Benchmark places responsibilities on both manufacturers and installers. The
purpose is to ensure that customers are provided with the correct equipment for
their needs, that it is installed, commissioned and serviced in accordance with the
manufacturer’s instructions by competent persons and that it meets the
requirements of the appropriate Building Regulations. The Benchmark Checklist
can be used to demonstrate compliance with Building Regulations and should be
provided to the customer for future reference.
Installers are required to carry out installation, commissioning and servicing work
in accordance with the Benchmark Code of Practice which is available from the
Heating and Hotwater Industry Council who manage and promote the Scheme.
Visit www.centralheating.co.uk for more information.
Building Regulations and the Benchmark Commissioning
Checklist
Building Regulations (England & Wales) require notification of
the installation of a heating appliance to the relevant Local
Authority Building Control Department. From 1 April 2005 this
can be achieved via a Competent Persons Self Certification
Scheme as an option to notifying the Local Authority directly.
Similar arrangements will follow for Scotland and will apply in
Northern Ireland from 1 January 2006.
The Health & Safety Executive operates the ‘Gas Safe Register’,
a self-certification scheme for gas heating appliances.
These arrangements represent a change from the situation
whereby compliance with Building Regulations was accepted as
being demonstrated by completion of the Benchmark Logbook
(which was then left on site with the customer).
With the introduction of Self Certification Schemes, the
Benchmark Logbook is being withdrawn. However, a similar
document in the form of a commissioning checklist and service
interval record is incorporated at the back of these instructions.
This company is a member of the Benchmark initiative and fully
supports the aims of the programme. Its aim is to improve the
standards of installation and commissioning of central heating
systems in the UK and to encourage the regular servicing of all
central heating systems to ensure safety and efficiency.
Building Regulations require that installations should comply
with manufacturer's instructions. It is therefore important that
the commissioning checklist is completed by the installer. The
relevant section of Building Regulations only relates to
dwellings. Therefore the checklist only applies if the appliance is
being installed in a dwelling or some related structure.
Applications for the copyright owner’s permission to reproduce or make other
use of any part of this publication should be made, giving details of the proposed
use, to the following address:
The Company Secretary, Baxi Heating UK Limited,
Brooks House, Coventry Road, Warwick. CV34 4LL
Full acknowledgement of author and source must be given.
WARNING: Any person who does any unauthorised act in relation to a
copyright work may be liable to criminal prosecution and civil claims for damages.
0086
The flowchart opposite gives guidance for installers on the
process necessary to ensure compliance with Building
Regulations.
IMPORTANT - Installation, Commissioning, Service & Repair
This appliance must be installed in accordance with the manufacturer’s instructions and
the regulations in force. Read the instructions fully before installing or using the
appliance.
In GB, this must be carried out by a competent person as stated in the Gas Safety
(Installation & Use) Regulations.
Definition of competence: A person who works for a Gas Safe registered company
and holding current certificates in the relevant ACS modules, is deemed competent.
In IE, this must be carried out by a competent person as stated in I.S. 813 “Domestic
Gas Installations”.
The addition of anything that may interfere with the normal operation of the appliance
without express written permission from the manufacturer or his agent could invalidate
the appliance warranty. In GB this could also infringe the Gas Safety (Installation and
Use) Regulations.
Warning - Check the information on the data plate is compatible with local supply
conditions.
All Gas Safe registered engineers carry an ID card with their licence number and a
photograph. You can check your engineer is registered by telephoning
0800 408 5500 or online at www.gassaferegister.co.uk
This company declare that no substances harmful to
health are contained in the appliance or used during
appliance manufacture.
The appliance is suitable only for installation in GB and IE
and should be installed in accordance with the rules in
force, and only used in a suitably ventilated location.
In GB, the installation must be carried out by a Gas Safe
Registered Installer. It must be carried out in accordance
with the relevant requirements of the:
• Gas Safety (Installation & Use) Regulations.
• The appropriate Building Regulations either The Building
Regulations, The Building Regulations (Scotland), Building
Regulations (Northern Ireland).
• The Water Fittings Regulations or Water Byelaws in
Scotland.
• The Current I.E.E. Wiring Regulations.
Where no specific instructions are given, reference should
be made to the relevant British Standard Code of Practice.
