Baxi Potterton Gold FSB 30 HE User Manual

Page 1
Installation & Service Instructions
Gold
FSB 30 HE
Floor Standing
Condensing Boiler
These instructions include the Benchmark Commissioning Checklist
and should be left with the user for safe keeping.
© Baxi Heating UK Ltd 2011
Page 2
Natural Gas
Potterton Gold FSB 30 HE
G.C. No. 41 592 32
The Benchmark Scheme
Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers are provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with the manufacturer’s instructions by competent persons and that it meets the requirements of the appropriate Building Regulations. The Benchmark Checklist can be used to demonstrate compliance with Building Regulations and should be provided to the customer for future reference.
Installers are required to carry out installation, commissioning and servicing work in accordance with the Benchmark Code of Practice which is available from the Heating and Hotwater Industry Council who manage and promote the Scheme. Visit www.centralheating.co.uk for more information.
Building Regulations and the Benchmark Commissioning Checklist
Building Regulations (England & Wales) require notification of the installation of a heating appliance to the relevant Local Authority Building Control Department. From 1 April 2005 this can be achieved via a Competent Persons Self Certification Scheme as an option to notifying the Local Authority directly. Similar arrangements will follow for Scotland and will apply in Northern Ireland from 1 January 2006.
The Health & Safety Executive operates the ‘Gas Safe Register’, a self-certification scheme for gas heating appliances.
These arrangements represent a change from the situation whereby compliance with Building Regulations was accepted as being demonstrated by completion of the Benchmark Logbook (which was then left on site with the customer).
With the introduction of Self Certification Schemes, the Benchmark Logbook is being withdrawn. However, a similar document in the form of a commissioning checklist and service interval record is incorporated at the back of these instructions.
This company is a member of the Benchmark initiative and fully supports the aims of the programme. Its aim is to improve the standards of installation and commissioning of central heating systems in the UK and to encourage the regular servicing of all central heating systems to ensure safety and efficiency.
Building Regulations require that installations should comply with manufacturer's instructions. It is therefore important that the commissioning checklist is completed by the installer. The relevant section of Building Regulations only relates to dwellings. Therefore the checklist only applies if the appliance is being installed in a dwelling or some related structure.
© Baxi Heating UK Ltd 2011 All rights reserved. No part of this publication may be reproduced or transmitted in any form or by any means, or stored in any retrieval system of any nature (including in any database), in each case whether electronic, mechanical, recording or otherwise, without the prior written permission of the copyright owner, except for permitted fair dealing under Copyrights, Designs and Patents Act 1988.
Applications for the copyright owner’s permission to reproduce or make other use of any part of this publication should be made, giving details of the proposed use, to the following address:
The Company Secretary, Baxi Heating UK Limited, Brooks House, Coventry Road, Warwick. CV34 4LL
Full acknowledgement of author and source must be given.
WARNING: Any person who does any unauthorised act in relation to a copyright work may be liable to criminal prosecution and civil claims for damages.
0086
The flowchart opposite gives guidance for installers on the process necessary to ensure compliance with Building Regulations.
ISO 9001
FM 00866
© Baxi Heating UK Ltd 2011
2
Page 3
Choose Building
Regulations Notification
Route
Installer Notification Guidelines
Competent Person's
Self Certification Scheme
Install and Commission this appliance to manufacturer's
instructions
Complete the
Benchmark Checklist
If you notify via the ‘Gas Safe
Register’, the register will issue
the Building Regulations
certificate on members’ behalf
Building Control
Contact your relevant Local
Authority Building Control
(LABC) who will arrange
an inspection or contact a government approved
inspector
Install and Commission this appliance to manufacturer's
instructions
Scheme Members only
Call ‘Gas Safe Register’ on:
0800 408 5577
or log onto:
www.gassaferegister.co.uk
within 10 days
You must ensure that the
certificate number issued by
the ‘Gas Safe Register’ is written
onto the Benchmark Checklist
‘Gas Safe Register’ will issue a
Building Regulations Compliance
Certificate to the property owner
and inform the relevant LABC
Complete the
Benchmark Checklist
LABC will record the data
and will issue a
certificate of compliance
© Baxi Heating UK Ltd 2011
3
Page 4
Legislation
IMPORTANT - Installation, Commissioning, Service & Repair
This appliance must be installed in accordance with the manufacturer’s instructions and the regulations in force. Read the instructions fully before installing or using the appliance.
In GB, this must be carried out by a competent person as stated in the Gas Safety (Installation & Use) Regulations.
Definition of competence: A person who works for a Gas Safe registered company and holding current certificates in the relevant ACS modules, is deemed competent.
In IE, this must be carried out by a competent person as stated in I.S. 813 “Domestic Gas Installations”.
The addition of anything that may interfere with the normal operation of the appliance without express written permission from the manufacturer or his agent could invalidate the appliance warranty. In GB this could also infringe the Gas Safety (Installation and Use) Regulations.
Warning - Check the information on the data plate is compatible with local supply conditions.
All Gas Safe registered engineers carry an ID card with their licence number and a photograph. You can check your engineer is registered by telephoning 0800 408 5500 or online at www.gassaferegister.co.uk
This company declare that no substances harmful to health are contained in the appliance or used during appliance manufacture.
The appliance is suitable only for installation in GB and IE and should be installed in accordance with the rules in force, and only used in a suitably ventilated location.
In GB, the installation must be carried out by a Gas Safe Registered Installer. It must be carried out in accordance with the relevant requirements of the:
• Gas Safety (Installation & Use) Regulations.
• The appropriate Building Regulations either The Building Regulations, The Building Regulations (Scotland), Building Regulations (Northern Ireland).
• The Water Fittings Regulations or Water Byelaws in Scotland.
• The Current I.E.E. Wiring Regulations.
Where no specific instructions are given, reference should be made to the relevant British Standard Code of Practice.
In IE, the installation must be carried out by a competent Person and installed in accordance with the current edition of I.S. 813 ‘Domestic Gas Installations’, the current Building Regulations and reference should be made to the current ETCI rules for electrical installation.
All systems must be thoroughly flushed and treated with inhibitor (see section 6.2).
The boiler meets the requirements of Statutory Instrument “ The Boiler (Efficiency)
o
Regulations 1993 N
3083” and is deemed to meet the requirements of Directive 92/42/EEC on the energy efficiency requirements for new hot water boilers fired with liquid or gaseous fuels:-
Type test for purpose of Regulation 5 certified by: Notified Body 0087.
Product/Production certified by: Notified Body 0086.
For GB/IE only.
Codes of Practice, most recent version should be used
In GB the following Codes of Practice apply: Standard Scope
BS 6891 Gas Installation. BS 5482 Part 1 Butane & Propane Gas Installation BS 5546 Installation of hot water supplies for domestic
BS EN 12828 Heating systems in buildings. BS EN 12831 Heating systems in buildings - Calculation of load. BS EN 14336 Installation & commissioning of water based
BS 6798 Installation of gas fired hot water boilers. BS 5440 Part 1 Flues. BS 5440 Part 2 Ventilation. BS 7074 Expansion vessels and ancillary equipment for
BS 7593 Treatment of water in domestic hot water
In IE the following Codes of Practice apply: Standard Scope
I.S. 813 Domestic Gas Installations. The following standards give valuable additional information; BS 5546 Installation of hot water supplies for domestic
BS EN 12828 Heating systems in buildings. BS EN 12831 Heating systems in buildings - Calculation of load. BS EN 14336 Installation & commissioning of water based
BS 7074 Expansion vessels and ancillary equipment for BS 7593 Treatment of water in domestic hot water
purposes.
heating systems.
sealed water systems. central heating systems.
purposes.
heating systems. sealed water systems. central heating systems.
4
© Baxi Heating UK Ltd 2011
Page 5
Contents
Section Page
1.0 Introduction 6
2.0 General Layout 7
3.0 Boiler Operation 8
4.0 Technical Data 9
5.0 Dimensions and Fixings 10
6.0 System Details 11
7.0 Site Requirements 15
8.0 Flue Options 20
9.0 Plume Displacement 25
10.0 Installation 29
11.0 Electrical 34
12.0 Commissioning the Boiler 36
13.0 Completion 38
14.0 Servicing the Boiler 39
15.0 Changing Components 42
16.0 Short Parts List 49
17.0 Fault Finding 50
Benchmark Checklist 58
© Baxi Heating UK Ltd 2011
5
Page 6
Optional Integral Timer
Position of Label
Fig. 1
Facia Securing Screws
1.0 Introduction
1.1 Description
1. The Potterton Gold FSB 30 HE is a gas fired room sealed fan assisted condensing central heating boiler.
2. The maximum output of the boiler is 30.18 kW (Non ­Condensing) 32.61 kW (Condensing).
3. The boiler is designed for use on Natural Gas (G20) only.
4. The boiler is suitable for fully pumped open vented and sealed systems, providing heating and hot water.
5. A label giving details of the model, serial number and Gas Council number is situated on the rear of the drop down facia panel (Fig. 1).
6. The boiler data badge is positioned on the air box door (Fig. 2).
7. The boiler is intended to be installed in residential / commercial / light industrial E.M.C. environments on a governed meter supply only.
Air Box Door
Case Securing Screws
8. The boiler must be installed with one of the purpose designed flues such as the standard horizontal flue kit, part no 236921.
1.2 Important Information
Man-made mineral fibre
• Some component parts of this boiler (insulation pads, gaskets and rope seals) are manufactured from man-made mineral fibre.
• Prolonged or excessive exposure to this material may result in some irritation to the eyes, skin or respiratory tract.
• It is advisable to wear gloves when handling these items.
• Irritant dust will only be released from the items if they are broken up or subjected to severe abrasion. In these instances a suitable dust mask and goggles should be worn.
• Always thoroughly wash hands after installation, servicing or changing components.
• When disposing of any items manufactured from man­made mineral fibre care must be exercised.
• If any irritation of the eyes or severe irritation of the skin is experienced seek medical attention.
6
© Baxi Heating UK Ltd 2011
Fig. 2
Data Badge
Page 7
2.0 General Layout
16
2.1 Layout (Figs. 3, 4, 5 & 6)
1. Condensate Pump
2. Flue Elbow (supplied in std. flue kit)
3. Heat Exchanger
4. Burner
5. Air Box
6. Fan Protection Thermostat - Black
Fig. 5
2
15 14
7. Fan Assembly
8. Condensate Trap
9. PCB Housing Assembly
17
18
10. Gas Tap
11. Gas / Air Ratio Valve
12. Flow Pipe Connection
13. Return Pipe Connection
14. Flow Temperature Safety Thermostat - Black
3
13
12
9
19
4
15. Flow Temperature Thermistor - Red
16. Flow Switch (dry fire protection)
17. Position of Optional Integral Timer Wiring
18. Pipe Access Panel
19. Manual Air Vent
6
5
Fig. 3
7
1
8
2.2 110Ø Concentric Flues & Optional Extras
KIT PART N
Standard Flue Kit 850mm (inc. elbow) 236921 Extended Flue Kit - 1.75M ( inc. elbow) 5111457 Flue Plume Deflector Kit 248167 Terminal Guard (suitable for use with above) 248484
FLUE EXTENSION KITS (110/70) Flue Extension 250mm 241692 Flue Extension 500mm 241694 Flue Extension 1000mm Flue Bend x 2 - 45°
Flue Bend - 93° (
VERTICAL FLUE Vertical Flue Terminal 242802 Vertical Flue Adaptor 5106888
See Section 7.12 for more flue option details
Integral Twin Channel Timer 5117696
(Use two kits for 2M etc.) 241695
(Reduce overall length of flue
by 0.5m when fitting this bend)
Reduce overall length of flue by 1m when fitting each bend)
o
241689
241687
Fig. 4
© Baxi Heating UK Ltd 2011
Fig. 6
11
10
7
Page 8
3.0 Boiler Operation
NO
Mains On.
Flow
temperature less
than set point ?
YES
System Pump
Running and Flow
switch made ?
YES
5 second
Fan Pre-Purge.
5 second
Ignition Period.
YES
Condensate Pump will
operate as necessary (3.1.9)
Ignition done
and less than 5
attempts made ?
3.1 Boiler Operation
1. Switched Live On: When switched live is supplied to the boiler and the flow temperature is less than the set point the sequence below commences.
2. Flow Switch: After 10 seconds if the flow switch has made then fan pre-purge occurs. After 10 seconds if the flow switch has not made then anti-cycle occurs.
3. Fan Pre-Purge: The flow switch is made and the fan is on while the spark generator and gas valve are off. After 5 seconds ignition occurs.
