC, 5A
V: Voltage pulse output, 14V +10%~ -20% (Max. 40mA)
None: No EVENT input, No CT (Current transformer); E: EVENT input is provided, No CT (Current transformer)
T: CT (Current transformer) is provided, No EVENT input; V: Valve control.
: to dis play th e process value or pa rameter type.
: to display the set point, parameter op eration read value,
Auto-t un ing LED ,
: Output LED ights when the output is ON.
Function key
Mode key
Temperature unit LED
Down key
. Press this key to increase values displayed on the SV display .
key
Up
1
, l
C : Celsius F : Fahrenheit
4 Specifications
Input Voltage 100 to 240VAC 50/60Hz
Operation Voltage Range 85% to 110% of rated voltage
Power Consumption 5VA max.
Memory Protection EEPROM 4K bit (non-volatile memory (number of writes: 100,000)
Display Method 2 line x 4 character 7-segment LED display Process value(PV): Red color, Set point(SV): Green color
Sensor Type
Control Mode PID, ON/OFF, Manual or PID program control (Ramp/Soak control)
Control Output
Display Accuracy 0 or 1 digit to the right of the decimal point (selectable)
Sampling Rate Analog input: 150 msec/ per scan Thermocouple or Platinum RTD: 400 msec/per scan
RS-485 Communication MODBUS ASCII / RTU communication protocol
Vibration Resistance 10 to 55Hz, 10m/s2 for 10min, each in X, Y and Z directions
Shock Resistance Max. 300m/ s2, 3 times in each 3 axes, 6 directions
Ambient Temperature 0 oC to +50 oC
Storage Temperature -20 oC to +65 oC
Altitude 2000m or less
Relative Humidity 35% to 80% (non-condensing)
5
Input Temperature Sensor Type Register Value LED Display Temperature Range
0~50mV Analog Input 17
4~20mA Analog Input 16
0~20mA Analog Input 15
0V~10V Analog Input 14
0V~5V Analog Input 13
Platinum Resistance (Pt100) 12
Platinum Resistance (JPt100) 11
Thermocouple TXK type 10
Thermocouple U type 9
Thermocouple L type 8
Thermocouple B type 7
Thermocouple S type 6
Thermocouple R type 5
Thermocouple N type 4
Thermocouple E type 3
Thermocouple T type 2
Thermocouple J type 1
Thermocouple K type 0
Note 1 : An external 250Ω precision resistor should be connected when the current input is selected as the input temperature sensor type..
Note 2 :
(Operation mode) must be set if user wish to specify decimal point position. Except for the thermocouple B, S, R type, the decimal
point positions of all the other thermocouple type input sensors can be set.
The default range of analog input is -999 ~ 9999. For example, when a 0~20mA analog input is selected as the input temperature sensor type, -999
indicates 0mA and 9999 indicates 20mA. If change the input range to 0 ~ 2000, then 0 indicates 0mA and 2000 indicates 20mA. One display scale is
equal to 0.01mA.
Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
3-wire Platinum RTD: Pt100, JPt100
Analog input: 0~5V, 0~10V, 0~ 20 m A, 4~20 m A, 0~50mV
Relay output: SPDT (SPST: 1/16 DIN and 1/32 DIN size), Max. load 250VAC, 5A resistive load
Voltage pulse output: DC 14V, Max. output current 40mA
Current output: DC 4 ~ 20m A output (Load resistance: Max. 600Ω)
Linear voltage output: 0~5V, 0~10V
Temperature Sensor Type and Temperature Range
-999 ~ 9999
-999 ~ 9999
-999 ~ 9999
-999 ~ 9999
-999 ~ 9999
-200 ~ 600
-20 ~ 400
-200 ~ 800
-200 ~ 500
-200 ~ 850
100 ~ 1800
0 ~ 1700
0 ~ 1700
-200 ~ 1300
0 ~ 600
-200 ~ 400
-100 ~ 1200
-200 ~ 1300
o
o
o
C
2
o
C
o
C
o
C
o
C
o
C
o
C
C
C
o
C
o
C
o
C
o
C
6
u
Operation
There are three modes of operation: operation, regulation and initial setting. When power is applied, controller gets into the operation mode.