In IE, the installation must be carried out by a competent
Person and installed in accordance with the current edition
of I.S. 813 ‘Domestic Gas Installations’, the current Building
Regulations and reference should be made to the current
ETCI rules for electrical installation.
All systems must be thoroughly flushed and treated
with inhibitor (see section 6.2).
The boiler meets the requirements of Statutory Instrument “ The Boiler (Efficiency)
o
Regulations 1993 N
3083” and is deemed to meet the requirements of Directive
92/42/EEC on the energy efficiency requirements for new hot water boilers fired with
liquid or gaseous fuels:-
Type test for purpose of Regulation 5 certified by:
Notified Body 0087.
Product/Production certified by:
Notified Body 0086.
For GB/IE only.
Codes of Practice, most recent version should be used
In GB the following Codes of Practice apply:
StandardScope
BS 6891Gas Installation.
BS 5482 Part 1Butane & Propane Gas Installation
BS 5546Installation of hot water supplies for domestic
BS EN 12828Heating systems in buildings.
BS EN 12831Heating systems in buildings - Calculation of load.
BS EN 14336Installation & commissioning of water based
BS 6798Installation of gas fired hot water boilers.
BS 5440 Part 1Flues.
BS 5440 Part 2Ventilation.
BS 7074Expansion vessels and ancillary equipment for
BS 7593Treatment of water in domestic hot water
In IE the following Codes of Practice apply:
StandardScope
I.S. 813Domestic Gas Installations.
The following standards give valuable additional information;
BS 5546Installation of hot water supplies for domestic
BS EN 12828Heating systems in buildings.
BS EN 12831Heating systems in buildings - Calculation of load.
BS EN 14336Installation & commissioning of water based
BS 7074Expansion vessels and ancillary equipment for
BS 7593Treatment of water in domestic hot water
purposes.
heating systems.
sealed water systems.
central heating systems.
purposes.
heating systems.
sealed water systems.
central heating systems.
1. The Potterton Gold FSB 30 HE is a gas fired room
sealed fan assisted condensing central heating boiler.
2. The maximum output of the boiler is 30.18 kW (Non Condensing) 32.61 kW (Condensing).
3. The boiler is designed for use on Natural Gas (G20)
only.
4. The boiler is suitable for fully pumped open vented and
sealed systems, providing heating and hot water.
5. A label giving details of the model, serial number and
Gas Council number is situated on the rear of the drop
down facia panel (Fig. 1).
6. The boiler data badge is positioned on the air box door
(Fig. 2).
7. The boiler is intended to be installed in residential /
commercial / light industrial E.M.C. environments on a
governed meter supply only.
Air Box Door
Case Securing Screws
8. The boiler must be installed with one of the purpose
designed flues such as the standard horizontal flue kit, part
no 236921.
1.2Important Information
Man-made mineral fibre
• Some component parts of this boiler (insulation pads,
gaskets and rope seals) are manufactured from man-made
mineral fibre.
• Prolonged or excessive exposure to this material may
result in some irritation to the eyes, skin or respiratory
tract.
• It is advisable to wear gloves when handling these items.
• Irritant dust will only be released from the items if they
are broken up or subjected to severe abrasion. In these
instances a suitable dust mask and goggles should be
worn.
• Always thoroughly wash hands after installation,
servicing or changing components.
• When disposing of any items manufactured from manmade mineral fibre care must be exercised.
• If any irritation of the eyes or severe irritation of the skin
is experienced seek medical attention.
Standard Flue Kit 850mm (inc. elbow)236921
Extended Flue Kit - 1.75M ( inc. elbow)5111457
Flue Plume Deflector Kit248167
Terminal Guard (suitable for use with above)248484
FLUE EXTENSION KITS (110/70)
Flue Extension 250mm241692
Flue Extension 500mm241694
Flue Extension 1000mm
Flue Bend x 2 - 45°
1. Switched Live On: When switched live is supplied to
the boiler and the flow temperature is less than the set
point the sequence below commences.
2. Flow Switch: After 10 seconds if the flow switch has
made then fan pre-purge occurs. After 10 seconds if
the flow switch has not made then anti-cycle occurs.
3. Fan Pre-Purge: The flow switch is made and the fan
is on while the spark generator and gas valve are off.
After 5 seconds ignition occurs.
4. Ignition: The flow switch is made, fan, spark
generator and gas valve are on. If a flame is detected
then burner on occurs. If a flame is not detected within
5 seconds and less than 5 ignition attempts have been
made then fan purge occurs. If a flame is not detected
within 5 seconds and 5 ignition attempts have been
made then ignition lockout occurs.