4. Ignition: The flow switch is made, fan, spark generator and gas valve are on. If a flame is detected then burner on occurs. If a flame is not detected within 5 seconds and less than 5 ignition attempts have been made then fan purge occurs. If a flame is not detected within 5 seconds and 5 ignition attempts have been made then ignition lockout occurs.
5. Burner On: The flow switch is made, fan and gas valve are on while the spark generator is off. Flow temperature is controlled by varying the fan speed (and thereby the gas rate) to achieve optimum operation. If the flow temperature is greater than the set point or the TRVs all shut down then fan post purge occurs.
Flame Detected ?
shut or Flow temperature
greater than set point ?
Fan Post Purge.
YES
YES
Burner On.
All TRVs
YES
5 second
All TRVs
shut down ?
Ignition done and 5 attempts made ?
YES
Ignition
Lockout.
6. Fan Post Purge: The fan is on while the spark generator and gas valve are off. After 5 seconds if the TRVs are shut down then anti-cycle occurs.
7. Anti-cycle: The fan, spark generator and gas valve are off.
8. Ignition Lockout: The fan, spark generator and gas valve are off. The boiler can only be reset by manually using the reset button.
9. Condensate Pump: Condensate accumulates in a reservoir within the pump assembly. The pump may run at any time, independent of boiler operation, to discharge the condensate to drain.
8
© Baxi Heating UK Ltd 2011
3 minute
Anti-cycle.
Page 9
4.0 Technical Data
Appliance Type C Appliance Category CAT I
Heat Input (Q)(Gross) Max Min
kW 33.76 10.3
Heat Output (P)
(Non Condensing 70° C Mean Water Temp)
Max Min
kW 30.18 9.2
Heat Output (P)
(Condensing 40° C Mean Water Temp)
Max Min
kW 32.61 10.0
Max Gas Rate (2H - G20 - 20mbar) (After 10 Mins)
kW Input 33.76
3
m
/hr 3.4
Inlet Pressure at Gas Valve (Natural Gas)
Min 18.1 mbar Max 22.5 mbar
(see Section 10.1)
Injector (Natural Gas)
Diameter 6.5mm
CO/CO2 Ratio 0.004
NOxClass 5
C
13
2H
33
Horizontal Flue Terminal Diameter - 110mm Dimensions Projection - 150mm
Connections
Gas Supply - 15mm Central Heating Flow - 28mm Central Heating Return - 28mm Condensate Drain (Pump) - 10mm o.d.
Outercase Dimensions
Casing Height - 850mm Casing Width - 390mm Casing Depth - 520mm
Minimum Clearances
(For unventilated compartments see Section 7.2)
Both Sides - 5mm Above Casing - 15mm Above Casing Under fixed worktop ­(It is recommended that any worktop is removable) - 25mm Front (For Servicing) - 500mm Front (In Operation) - 5mm
Weights kg Packaged Boiler Carton - 49.5 Packaged Flue Kit - 3.6 Installation Lift Weight - 37.5 Installed Weight (dry) - 44.5
Recommended System Temperature Drop
Condensing 20°C
Electrical Supply 230V~ 50Hz The boiler must be connected to an earthed supply. A permanent and switched live are required. The boiler has a 4 wire connection.
Power Consumption 80W
External Fuse Rating 3A
Internal Fuse Rating (BS 4265)
Fuse 3.15 AT (PCB)
Electrical Protection IPXX
Water Content
litres 2.6
Static Head
max 30 metres min 1 metre
Low Head 0.2m min System Detail
Fully pumped open vented & sealed systems. No bypass required.
Controls
boiler thermostat, safety thermostat, flow switch, electronic flame sensing, temperature protection thermostat & condensate blockage and level sensors
Boiler Flow Temperature (adjustable)
55° C to 78° C (± 5° C)
Condensate Pump
Head 3 metres Flow Rate 1.8 l/min Connection 10mm o.d. (pipe supplied)
SEDBUK Declaration
SAP 2005 Seasonal Efficiency
model is 90.9%
This value is used in the UK Government’s Standard Assessment Procedure (SAP) for energy rating of dwellings. The test data from which it has been calculated has been certified by 0087.
© Baxi Heating UK Ltd 2011
Boiler Hydraulic Resistance Chart
220 200 180 160 140 120 100
80 60
Pressure Drop (mbar)
40 20
010203040
Water Flow Rate (litres/min)
91 83 75 66 58 50 42 33 25 17
8
Pressure Drop (in wg)
9
Page 10
5.0 Dimensions and Fixings
DIMENSIONS
At least
1.5°
A 850mm B 520mm C 390mm
A
D 125mm Ø Min. E 175mm F 150mm
B
D
C
The 1.5° fall provided by the elbow is to allow condensate to run back to the boiler, for discharge through the
Flue Ø 110mm
condensate disposal system.
Fig. 7
Fig. 8
F
E
SIDE FLUE (left and right)
Y
For every 1m of horizontal flue length, the clearance above the top
X
At least
1.5°
of the flue elbow should be 27.5mm to incorporate the 1.5° fall in the flue from the terminal to the elbow. It is
especially important to consider this when fitting the boiler under a work top !
Flue length (Y)
up to 1m
1m - 2m 2m - 3m 3m - 4m
Clearance (X)
27.5mm 55mm
82.5mm
110mm
10
© Baxi Heating UK Ltd 2011
Page 11
6.0 System Details
6.1 Water Circulating Systems
1. The boiler is suitable for use with open vent fully pumped systems and sealed systems .
The following conditions should be observed on all systems:
•The static head must not exceed 30m of water.
•The boiler must not be used with a direct cylinder.
•Drain cocks should be fitted to all system low points.
•All gas and water pipes and electrical wiring must be installed in a way which would not restrict the servicing of the boiler.
•Position isolating valves as close to circulating pump as possible.
6.2 Treatment of Water Circulating
Systems
1. All recirculatory water systems will be subject to corrosion unless they are flushed and an appropriate water treatment is applied. To prevent this, follow the guidelines given in BS 7593 “Treatment of Water in Domestic Hot Water Central Heating Systems” and the treatment manufacturers instructions.
2. Treatment must involve the use of a proprietary cleanser, such as Sentinel X300 or X400, or Fernox F3 and an inhibitor such as Sentinel X100 or Fernox MB-1.
3. Full instructions are supplied with the products, for further information contact Sentinel (0800 389 4670) or Fernox (0870 870 0362).
Failure to flush and add inhibitor to the system will invalidate the appliance warranty.
4. It is important to check the inhibitor concentration after installation, system modification and at every service in accordance with the inhibitor manufacturer’s instructions. (Test kits are available from inhibitor stockists.)
5. For information or advice regarding any of the above contact Technical Enquiries 0844 871 1555.
© Baxi Heating UK Ltd 2011
11
Page 12
Boiler Air
Vent
Boiler Air
Vent
Fig. 9
Boiler
Boiler
1000mm
Min
Copper
0.5m
Copper
500mm
150mm
Return
1m
Max
45°
15mm Cold Feed
Copper
0.5m
22mm Open Vent
400mm
Min Head
Pump
Flow Return
Flow
6.0 System Details
6.3 Pipework
1. The sizes of flow and return pipes from the boiler should be determined by normal methods, according to the requirements of the system.
2. The connection tails for the boiler are 28mm diameter. The 28mm section of the tails can be cut back to 22mm if required.
3. The flow & return tails are push - fit ‘O’ ring and clip connections within the boiler case.
4. A 20 °C drop in temperature across the system is recommended for condensing boilers. Existing radiators may be oversized and so allow this, but where radiator sizing is marginal it may be advisable to retain a system temperature drop of 11°C.
5. In systems using non-metallic pipework it is necessary to use copper pipe for the boiler Flow and Return. The copper must extend at least 1 metre from the boiler and include any branches (Fig. 9).
Boiler Air
Vent
Fig. 10
Fig. 11
Boiler
Typical Low Head Installation
45°
15mm Cold Feed
22mm Open Vent
400mm
Min Head
150mm
Max
Return
500mm
1000mm
Min
If Conditions Require,
This System Possible
Pump
6. This boiler does not require a bypass.
6.4 Low Head Installation
1. Using a close couple arrangement the minimum head is as shown in the diagrams (Figs. 10 & 11) subject to the following conditions:
a) The pump being adjusted to give a 20°C drop across
the boiler. b) The pump must be fitted on the flow. c) The pump must be fitted in accordance with the
pump manufacturer's instructions. d) The open vent pipe must be taken up from a tee in a
horizontal section of the flow pipe.
Flow
2. For heads below 400mm then an alternative utilising a combined vent and feed pipe may be connected (Fig. 12). This must be a minimum of 22mm diameter. It is recommended that an air separator is fitted when using a combined feed and vent pipe.
6.5 Air Vents
Boiler Air
12
© Baxi Heating UK Ltd 2011
Vent
Fig. 12
200mm
Min
Boiler
22mm Feed & Vent Pipe
Air
Separator
Return
Alternative Low Head Installation
Pump
Flow
For correct operation of the flow switch the boiler and system MUST be completely vented.
1. A manual air vent is fitted on the flow pipe, to enable complete venting of the boiler. The pipe access panel must be removed to do this.
2. Additional vents should be fitted at suitable points on the system as required.
Page 13
g/y
S Plan
Valve
Cylinder
Stat
Room
Stat
Boiler Connection
(4 Core Wire)
Pump
Timer
230V 50Hz
LNE
L N
CH on
HW on
LNE
S/L NE
Motor
S Plan
Valve
Motor
o
o
gr
b
g/y
b
gr
br
br
P/L
System Control
Wiring Centre
Key to colours
b-Blue br - Brown w-White o - Orange gr - Grey g/y - Green/Yellow
230V 50Hz
LNE
g/y
Room
Stat
6.0 System Details
6.6 System Controls & Wiring
This boiler requires a permanent live for operation of the condensate pump and frost protection.
b
w
Cylinder
Stat
1
C2
Y Plan
Diverter
Valve
gr
o
1. To comply with Part L1 of the Building Regulations the heating system into which the boiler is installed should include the following:
a) zone controls b) timing controls c) boiler control interlocks
System Control
S/L NE
P/L
Wiring Centre
Timer
L N
CH on HW on HW off
LNE
Pump
Y Plan, Room Thermostat System, CH Interlocked By Room Thermostat, DHW Interlocked By Cylinder Thermostat
At least the Radiator(s) near the Room Thermostat not TRV’d Pump run from Switched Live
Boiler Connection
(4 Core Wire)
2. Such a system needs to be fully pumped and must provide independent temperature and time control to both the heating and hot water circuits and have a boiler and system pump interlock.
3. The boiler should be controlled so that it operates on demand only. Where it is proposed to effect control by thermostatic radiator valves a room thermostat should also be provided to switch off the boiler when there is no demand for heating.
S Plan, Room Thermostat System, CH Interlocked By Room Thermostat, DHW Interlocked By Cylinder Thermostat
At least the Radiator(s) near the Room Thermostat not TRV’d Pump run from Switched Live
© Baxi Heating UK Ltd 2011
13
Page 14
Table. 1
Safety
Valve
Fig. 13
Air
Vent
Pressure
Gauge
Boiler
System Drains at Low Point
Filling Point
Pump
Expansion Vessel
Max Boiler Flow
Temp = 82° C
Method of determining minimum expansion
vessel volume for sealed systems.
Vessel Charge Pressure (Bar)
Initial System
Pressure (Bar)
0.5
0.5
1.0
1.5
2.0
1.0
1.0
1.5
2.0
1.5
Example :-
System Volume = 75 litres
1.5
2.0
Vessel Charge Pressure = 1.0 bar Initial System Pressure = 1.5 bar
Then :-
75 x 0.152 = 11.4 litres Expansion Vessel Volume
NOTE
Where a vessel of the calculated size is not obtainable then
the next available larger size should be used.
3 Litre Top Up Bottle (if required)
Radiator Circuit
Multiply Total
Water Content Of
System By (Litres)
0.067
0.112
0.207
0.441
0.087
0.152
0.330
0.125
0.265
6.0 System Details
6.7 Sealed Systems (Fig. 13)
1. SAFETY VALVE - A safety valve complying with the requirements of BS 6750 Part 1 must be fitted close to the boiler on the flow pipe by means of a horizontal or vertically upward connection with no intervening valve or restrictions and should be positioned to facilitate testing. The valve should be pre-set and non-adjustable to operate at a pressure of 3 bar (45 Ibf/in arranged to discharge any water or steam through a pipe to a safe outlet position.
2. PRESSURE GAUGE - A pressure gauge of minimum range 0-4 bar (0-60 Ibf/in
2
) with a fill pressure indicator must be fitted to the system, preferably at the same point as the expansion vessel in an easily visible position.
