Applications for the copyright owner’s permission to reproduce or make other use of any part of
this publication should be made, giving any details of the proposed use to the following address:
The Company Secretary,BAXI Heating UK Ltd,The Wyvern Business Park,Stanier Way,Derby DE21 6BF.
Full acknowledgement of author and source must be given.
WARNING: Any person who does any unauthorised act in relation to a copyright work may be
liable to criminal prosecution and civil claims for damages.
Potterton Solar - Solar Thermal Domestic Hot Water System2
.0Commissioning of system
1
1.1Commissioning - General
The Potterton Solar system uses a sealed system indirect
solar primary circuit which must be filled with the solar
heat transfer fluid provided. This is pre-diluted to the
appropriate strength (40% glycol/60%water) and should
not be diluted further. Use only the fluid supplied.
Additional canisters of solar fluid are available in 10 litre
(5119550) and 20 litre (5119549) bottles.
DO NOT mix the fluid with other types.
The system should be filled when there is no direct
radiation from the sun. If direct radiation occurs the
collector panels should be shaded by covering them
during filling and flushing.
Although the solar heat transfer fluid is non corrosive
and biodegradable appropriate precautions should be
taken when handling.
- Wear protective gloves and goggles.
- Wash with soap and water if the fluid comes into
contact with skin.
- If fluid gets into eyes, immediately rinse with large
quantities of clear running water.
- A full safety and specification sheet can be obtained
by request.
The solar heat transfer fluid must be pumped into the
system.The pump can be electric or manual but must be
capable of producing a pressure of at least 2 bar.
The system should be thoroughly flushed to remove any
contaminants in the solar primary circuit prior to filling
with the heat transfer fluid
Potterton Solar - Solar Thermal Domestic Hot Water System3
Fig. 1
.0Commissioning of system
1
3
4
5
1
1.2Flushing the pipework
Before the system is commissioned the pipework must
be flushed to remove any contaminants. It is recommended
that this is done using the solar heat transfer fluid as it
will be impossible to fully drain all parts of the system.
Connect the flushing pipes to the fill & drain valve on
the safety group (Fig. 1 Item 1) and to the fill & drain
valve on the flow meter (Fig. 1 Item 2).
Fig. 2
2
6
7
Filling pump
Filter
Open the fill & drain valves.
Turn the slot of the adjusting screw (Fig. 1 Item 3) in the
return so the slot is vertical to open the non-return
valve.
Turn the left hand isolating valve with integral
thermometer in the flow (Fig. 1 Item 4) in the direction
indicated by the arrow (to a 45° position) to open the
non-return valve.
Ensure that the right hand isolating valve with integral
thermometer in the return (Fig. 1 Item 5) is open
indicated by the dot on the thermometer bezel being
at the top.
Turn the slot of the adjusting screw of the flow meter
(Fig. 1 Item 6) in the return vertically to open the flow
limiter (Fig. 1 Item 7).
Flush the solar primary pump by pumping the fluid into
the system via the fill and drain valve on the safety group.
Close right hand isolating valve (dot on thermometer
bezel at 9 o’clock position). Flush solar primary pipework
and panels via the fill and drain valve on the safety group.
If reusing flushed fluid ensure this is filtered before reintroducing into the system (see Fig. 2).
Fig. 3
Solar fluidSolar fluid
1.3Filling the pipework
Close the fill and drain valve (Fig. 3 Item 2) on the flow
meter. Open the righthand isolating valve (Fig. 3. Item 1)
with integral thermometer by turning so that the dot on
the bezel is at the top. Fill the solar primary system by
pumping in fluid until the system pressure reads 1.5 to
1
3
2
2.0 bar. Close the fill and drain valve (Fig. 3. Item 3) on
the safety group.
Potterton Solar - Solar Thermal Domestic Hot Water System4
2.0Commissioning of hydraulic station
2.1Check pressure in the solar primary
pipework
After flushing and filling the solar primary system with
eat transfer fluid the pressure must be checked.
h
Pressure test the system (6 bar). Observe the maximum
pressure ratings of all components concerned.
Check the solar heating system for leaks.
Close the fill and drain valve on the safety group.
