Baxi Sirius FS 90, Sirius FS 105, Sirius FS 130, Sirius FS 160 Installation, Operation & Maintenance Manual

Page 1
Working towards a cleaner future
Sirius FS 90-105-130-160
Floor Standing Condensing Gas Boilers
Installation, Operation & Maintenance Manual
To be kept by the user October 2010
Page 2
2
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE USER
Dear Customer,
We are sure your new boiler will comply with all your requirements.
Do not dispose of this booklet. This manual contains the information, which will help you to
run your boiler correctly and efciently.
POTTERTON COMMERCIAL boilers bear the CE mark in compliance with the basic requirements as laid down in the following Directives:
- Gas Directive 90/396/EEC
- Efciency Directive 92/42/EEC
- Electromagnetic Compatibility Directive 2004/108/EEC
- Low Voltage Directive 2006/95/EC
Do not leave any parts of the packaging (plastic bags, polystyrene, etc.) within children’s reach as they are a potential source of danger.
ATTENTION
This boiler can only be installed and operate
in permanently, ventilated rooms in accordance with
BS6644
Page 3
3
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE USER
1. Instructions prior to installation 4
2. Instructions prior to commissioning 4
3. Commissioning of the boiler 5
4. Filling the boiler 12
5. Switching the boiler off 12
6. Prolonged standstill of the system. Frost protection 12
7. Servicing instructions and gas change 12
8. General information 13
9. Instructions prior to installation 13
10. Boiler installation and dimensions 14
11. Chimney ue connection 21
12. Connecting the mains supply 23
13. Adjusting the gas valves and gas change 29
14. Setting the boiler parameters 33
15. Control and operation devices 34
16. Positioning of the ignition and ame sensing electrode 35
17. Check of combustion parameters 35
18. Activating the chimney-sweep function 36
19. Annual service 36
20. Boiler schematic 37
21. Illustrated wiring diagram 38-39
22. Technical data 40
CONTENTS
INSTRUCTIONS PERTAINING TO THE USER
INSTRUCTIONS PERTAINING TO THE INSTALLER
Page 4
4
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE USER
This boiler is designed to heat water at a lower than boiling temperature at atmospheric pressure. The boiler must be connected to a central heating system and/or to a domestic hot water supply system in compliance with its performances and output power.
The boiler must be installed by a Qualied Service Engineer and ensure the following operations are carried out:
a) Check that the boiler is t for operation with the type of gas available. For more details see the notice on the packaging
and the label on the appliance itself.
b) Careful checking that the ue terminal draft is appropriate; that the terminal is not obstructed and that no other appliance
exhaust gases are expelled through the same ue duct, unless the ue is especially designed to collect the exhaust gas
coming from more than one appliance, in conformity with the standards and regulations in force.
c) Careful checking that, in case the ue has been connected to pre-existing ue ducts, thorough cleaning has been carried
out in that residual combustion products may come off during operation of the boiler and obstruct the ue duct.
d) To ensure correct operation of the appliance and avoid invalidating the warranty, observe the following precautions:
1. Heating circuit
1.1. New system Before proceeding with installation of the boiler, the system must be cleaned and ushed out thoroughly to eliminate
residual thread-cutting swarf, solder and solvents if any, using suitable proprietary products.
To avoid damaging metal, plastic and rubber parts, use only neutral cleaners, i.e. non-acid and non alkaline. The
recommended products for cleaning are:
SENTINEL X300 or X400 and FERNOX heating circuit restore. The use of this product must be strictly in accordance
with the maker’s directions. Finally the system must be dosed with a suitable inhibitor at 1% system volume.
1.2. Existing system
Before proceeding with installation of the boiler, the system must be cleaned and ushed out to remove sludge and
contaminants, using suitable proprietary products as described in section 1.1.
To avoid damaging metal, plastic and rubber parts, use only neutral cleaners, i.e. non-acid and non-alkaline such
us SENTINEL X100 and FERNOX heating circuit protective. To use this product proceed strictly in accordance with the maker’s directions. Dose with inhibitor.