3. EXPANSION VESSEL - An expansion vessel complying with the requirements of BS 4814 must be fitted to the system by means of a connection close to the inlet side of the circulating pump in accordance with the manufacturers instructions, the connecting pipe being unrestricted and not less than 15mm ( The volume of the vessel should be suitable for the system water content and the nitrogen or air charge pressure should not be less than the system static head (See Table. 1).
Further details of sealed system design can be obtained from BS 5449 and the British Gas publication entitled 'Specifications for Domestic Wet Central Heating Systems'.
4. FILLING POINT - A filling point connection on the central heating return pipework must be provided to facilitate initial filling and pressurising and also any subsequent water loss replacement / refilling. The sealed primary circuits may be filled or replenished by means of a temporary connection between the primary circuit and a supply pipe provided a ‘Listed’ double check valve or some other no less effective backflow prevention device is permanently connected at the inlet to the circuit and the temporary connection is removed after use. The filling method adopted must be in accordance with all relevant water supply regulations and use approved equipment. Your attention is drawn to, for GB: Guidance G24.2 and recommendation R24.2 of the Water Regulations Guide. for IE: the current edition of I.S. 813 “Domestic Gas Installations”.
5. MAKE UP SYSTEM - A method of replacing water lost from the system should be provided either by means of a make up vessel of not more than 3 litres (5 pints) capacity, mounted above the highest point of the system, or by re-pressurisation of the system.
2
). It must be
1
/2in) nominal size.
Fig. 14
14
© Baxi Heating UK Ltd 2011
Mains Inlet
Stop Valve
Double Check Valve
Temporary Hose
Stop Valve
6. VENTING - A method of venting the system during filling and commissioning must be provided by fitting automatic air vents or by venting manually.
7. HOT WATER STORAGE - The hot water storage vessel must be of the indirect coil type.
8. COMPONENTS - All components used in the system must be suitable for operation at 110°C (230°F) and at the pressure allowed by the safety valve.
CH Return
Page 15
Zone 1
Zone 2
Window Recess
Zone 2
7.0 Site Requirements
7.1 Location
NOTE: Due to the high efficiency of the boiler a plume of water vapour will be discharged from the flue. This should be taken into account when siting the flue terminal.
1. The boiler must be fitted on a suitable flat and level surface capable of supporting the weight. Any wall behind the boiler must be at 90° to the floor to allow case top cover to fit correctly.
2. The flue must pass through an outside wall or roof and discharge to atmosphere in a position permitting satisfactory removal of combustion products and providing an adequate air supply.
Fig. A
Zone 1
Zone 0
Zone 0
Window Recess
Zone 2
0.6 m
In GB Only
Window Recess Zone 2
Zone 2
2.25 m
Ceiling
Outside Zones
3. The boiler should be fitted within the building unless otherwise protected by a suitable enclosure i.e. garage or outhouse.
4. The boiler incorporates a frost protection device. This will only protect the boiler. To ensure protection of the system pipework and components it is recommended to incorporate an appropriate device within the system controls.
5. If the boiler is fitted in a room containing a bath or shower, it can only be fitted in Zone 3, (Figs. A & B shows zone dimensions for a bathtub. For other examples refer to the Current I.E.E. Wiring Regulations). Reference must be made to the relevant requirements:­In GB this is the current I.E.E. Wiring Regulations and Building Regulations. In IE reference should be made to the current edition of I.S. 813 “Domestic Gas Installations” and the current ETCI rules.
6. If the boiler is to be fitted into a building of timber frame construction then reference must be made to the current edition of Institute of Gas Engineers Publication IGE/UP/7 (Gas Installations in Timber Framed Housing).
© Baxi Heating UK Ltd 2011
Fig. B
0.6 m
In GB Only
7.2 Compartment
1. Where the boiler is installed in a cupboard or compartment, no air vents are required for cooling purposes providing that the minimum dimensions below are maintained.
Width 400mm Height 875mm Depth 525mm
2. Any compartment should be large enough to house the boiler only.
15
Page 16
5mm Min
390mm
5mm Min
15mm Min (25mm if under non removable worktop)
7.0 Site Requirements
7.3 Clearances (Figs. 15 &16)
1. These dimensions include the necessary clearances around the boiler for case removal, spanner access and air movement. Additional clearances may be required for the passage of pipes around local obstructions such as joists running parallel to the front face of the boiler. For side flue installations also See Section 8.1, Figs. 20 & 21.
2. It is recommended that any worktop is removable for servicing access.
Fig. 15
850mm
7.4 Gas Supply
1. Check that the information concerning the state of adjustment given on the data plate is compatible with local supply conditions.
2. The gas installation should be in accordance with the relevant standards. In GB this is BS 6891. In IE this is the current edition of I.S. 813 “Domestic Gas Installations”.
3. The connection to the boiler is a 15mm tail on the gas service cock. The tail protrudes through the boiler rear panel and is protected by a transit bracket which may be removed to aid connection.
4. Ensure that the pipework from the meter to the boiler is of adequate size. (If the boiler is further than 3 metres from the Gas Meter 22mm pipe should be used). Do not
use pipes of a smaller diameter than the boiler gas connection.
7.5 Electrical Supply
1. External wiring must be correctly earthed, polarised and in accordance with relevant regulations/rules. In GB this is the current I.E.E. Wiring Regulations. In IE reference should be made to the current edition of ETCI rules.
500mm Min
For Servicing
Purposes
5mm Min
Fig. 16
16
© Baxi Heating UK Ltd 2011
2. The mains supply is 230V ~ 50Hz fused at 3A.
NOTE: “The method of connection to the electricity supply must facilitate complete electrical isolation of the appliance and system”.
Connection may be via a fused double-pole isolator with a contact separation of at least 3mm in all poles, which must be in an accessible position to the user and serve the boiler and system controls only.
There is no method of isolating the boiler at the user interface.
3. Four core cable is required to supply the boiler as a permanent live is necessary for the operation of the condensate pump and frost protection.
520mm
In Operation
Page 17
7.0 Site Requirements
4
3
2
Head (metres)
1
0
1.5
Min. radius 100mm
Point ‘A’
Condensate Pump Flow Graph
2
2.5
Flow (l/min)
3.5
3
Gravity Drain min. fall 3°
7.6 Condensate Drain - General
Failure to install the condensate discharge pipework correctly will affect the reliable operation of the boiler.
1. Ensure the discharge of condensate complies with any national or local regulations in force.
BS 6798 & Part H1 of the Building Regulations give further guidance.
2. If any further drain pipe is required (additional to that supplied with the boiler), it should be run in a proprietary material e.g. PVC, PVC-U, ABS, PVC-C or PP.
4
3. Metal pipework is NOT suitable for use in condensate discharge systems.
4. Any pipe fitted externally must be kept as short as possible to minimise the potential of freezing and must be insulated using waterproof material.
5. When discharging condensate into a soil stack or waste pipe the effects of existing plumbing must be considered.
7.7 Condensate Disposal
Fig. A
Boiler
Max. Head
3 metres
Note: The point of discharge from the pumped length of condensate pipe (point ‘A’) must not be below the level of the pump, whether discharging direct into a drain or into an additional gravity drain.
Alternative Horizontal
Discharge
10mm PVC Pipe
(8.5mm I.D.)
Securing Clip
8.5mm Ø O.D.
1. This boiler incorporates an automatic pumped condensate system. See the graph opposite for available pump flow rates.
2. 3.5 metres of flexible 10mm PVC pipe are supplied with the boiler. 0.5 metres of this length remains coiled within the boiler to allow removal of the pump assembly. This must not be uncoiled to provide extra length.
3. A fitting and securing clip (Fig. B) to accept the 10mm PVC pipe and connect to 21.5mm overflow pipe is also supplied.
4. The 10mm pipe can be routed to a maximum of 3 metres vertically and then discharge via gravity or be routed horizontally (Fig. A). A combination of vertical and horizontal runs is permissible.
5. The pipe must be supported, either using suitably spaced clips or run within larger diameter pipe. When using clips take care not to deform the pipe.
6. When routing the pipe through a wall it must be suitably sleeved. Also the pipe must not be exposed to sources of heat, and should be protected in locations where it may be damaged.
7. The pipe should be routed so that any sharp bends, dips and loops are avoided. A minimum radius of 100mm is recommended for any bends. No slope is necessary and air breaks are not required on the pumped part of the condensate run.
Condensate Pipe Direct Connect Fitting
© Baxi Heating UK Ltd 2011
Fig. B
21.5mm Ø O.D. to fit
Overflow Pipe
8. If the boiler is fitted in an unheated location the entire length of condensate pipe should be treated as external, and run within insulated larger diameter pipe.
17
Page 18
7.0 Site Requirement
10°
10°
Termination via internal discharge branch e.g sink waste - downstream
Direct Connect Fitting
Sink
From Boiler
Fig. C
Pipe must terminate above water level but below surrounding surface
From Boiler
Branch of Tee to be ± 10° from vertical
Termination to an internal soil and vent pipe
Direct Connect Fitting
Min. 450mm
Fig. D
7.7 Condensate Disposal (cont.)
9. Ensure that the condensate can discharge freely (without blockage or restriction of the pipe) into the drain.
10. Examples are shown of condensate pipe methods of termination:-
i) via an internal discharge branch
(e.g. sink waste) - Fig. C.
ii) to an internal or external soil and vent pipe -
Fig. D.
iii) to a drain or gully - Fig. E. Ensure that the
condensate can discharge freely (without blockage or restriction of the pipe) into the drain.
iv) to a soakaway - Fig. F.
Termination to a drain or gully
From Boiler
Fig. E
Pipe must terminate above water level but below surrounding surface
Termination to a purpose made soak-away
From Boiler
Fig. F
500mm Min
Holes in the soak-away must face away from the building
18
© Baxi Heating UK Ltd 2011
Page 19
300 min
Terminal Assembly
Top View Rear Flue
Property Boundary Line
Table. 2
Terminal Position with Minimum Distance (Fig. 17) (mm)
AaDirectly below an opening, air brick, opening
windows, etc. 300 BaAbove an opening, air brick, opening window etc. 300 CaHorizontally to an opening, air brick, opening window etc. 300 D Below gutters, soil pipes or drain pipes. 25 E Below eaves. 25 F Below balconies or car port roof. 25 G From a vertical drain pipe or soil pipe. 25 H From an internal
(i)
or external
(ii)
corner.
(i)
(ii)
25
115 I Above ground, roof or balcony level. 300 J From a surface or boundary line facing a terminal. 600 K From a terminal facing a terminal (Horizontal flue). 1200
From a terminal facing a terminal (Vertical flue). 600
L From an opening in carport (e.g. door, window)
into the dwelling. 1200 M Vertically from a terminal on the same wall. 1500 N Horizontally from a terminal on the same wall. 300
R From adjacent wall to flue (vertical only). 300 S From an adjacent opening window (vertical only). 1000 T Adjacent to windows or openings on pitched and flat roofs 600 U Below windows or openings on pitched roofs 2000
a
In addition, the terminal should be no nearer than 150 mm to an opening in the building fabric formed for the purpose of accommodating a built-in element such as a window frame. See BS 5440 Pt. 1.
7.0 Site Requirements
7.8 Flue
NOTE: Due to the high efficiency of the boiler a plume of water vapour will be discharged from the flue. This should be taken into account when siting the flue terminal.
1. The following guidelines indicate the general requirements for siting balanced flue terminals. For GB recommendations are given in BS 5440 Pt.1. For IE recommendations are given in the current edition of I.S. 813 “Domestic Gas Installations”.
2. If the terminal discharges onto a pathway or passageway, check that combustion products will not cause a nuisance and that the terminal will not obstruct the passageway.
3. When siting the flue take into consideration the effect the plume of water vapour may have on neighbours .
4. Adjacent surfaces close to the flue terminal may need protection from the effects of condensation. Alternatively a flue deflector kit (part no. 248167) is available.
5. For installation of the flue into an internal corner at the 25mm dimension the flue plume deflector kit (part no. 248167) must be fitted.
NOTE: The distance from a fanned draught boiler terminal installed parallel to a boundary may not be less than 300mm in accordance with the diagram below, unless the flue deflector kit is used (see 7.8.6 opposite)
*
Fig. 16a
IMPORTANT: If fitting a Plume
Displacement Flue Kit, the air inlet must be a minimum of 150mm from any opening windows or doors.
U
D
C
I
A
E
S
F
A
H
H
R
I
F
T
J,K
N
M
I
B
L
A
G
I
6. * Reduction to the boundary is possible down to 25mm but
*
the flue plume deflector kit (part no. 248167) must be fitted.
7. If a terminal is less than 2 metres above a balcony, above ground or above a flat roof to which people have access, then a suitable terminal guard must be provided.