Press the
mode. Pressing the
PV/SV: Sets the temperature set point and displays the temperature process value. Use
Setting method: While in any function mode, press the
key to switch to regulation mode. If the key is pressed for more than 3 seconds, controller will switch to the initial setting
key while in the regulation mode or initial setting mode, forces the controller to return to the operation mode.
keys to set the temperature set point.
key to select the desired function and use the keys to change settings.
Press
key to save the changes.
The next flow chart shows how to switch for settings and internal functions:
Regulation ModeOperation Mode
Auto-tuning
(Set in PID control and RUN mode)
Press
4 groups PID modes (n=0~3). When n=4,
PID control is auto regulated.
Press
PD control offset
(When PID control is ON and Ti=0,
set the value of PdoF.
Press
(Set in ON/OFF control mode)
Press
setting
Heating hystereisis setting
Press key less than 3 sec
Press key
Regulation Mode
set temperature set point
Press
Press
Start pattern setting (PI D
program control and
Press
Press
Operation Mode
Use key to
Control setting RUN or STOP
Time settin g .
Decimal point position selection
(except for B, S, R type, all the
other types can be set)
Press key more than 3 sec
Press key
Press
do not display when analog input
Press
Press
Press
Initial Setting Mode
Initial Setting Mode
Set input type
Set temperature unit
Set upper-limit of
temperature range
Se t lower-limit of
temperature range
Cooling hystereisis setting
(Set in ON/OFF control mode)
Press
or
(Set in PID control mode)
Press
Heating/Cool ing
control cycle setting
Control cycle setting
of 2nd output group
(Set in PID control and Dual Loop
output control mode)
Press
P value of 1st & 2nd output gro
during dual loop output control
P value of 2nd output group =
Press
x (P value of 1st output group)
(This parameter is available only when
ALA1 function enables)
Press
(This parameter is available only when
ALA1 function enables)
Press
(This parameter is available only when
ALA2 function enables)
Press
(This parameter is available only when
ALA2 function enables)
Press
Upper-limit alarm 1
Lower-limit alarm 1
Upper-limit alarm 2
Lower-limit alarm 2
Select control mode
(See "Pattern and set Editing
selection" for detail)
Press
Select heatin g/c ooling contro l
or dual loop output control
Press
Alarm 1 mode setting
Press
Alarm 2 mode setting
Press
Dead Band (Set in Dual Loop
output control mode)
Press
Swit ch set tin g f or feedback
signal of valve. (Display when
valve control is ON)
Press
Autom atica lly regulat e
feedback value.
(Dis play when valve control is ON )
Press
Press
Upper-limit alarm 3
(This parameter is available only when
ALA3 function enables)
Press
Lower-limit alarm 3
(This parameter is available only when
ALA3 function enables)
Press
Setting lock mode
Press
Press
Press
Press
Alarm 3 mode setting
Set system alarm
Communication write function
enable/ disa ble
3
full close to full open. (Display when
valve control is ON)
Press
(Displ ay when valv e con trol is ON)
Press
Press
Time setting for valve from
Va lv e Dea d Band s et t i ng.
Display and adjust output value
(Display in PID control mode and manual
RUN mode)
(Display in dual loop PID control mode and
manual RUN mode)
of 1st output group
Press
Display and adjust output value
of 2nd output group
Press
ASCII, RTU communication
format selection
Press
Communi cation address
setting
Press
Upper-limit regulation of
valve output with feedback to
controller. (Display when valve
sign al fee dback func t ion is ON)
Press
Lower -l im it reg ulation of
valve output with fee dback to
controller. (Display when valve
signal feedback function is ON)
Press
Regula te temperature
deviation value
Press
In c ase of using an external CT,
the controller displays the current
value being measured by CT, if
the control output is ON
Press
to return to set target temperature
Valve output with feedback.
(Display when valve feedback
function is ON)
Press
DA value feedback of valve.