Fig. 4
2.2Ensure the solar primary system is free
from air
Switch on the power supply to the solar differential
temperature controller.
2
Manually switch the circulation pump ON and OFF
via the solar differential temperature controller
(see section 3.1.7) to pump fluid around the solar
primary system.
1
Turn the pump off and open the airbleed screw on the
air separator (Fig. 4 Item 1). Bleed any air from the air
separator. If the system pressure drops top up by opening
the fill and drain valve (Fig. 4 Item 2) on the safety group
and pumping in more solar fluid to restore the pressure.
This must be repeated until the pressure remains stable.
2.3Setting the system pressure
During commissioning, the system pressure should be
0.7 bar above the static pressure (1 metre height
differential equals 0.1 bar). However, it must be at least
1.5 bar and no higher than 2.2 bar.
Determine the system pressure when the system is
cold (20°C).This should be recorded on the
Commissioning Record Sheet (page 21).
If the pressure is too low you should pump additional
heat transfer fluid into the system; the fill & drain valve
on the safety group (Fig. 4 Item 2) needs to be opened
for this purpose.When system pressure is correctly set,
ensure the fill and drain valve is closed and remove filling
hose from safety group.
Potterton Solar - Solar Thermal Domestic Hot Water System5
Fig. 5
.0Commissioning of hydraulic station
2
2
Table 1
Flow rate
(when system is cold)
Collectorsl/min
1approx. 2
2approx. 4
3approx. 6
1
2.4Checking and adjusting the flow rate
Adjust the flow rate when the system is cold (20°C)
(see Fig. 5).
The flow rate should be adjusted to give the optimum
flow rate depending on the number and type of
collector panels connected.
5
3
4
Turn the slot of the adjusting screw (Fig. 5 Item 1) below
the return temperature gauge horizontally to close the
non-return valve.
Turn the l.h. isolating valve with integral thermometer in
the flow (Fig. 5 Item 2) as far as it will go in the direction
indicated by the arrow to close the non-return valve (dot
on bezel on top).
Turn the slot of the adjusting screw (Fig. 5 Item 3) in the
return vertically to open the flow limiter on the flow
meter (Fig. 5 Item 4).
Manually operate the solar pump (see section 3.1.7).
Set the solar pump switch (Fig. 5 Item 5) so that the
required flow rate is achieved or exceeded with the
lowest possible setting.The flow limiter adjusting screw
(Fig. 5 Item 3) can be used to fine-tune the flow rate.
Depending on the number and type of collectors installed,
set the required flow rate from table (SeeTable 1).
Fig. 6
The float in the flow meter will indicate the circulation
flow rate through the flow meter sight glass.
Adjust screw of the flow limiter (Fig. 5 Item 3) with a
screwdriver, until the upper edge of the float in the sight
glass indicates the required flow rate.
Set manual pump operation to off.
1
3
2
2.5Installation of the thermal insulation
Refit the controller mounting moulding (Fig. 6 Item 1)
onto the rear moulding.
Push the front thermal insulation (Fig. 6 Item 2) against
the rear thermal insulation section (Fig. 6 Item 3) until it
clips into place.
Potterton Solar - Solar Thermal Domestic Hot Water System6
1
2
4
35
Fig. 7
.0Commissioning of solar controller
3
3.1Overview of display and operating elements
(see Fig. 7).
NumberDescription
1Display with graphic symbols
2Control button scroll upwards / +
3Control button exit / break-off
4
5Control button choice / confirmation
3.1.1 Explanation of graphic symbols
Graphic symbolDescriptionIndication in operation
Main Menu
Menu "Info"
Control button scroll downwards / –
Menu "Programming"
Menu "Manual operation"
Menu "Basic adjustment"
Graphic symbolDescriptionIndication in operation
Indicator values
dTTemperature difference
minMin valueAppears when minimum values are indicated
maxMax valueAppears when maximum values are indicated
minTimeframe 1 startAppears when the differential controller is active
0:00(timeframe 1-3) or tube collector is active (timeframe 4)
1
MaxTimeframe 1 stopAppears when the differential controller is active
23:59(timeframe 1-3) or tube collector is active (timeframe 4)
1
5 x 7 segment display.Display of all values, display flashes when
Presentation of figures 00000 to 99999a value is changed
When symbol flashes it is possible for it to be
selected. If that symbol is chosen by pressing the
button, the symbol remains static (not flashing).