8. If required a suitable terminal guard (part no. 248484) is available from Potterton for use with the flue deflector. See also Section 8.8.
9. For fitting under low soffits and eaves the Plume Displacement Kit or Flue Deflector Kit is recommended.
IMPORTANT:
• Only ONE 25mm clearance is allowed per installation.
• Under car ports we recommend the use of the plume displacement kit.
• The terminal position must ensure the safe and nuisance - free dispersal of combustion products.
Plume Displacement Kit
I
J,K
Air Inlet
© Baxi Heating UK Ltd 2011
Likely flue positions requiring a flue terminal guard
Fig. 17
Fig. 17a
150mm MIN.
Opening Window or Door
19
Page 20
8.0 Flue Options
8.1 Horizontal Flue Systems
Only a flue approved with the Potterton Gold FSB HE 30 can be used.
(ii)
Plume Displacement 70/110 dia Kit
1M Extensions, 45° & 93° bends are also available - see Section 9.0
Horizontal Flue System Examples
(ii)
(i)
(i)
Concentric The maximum equivalent lengths are 4m (horizontal) or
(vertical). Their lengths exclude the standard elbow and flue/terminal assembly (horizontal) and terminal assembly (vertical).
Any additional “in line” bends in the flue system must be taken into consideration. Their equivalent lengths are:
Concentric Pipes: 45° bend 0.5 m
93° bend 1.0 m
NOTE: Flue length is measured from point (i) to (ii) as shown.
IMPORTANT: All flue systems must be securely supported at least once every metre. Suitable pipe supports are available as accessories.
NOTE: Horizontal flue pipes should always be installed with a 1.5° fall from the terminal to allow condensate to run back to the boiler.
This bend is equivalent to
0.5 metre
A
B
(ii)
This bend is equivalent to
0.5 metre
(i)
Total equivalent length = A+B+2x45°Bends
20
© Baxi Heating UK Ltd 2011
Page 21
(ii)
(i)
(ii)
Vertical Flue System Examples (Twin Pipe)
8.0 Flue Options
8.2 Twin & Vertical Flue Systems
Concentric The maximum equivalent lengths are 4m (vertical). Their
lengths exclude the standard elbow and terminal assembly (vertical).
Twin Flue The total maximum equivalent flue length is 150m. NOTE: Each 1m of flue duct should be calculated as 2m.
Any additional “in line” bends in the flue system must be taken into consideration. Their equivalent lengths are:
Concentric Pipes: 135° bend 0.5 m
93° bend 1.0 m
Twin Flue Pipe: 135° bend (air duct) 1.3 m
135° bend (flue duct) 2.6 m 90° bend (air duct) 4.8 m 90° bend (flue duct) 9.6 m
(i)
Vertical Flue System Examples
Total Equivalent Length = A+B+C+1x90°Bend
All vertical and angled runs must be included, measured from the boiler adaptor (point X) to the joint with the flue terminal (point Y). One 91.5° bend or two 135° bends can be included without reduction of the flue length.
If further elbows are required the flue length must be reduced by the following amounts:-
1 metre for each 91.5° bend
(ii)
0.5 metre for each 135° bend
B
A
(i)
Roof
Terminal
C
This bend is equivalent to 1 metre
IMPORTANT: All flue systems must be securely supported at least once every metre. Suitable pipe supports are available as accessories.
The total equivalent length
for this example is
17.2 + 34.4 = 51.6 metres.
AIR DUCT
1m extension
135°bend
91.5°bend
1m extension
135°bend
91.5°bend
Equivalent
Length Value
1m
1.3m
4.8m Equivalent Length Air Duct = 17.2m
Equivalent
Length Value
2m
2.6m
9.6m
Equivalent Length Flue Duct = 34.4m
Noof
fittings/pipes
5 2 2
FLUE DUCT
Noof
fittings/pipes
5 2 2
Sub total
5.0m
2.6m
9.6m
Sub total
10.0m
5.2m
19.2m
© Baxi Heating UK Ltd 2011
21
Page 22
8.0 Flue Options
8.3 Flue Accessories
Key Accessory Size Code No
FLUE GROUP B
A
E
C
D
A1
T
B
K
S
Concentric Flue System 110mm diameter
A1 Horizontal Flue Terminal 850mm 243013BAX A Horizontal Flue Terminal (incl elbow) 236921 B Flue Extension 1000mm 241695
500mm 241694
250mm 241692 C Flue Bend 93° 241687 D Flue Bend (pair) 135° 241689 U Pipe Support 110mm 243014BAX T Vertical Flue Boiler Adaptor 5106888 S Flue Terminal Deflector 248167
FLUE GROUP P Twin Flue System 80mm diameter
E Flue Extension (pair) 1000mm 246137
500mm 246136
250mm 246135 F Flue Bend (pair) 90° 5121560 G Flue Bend (2 pair) 135° 5121561 J Vertical Flue Boiler Adaptor Kit 242757 W Pipe Support (pair) 80mm 5111081
FLUE GROUP B,P Vertical Flue Kits
K Vertical Flue Terminal 242802 L Pitched Roof Flashing 25°/50° 243015 M Roof Cover Plate 243131 N Flat Roof Flashing 243016BAX
G
F
M
U,W
L
22
© Baxi Heating UK Ltd 2011
N
J
Page 23
For Vertical Flues
8.0 Flue Options
Vertical Flue Adaptor
Gasket
Blank Plate
Air Duct Adaptor
8.4 For Vertical Flue Systems
1. Undo the screws securing the blanking plate to the boiler top panel. Discard the plate.
2. Fix the vertical adaptor and gasket to the top panel with the previously removed screws.
8.5 For Twin Flue Systems
1. Undo the screws securing the blanking plate to the boiler top panel. Discard the plate.
2. Fix both the air and flue adaptors with their gaskets onto the boiler top panel. Secure with screws.
For Twin Flues
Gasket
Flue Duct Adaptor
Gasket
© Baxi Heating UK Ltd 2011
23
Page 24
Cut the same amount off the Air Duct & Flue Duct
Air Duct
Flue Duct
Push Fit Adaptor
Approx
1425mm
8.0 Flue Options
8.6 For Roof Terminals
1. In the case of a pitched roof 25 - 50 degrees, position the lead tile to replace/flash over existing roof tiling. Make an aperture in the roof suitable for the lower tube of the roof terminal and ensure the integrity of the roof cover is maintained. The adjustable plastic collar can either be positioned on the lead tile or the lower tube of the roof terminal prior to the final positioning of the vertical flue through the tile. Check the collar is correctly located to suit required roof pitch (either 25° to 38° or 37° to 50°). From inside the roof adjust the flue to a vertical position and secure to the roof structure with the clamp supplied.
2. For flat roof installations the aluminium flashing must be incorporated into the roof covering and the appropriate aperture made in the roof decking. The vertical flue is lowered onto the flashing making sure the collar of the flue locates securely with the flashing. (A mastic seal may be necessary). From inside the roof, adjust the flue to a vertical position and secure to the roof structure with the clamp supplied.
IMPORTANT: If the boiler is not fitted immediately after the flue system, temporary precautions must be taken to prevent rain entry into the room of installation. Any precautionary measures must be removed prior to commissioning the boiler.
270mm 800mm
Fig. 18
Flue Deflector
Fig. 18a
8.7 Flue Dimensions
The standard horizontal flue kit allows for flue lengths
5
between 270mm (10
/8”) and 800mm (32”) from elbow to
terminal (Fig. 18).
The maximum permissible equivalent flue length is: 4 metres.
NOTE: Each additional 45° of flue bend will account for an equivalent flue length of 0.5m. eg. 45° = 0.5m, 90° = 2 x 45° = 1m etc.
8.8 Terminal Guard (Fig. 19)
1. When codes of practice dictate the use of terminal guards, they can be obtained from most Plumbers’ and Builders’ Merchants.
2. When ordering a terminal guard, quote the appliance model number.
3. The flue terminal guard should be positioned centrally over the terminal and fixed as illustrated.
24
© Baxi Heating UK Ltd 2011
8.9 Flue Deflector (Fig. 18a)
1. If required, push the flue deflector over the terminal end and rotate to the optimum angle for deflecting plume. Secure the deflector to the terminal with screws provided.
Fig. 19
Page 25
Plume Outlet (‘Peak’ MUST be Uppermost)
0.94 metre
9.0 Plume Displacement
9.1 Plume Displacement Kit (P.D.K.)
Kit No 5121371
Content of kit
1 70/110 Concentric Flue 1 1m 70 Dia Exhaust Flue Pipe 2 Support Brackets 1 93° Elbow/Plume Outlet Assembly 1 Flue Trim 2 “O” Rings 1 Elbow with Gasket
1. This kit is recommended for installations where the condensate plume emitted from the flue may cause a nuisance or affect the surroundings.
2. The terminal must be positioned outside the building with the outlet connection upwards.
3. The 70Ø pipe connects to the outlet of the concentric terminal assembly. The elbow/plume outlet must be fitted to the end of the 70Ø pipe.
45°
45°
Outlet must be at least 45° from wall face
Fig. C
‘Peak’ MUST be Uppermost
NOTE: The plume outlet must always be at least 45° to
the wall, with the ‘peak’ uppermost to prevent rain entry (Figs. A & B), and be at least 2 metres above ground level. It must be secured as shown in Fig. C.
The outlet must be positioned so that any condensate plume is directed away from adjacent surfaces.
4. It is possible to reduce or increase (with the addition of extensions) the length of either or both the 70/110 concentric and 70Ø exhaust.
5. Standard concentric flue extension kits may be added between the boiler elbow and the terminal assembly.
6. The minimum length of the concentric flue is 100mm when measured from the edge of the boiler flue elbow. There is a further 45mm engagement into the elbow.
IMPORTANT: The maximum equivalent length of concentric flue is:- 4 metres Additional elbows may be fitted in the concentric flue, but the equivalent length must be reduced by 1 metre (93° elbow) or 0.5 metres (45° elbow).
Fig. A
Outlet Connection upwards
© Baxi Heating UK Ltd 2011
500mm Min.
Fig. B
7. 70Ø 1 metre extensions (including support bracket), and additional 93° & 45° elbows are available. Any additional 93° & 45° elbows must be accounted for when calculating flue lengths. 70Ø 93° elbows are equivalent to 3.5 metres of straight length and 45° elbows to 1 metre.
NOTE: Permitted positions of the plume outlet relative to doors, windows etc. are the same as for conventional concentric flues as detailed in the main Installation & Servicing Instructions and BS5440 Pt. 1. It is NOT necessary to fit a terminal guard over the air inlet or the plume outlet.
25
Page 26
30
28
26
24
22
20
18
16
14
12
10
70Ø Exhaust (metres)
8
6
4
2
0
0
Example 1
30
1
Concentric 70/110 Flue (metres)
Flue Lengths - Not Permissible
70Ø Exhaust
234
30
28
26
24
22
20
18
16
14
12
10
70Ø Exhaust (metres)
8
6
4
2
0
0
Example 3 Flue Lengths - OK
30
28
26
24
22
20
18
16
14
12
10
70Ø Exhaust (metres)
8
6
4
2
0
Example 2 Flue Lengths - OK
30
1
234
Concentric 70/110 Flue (metres)
0
1
30
234
Concentric 70/110 Flue (metres)
Support Bracket
9.0 Plume Displacement
9.2 Determining Permissible Lengths - P.D.K.
In the graph the solid line diagonal represents the relationship between the concentric flue assembly (and any extensions) and the 70Ø exhaust (and any extensions or additional bends).
Example 1 - Not Permissible
If, for instance, a concentric length of 3.25 metres was required and the 70Ø exhaust needed to be 10 metres the graph shows that this combination would NOT be permissible as the intersection point would be above the solid diagonal line.
Example 2 - Flue Lengths OK
Where both lengths have been determined they can be applied to the graph to check that the installation is permissible. For example, if it was known that 2 metres of concentric flue and 4 metres of 70Ø exhaust were required, the values could be applied to the graph as shown in Example 2.. As the point of intersection of the dotted lines is below the solid diagonal line, the combination of lengths is shown to be acceptable.
Example 3 - Flue Lengths OK
In the example shown, assume that the concentric part of the flue needs to be 2 metres long. Find the position of ‘2’ on the horizontal axis of the graph and then project upwards to the solid diagonal line. This is represented by the vertical thick dotted line. Where this dotted line intersects with the solid diagonal line on the graph, project across to the vertical axis. As can be seen this corresponds with 14 metres. Therefore, the total equivalent length of the 70Ø exhaust can be up to 14 metres. Any elbow equivalencies must be accounted for i.e. 93° elbows are equal to 1 metre, each 45° elbow to 0.5 metres.