(Display when valve feedback
function is ON)
PressBack to target tempe ra t ur e
Communication baud
rate setting
Press
Data length setting
Press
Parity bit setti n g
Press
Regulate upper-limi t of analog
output value
(The setting display when analog output)
Press
Regulate lower-limit of analog
(The setting display when analog output)
Press
output value
to return to auto-tuning mode
Stop bit setting
Press to return input type setting
* 1 Scale = 2.8uA = 1.3mV for tuning output value
PID mode selection: any one of 4 groups PID modes (n=0~3) can be selected. When n=4, program will automatically select 1 group PID that is
most useful for target temperature.
Press
Select n=0~4 to
decide PID mode.
0~3 groups PI D
PID s etting: n=0.
Proportion band s etting: n=0.
Ti setting: n=0.
Td setting: n=0.
Integral deviation setting: n=0.
AT setting.
Press
back t o PID deviation setting
Press
Press
Press
Press
Pattern and step editing selection: edit
Select desired editing pattern
number
select OFF
Press
Exit pattern and step editing selection
select number
Switc h to and continue setting
in parameter. The following display is the example operation of pattern No. 0.
Edit temperature of step No. 0
of pattern No. 0
Press
Edit time of step No. 0 of
Press
pattern No. 0, unit is hh.mm
Set step No. 07 in order
Edit temperature of step No. 7
of p attern No. 0
Press
Press to set actual step No.
Edit time of step No. 7 of
pattern No. 0, unit is hh.mm
PID setting: n=3.
Proportion band setting: n=3.
Ti setting: n=3.
Td setting: n=3.
Integral deviation setting: n=3.
AT setting.
Press
back to PI D deviat ion s et t ing
Select actual step No. when
program control is executing
Press
Set additional execution cycle
number( 0 to 99)
Press
Set link pattern, OFF indicates
the program end
Press to return patt ern No. editing
mode
Press
Press
Press
Press
4
7
Dual Loop Output Control (Heating / Cooling Control)
Temperature control can be achieved either by heating or cooling. In DTB series, heating and
cooling can be operated simultaneously (Dual Loop output control) to perform temperature
control. When Dual Loop output control are used, two control outputs must be connected to the
heating and cooling devices. Please refer to the following for the operation:
: This parameter is used to select heating or cooling action if operate either heating or
cooling function in this controller. When selecting
control, and when selecting
, 1st output group is cooling (forward) control. At this
moment, 2nd output group is regarded as an alarm output. If user select
, 1st output group is heating (reverse)
or, it
indicates that user can operate Dual Loop output control function in this controller. When
selecting
(forward) control. When selecting
, 1st output group is heating (reverse) control and 2nd output group is cooling
, 1st output group is cooling (forward) control and 2nd
output group is heating (reverse) control.
In DTB series, P (Proportional Band), I(Integral Time) and D(Derivative Time) parameters are
automatically set by using the Auto-tuning (AT) function.
: This parameter is for the control mode that must be Dual Loop output control with PID
control method configured. The value of P, I and D of 1st output group can be set immediately.
The P value of 2nd output group is equal to (P value of 1st output group) x
and the
value of I and D of 2nd output group are the same as the value of I and D of 1st output group.
: Dead Band, shown as the following figure 1, 2 and 3. This parameter sets an area in
which the heating and cooling control output is 0 centering around the set point in a Dual Loop
output control mode.
: Settings lock. To avoid incorrect operation, two key lock functions are provided.
: Lock 1 can lock all settings. All parameters and temperature settings can be locked to
disable changes.
: Lock 2 can lock settings except the SV (Set point) value. All
parameters and temperature settings can be locked with the exception of the SV value. Press
and key simultaneously, the “Lock” status can be released.