5. Burner On: The flow switch is made, fan and gas
valve are on while the spark generator is off. Flow
temperature is controlled by varying the fan speed (and
thereby the gas rate) to achieve optimum operation. If
the flow temperature is greater than the set point or
the TRVs all shut down then fan post purge occurs.
Flame Detected ?
shut or Flow temperature
greater than set point ?
Fan Post Purge.
YES
YES
Burner On.
All TRVs
YES
5 second
All TRVs
shut down ?
Ignition done and
5 attempts made ?
YES
Ignition
Lockout.
6. Fan Post Purge: The fan is on while the spark
generator and gas valve are off. After 5 seconds if the
TRVs are shut down then anti-cycle occurs.
7. Anti-cycle: The fan, spark generator and gas valve
are off.
8. Ignition Lockout: The fan, spark generator and gas
valve are off. The boiler can only be reset by manually
using the reset button.
9. Condensate Pump: Condensate accumulates in a
reservoir within the pump assembly. The pump may
run at any time, independent of boiler operation, to
discharge the condensate to drain.
Both Sides- 5mm
Above Casing- 15mm
Above Casing
Under fixed worktop (It is recommended that any
worktop is removable)- 25mm
Front (For Servicing)- 500mm
Front (In Operation)- 5mm
Electrical Supply230V~ 50Hz
The boiler must be connected to an earthed
supply. A permanent and switched live are
required. The boiler has a 4 wire connection.
Power Consumption 80W
External Fuse Rating 3A
Internal Fuse Rating (BS 4265)
Fuse3.15 AT (PCB)
Electrical Protection IPXX
Water Content
litres2.6
Static Head
max30 metres
min1 metre
Low Head 0.2m min
System Detail
Fully pumped open vented & sealed systems.
No bypass required.
Controls
boiler thermostat, safety thermostat,
flow switch, electronic flame sensing,
temperature protection thermostat &
condensate blockage and level sensors
This value is used in the UK Government’s Standard
Assessment Procedure (SAP) for energy rating of
dwellings. The test data from which it has been
calculated has been certified by 0087.
1. The boiler is suitable for use with open vent fully
pumped systems and sealed systems .
The following conditions should be observed on all
systems:
•The static head must not exceed 30m of water.
•The boiler must not be used with a direct cylinder.
•Drain cocks should be fitted to all system low points.
•All gas and water pipes and electrical wiring must be
installed in a way which would not restrict the servicing
of the boiler.
•Position isolating valves as close to circulating pump as
possible.
6.2Treatment of Water Circulating
Systems
1. All recirculatory water systems will be subject to
corrosion unless they are flushed and an appropriate
water treatment is applied. To prevent this, follow the
guidelines given in BS 7593 “Treatment of Water in
Domestic Hot Water Central Heating Systems” and the
treatment manufacturers instructions.
2. Treatment must involve the use of a proprietary
cleanser, such as Sentinel X300 or X400, or Fernox F3
and an inhibitor such as Sentinel X100 or Fernox MB-1.
3. Full instructions are supplied with the products, for
further information contact Sentinel (0800 389 4670) or
Fernox (0870 870 0362).
Failure to flush and add inhibitor to the system will
invalidate the appliance warranty.
4. It is important to check the inhibitor concentration after
installation, system modification and at every service in
accordance with the inhibitor manufacturer’s instructions.
(Test kits are available from inhibitor stockists.)
5. For information or advice regarding any of the above
contact Technical Enquiries 0844 871 1555.
1. The sizes of flow and return pipes from the boiler
should be determined by normal methods, according to
the requirements of the system.
2. The connection tails for the boiler are 28mm diameter.
The 28mm section of the tails can be cut back to 22mm if
required.
3. The flow & return tails are push - fit ‘O’ ring
and clip connections within the boiler case.
4. A 20 °C drop in temperature across the system is
recommended for condensing boilers. Existing radiators
may be oversized and so allow this, but where radiator
sizing is marginal it may be advisable to retain a system
temperature drop of 11°C.
5. In systems using non-metallic pipework it is necessary
to use copper pipe for the boiler Flow and Return. The
copper must extend at least 1 metre from the boiler and
include any branches (Fig. 9).