Y
Concentric 70/110 Flue (MUST be installed horizontally)
Additional Accessories
A - 93° Elbow 5117381 B - 45° Elbow (Pair) 5117382 C - 1 metre 60Ø Extension 5117380
26
© Baxi Heating UK Ltd 2011
45° Elbow
Flue Length - Worked Example
X
93° Elbow
1 metre Extension
1 metre supplied in kit
Concentric Flue
Fig. D
In Fig. D opposite an additional 93° elbow and pair of 45° elbows have been included in the 70Ø exhaust. Also 3 straight extension pieces have been used.
To calculate total length:­Length of 70Ø supplied in kit = 1 metre 3 x 1 metre Extensions = 3 metres 1 x 93° Elbow = 1 metre 2 x 45° Elbow = 1 metre (0.5 metres each)
Total 70Ø = 6 metres
After consulting the table in Example 3 it can be determined that the concentric flue could be up to approximately 3.25 metres long.
Page 27
Min. 2 metres
Min. 0.3 metres
This section of the flue MUST be horizontal
9.0 Plume Displacement
9.3 General Fitting Notes - P.D.K.
1. Cut a hole in the external wall which the horizontal concentric flue assembly will pass through.
2. When completed the terminal must be at least 2 metres above ground level (Fig. E).
3. Measure and cut to size the concentric assembly and any extensions that are being used.
4. Insert the concentric assembly through the hole from outside the building and mark the position of the flue trim securing holes.
5. Drill and plug the wall to accept the flue trim securing screws, and re-insert the concentric assembly through the wall.
6. Connect any extensions that are being used to the concentric assembly. Engage the extension or concentric assembly in the boiler flue elbow.
Fig. F
Fig. E
7. Fit the boiler flue elbow to the boiler top panel, ensuring the gasket is in place (Fig. F).
Ensure that the concentric assembly is horizontal and that the external air inlet is to the bottom. Any extensions should fall back to the boiler.
8. Use suitable brackets to support the concentric assembly and any extensions, and make good inside and outside. Secure the flue trim to the wall.
9. The 70Ø exhaust can now be fitted to the spigot at the terminal end.
10. If it is necessary to shorten the 70Ø exhaust or any of the extensions, the excess material must be cut from the plain end of the pipe.
11. Determine the position of the 70Ø exhaust and mark on the wall a suitable position for the support bracket. Drill and plug the wall. If extensions are being used, a support bracket is supplied in each kit.
12. Engage the M6 threaded part of the mounting bolt in the boss on the support bracket. Using the bracket for leverage, screw the mounting bolt into the plugged hole until the bracket is secure and level (Fig. G).
Fig. G
© Baxi Heating UK Ltd 2011
13. Slacken the two screws securing the retaining strap to the bracket, and pivot the strap aside to allow fitting the 70Ø exhaust.
14. Complete the installation of the 70Ø exhaust, securing in the brackets. Fit the 93° elbow and plume outlet. Ensure the plume outlet is at least 45° to the wall and that the ‘peak’ is uppermost.
15. Continue with installation and commissioning of the boiler.
27
Page 28
9.0 Plume Displacement
Plume Outlet
Fig. H
200mm Min.
500mm Min.
Elbow
9.3 General Fitting Notes - P.D.K. (cont.)
16. For aesthetic purposes it is permissible to route the 70Ø exhaust in an enclosed box, but the air inlet and plume outlet MUST remain in free air.
17. It is also possible to separate the plume outlet from the 93° elbow to allow the flue to be installed as shown in Fig. H.
18. When the plume outlet is positioned under a balcony or other projection (Figs. I & J) it must protrude at least 200mm (it is not necessary to extend it further than this).
Fig. I
Fig. J
200mm Min.
28
© Baxi Heating UK Ltd 2011
Page 29
Edge of Boiler
Example
2m
125mm
10.0 Installation
Centre Hole
Fig. 20
Flue Duct Hole Offset V (mm)
V
Fig. 21
EXAMPLE: If the boiler is 2 metres away from corner of wall the flue
Example
V = 55mm
Horizontal
Side Flue
Centre Line
duct hole will be 55mm higher than the horizontal side flue centre line. This will maintain an approx. 1.5° backfall to the boiler. It is especially important to consider this when fitting the boiler under a work top !
Wall Thickness
up to 227mm up to 750mm
up to 1200mm
Template
Backfall to the boiler, ie. 2m flue offset (V) position 55mm
13.5 27.5 55 82.5 110
0.5
1.0
2.0
3.0
4.0 (metres)
125mm core drill 150mm core drill 175mm core drill
(mm)
Flue Hole ø
Check Site Requirements before commencing.
10.1 Initial Preparation & Installation
1. Remove the outer carton.
2. For the boiler to operate correctly it must be level in both planes. Place the fixing template in the proposed boiler position ensuring that it is level.
3. Mark the centre of the flue hole (rear exit). For side exit: project the horizontal side flue centre line into the corner of the room and along the wall to where the flue hole will be drilled. (Fig. 20). The diagram (Fig. 21) shows the dimensions required to ensure any horizontal flue is installed with the correct fall to the boiler. Mark the offset (V) dimension and if required, mark the position of the gas, water and condensate pipes. Remove the template.
4. Cut the hole for the flue (minimum diameter 125mm, see table (Fig. 20) for wall thicknesses and flue hole diameters).
5. Complete any pipework and wiring that will be inaccessible once the boiler is in position.
1.5°
6. Undo the securing screws and remove the facia, front door panel and top panel (see Figs. 1 & 2 on page 6). Remove the securing screw and disengage the pipe access panel.
10.2 Making the Water Connections
1. If desired the flow and return tails supplied with the boiler can be fitted at this stage and secured with the spring clips. The flow and return connections are identified on the boiler rear panel. The flow pipe incorporates a manual air vent.
2. Note that the seal is made by use of an ‘O’ ring, therefore some pipe movement will be evident even though a water tight seal has been achieved. Excessive force could result in damage to the connection.
Flow Tail
Return Tail
Transit Bracket
Gas Connection
© Baxi Heating UK Ltd 2011
Fig. 22
Hole for Electrical Cable
Hole for Condensate Drain Outlet
3. Make all soldered joints before connecting the tails to the boiler to avoid damaging the ‘O’ rings.
4. Refit the pipe access panel.
10.3 Making the Gas Connection
1. The connection to the boiler is a 15mm tail on the gas service cock. The tail protrudes through the boiler rear panel and is protected by a transit bracket which may be removed to aid connection (see Fig. 22).
2. If solder joints are being used for the gas connection, remove the gas tap from the valve as excessive heat may damage the ‘O’ ring seal.
10.4 Priming the Condensate Trap
1. Using a funnel and tube, carefully pour approximately 1 cupful (250ml) of tap water into the flue products exhaust at the terminal or flue elbow sampling point to ensure a seal is made in the trap.
29
Page 30
At least
1.5°
Wall Thickness
10.0 Installation
10.5 Fitting the Standard Flue
IMPORTANT: The flue should always be installed with at least 1.5° fall from terminal to elbow, to allow condensate to run back to the boiler.
1. The standard flue is suitable for lengths 270mm minimum to 800mm maximum (measured from the edge of the flue elbow outlet).
Rear Flue: maximum wall thickness - 575mm Side Flue: maximum wall thickness - 535mm
2. For rear exit - measure the wall thickness (Fig. 26) and to this dimension add 270mm. This dimension to be known as (X).
i.e. (X) = wall thickness + 270
3. Take the flue and mark off (X) from the terminal end as indicated in the diagram (Fig. 27).
4. For side exit - measure the distance from the edge of the boiler case to the inner face of the wall (Fig. 26) and to this dimension add the wall thickness + 280mm. This dimension to be known as (Z).
Fig. 26
Fig. 27
Waste
(Z) = Side Exit
(X) = Rear Exit
Flue
Edge of Boiler Case to Wall
Wall Thickness
i.e. (Z) = case to wall + wall thickness + 280
5. Take the flue and mark off (Z) from the terminal end as indicated (Fig. 27).
Before cutting check your dimensions !
6. The flue tubes are fixed together. Cut through both tubes whilst resting the flue on the semi-circular packing pieces. Deburr both tube ends.
NOTE: When cutting ensure the cut does not interfere with the inner flue support bracket (Fig. 27a).
30
© Baxi Heating UK Ltd 2011
Inner Flue Support Bracket
Fig. 27a
Page 31
10.0 Installation
10.5 Fitting the Standard Flue (Cont)
Inner Flue Support Bracket
Flue
Flue Elbow
Fig. 28
Fig. 29
7. Ensure the inner flue support bracket is positioned in the flue (Fig. 28).
8. Engage the flue into the flue elbow using soap solution to ease the engagement, ensuring the flue terminal is positioned as shown (Fig. 29).
9. Place the gasket over the flue exit on the boiler.
10. Slide the flue assembly through the hole in the wall.
11. Engage the elbow on to the flue connection on top of the boiler. Secure with the four screws supplied in the kit.
12. Make good between the wall and air duct outside the building ensuring the 3° drop between the terminal and elbow.
13. The flue trim should be fitted once the installation is complete and the flue secure (Fig. 30). Apply a suitable mastic to the inside of the trim and press against the wall finish, making sure the brickwork is dust free and dry.
Gasket
14. If necessary fit a flue plume deflector kit and/or terminal guard (see Sections 7.6 & 8.8).
Fig. 30
Flue Trim
© Baxi Heating UK Ltd 2011
Shaded Areas indicate Recommended Handling Points
31
Page 32
Min. radius 100mm
10°
10°
Point ‘A’
Boiler
Fig. A
Condensate Pipe Direct Connect Fitting
Gravity Drain min. fall 3°
Max. Head
3 metres
Alternative Horizontal
Discharge
Note: The point of discharge from the pumped length of condensate pipe (point ‘A’) must not be below the level of the pump, whether discharging direct into a drain or into an additional gravity drain.
10mm PVC Pipe
(8.5mm I.D.)
Securing Clip
10.0 Installation
10.6 Making the Condensate Drain
Connection
1. 3.5 metres of flexible 10mm PVC pipe are supplied with the boiler, ready connected to the pump. 0.5 metres of this length remains coiled within the boiler to allow removal of the pump assembly. This must not be uncoiled to provide extra length.
2. A fitting and securing clip (Fig. B) to accept the 10mm PVC pipe and connect to 21.5mm overflow pipe is also supplied. When using this fitting to connect to a 21.5mm overflow tee piece the branch must be vertical ± 10° (Fig. C).
3. Feed the pipe through the grommet in the rear panel and connect to the drain system.
Fig. B
Termination via internal discharge branch e.g sink waste - downstream
Direct Connect Fitting
Sink
From Boiler
Fig. C
Termination to a drain or gully
From Boiler
Fig. E
Pipe must terminate above water level but below surrounding surface
From Boiler
8.5mm Ø O.D.
21.5mm Ø O.D. to fit
Overflow Pipe
Termination to an internal soil and vent pipe
Direct Connect Fitting
Min. 450mm
Fig. D
Pipe must terminate above water level but below surrounding surface
Termination to a purpose made soak-away
From Boiler
Branch of Tee to be ± 10° from vertical
500mm Min
Holes in the soak­away must face away from the building
4. The 10mm pipe can be routed to a maximum of 3 metres vertically and then discharge via gravity or be routed horizontally (Fig. A). A combination of vertical and horizontal runs is permissible.
5. The pipe must be supported, either using suitably spaced clips or run within larger diameter pipe. When using clips take care not to deform the pipe.
6. When routing the pipe through a wall it must be suitably sleeved. Also the pipe must not be exposed to sources of heat, and should be protected in locations where it may be damaged.
7. The pipe should be routed so that any sharp bends, dips and loops are avoided. A minimum radius of 100mm is recommended for any bends. No slope is necessary and air breaks are not required on the pumped part of the condensate run.
8. If the boiler is fitted in an unheated location the entire length of condensate pipe should be treated as external, and run within insulated larger diameter pipe.
9. Ensure that the condensate can discharge freely (without blockage or restriction of the pipe) into the drain.
10. Examples are shown of condensate pipe methods of termination:-
i) via an internal discharge branch
(e.g. sink waste) - Fig. B.
ii) to an internal or external soil and vent
pipe - Fig. C.
iii) to a drain or gully - Fig. D. Ensure that
the condensate can discharge freely (without blockage or restriction of the pipe) into the drain.
iv) to a soakaway - Fig. E.
32
© Baxi Heating UK Ltd 2011
Fig. F
Page 33
10.0 Installation
10.7 Making The Electrical Connections
WARNING: This boiler must be earthed
IMPORTANT: Four core cable is required to supply the boiler as a permanent live is necessary for the operation of the condensate pump and frost protection.