ºCTemperature in Celsius
KTemperature difference in Kelvin
hOperating hours
kWhProductivity indication in kWh
Potterton Solar - Solar Thermal Domestic Hot Water System7
.0Commissioning of solar controller
!
ok?
3
Graphic symbolDescriptionIndication in operation
Measuring points assignment
Temperature measuring point collector array 1
Temperature measuring point collector array 2
Temperature measuring point storage tank 1 lower
(storage tank 1 charging)
Temperature measuring point storage tank lower
(storage tank 2 charging)
Temperature measuring point collector - return
Temperature measuring point storage tank upper
(thermostat function)
Antifreezing sensor or universal temperatures
measuring point (T6) (no sensor monitoring)
2nd temperature differential controller
Operating hours, energy productivity measurement
Status indication
Solar circulation pumpSymbol revolves when solar circulation pump is on
Switch output 1 is activeAppears when switch output 1 is active (on)
Switch output 2 is activeAppears when switch output 2 is active (on)
Switch output 3 is activeAppears when switch output 3 is active (on)
Reference to system faultDisplay flashes when a fault occurs in the system
Safety query for value changes which are to be stored
Input value can be either
rejected oraccepted
Potterton Solar - Solar Thermal Domestic Hot Water System8
ok?
ButtonFunctionDescription
"Up"• Step up through menu
"+"• Value change: Increase of the indicated value by 1, holding the button down will
automatically increase values
"Call"• Call up of main menu, step down through menu
"Down"• Value change: Decrease of the indicated value by 1, holding the button down will
automatically decrease values
"Scroll left"• In main menu, scrolls to the left
"Exit"• Exit current menu
• Exit menu point
"Break-off"• Break-off value change without storing
"Scroll right"• In main menu, scrolls to the right
"Choice"• Choosing one menu point
"Confirmation"• Confirmation of value change, stores value change
3.1.2 Button function
Operation and programming of the Potterton Solar
differential temperature controller is by means of 4 operating
buttons.By means of pressing these buttons you can:
• recall display values
• carry out controller adjustments
The graphic symbols on the display step through the
operating structure and show clearly the current menu
oints, display values or parameters.
p
Operating buttons have the following functions:
Example of setting procedure
ButtonFunctionIcon after operation stepDescription
"Exit"
"Scroll right"
"Call"
"Down"
"Choice"
"Up"
"Confirm"
Max
65°C
dT min
3K
dT min
3K
dT min
4K
dT min
4K
Currently selected menu icon will flash
Exit menu's "Info"
Choosing menu "Programming"
Chosen menu icon will flash
Call up menu "Programming", the first menu
point appears
Repeated pressing up to menu point
"S1 dTmin" appears
Choosing presented character
When chosen, value to be changed will flash
Increase of parameter
Confirmation of the character
"ok?" icon will flash
"Confirm"
"Exit"
"Scroll left"
"Call"
Potterton Solar - Solar Thermal Domestic Hot Water System9
4K
60°C
dT min
Storing of the parameter
When stored, icon will stop flashing
Exit menu "Programming"
Currently selected menu icon will flash
Choosing menu "Info"
Chosen menu icon will flash
Call up menu "Info"
MenuDescription
InfoMain menu for automatic regulation of solar system
• Indication of current measured values
• Indication of system condition
• Indication of error messages
• Indication of operating hours and energy productivity (if installed)
ProgrammingChanges to programmable values (parameters)
.0Commissioning of solar controller
3
3.1.3 Operating menu
To make the operation of the controller clear, operating
nd display functions are divided into 4 main menus.
a
These are
• Info
• Programming
• Manual operation
• Basic adjustment
Each active menu is shown in the upper line of the
display by its corresponding icon.
Note: Changes can affect systemfunctions!
Manual operationSwitching on and off connected pumps / valves by hand. Overrides automatic regulation.
Basic adjustmentInformation about basic adjustment for system function
Important
Adjustments and changes in this menu must be carried out only by a competent
installer or service engineer.
Potterton Solar - Solar Thermal Domestic Hot Water System10
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.