Heatin g hysteresis
ON
Heatin g
OFF
Figure 1. Output
Output
HeatingCooling
0
Figure 2. PID Dead Band is positive control,
Set point
operation of ON/OFF control
during dual loop output control
Set point
Dead band: dead
band width=positive
Output
Heati n g
0
Figure 3. PID Dead Band is negative control,
Dead band: dead
band width=negative
Cooling
Set point
Dead band
Cooling hysteresis
Cooli ng
PV
PV
PV
5
8 Alarm Outputs
A
There are up to three groups of alarm outputs and each group allows thirteen alarm types in the initial setting mode. The alarm output is
activated whenever the process temperature value (PV) is getting higher or lower than the set point of alarm limit.
Set
Value
Alarm Type Alarm Output Operation
0 Alarm function disabled Output is OFF
1 Deviation upper- and lower-limit:
This alarm output operates when PV value is higher than the setting value SV+(AL-H) or lower than the
setting value SV-(AL-L).
2 Deviation upper-limit:
This alarm output operates when PV value is higher than the setting value SV+(AL-H).
3 Deviation lower-limit:
This alarm output operates when PV value is lower than the setting value SV-(AL-L).
4 Reverse deviation upper- and lower-limit:
This alarm output operates when PV value is in the range of the setting value SV+(AL-H) and the setting
value SV-(AL-L).
5 Absolute value upper- and lower-limit:
This alarm output operates when PV value is higher than the setting value AL-H or lower than the setting
value AL-L.
6 Absolute value upper-limit:
This alarm output operates when PV value is higher than the setting value AL-H.
7 Absolute value lower-limit:
This alarm output operates when PV value is lower than the setting value AL-L.
8 Deviation upper- and lower-limit with standby sequence:
This alarm output operates when PV value reaches set point (SV value) and the value is higher than the
setting value SV+(AL-H) or lower than the setting value SV-(AL-L).
9 Deviation upper-limit with standby sequence:
This alarm output operates when PV value reaches set point (SV value) and the reached value is higher
than the setting value SV+(AL-H).
10 Deviation lower-limit with standby sequence: this alarm output operates when PV value reaches the set
point (SV value) and the reached value is lower than the setting value SV-(AL-L).
11 Hysteresis upper-limit alarm output:
This alarm output operates if PV value is higher than the setting value SV+(AL-H). This alarm output is
OFF when PV value is lower than the setting value SV+(AL-L).
12 Hysteresis lower-limit alarm output:
This alarm output operates if PV value is lower than the setting value SV-(AL-H). This alarm output is OFF
when PV value is higher than the setting value SV-(AL-L).
13 CT alarm output:
This alarm operates when the current measured by transformer (CT) is lower th an AL-L or higher than
AL-H (This alarm output is available only for the controller with current transformer).
14
When program control is end status, alarm output is ON.
15
When RAMP UP status happens to PID program control, alarm output is ON.
16
When RAMP DOWN status happens to PID program control, alarm output is ON.
17
When SOAK status happens to PID program control, alarm output is ON.
18
When RUN status happens to PID program control, alarm output is ON.
ON
OFF
SV-(AL-L)
ON
OFF
ON
OFF
SV-(AL-L)
ON
OFF
SV-(AL-L)
ON
OFF
ON
OFF
ON
OFF
ON
OFF
SV-(AL-L)SV+(AL-H)
ON
OFF
ON
OFF
SV-(AL-L)
ON
OFF
ON
OFF
ON
OFF
AL-L
AL-L
AL-L
SV
SV
SV
SV
AL-H
SV
SV
SV
AL-L
SV+(AL-H)
SV+(AL-H)
SV+(AL-H)
SV+(AL-H)
AL-H
AL-L
SV
Note: AL-H and AL-L include AL1H, AL2H, AL3H and AL1L, AL2L, AL3L
AL-H
L-H
AL-H
6
9 Current Transformer (CT) Function
The Current Transformer (CT) function is used with the alarm output. When using a current transformer (CT) with the controller, change the
corresponding alarm output mode to mode 13 (alarm output set value is 13), then turn to operation mode and set the current lower-limit and
current upper-limit. You can set current alarm range between 0.5A ~ 30A, display resolution is 0.1A and measure accuracy is +/- 0.5A.