1. The electrical connections are on the right hand side of the boiler. Depending upon the nature of the installation it may be preferable to wire up to the boiler first before manoeuvering into position.
2. Undo the two screws securing the cable clamp and place to one side (Fig. 31).
3. Route the incoming electrical cable(s) from the system control wiring centre through the grommet in rear of the boiler and the grommet in the support bracket. This will prevent damage to the cable(s).
4. Lay the cable through the cable clamp to gauge the length of wire required when it is connected to the 4-way terminal block.
Cable Clamp
4-way Terminal Block
S/L N
Fig. 31
P/L
5. Connect the (S/L), ( ), (N) and (P/L) wires to the 4-way terminal block (Fig. 33) and refit the cable clamp (Fig. 31).
INTEGRAL PROGRAMMER If the optional integral programmer is being fitted it can be done at this stage. Consult the instructions supplied in the programmer kit.
Check the electrical installation for; earth continuity, short circuits, resistance to earth, correct polarity and fuse rating.
Fig. 32
Fig. 33
Wiring from System
Controls
Switched Live
S/L
Earth Neutral
N
Permanent Live
P/L
© Baxi Heating UK Ltd 2011
33
Page 34
11.0 Electrical
11.1 Schematic Wiring Diagram
Spark Electrode
Condensate
g/y
Flame
Detection
Electrode
g/y
op
Tr ap
w
Condensate Removal System
Condensate
Flow
Over-Level Switch
bk
w
Fan
Overheat
Thermostat
bk
Gas
Valve
w
r
bk
bk
Overheat
Thermostat
Condensate Pump
LN
b
br
r
Condensate Level Switch
Flow
Thermistor
r
r
325 Vdc DC Fan
g/y
b
g
w
br
CH
Flow
Switch
gy
gy
gy
gy
Fuse 3.15 AT
PCB
DHW Out
b
br
o
Electrical
Filter
g/y
DHW Off
Out
CH Out
Optional Internal Timer
o
v
y
b
br
Earths not shown to aid
clarity of diagram
Key To Wiring Colours
b- Blue bk - Black w- White br - Brown gy - Grey o - Orange
r- Red g - Green g/y- Green/Yellow op - Opaque y - Yellow v - Violet
S/L
Permanent Live
Neutral
Earth
Switched Live
Boiler Connection (4 Core Cable)
P/L
N
34
© Baxi Heating UK Ltd 2011
Page 35
Flow Thermistor
11.0 Electrical
11.2 Illustrated Wiring Diagram
P/L
N
S/L
gy
gy
Layout of PCB Pins
g/y
CH Flow Switch
br
r
r
b
g/y
o
g/y
Electrical Filter
b
Main PCB
br
br
Spark Electrode
Flame Detection Electrode
g/y
g/y
w
op
w
Condensate Trap
g
r
bk
w
r
b
w
gy
gy
br
b
bk
bk
Gas Valve
Fan Overheat Thermostat
Fan
© Baxi Heating UK Ltd 2011
g/y
bk
Flow Overheat Thermostat
Wiring Key b- Blue
bk - Black br - Brown r- Red w- White g/y - Green/Yellow g - Green gy - Grey op - Opaque y - Yellow
35
Page 36
IN OUT
Flue Sampling Point
12.0 Commissioning the Boiler
12.1 Commissioning the Boiler
WARNING: The PCB Control and Fan Assembly are 325 Vdc. Isolate at supply before access.
1. Reference should be made to BS:EN 12828 & 14336 when commissioning the boiler.
DO NOT check gas pressure here
Inlet Gas Pressure Test Point
Low
High
Central Heating Control Knob
(No OFF Position)
Manual Air Vent
Gas Service
Cock
Fig. 35
Open
Fig. 36
Turn the Central Heating Control Knob clockwise to increase or anticlockwise to decrease the boiler flow temperature.
Fig. 34
2. At the time of commissioning, complete all relevant sections of the Benchmark Checklist at the rear of this publications.
3. Flush the whole system using a suitable flushing agent (see Section 6.2) and vent the radiators. Check for water leaks.
4. Refill the system with inhibitor following the inhibitor manufacturer’s instructions and BS 7593 Code of Practice for Treatment of Water in Domestic Hot Water Central Heating Systems (see Section 6.2).
5. Complete the label supplied with the inhibitor and attach to the inside of the boiler case. Detail of system treatment should be added for future reference.
6. Turn the gas supply on and purge according to in GB BS 6891 and in IE I.S. 813 “Domestic Gas Installations”.
7. Turn the gas service cock anticlockwise to the ON position and check for gas tightness up to the gas valve (Fig. 34). Turn the power to the boiler ON.
IMPORTANT: The combustion for this appliance has been checked, adjusted and preset at the factory for operation on the gas type specified on the appliance data plate. No measurement of the combustion is necessary. Do not adjust the air/gas ratio valve.
8. Having checked:
•That the boiler has been installed in accordance with these instructions.
•The integrity of the flue system and the flue seals.
•The integrity of the boiler combustion circuit and the relevant seals.
Proceed to put the boiler into operation as follows:
Reset Button
Reset
Mains On
(Green Light)
Burner On
(Green Light)
Flame Failure
(Red Light)
Condensate Pump
(Green Light)
36
© Baxi Heating UK Ltd 2011
The Reset Button should extinguish the Flame Failure Light and restore normal operation.
This indicates that there is electricity to the Boiler.
This indicates that the Burner has fired up and is heating your system.
If Flame Failure Light is ON. Press the Reset Button. If Flame Failure occurs persistently consult your Installer or Service Engineer.
This indicates that the Condensate Pump is running. The pump ONLY runs when the condensate reservoir is full.
Fig. 36a
12.2 Priming the Condensate Pump
1. Using a funnel and tube, carefully pour approximately 1litre of tap water into the flue products exhaust at the terminal or flue elbow sampling point to fill the trap and allow the condensate pump reservoir to fill.
2. Continue filling with water until the condensate pump operates.
3. Check that the condensate drain pipework is not leaking and that it is discharging correctly to drain.
4. See Fig. 36a for operation of LEDs on boiler facia.
Page 37
IN OUT
DO NOT check gas pressure here
12.0 Commissioning the Boiler
12.3 Check the Operational (Working) Gas
Inlet Pressure
1. Ensure that all controls are calling for heat and maximum load is applied to the system.
2. With the boiler operating in the maximum rate condition check that the operational (working) gas pressure at the inlet gas pressure test point is in accordance with B.S. 6798 & B.S. 6891.
3. Ensure that this inlet pressure can be obtained with all other gas appliances in the property working.
Measure the Gas Rate
4. With any other appliances & pilot lights turned OFF the gas rate can be measured. It should be as shown in Section 4.0 Technical Data.
5. Carefully read and complete all sections of the Benchmark Commissioning Checklist at the rear of this publication that are relevant to the boiler and installation. These details will be required in the event of any warranty work. The publication must be handed to the user for safe keeping and each subsequent regular service visit recorded.
Inlet Gas Pressure Test Point
Fig. 36b
6. For IE, it is necessary to complete a “Declaration of Conformity” to indicate compliance with I.S. 813. An example of this is given in I.S. 813 “Domestic Gas Installations”. This is in addition to the Benchmark Commissioning Checklist.
© Baxi Heating UK Ltd 2011
37
Page 38
Outercase Securing
Screws
13.0 Completion
13.1 Fitting The Case Panels & Facia
1. Refit the case top panel and front door, securing with the screws previously removed (Fig.37).
2. Locate the facia panel and secure with the screws previously removed (Fig. 38).
3. The “Important Ventilation Information” label can be removed unless the boiler is installed in an unventilated compartment.
13.2 ‘Benchmark’ Checklist
1. Carefully read and complete all sections of the Benchmark Commissioning Checklist at the rear of this publication that are relevant to the boiler and installation. These details will be required in the event of any warranty work. The publication must be handed to the user for safe keeping and each subsequent regular service visit recorded.
Facia Securing Screws
2. For IE, it is necessary to complete a “Declaration of Conformity” to indicate compliance to I.S. 813. An example of this is given in I.S. 813 “Domestic Gas Installations”. This is in addition to the Benchmark Commissioning Checklist.
Fig. 37
13.3 Handover
1. Instruct the user in the operation of the boiler and system controls. Hand over the User’s Operating, Installation and Servicing Instructions, giving advice on the necessity of regular servicing.
2. Demonstrate to the user the action required if a gas leak occurs or is suspected. Show them how to turn off the gas supply at the meter control, and advise them not to operate electric light or power switches, and to ventilate the property.
3. Show the user the location of the system control isolation switch, and demonstrate its operation.
4. Advise the user that they may observe a plume of vapour from the flue terminal, and that it is part of the normal efficient operation of the boiler.
38
© Baxi Heating UK Ltd 2011
Fig. 38
Page 39
14.0 Servicing the Boiler
14.1 Annual Servicing
WARNING: The PCB Control and Fan Assembly are 325 Vdc. Isolate system controls before access.
IMPORTANT: When servicing ensure that both the gas and electrical supplies, including Switched and Permanent Live to the boiler are isolated before any work is started. The four LEDs on the facia will all be OFF.
It is important to isolate the electrical supply at the system isolation switch as it is not possible to do this on the boiler itself.
Hazardous materials are not used in the construction of this product, however reasonable care during service is recommended - see Section 1.2.
When replacing the combustion box door after servicing it is essential that the retaining screws are tightened fully.
1. For reasons of safety and economy, it is recommended that the boiler is serviced annually. Servicing must be performed by a competent person in accordance with B.S. 7967-4.
2. After servicing, complete the relevant Service Interval Record section of the Benchmark Commissioning Checklist at the rear of this publication.
IMPORTANT:During routine servicing, and after any maintenance or change of part of the combustion circuit, the following must be checked:-
•The integrity of the complete flue system and the flue seals.
•The integrity of the boiler combustion circuit and relevant seals as described in Section 14.2.
•The operational gas inlet pressure as described in Section
12.2.1 to 12.2.3 and the gas rate as described in 12.2.4.
•The combustion performance as described in ‘Check the
Combustion Performance’ (14.1.4 to 14.1.6 below).
3. Competence to carry out Checking Combustion
Performance
B.S. 6798 ‘Specification for Installation & Maintenance of Gas Fired Boilers not exceeding 70kW’ advises that:-
• The person carrying out a combustion measurement should have been assessed as competent in the use of a flue gas analyser and the interpretation of the results.
• The flue gas analyser used should be one meeting the requirements of BS7927 or BS-EN50379-3 and be calibrated in accordance with the analyser manufacturers’ requirements.
• Competence can be demonstrated by satisfactory completion of the CPA1 ACS assessment, which covers the use of electronic portable combustion gas analysers in accordance with BS 7967, Parts 1 to 4.
2
Check the Combustion Performance (CO/CO
ratio)
4. Set the boiler to operate at maximum rate as described in
Section 12.2.
5. Remove the cap from the flue sampling point, insert the
2
analyser probe and obtain the CO/CO
ratio. This must be
less than 0.004.
2
6. If the combustion reading (CO/CO
ratio) is greater than this, and the integrity of the complete flue system and combustion circuit seals has been verified, and the inlet gas pressure and gas rate are satisfactory either:
•Perform the ‘Annual Servicing - Inspection’ (Section 14.2) &
re-check.
•Replace the gas valve (Section 15.8) & re-check.
© Baxi Heating UK Ltd 2011
39
Page 40
14.0 Servicing the Boiler
14.2 Annual Servicing - Inspection
WARNING: The PCB Control and Fan Assembly are 325 Vdc. Isolate system controls before access
1. Ensure that the boiler is cool.
2. Remove the facia and front door panel.
Air Box Door Panel
Spark
Sleeve
Earth
Sensing
Lead Terminals
Fig. 40
Fig. 39
3. Release the four
1
/4turn screws securing the air box door
panel and remove the panel (Fig. 39).
4. Disconnect the three leads from the terminals (Fig. 40).
5. Undo the four screws securing the combustion box door and remove the door (Fig. 41).
6. Visually check for debris/damage and clean or replace if necessary the following:
a) Burner. b) Heat exchanger fins. c) Fan compartment d) Insulation. e) Door seals-Important: Pay particular attention to
the condition of the combustion box door seals.
f) Electrodes. g) The condensate trap. h) The condensate pump
i) Top of heat exchanger.
(Check also for condensate leaks).
40
© Baxi Heating UK Ltd 2011
Combustion Box
Door Panel
Fig. 41
Page 41
Flue Sampling Point
14.0 Servicing the Boiler
14.2 Annual Servicing - Inspection (Cont)
7. To clean the heat exchanger and burner proceed as follows:
a) Disconnect the electrical leads to the fan component protection sensor (Fig. 42).