Remember that the presence of foreign matter in the heating system can adversely affect the operation of the boiler
(e.g. overheating and noisy operation of the heat exchanger).
Failure to observe the above will render the warranty null and void.
1. INSTRUCTIONS PRIOR TO INSTALLATION
Initial lighting of the boiler must be carried out by a qualied service engineer. Ensure the following operations are carried
out: a) compliance of boiler parameters with (electricity, water, gas) supply systems settings. b) compliance of installation with the standards and regulations in force. c) appropriate connection to the power supply and earthing of the appliance. Failure to observe the above will render the warranty null and void.
The instructions shall state the substance of the following: This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concer­ning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
2. INSTRUCTIONS PRIOR TO COMMISSIONING
Page 5
5
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE USER
KEYS DISPLAY SYMBOLS
Central heating mode setting key
Data display reset key
Parameter setting key (increase value)
Parameter setting key (decrease value)
Program access and scroll key
Program access and scroll keys
Reset key
Domestic hot water temperature setting key
Central heating water temperature setting key
Domestic hot water on/off key
Resettable alarm warning
MAIN display
SECONDARY display
Flame present (on)
Outdoor temperature
Standby (off)
Operation in manual mode at minimum tem­perature
Operation in manual mode at the maximum temperature set
Operation in automatic mode
Operation in central heating mode
Operation in domestic hot water mode
020503_1100
Figure 1
IMPORTANT: Domestic Hot Water (D.H.W.) instructions discribed here, are to be taken into account only if the boiler is connected to a D.H.W. production system.
To correctly light the burner proceed as follows:
1) Provide power supply to the boiler;
2) Open the gas cock;
3) Follow the directions given below regarding the adjustments to be made at the boiler control panel.
3. COMMISSIONING OF THE BOILER
Page 6
6
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE USER
020503_0800
Figure 2
Automatic operation. Operation of the boiler is controlled by the timed program as described
in point 3-5.1 “Daily timed program for operation of the central heating system”;
Manual operation at the maximum temperature set. The boiler comes into operation regardless
of the timed program set. The operating temperature is that set using the key (point 3-3:
“Setting the maximum central heating temperature”);
Manual operation at minimum temperature. The operating temperature is that set in point
3-6: “setting the minimum central heating temperature”.
Standby. The boiler does not work in central heating mode, although the antifreeze function is
still enabled.
(1) Domestic hot water on/off key: This key can be pressed to activate or deactivate this function,
which is identied on the display by a black cursor line under the symbol .
(4) Reset key. In case of a fault, referred to in point 3-7 “Faults and resetting the boiler”, the boiler can
be restarted by pressing this key for at least two seconds (see 3-8).
If this key is pressed with no fault present, the display will show the message “E153”, and the same key
has to be pressed again (for at least two seconds) to restart the boiler.
(9) Data key. This key can be pressed repeatedly to display the following information:
- Temperature (°C) of the domestic hot water ( );
- outdoor temperature (°C) ( ); only provided with the outdoor temperature sensor probe connected.
Press either of the keys to return to the main menu.
Dash
“Automatic mode”
active
(2)
Central heating water temperature setting key.
This key can be pressed to set the central heating
water output temperature as described in point 3-3.
(3) Domestic hot water temperature setting key. This key can be pressed to set the domestic hot
water temperature as described in point 3-4.
(10) Central heating mode operating key
.
The key can be pressed to activate four boiler central heating operating modes; these modes are
identied by a black cursor line underneath the relative symbol on the display, and are as follows:
3.1 DESCRIPTION OF KEYS
Page 7
7
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE USER
Press either of the keys to access the programming function;
the display will show the letter P followed by a number (program line);
Press the keys until the display shows P1, referring to the time to be set;
Press the keys to set the time; on the display, the letter P will start to ash;
Press the key to save and exit the programming function;
020503_0700
Figure 3
3.2 SETTING THE TIME
- Press the key (2-gure 1) to set the central heating water temperature;
- Press the keys to set the temperature required;
- Press either of the keys (1 or 10 - gure 1) to save and return to the main menu.