10 EVENT Inputs Function
5
There are two optional event inputs (contact inputs) supported (EVENT1and EVENT2) in DTB series.
EVENT1: RUN/STOP operation can be executed by RUN/STOP parameters (Operation Mode) or via the communication. User also can
control RUN/STOP operation by EVENT 1 in DTB series. The control output is ON if the circuit of EVENT 1 is open when the
controller is operating. Otherwise, the controller will stop output if the circuit of EVENT 1 is short or when the system parameter of
the controller is set to STOP mode.
EVENT2: DTB series allows user can switch two temperature setting value by changing the status (open/short) of EVENT 2. Each
temperature setting value has independent control parameters.
11 PID Program Control (Ramp/Soak Program Control)
Description of Function and Parameters Setting:
PID program control by 8 patterns (Pattern No. 0~7) is supported in DTB series. Each pattern contains 8 steps (step No. 0 ~ 7), one Link
Pattern parameter, one Cycle parameter and one Actual Step parameter.
Start Pattern:
is in operation mode and it is used to set the Start Pattern of PID program control (This parameter appear in
mode only).
Steps : Include set point X and execution time T, these two parameters setting. The set point (SV) should reach temperature X after the period
of execution time T. If the set point is the same as the result of the previous setting, then it is called Soak program control. If not, then it
is called Ramp program control. Therefore, PID program control is also called Ramp/Soak program control. The default of step No. 0
in this controller is Soak program control. The controller will control the temperature (PV) to reach the set point X and then keep the
temperature at set point X. The period of execution time is time T which provided by step No. 0.
Link Pattern Parameter : For example, when set
0. If set to
, it indicates the program will stop after executing the current pattern and the temperature will keep at the set point of
to 2, it indicates that pattern No. 2 will execute next after the execution of pattern No.
the last step.
Cycle Parameter : Additional execution cycle number. For example, when set
to 2, it indicates that pattern No. 4 should execute twice
in addition. Include origin one time execution, total execute three times.
Actual Step Parameter : Execution step number per pattern (can set to 0 ~ 7). For example, when set
to 2, it indicates that pattern No
7 will not execute other steps than step 0 to step2.
Execution : When
is set to , the program will start to execute in order from the step 0 of start pattern. When is set to
, the program will stop and the control output is disabled. When is set to , the program will stop and the temperature
at that time will be controlled at the set point before program stop. Select
step 0 of start pattern. When
point before program hold. Select
is set to , the program will hold and the temperature at that time will be controlled at the set
again, then the program will follow the step before hold and start to execute through the rest
again, then the program will restart and execute from
of the time.
Display : During PID program control, the SV default display is P-XX, P indicates the current execution pattern and XX indicates the current
execution step. Press
current execution step will display on SV display. After select
execution step will display on SV display.
12 PID Control
One group can be selected from any one of 4 groups PID parameters (P, I, D, IOF) for PID control. After AT, PID value and temperature setting
will be stored in the selected one group.
to change the display item. After select , press key, and then the temperature set point of the
, press key, and then the residual time of the current
~: PIDn, n=0~4 from which 0~3 correspond to each PID parameter. : n=4, auto PID
parameter. Program will automatically select a most useful PID parameter based on current temperature setting. Displayed SV values
correspond to
~
~: Temperature setting corresponded to the selected PID parameter via user-defined or AT.
Valve Control:
When use valve control as output control, there are 2 Relay outputs for motor forward/reverse control, one (output 1) for valve open the other
(output 2) for valve close. The output volume is controlled by valve open/close and it can be set with feedback function enabled or disabled.
When feedback is disabled, output 1 will keep output while valve fully opens and output 2 will keep output while valve fully closes. But if
feedback is enabled, please follow the parameter setting for valve control as follows:
: Time for valve from full close to full open.
: Dead Band setting of valve. The value of current valve output minus previous one must be greater than Dead Band value; otherwise,
valve will remain OFF.
: Signal feedback setting, ON for enabling feedback and OFF for disabling feedback.
When
set to ” 1”, it means signal feedback function is activated and will come up selections as follows:
a.
b.
c.