Injector Pipe
Injector Pipe Retaining
Screw
Protection
Sensor Leads
Fig. 42
Wing Nuts
Central Insulation Panel
Fig. 41a
Electrical Supply
Trap to Condensate Pump Inlet Pipe
Fan
Sensor
Leads
Condensate
Lock Nut
Fig. 43
Securing Nut
Trap
Service Drain Plug
b) Loosen the screw retaining the gas injector pipe at the venturi (Fig. 42).
c) Undo the two wing nuts to disconnect the fan (Fig. 42).
d) Remove the fan and disconnect the electrical supply to it (Fig. 42).
e) Remove the gas injector pipe from the gas valve (push-fit) (Fig. 42).
f) Remove the condensate trap drain plug and place a vessel underneath to catch the condensate (care should be taken as this could be hot). The condensate drain pipe may be removed to increase access.
g) Undo the condensate trap securing nut, lock nut and the condensate drain pipe. Remove the condensate trap and disconnect the sensor leads (Fig. 43). Clean the trap and refit the drain plug.
h) Remove the two screws securing the burner and remove the burner. Visually inspect the internal burner baffle for obstruction, check seal around baffle for cracks/damage. Clean with a soft brush.
i) Loosen the two screws retaining the heat exchanger support bracket and slide to the left to remove (Fig. 44).
j) Remove the four screws securing the heat exchanger/combustion box base and withdraw the base.
k) Lower the central insulation panel and check condition (Fig. 44). Replace the lower insulation pad if necessary.
Combustion Box Base
Burner Securing
Screws
© Baxi Heating UK Ltd 2011
Burner
Combustion
Box Base
Heat Exchanger Support Bracket
Securing Screws
Fig. 44
l) Ensure the heat exchanger fins are clear of any obstruction.
m) Check condition of all seals. Important: Pay
particular attention to the condition of the combustion box door seals.
n) Reassemble in reverse order and check for leaks.
8. Check the operation of the condensate pump and drain pipework (see Section 10.1)
2
9. Check CO/CO
ratio at flue sampling point (Fig.41a).
See section 4.0.
10. Complete the relevant Service Interval Record section of the Benchmark Commissioning Checklist at the rear of this publication and then hand it back to the user.
41
Page 42
15.0 Changing Components
15.1 Changing Components & Preparation
WARNING: The PCB Control and Fan Assembly are 325 Vdc. Isolate system controls before access.
IMPORTANT: Ensure that both the gas and electrical supplies, including Switched and Permanent Live to the boiler are isolated before any work is started. The four facia LEDs will be all OFF.
It is important to isolate the electrical supply at the system isolation switch as it is not possible to do this on the boiler itself.
Hazardous materials are not used in the construction of this product, however reasonable care is recommended
- see Section 1.2. When replacing the combustion box door it is essential
that the retaining screws are tightened fully.
Remove the facia and front door panel.
Safety
Thermostat
(Black)
Fig. 45
Heat Exchanger
Manifold
Drain Point
Electrical Connections
Flow Temperature Thermistor (Red)
Tube
Pipe Access
Panel
For the replacement of some components it will be necessary to drain the boiler. Proceed as follows:-
1. Isolate the water circuit and drain the system as necessary. A drain point is located on the heat exchanger manifold at the right hand side of the boiler (Fig. 45) to enable the heat exchanger to be drained.
2. Place a tube on the drain point to drain water away from the electrics. Turn anticlockwise to open (Fig. 45).
3. After changing a component recommission the boiler where appropriate and check the inhibitor concentration (see Section 6.2 and 10.1).
The thermistor, safety thermostat, interface PCB and the flow switch can be accessed after removal of the pipe access panel (Fig. 46).
15.2 Flow Temperature Thermistor and
Safety Thermostat
(Fig. 46)
1. The procedure is the same for both the thermistor and the safety thermostat.
2. Remove the pipe access panel and disconnect the electrical connections from the sensor.
42
© Baxi Heating UK Ltd 2011
Fig. 46
3. Remove the sensor from the pipe.
4. Fit the new thermistor or safety thermostat and reassemble in reverse order.
Page 43
Support Bracket
Pipe Access
Panel
15.0 Changing Components
15.3 Flowswitch (Fig. 47)
1. Drain the boiler (see Section 13.1 paragraph 2 & 3).
2. Remove the pipe access panel and remove the securing clip from the ‘O’ ring joint between the flow pipe and the system. Undo screws on support bracket.
3. Remove the securing clip from the ‘O’ ring joint between the flow pipe and the flowswitch.
4. Remove the two screws securing the flow switch to the boiler.
5. Disconnect the inline electrical connection and remove the flowswitch.
Flow Switch
Over Level Switch
Clip
Flow Pipe
Fig. 47
6. Fit the new flowswitch and reassemble in reverse order.
7. Recommission the boiler and check the inhibitor concentration (see Section 6.2 and 10.1).
15.4 Condensate Pump - Complete (Fig. 47a)
1. Remove the pipe from the trap to the pump inlet and disconnect the electrical plug.
2. Lift the pump off the support studs and ease it forwards. Release the snap fit clip and disconnect the condensate outlet pipe.
3. Connect the condensate outlet pipe to the new pump using the new clip provided.
4. With the new pump in place on the studs, refit the trap discharge pipe, ensuring the ‘O’ ring is in place. Reconnect the electrical plug.
5. Neatly coil the excess condensate outlet pipe adjacent to the pump, ensuring that it is not kinked or restricted.
6. Check operation of the pump - See Section 10.2.
Fig. 47a
Level Switch
© Baxi Heating UK Ltd 2011
Condensate Pump (Cover Removed)
15.5 Condensate Pump - Level Switches
(Fig. 47a)
1. Remove the complete Condensate Pump as described in Section 13.4, and remove the cover.
2. Disconnect the wires from the switch(es) and remove the retaining screws. On the Level Switch remove the circlip and washers connecting the plunger to the actuating arm.
3. Fit the new switch(es). Align the actuating arm of the Level Switch with the plunger, ensuring that there is a washer at each side of the arm.
4. Reconnect the wires. On the Over Level Switch there is no connection to the lower spade terminal.
5. Check operation of the pump - See Section 10.2.
43
Page 44
Control Knob
Fig. 48
Plastic Button Cover
PCB Housing Securing Screw
15.0 Changing Components
15.6 PCB (Figs. 48 & 49)
WARNING: The PCB Control and Fan Assembly are 325 Vdc. Isolate system controls before access.
1. Pull the control knob off the spindle and remove the plastic button cover. Refit them onto the new PCB (Fig. 48).
2. Remove the top right hand securing screw and swing out the PCB housing. Remove the PCB cover and disconnect the electrical plugs noting their positions
3. Remove the screw securing the PCB to the housing. The PCB can be removed from the housing.
4. Ensure that the two jumpers are fitted to the new PCB as shown (Fig. 49).
5. Reconnect the plugs, fit the new PCB to the housing and reassemble in reverse order.
Hinge open PCB Housing
Blue (CN11) Jumper
Red (CN12) Jumper
Fig. 49
44
© Baxi Heating UK Ltd 2011
Page 45
Air Box Door Panel
15.0 Changing Components
The fan and venturi, gas valve, injector pipe, condensate trap, fan protection sensor, spark and sensing electrodes can be accessed and changed on the removal of the airbox door panel.
1. Remove the airbox door panel by loosening the four
1
/4turn screws (Fig. 50).
15.7 Spark and Sensing Electrodes
(Fig. 51)
1. Disconnect all three leads from tabs. Spark - Opaque cable Earth - Green/Yellow cable Sensing - White cable
2. Remove the two screws securing each of the
electrodes to the combustion box door and remove the electrodes.
3. Fit the new electrodes (and new gasket, as required)
and reassemble in reverse order.
Spark
Earth
Injector Pipe
Screw
Sensing
Fig. 51
Combustion
Box Door
Injector
Opening
Gasket
Fig. 50
15.8 Fan (Fig. 52)
WARNING: The PCB Control and Fan Assembly are 325 Vdc. Isolate system controls before access.
1. Loosen the screw holding the injector pipe into the
venturi.
2. Remove the electrical connections to the fan and
protection sensor on the fan.
3. Remove the wing nuts securing the fan to the base of
the combustion box.
4. Lower the fan and remove.
5. If changing the fan, remove the screws securing the
venturi and fan protection sensor bracket, noting the positions of the injector opening and sensor bracket, fix them to the new fan.
6. Fit the new fan and reassemble in reverse order.
Fan
The injector pipe, condensate trap and gas valve can be changed after the removal of the fan.
Electrical Connections
© Baxi Heating UK Ltd 2011
Protection
Sensor
Fig. 52
Venturi
Wing Nuts
Electrical Connection
45
Page 46
15.0 Changing Components
The removal of the fan is necessary to enable the changing of the injector pipe, condensate trap and gas valve (see section
13.6).
15.9 Injector Pipe (Fig. 53)
1. Remove the injector pipe by pulling out from the ‘O’ ring
joint in the gas valve.
2. Fit the new injector pipe and reassemble in reverse order.
Injector Pipe
Boiler Side
Fig. 53
Gas Valve
Securing Screws
Aluminium
Spacer
Case Pressure Pipe
Gasket
‘O ring’
Electrical Plug
Gas Valve
Gas Tap
15.10 Gas Valve (Fig. 53)
IMPORTANT: After replacing the valve the CO2must be checked as detailed in Section 14.1.4 to 14.1.6. Only change the valve if a suitable calibrated combustion analyser is available, operated by a competent person ­see Section 14.1.3.
1. Isolate gas supply and disconnect the gas tap by removing
the four screws.
2. If required remove the condensate pump to increase access
(see Section 13.4) and undo the case pressure pipe from the valve.
3. Disconnect the electrical plug from the gas valve.
4. Remove the fan (see Section 13.6) and injector pipe.
5. Remove the two gas valve securing screws from inside the
air box holding the gas valve, and remove the valve.
6. Remove the aluminium spacer and its gasket from the gas
valve.
7. Fit the aluminium spacer and its gasket to the new valve.
Securing
Nut
Sensor
Leads
Condensate
Trap
Lock Nut
Trap to Condensate Pump Inlet Pipe
46
© Baxi Heating UK Ltd 2011
Service Drain Plug
Fig. 54
8. Fit the new gas valve and reassemble in reverse order.
NOTE: Check for gas tightness after replacing gas valve.
9. Check the CO
2
level. If the level is greater than that quoted,
telephone the Technical Enquiries for further advice.
15.11 Condensate Trap (Fig. 54)
1. Disconnect the condensate trap from the base of the heat
exchanger.
2. Disconnect the condensate drain ‘O’ ring connection from
the condensate trap and condensate pump. For ease of access also remove the pump.
3. Undo the condensate trap lock nut.
4. Remove the condensate trap from the boiler.
5. Disconnect the sensor leads.
6. Fit the new condensate trap and reassemble in reverse
order. When refitting the pipe from the trap to the pump ensure that all seals and connections are made.
7. Prime the condensate trap (fill first chamber), check for leaks
(see Section 8.5).
Page 47
15.0 Changing Components
Combustion Box
Door Panel
Burner
Fig. 55
Support Bracket
Return
Connection
Fig. 57
The burner and heat exchanger can be changed after removal of the combustion box door. To change the heat exchanger, the fan and burner must be removed first (see section 13.6 and 13.10).
1. Remove the combustion box door by removing the
four securing screws (Fig. 55).
IMPORTANT: On refitting the combustion box door check the condition of the combustion box door seals.
15.12 Burner (Fig. 56)
1. Remove the two screws securing the burner to the
base of the combustion box.
2. Remove the burner carefully from the combustion
box base.
3. Check the burner seal on the heat exchanger base,
replace if necessary. Fit the new burner and reassemble in reverse order.
Fig. 56
Securing Screws
Fig. 58
Heat Exchanger
Manifold
Flow
Switch
15.13 Heat Exchanger
1. Drain the boiler (see section 13.1 paragraph 2 & 3).
2. Remove all components in the base of the airbox.
3. Undo the screws on the support bracket. Remove
the screws securing the flow switch and return connections and remove the connections (Fig. 57).
4. Remove the screws securing the heat exchanger
manifold and remove the manifold (Fig. 58).
5. Ease the combustion box left hand side panel to clear
the stud, lift the heat exchanger assembly (Fig. 59) and rotate the bottom upwards whilst pulling it forwards out of the airbox.
6. Ensure that the heat exchanger is disengaged from
the flue elbow and clear of the stud in the left hand side of the combustion box.