Boiler Air
Vent
Fig. 10
Fig. 11
Boiler
Typical Low Head Installation
45°
15mm
Cold
Feed
22mm
Open Vent
400mm
Min Head
150mm
Max
Return
500mm
1000mm
Min
If Conditions Require,
This System Possible
Pump
6. This boiler does not require a bypass.
6.4Low Head Installation
1. Using a close couple arrangement the minimum head is
as shown in the diagrams (Figs. 10 & 11) subject to the
following conditions:
a) The pump being adjusted to give a 20°C drop across
the boiler.
b) The pump must be fitted on the flow.
c) The pump must be fitted in accordance with the
pump manufacturer's instructions.
d) The open vent pipe must be taken up from a tee in a
horizontal section of the flow pipe.
Flow
2. For heads below 400mm then an alternative utilising a
combined vent and feed pipe may be connected (Fig. 12).
This must be a minimum of 22mm diameter. It is
recommended that an air separator is fitted when using a
combined feed and vent pipe.
This boiler requires a permanent live for
operation of the condensate pump and frost
protection.
b
w
Cylinder
Stat
1
C2
Y Plan
Diverter
Valve
gr
o
1. To comply with Part L1 of the Building Regulations the
heating system into which the boiler is installed should
include the following:
a) zone controls
b) timing controls
c) boiler control interlocks
System Control
S/LNE
P/L
Wiring Centre
Timer
L
N
CH on
HW on
HW off
LNE
Pump
Y Plan, Room Thermostat System, CH Interlocked By Room Thermostat,
DHW Interlocked By Cylinder Thermostat
At least the Radiator(s) near the Room Thermostat not TRV’d
Pump run from Switched Live
Boiler Connection
(4 Core Wire)
2. Such a system needs to be fully pumped and must
provide independent temperature and time control to
both the heating and hot water circuits and have a boiler
and system pump interlock.
3. The boiler should be controlled so that it operates on
demand only. Where it is proposed to effect control by
thermostatic radiator valves a room thermostat should
also be provided to switch off the boiler when there is
no demand for heating.
S Plan, Room Thermostat System, CH Interlocked By Room Thermostat,
DHW Interlocked By Cylinder Thermostat
At least the Radiator(s) near the Room Thermostat not TRV’d
Pump run from Switched Live
Vessel Charge Pressure = 1.0 bar
Initial System Pressure = 1.5 bar
Then :-
75 x 0.152 = 11.4 litres
Expansion Vessel Volume
NOTE
Where a vessel of the calculated size is not obtainable then
the next available larger size should be used.
3 Litre
Top Up Bottle
(if required)
Radiator
Circuit
Multiply Total
Water Content Of
System By (Litres)
0.067
0.112
0.207
0.441
0.087
0.152
0.330
0.125
0.265
6.0System Details
6.7Sealed Systems (Fig. 13)
1. SAFETY VALVE - A safety valve complying with the
requirements of BS 6750 Part 1 must be fitted close to
the boiler on the flow pipe by means of a horizontal or
vertically upward connection with no intervening valve
or restrictions and should be positioned to facilitate
testing. The valve should be pre-set and non-adjustable
to operate at a pressure of 3 bar (45 Ibf/in
arranged to discharge any water or steam through a pipe
to a safe outlet position.
2. PRESSURE GAUGE - A pressure gauge of minimum
range 0-4 bar (0-60 Ibf/in
2
) with a fill pressure indicator
must be fitted to the system, preferably at the same
point as the expansion vessel in an easily visible position.
3. EXPANSION VESSEL - An expansion vessel
complying with the requirements of BS 4814 must be
fitted to the system by means of a connection close to
the inlet side of the circulating pump in accordance with
the manufacturers instructions, the connecting pipe being
unrestricted and not less than 15mm (
The volume of the vessel should be suitable for the
system water content and the nitrogen or air charge
pressure should not be less than the system static head
(See Table. 1).
Further details of sealed system design can be obtained
from BS 5449 and the British Gas publication entitled
'Specifications for Domestic Wet Central Heating
Systems'.
4. FILLING POINT - A filling point connection on the
central heating return pipework must be provided to
facilitate initial filling and pressurising and also any
subsequent water loss replacement / refilling. The sealed
primary circuits may be filled or replenished by means of
a temporary connection between the primary circuit and
a supply pipe provided a ‘Listed’ double check valve or
some other no less effective backflow prevention device
is permanently connected at the inlet to the circuit and
the temporary connection is removed after use. The
filling method adopted must be in accordance with all
relevant water supply regulations and use approved
equipment.