: Upper/Lower limit of valve feedback by auto-tuning. must set tofor showing up this selection.
: D/A value when value fully opens. Set to be ”1” for auto setting or ”0” for manual setting.
: D/A value when value fully closes. Set to be ”1” for auto setting or “0” for manual setting.
Note: If feedback function setting is with problem, program will see the setting as feedback disabled.
2. Non-supported formats: 7, N, 1 or 8, O, 2 or 8, E, 2
3. Communication protocol: Modbus (ASCII or RTU)
4. Function code: 03H to read the contents of register (Max. 8 words). 06H to write 1 (one) word into register. 02H to read the bits data (Max.
16 bits). 05H to write 1 (one) bit into register.
5. Address and Content of Data Register:
Address Content Explanation
1000H Process value (PV)
1001H Set point (SV) Unit is 0.1, oC or oF
1002H Upper-limit of temperature range The data content should not be higher than the temperature range
1003H Lower-limit of temperature range The data content should not be lower than the temperature range
1004H Input temperature sensor type Please refer to the contents of the “Temperature Sensor Type and Temperature Range” for detail
1005H Control method 0: PID, 1: ON/OFF, 2: manual tuning, 3: PID grogram control
1006H Heating/Cooling control selection 0: Heating, 1: Cooling, 2: Heating/Cooling, 3: Cooling/Heating
1007H 1st group of Heating/Cooling control
cycle
1008H 2nd group of Heating/Cooling control
cycle
1009H PB Proportional band 0.1 ~ 999.9
100AH Ti Integral time 0~9999
100BH Td Derivative time 0~9999
100CH Integration default 0~100%, unit is 0.1%
100DH Proportional control offset error value,
when Ti = 0
100EH The setting of COEF when Dual Loop
output control are used
100FH The setting of Dead band when Dual
Loop output control are used
1010H Hysteresis setting value of the 1st
output group
1011H Hysteresis setting value of the 2nd
output group
1012H Output value read and write of Output 1 Unit is 0.1%, write operation is valid under manual tuning mode only.
Measuring unit is 0.1, updated one time in 0.4 second
The following reading value display indicates error occurs:
8002H : Initial process (Temperature value is not got yet)
8003H : Temperature sensor is not connected
8004H : Temperature sensor input error
8006H : Cannot get temperature value, ADC input error
8007H : Memory read/write error
0~99, 0:0.5 sec
0~99, 0:0.5 sec
0~100%, unit is 0.1%
0.01 ~ 99.99
-999 ~ 9999
0 ~ 9999
0 ~ 9999
1013H Output value read and write of Output 2 Unit is 0.1%, write operation is valid under manual tuning mode only.
1014H Upper-limit regulation of analog linear
output
1015H Lower-limit regulation of analog linear
output
1016H Temperature regulation value -999~+999, unit: 0.1
1017H Analog decimal setting 0 ~ 3
1018H Time for valve from full open to full
close
1019H Dead Band setting of valve 0~100%; unit: 0.1%
101AH Upper-limit of feedback signal set by
valve
101BH Lower-limit of feedback signal set by
valve
101CH PID parameter selection 0~4
101DH SV value corresponded to PID value Only valid within available range, unit: 0.1 scale
1020H Alarm 1 type Please refer to the contents of the “Alarm Outputs” for detail
1021H Alarm 2 type Please refer to the contents of the “Alarm Outputs” for detail
1022H Alarm 3 type Please refer to the contents of the “Alarm Outputs” for detail
1023H System alarm setting 0 : None (default), 1~3 : Set Alarm 1 to Alarm 3