7. Fit the new heat exchanger and reassemble in reverse
order.
Heat Exchanger
© Baxi Heating UK Ltd 2011
Assembly
Fig. 59
8. Recommission the boiler and check the inhibitor
concentration (see Section 6.2 and 10.1).
47
Page 48
Upper Insulation Pad
Lower Insulation Pad
Central Insulation Panel
Burner
Fig. 60
15.0 Changing Components
15.14 Heat Exchanger Lower Insulation Pad
(Fig. 60)
1. Remove all components in the base of the airbox.
2. Remove the burner (see section 13.10).
3. Remove the four bolts securing the combustion box base.
4. Remove the combustion box base.
5. Pull the central insulation panel down from the centre of the heat exchanger and remove the lower insulation pad.
6. Fit the new insulation pad and reassemble in reverse order.
15.15 Heat Exchanger Upper Insulation Pad
(Fig. 60)
1. Remove all components in the base of the airbox.
Burner Securing
Screws
Combustion Box Base
Support Bracket
Combustion Box Base
Securing Screws
2. Remove the burner (see section 13.10).
3. Remove the heat exchanger (see section 13.11).
4. Remove the four bolts securing the combustion box base.
5. Remove the combustion box base.
6. Pull the central insulation panel down from the centre of the heat exchanger.
7. Fit the new insulation pad and reassemble in reverse order.
48
© Baxi Heating UK Ltd 2011
Page 49
16.0 Short Parts List
Short Parts List
ABC
Key G.C. Description Manufacturers No. No. Part No.
A E06 058 Flow Temperature
B E06 059 Flow Switch 242459
C E06 060 Safety Thermostat
D PCB 5129147
E Fan 5109925
E
F Gas Valve 241900
Thermistor (Red) 240670
(Black) 242235
D
G
G E06 085 Viewing Window 242484
H Condensate Trap 5111714
I Electrodes Kit 5132366
J Burner Assy 5107430
K E06 097 Heat Exchanger Assy 242497
L Control Knob 5109996
F
M Condensate Pump 5117661
I
N Level Switch 5117591
O Over Level Switch 5117592
H
J
© Baxi Heating UK Ltd 2011
M
K
N
O
L
49
Page 50
Mains On
LED Light (Green)
Boiler On
LED Light (Green)
denotes LED flashing
*
Lockout
LED Light (Red)
17.0 Fault Finding
NOTE: The fan is supplied with 325 Vdc.
Fan Fault Finding should only be carried out after the boiler has been electrically isolated.
General Fault Finding should only be carried out by someone who is appropriately qualified.
Lights
Off Off Off
Lights
Off On
*
Lights
On
*
*
Lights
On Off On
YES
YES
YES
YES
Go to Electrical Supply
section of the fault finding
instructions.
Live & Neutral Reversed
Incoming Live and Neutral
reversed.
Go to Dry-Fire
section of the fault finding
instructions.
Go to Ignition Lockout section
of the fault finding instructions.
Lights
On On
*
Lights
Off onn
*
*
Lights
On On On
Lights
On onn
*
*
YES
YES
YES
YES
Go to Thermistor section
of the fault finding
instructions.
Low Electrical Supply
Incoming Voltage less than
180V. Check System
Controls & System Wiring.
Otherwise contact Electricity
LV Wiring Harness
Ensure the small 8 way
connector is securely plugged
into the PCB. If the fault
persists replace wiring harness.
PCB Fault
Replace PCB.
Provider.
Lights
On Off on
On on onn
50
© Baxi Heating UK Ltd 2011
Lights
*
Lights
On On
*
*
*
YES
YES
Go to Overheat Lockout section of the fault finding
instructions.
Go to Fan Lockout
section of the fault finding
instructions.
Lights
On On onn
*
Lights
On
*
*
YES
YES
YES
PCB Fault
Replace PCB.
PCB Fault
Replace PCB.
Go to Condensate Pump section of the fault finding
instructions.
Page 51
ELECTRICAL SUPPLY
Lights
Off Off Off
17.0 Fault Finding
240V at A ?
YES
240V at B ?
YES
240V at C ?
YES
240V at D ?
NO
NO
NO
NO
No Permanent Live to
boiler. Check Mains Fuse
and
System Wiring.
No Switched Live to boiler. Check System Controls and System
Wiring.
Check P/L wiring from terminal block to PCB.
Check S/L wiring from terminal block to PCB.
S/L
A
B
P/L
N
YES
PCB fuse OK ?
YES
Replace PCB.
NO
Check for short circuit on
condensate pump, fan &
gas valve. Replace if
shorted & replace fuse.
Fuse
C
D
© Baxi Heating UK Ltd 2011
51
Page 52
DRY-FIRE
*
Lights
*
On
17.0 Fault Finding
Is the
system full of water ?
YES
Is the
pump running ?
YES
Unplug
5-way PCB
connector. Is
there continuity
between H
NO
NO
NO
YES
Fill system with water and
bleed out all air.
Pump or Pump Wiring
fault.
Replace PCB.
H
Viewed from
Wire Entry end
Disconnect
Flow Switch Inline
connector. With pump running is
there continuity across flow
switch ?
NO
Remove
flow switch from boiler.
Is there a physical blockage to
the paddle within the
flow switch ?
YES
Remove Blockage.
YES
NO
Wires from inline
connector to PCB faulty.
Is there a
blockage in the system ?
YES
Remove Blockage.
NO
Replace Flow Switch.
52
© Baxi Heating UK Ltd 2011
Page 53
IGNITION LOCKOUT
Is there
gas at gas valve inlet ?
YES
NO
Lights
On Off On
Check isolation valve and
gas supply.
17.0 Fault Finding
I
Gas Valve 5-way
Connector Plug
J
Reset Lockout.
Is there gas flow
(check at meter) ?
YES
Is
there at least
18mbar dynamic at gas valve
inlet ?
YES
Is
Condensate Trap
blocked or water on
terminals ?
NO
Is
Condensate Pump
reservoir full ?
NO
YES
YES
NO
Remove Gas Valve & check
inlet filter for blockage.
Otherwise incorrect gas supply
to boiler.
Clear blockage and dry
sensors.
Check and if necessary
change over level switch
(see Section 13.5)
Remove
5-way connector
from gas valve. Is there 240
Vdc between I & J
during ignition ?
NO
Remove
the larger of the
two 6-way PCB connectors.
Is there continuity from I to L
& from J to K ?
YES
Replace PCB.
6-way Connector
YES
Replace Gas Valve.
NO
K L
Lead from PCB to Gas
Valve faulty.
NO
Is
spark or flame detection
probe damaged ?
NO
Is
spark gap between 3 and
4mm ?
YES
Is
wiring from PCB
to spark probe & flame
detection probe OK ?
NO
Rectify wiring.
YES
NO
YES
Replace spark or flame
detection probe and
gaskets.
Set spark gap to 3.5mm.
Is the
burner blocked or
damaged ?
YES
Clean burner or replace as
necessary.
NO
Replace PCB.
© Baxi Heating UK Ltd 2011
53
Page 54
OVERHEAT LOCKOUT
Lights
On Off onn
17.0 Fault Finding
*
Disconnect
black stat on flow pipe.
When flow < 60° C is there
continuity across stat ?
YES
Reconnect stat.
Disconnect fan stat.
When fan temp < 60° C
is there continuity
across stat ?
YES
Reconnect stat.
Disconnect the larger of
the 6-way PCB connectors.
Is there continuity
across M ?
YES
Disconnect
thermistor
(red sensor on flow pipe).
Is resistance between
0.5kë & 20kë ?
NO
NO
NO
NO
Replace Stat.
Replace Stat.
Wiring from PCB to
thermostats faulty.
Replace thermistor.
M
6-way Connector
YES
Is
combustion chamber
door seal damaged or not in
place ?
NO
Replace PCB.
YES
Replace combustion
chamber door seal & trim
seal.
54
© Baxi Heating UK Ltd 2011
Page 55
FAN LOCKOUT
Lights
On on on
*
*
17.0 Fault Finding
NOTE: The fan is supplied with 325 Vdc.
Fan Fault Finding should only be carried out after the boiler has been electrically isolated.
Unplug
3-way PCB connector
& unplug fan. Is there
continuity from N to O &
from P to Q ?
YES
Unplug
the smaller of the
6-way PCB connector. Is there
continuity from R to S & from T
to U & from
V to W ?
YES
Replace fan.
NO
NO
Rectify wiring.
Rectify wiring.
N
P
R
T
V
Fan
Connection
Fan
Connection
PCB
Connection
O Q
PCB
Connection
S U W
Viewed from
Wire Entry end
© Baxi Heating UK Ltd 2011
55
Page 56
THERMISTOR
Lights
On On
*
17.0 Fault Finding
Unplug
thermistor,
Is thermistor resistance between
0.5kë & 20kë ?
YES
Plug in
thermistor, leave
8-way connector unplugged.
Is resistance at D between
0.5kë & 20kë ?
YES
Replace PCB.
NO
NO
Replace thermistor.
Wiring from PCB to
thermistor faulty.
D
Viewed from
Wire Entry end
56
© Baxi Heating UK Ltd 2011
Page 57
CONDENSATE PUMP
17.0 Fault Finding
Reset boiler
and add approx. 1 litre
tap water to the condensate
system via the flue or
sample point
Does the
pump motor run as
the condensate level
rises ?
YES
NO
On Off On
Condensate pump over level
switch activated - pump
reservoir level too high
resulting in ignition lockout.
Mechanical fault
on float, linkage or switch. Mechanical fault on pump
or impellor.
YES
If fault cannot be rectified
replace level switch or
pump assembly.
Lights
NO
Condensate pump level switch
activated for longer than 3
minutes - boiler locks out.
Boiler will try to relight 4 times
5Vdc at A ?
No - replace PCB
5Vdc at B ? No - check wiring.
240V across C & D ?
No - replace level
switch
Go to diagram for
connections to check
Lights
On
*
*
in 5 minutes.
Is motor
resistance across C & D
approx. 40 ohms ?
No - replace pump
assembly
As the pump motor runs
does the condensate flow to
drain ?
YES
Is
condensate flow
rate at least 1.8 l/min and run
time less than 3
minutes ?
YES
NO
NO
Condensate pump
outlet back check valve blocked or seized shut.
YES
If fault cannot be rectified
replace pump assembly.
Condensate pipe
has high resistance - too long
or restricted, head greater than
3 metres.
YES
Rectify fault, replacing or
re - routing pipe
if necessary.
NO
NO
Condensate pipe
blocked or kinked, or outlet
blocked or frozen
at drain.
YES
Rectify fault, replacing pipe
if necessary.
Pump motor or
impellor worn - replace
pump assembly
Condensate Pump Assembly
Condensate
Over-Level Switch
Condensate Pump
Motor
LN
Condensate Level Switch
Does
pump motor stop
as level in reservoir
falls ?
YES
Operation correct
© Baxi Heating UK Ltd 2011
NO
Mechanical fault on
float, linkage or level switch.
After 3 mins boiler
will lock out.
YES
If fault cannot be rectified
replace level switch or
pump assembly.
‘C’
‘D’
gy
‘B’
gy
PCB
‘A’
57
Page 58
Failure to install and commission according to the manufacturer’s instructions and complete this Benchmark Commissioning Checklist will invalidate the warranty. This does not affect the customer’s statutory rights.
If yes, and if required by the manufacturer, has a water scale reducer been fitted?
CONDENSING BOILERS ONLY
The condensate drain has been installed in accordance with the manufacturer’s instructions and/or BS5546/BS6798 Yes
If the condensate pipe terminates externally has the pipe diameter been increased and weatherproof insulation fitted? Yes
58
Page 59
Service Record
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Signature:
It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed.
Service Provider
Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer’s instructions.
Always use the manufacturer’s specified spare part when replacing controls.
Service 1 Service 2
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Signature:
Service 3 Service 4
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Signature:
Service 5 Service 6
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Signature:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Operative ID No.
Comments:
Signature:
Service 7 Service 8
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Signature:
Service 9 Service 10
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Signature:
59
Page 60
All descriptions and illustrations provided in this leaflet have been carefully prepared but we reserve the right to make changes and improvements in our products which may affect the accuracy of the information contained in this leaflet. All goods are sold subject to our standard Conditions of Sale which are available on request.
POTTERTON
A Trading Division of Baxi Heating UK Ltd (3879156)
Brooks House, Coventry Road, Warwick. CV34 4LL After Sales Service 0844 871 1560 Technical Enquiries 0844 871 1555 Website www.potterton.co.uk e&oe
© Baxi Heating UK Ltd 2011
Comp No. 720896601 (6/11)
Loading...