Your attention is drawn to, for GB: Guidance G24.2 and
recommendation R24.2 of the Water Regulations Guide.
for IE: the current edition of I.S. 813 “Domestic Gas
Installations”.
5. MAKE UP SYSTEM - A method of replacing water
lost from the system should be provided either by
means of a make up vessel of not more than 3 litres (5
pints) capacity, mounted above the highest point of the
system, or by re-pressurisation of the system.
6. VENTING - A method of venting the system during
filling and commissioning must be provided by fitting
automatic air vents or by venting manually.
7. HOT WATER STORAGE - The hot water storage
vessel must be of the indirect coil type.
8. COMPONENTS - All components used in the system
must be suitable for operation at 110°C (230°F) and at
the pressure allowed by the safety valve.
CH
Return
Zone 1
Zone 2
Window
Recess
Zone 2
7.0Site Requirements
7.1Location
NOTE: Due to the high efficiency of the boiler a
plume of water vapour will be discharged from the
flue. This should be taken into account when siting
the flue terminal.
1. The boiler must be fitted on a suitable flat and level
surface capable of supporting the weight. Any wall behind
the boiler must be at 90° to the floor to allow case top
cover to fit correctly.
2. The flue must pass through an outside wall or roof and
discharge to atmosphere in a position permitting
satisfactory removal of combustion products and
providing an adequate air supply.
Fig. A
Zone 1
Zone 0
Zone 0
Window
Recess
Zone 2
0.6 m
In GB Only
Window Recess
Zone 2
Zone 2
2.25 m
Ceiling
Outside Zones
3. The boiler should be fitted within the building unless
otherwise protected by a suitable enclosure i.e. garage or
outhouse.
4. The boiler incorporates a frost protection device. This
will only protect the boiler. To ensure protection of the
system pipework and components it is recommended to
incorporate an appropriate device within the system
controls.
5. If the boiler is fitted in a room containing a bath or
shower, it can only be fitted in Zone 3, (Figs. A & B
shows zone dimensions for a bathtub. For other
examples refer to the Current I.E.E. Wiring Regulations).
Reference must be made to the relevant requirements:In GB this is the current I.E.E. Wiring Regulations and
Building Regulations.
In IE reference should be made to the current edition of
I.S. 813 “Domestic Gas Installations” and the current
ETCI rules.
6. If the boiler is to be fitted into a building of timber
frame construction then reference must be made to the
current edition of Institute of Gas Engineers Publication
IGE/UP/7 (Gas Installations in Timber Framed Housing).
1. Where the boiler is installed in a cupboard or
compartment, no air vents are required for cooling
purposes providing that the minimum dimensions below
are maintained.
Width400mm
Height875mm
Depth525mm
2. Any compartment should be large enough to house
the boiler only.
15
5mm Min
390mm
5mm Min
15mm Min
(25mm if under
non removable
worktop)
7.0Site Requirements
7.3Clearances (Figs. 15 &16)
1. These dimensions include the necessary clearances
around the boiler for case removal, spanner access and air
movement. Additional clearances may be required for the
passage of pipes around local obstructions such as joists
running parallel to the front face of the boiler. For side flue
installations also See Section 8.1, Figs. 20 & 21.
2. It is recommended that any worktop is removable for
servicing access.
Fig. 15
850mm
7.4Gas Supply
1. Check that the information concerning the state of
adjustment given on the data plate is compatible with local
supply conditions.
2. The gas installation should be in accordance with the
relevant standards. In GB this is BS 6891. In IE this is the
current edition of I.S. 813 “Domestic Gas Installations”.
3. The connection to the boiler is a 15mm tail on the gas
service cock. The tail protrudes through the boiler rear
panel and is protected by a transit bracket which may be
removed to aid connection.
4. Ensure that the pipework from the meter to the boiler
is of adequate size. (If the boiler is further than 3 metres
from the Gas Meter 22mm pipe should be used). Do not
use pipes of a smaller diameter than the boiler gas
connection.
7.5Electrical Supply
1. External wiring must be correctly earthed, polarised and
in accordance with relevant regulations/rules. In GB this is
the current I.E.E. Wiring Regulations. In IE reference
should be made to the current edition of ETCI rules.