1024H Upper-limit alarm 1 Please refer to the contents of the “Alarm Outputs” for detail
1025H Lower-limit alarm 1 Please refer to the contents of the “Alarm Outputs” for detail
1026H Upper-limit alarm 2 Please refer to the contents of the “Alarm Outputs” for detail
1027H Lower-limit alarm 2 Please refer to the contents of the “Alarm Outputs” for detail
1028H Upper-limit alarm 3 Please refer to the contents of the “Alarm Outputs” for detail
1029H Lower-limit alarm 3 Please refer to the contents of the “Alarm Outputs” for detail
102AH Read LED status b0 : Alm3, b1: Alm2, b2: F, b3: oC, b4: Alm1, b5: OUT2, b6: OUT1, b7: AT
102BH Read pushbutton status b0 : Set, b1 : Select, b2 : Up, b3 : Down. 0 is to push
102CH Setting lock status 0 : Normal, 1 : All setting lock, 11 : Lock others than SV value
102DH CT read value Unit: 0.1A
102FH Software version V1.00 indicates 0x100
1 Unit = 2.8uA(Current Output) = 1.3mV(Linear Voltage Output)
1 Unit = 2.8uA(Current Output) = 1.3mV(Linear Voltage Output)
0.1~999.9
0~1024
0~1024
8
1030H Start pattern number 0 ~ 7
1040H~
1047H
1050H~
1057H
1060H~
1067H
2000H~
203FH
2080H~
20BFH
Actual step number setting inside the
correspond pattern
Cycle number for repeating the
execution of the correspond pattern
Link pattern number setting of the
correspond pattern
Pattern 0~7 temperature set point
setting; Pattern 0 temperature is set to
2000H~2007H
Pattern 0~7 execution time setting
Pattern 0 time is set to 2080H~2087H
0 ~ 7 = N, indicate that this pattern is executed from step 0 to step N
0 ~ 99 indicate that this pattern has been executed for 1 ~ 100 times
0 ~ 8, 8 indicates the program end. 0~7 indicates the next execution pattern number after executing
the current pattern
-999 ~ 9999
Time 0 ~ 900 (1 minute per scale)
6. Address and Content of Bit Register: ( First bit of reading will put into LSB, Write data = FF00H for bit set, 0000H for bit clear)
0810H Communication write-in selection Communication write in disabled: 0 (default), Communication write in enabled: 1
0811H Temperature unit display selection oC / linear input (default) : 1 , oF : 0
0812H Decimal point position selection Except for the thermocouple B, S, R type, all the other thermocouple type are valid. (0 or 1)
0813H AT setting OFF: 0 (default), ON : 1
0814H Control RUN/STOP setting 0: STOP, 1 : RUN (default)
0815H
0816H
STOP setting for PID program
control
Temporarily STOP for PID program
control
0: RUN (default), 1: STOP
0: RUN (default), 1: Temporarily STOP
0817H Valve feedback setting status 0: w/o feedback (default), 1: feedback function
0818H Auto-tuning valve feedback status 0: Stop AT (default), 1: Start AT
7. Communication Transmission Format : Command Code: 02: read N bits, 05: write 1 bits, 03: read N words, 06: write 1 words
9
14 Panel Cutout and Terminals Identification
A
+
L
Panel Cutout (dimensions are in millimeter and inch)
Terminals Identification
DTB4824
DTB4848
.
in
m
0
.
0
6
DTB4896
DTB9696
65.0 min.
(2.56)
2
0
6
.
.
0
0
0
0
-
-
+
+0.6
-0
+0.02
-0
+
mm
(in)
)
7
0
.
2
.8
2
0
(
.
n
)
i
8
m
5
.
0
.
1
(
0
4
44.8
(1.76)
DTB4848
65.0 min.
(2.56)
)
6
3
.
2
(
45.0
(1.77)
+0.6
-0
+0.02
-0
mm
(in)
2
6
0
.
.
0
0
0
0
+
+
-
-
)
0
7
.
7
5
.
4
1
(
(EVENT & CT selection)
DTB4824
DTB4896/DTB9696
OUT 2/
ALM
+
7
V
OUT 1
RS-485
-
-
-
98
+
V
+
10
1112
143256
LN
AC 100~240V
50/60 Hz 5VA
RTD
!