NOTE: “The method of connection to the electricity
supply must facilitate complete electrical isolation of the
appliance and system”.
Connection may be via a fused double-pole isolator with a
contact separation of at least 3mm in all poles, which mustbe in an accessible position to the user and serve the
boiler and system controls only.
There is no method of isolating the boiler at the user
interface.
3. Four core cable is required to supply the boiler as a
permanent live is necessary for the operation of the
condensate pump and frost protection.
520mm
In Operation
7.0Site Requirements
4
3
2
Head (metres)
1
0
1.5
Min. radius 100mm
Point ‘A’
Condensate Pump Flow Graph
2
2.5
Flow (l/min)
3.5
3
Gravity Drain min. fall 3°
7.6Condensate Drain - General
Failure to install the condensate discharge pipework
correctly will affect the reliable operation of the boiler.
1. Ensure the discharge of condensate complies with any
national or local regulations in force.
BS 6798 & Part H1 of the Building Regulations give further
guidance.
2. If any further drain pipe is required (additional to that supplied
with the boiler), it should be run in a proprietary material
e.g. PVC, PVC-U, ABS, PVC-C or PP.
4
3. Metal pipework is NOT suitable for use in condensate
discharge systems.
4. Any pipe fitted externally must be kept as short as possible to
minimise the potential of freezing and must be insulated using
waterproof material.
5. When discharging condensate into a soil stack or waste pipe
the effects of existing plumbing must be considered.
7.7Condensate Disposal
Fig. A
Boiler
Max. Head
3 metres
Note: The point of discharge from
the pumped length of condensate
pipe (point ‘A’) must not be below
the level of the pump, whether
discharging direct into a drain or
into an additional gravity drain.
Alternative Horizontal
Discharge
10mm PVC Pipe
(8.5mm I.D.)
Securing Clip
8.5mm Ø O.D.
1. This boiler incorporates an automatic pumped condensate
system. See the graph opposite for available pump flow rates.
2. 3.5 metres of flexible 10mm PVC pipe are supplied with the
boiler. 0.5 metres of this length remains coiled within the boiler
to allow removal of the pump assembly. This must not be
uncoiled to provide extra length.
3. A fitting and securing clip (Fig. B) to accept the 10mm PVC
pipe and connect to 21.5mm overflow pipe is also supplied.
4. The 10mm pipe can be routed to a maximum of 3 metres
vertically and then discharge via gravity or be routed horizontally
(Fig. A). A combination of vertical and horizontal runs is
permissible.
5. The pipe must be supported, either using suitably spaced clips
or run within larger diameter pipe. When using clips take care
not to deform the pipe.
6. When routing the pipe through a wall it must be suitably
sleeved. Also the pipe must not be exposed to sources of heat,
and should be protected in locations where it may be damaged.
7. The pipe should be routed so that any sharp bends, dips and
loops are avoided. A minimum radius of 100mm is
recommended for any bends. No slope is necessary and air
breaks are not required on the pumped part of the condensate
run.
8. If the boiler is fitted in an unheated location the entire length
of condensate pipe should be treated as external, and run within
insulated larger diameter pipe.
17
7.0Site Requirement
10°
10°
Termination via internal discharge branch e.g
sink waste - downstream
Direct Connect Fitting
Sink
From Boiler
Fig. C
Pipe must terminate
above water level but
below surrounding surface
From Boiler
Branch of Tee to be
± 10° from vertical
Termination to an internal soil and vent pipe
Direct Connect Fitting
Min. 450mm
Fig. D
7.7Condensate Disposal (cont.)
9. Ensure that the condensate can discharge freely (without
blockage or restriction of the pipe) into the drain.
10. Examples are shown of condensate pipe methods of
termination:-
i) via an internal discharge branch
(e.g. sink waste) - Fig. C.
ii) to an internal or external soil and vent pipe -
Fig. D.
iii) to a drain or gully - Fig. E. Ensure that the
condensate can discharge freely (without
blockage or restriction of the pipe) into the
drain.
iv) to a soakaway - Fig. F.
Termination to a drain or gully
From Boiler
Fig. E
Pipe must terminate above
water level but below
surrounding surface
Termination to a purpose made
soak-away
From Boiler
Fig. F
500mm Min
Holes in the soak-away must
face away from the building