DTB4848
(NO EVENT & CT)
OUT1
14V
DC
NO
-
or
4~20mA
or
0~10V
RTD
+
IN
-
1
2
+
COM
3
+
4
Tc
5
-
10
+
+
6
7
8
COM
9
OUT2/
ALM3
NO
DATARS-485
DATA+
14V
Tc
IN
11
-
12
DC
ALM 2
13
+
ALM 1
14
3A
250Vac
15
COM
L
C 100 ~ 24 0 V
50/60 Hz
5VA
N
DATA-DATA+
-
-
3A
250Vac
DATA+
1
4
5
10
11
2
12
3
13
14
15
6
16
7
17
8
18
9
19
20
RS-485
DATA-
SG
Ev1
CT
Ev2
ALM1
COM
RTD
+
+
Tc
IN
--
DTB9696RRV
AC 100~240V
50/6 0 Hz
5VA
N
ALM2
COM
OUTPUT2/ALM3
COM
NC
5A
250Vac
NO
NC
OUTPUT1
5A
250Vac
NO
14VDC4~20mA
COM
14V
or
+
-
-
or
0~10V
DC
10
15 External Dimensions
DTB4824 DTB4848
44.75 mm
(1.76 in)
Dimensions are in millimeter (inch)
)
m
in
m
7
0
8
.
.
2
0
2
(
44.8 mm
)
m
in
m
4
0
9
.
.
4
0
(
2
(1.76 in)
m
)
m
in
5
6
8
8
.
.
1
0
(
2
2
6
0
.
.
0
0
0
0
+
+
)
m
in
m
7
0
7
.
.
5
1
(
4
+0.6
45.0 mm
(1.77 in)
)
m
in
m
9
0
8
.
.
8
1
(
4
0
+0.02
0
m
)
m
in
5
6
7
7
.
.
4
1
(
4
48.0 mm
(1.89 in)
DTB4896 DTB9696
3.4 mm
(0.13 in)
99.8 mm
(3.93 in)
48.0 mm
(1.89 in)
44.0 mm
(1.73 in)
0
0
+0.6
+0.02
91.5 mm
(3.60 in)
+0.6
0
+0.02
0
91.0 mm(3.58 in)
96.0 mm
(3.78 in)
48.0 mm
(1.89 in)
95.7 mm(3.77 in)
98.2 mm(3.87 in)
12.8 mm
(0.50 in)
44.5 mm
(1.75 in)
79.2 mm(3.12 in)
9.5 mm
(0.37 in)
96.0 mm
(3.78 in)
15.8 mm
(0.62 in)
98.0 mm
(3.86 in)
80.0 mm
(3.15 in)
91.0 mm
(3.58 in)
+0.6
0
+0.02
0
79.2 mm
(3.12 in)
+0.6
0
91.0 mm
0
+0.02
(3.58 in)
90.8 mm
11
Mounting
16
Mounting MethodMounting Bracket Installation
Step 1 : Insert the controller through the panel cutout.
Step 2 : Insert the mounting bracket into the mounting groove at the top and
om of the controller
bott
Step 3 : Push the mounting bracket forward until the bracket stops at panel
wall.
Step 4 : Insert and tighten screws on bracket to secure the controller in place.
(The screw torque should be 0.8kgf-cm to 1.5kgf-cm)
DTB4824 Mounting Method:
CT Wiring Method (if CT function is selected)
DTB4848/4896/9696 Mounting Method:
3
2
1
17
Communication error code response description:
Error status 102EH/4750H PV read back 1000H/4700H Error status
0001H N/A PV unstable
0002H 8002H Re-initial, No temperature at this time
0003H 8003H Input sensor did not connect
0004H 8004H Input signal error
0005H N/A Over input range
0006H 8006H ADC fail
0007H N/A EEPROM read/write error
Display message:
Power
PV
DTB series, Firmware V1.50
ON Normal display
SVOutput VR type with Event option Set value
Sensor didn’t connect Input error
PVNoError
SVConnectInput
EEPROM error Input over range
PV
Error
SVEEPROM
Error Acknowledge and Display
Present value
PV flash when over
0
6
.
8
m
m
M
a
x
.
12
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.