N.B – With the outdoor sensor connected, the key (2 - gure 1) can be used to shift the central heating curve.
Press the keys to decrease or increase the room temperature in the premises to be heated.
3.3 SETTING THE MAXIMUM CENTRAL HEATING TEMPERATURE
- Press the key (3-gure 1) to set the maximum domestic hot water temperature;
- Press the keys to set the temperature required;
- Press either of the keys (1 or 10 - gure 1) to save and return to the main menu.
3.4 SETTING THE MAXIMUM DOMESTIC HOT WATER TEMPERATURE
Page 8
8
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE USER
- Press either of the keys to access the programming function;
a) press these keys until the display shows P11, referring to the program start time;
b) press the keys to set the time;
- Press the key; the display will show P12, referring to the program end time;
- Repeat the operations described in points a and b until the third and last cycle is reached (program line
P16);
- Press the key to save and exit from the programming function.
3.5 SETTING THE DAILY PROGRAM FOR OPERATION IN CENTRAL HEATING AND DOMESTIC HOT WATER MODES
3.5.1 Setting the daily times for central heating mode operation
3.5.2 Setting the daily times for domestic hot water mode operation
- Factory setting of D.H.W. function is enable (ON) while is disabled D.H.W. daily times program. To enable
D.H.W. daily times program see section 14 (parameter H91).
Setting the daily times for domestic hot water mode operation-Carry out the operations described in section
3.5.1 for program lines 31 to 36.
3.6 SETTING THE MINIMUM CENTRAL HEATING TEMPERATURE
- Press either of the keys to access the programming function;
- Press these keys until the display shows P5, referring to the temperature to be set;
- Press the keys to set the temperature required. This operating mode is enabled when minimum temperature central heating mode “ ” is activated or when
the daily central heating program does not require heat.
N.B – With the outdoor sensor connected, parameter P5 can be used to set the minimum room tempe­rature in the premises to be heated (night set-back).
Page 9
9
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE USER
Range
0…23:59
25..80
00:00…24:00
00:00…24:00
00:00…24:00
00:00…24:00
00:00…24:00
00:00…24:00
00:00…24:00
00:00…24:00
00:00…24:00
00:00…24:00
00:00…24:00
00:00…24:00
0...1
Factory
setting
———-
25
6:00
22:00
0:00
0:00
0:00
0:00
0:00
24:00
0:00
0:00
0:00
0:00
0
Parameter description
Time of day setting
Minimum central heating temperature setting (°C)
Start of rst daily period of automatic central heating
End of rst daily period of automatic central heating
Start of second daily period of automatic central heating
End of second daily period of automatic central heating
Start of third daily period of automatic heating
End of third daily period of automatic central heating
Start of rst daily period of domestic hot water production
End of rst daily period of domestic hot water production
Start of second daily period of domestic hot water production
End of second daily period of domestic hot water production
Start of third daily period of domestic hot water production
Fine End of third daily period of domestic hot water production
Reset of daily central heating and domestic hot water production programs (factory settings).
Press the - + keys together for about 3 seconds; the number 1 appears on the display. Conrm by pressing either of the keys
Parameter
N.
P1
P5
P11
P12
P13
P14
P15
P16
*
P31
*
P32
*
P33
*
P34
*
P35
*
P36
P45
*
Parameters for program lines P31 to P36 are displayed only if Domestic Hot Water (D.H.W.) program (pa­rameter H91 see section 14) is activated.
3.7 TABLE FOR USER-SETTABLE PARAMETERS
Page 10
10
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE USER
If a fault occurs, a ashing warning code appears on the display. The fault warnings appear on the main display (gure 1 a) together with the symbol (Figure 4).
To reset, press the reset button for at least two seconds.
020503_0500
Figure 4
020503_0600
Figure 4.1
Fault warnings appear on the secondary display (gure 1 b) alternating with the time, both of them ashing (gure 4.1). It is not possible to reset malfunction warnings which appear on the secondary display as the cause of the alarm has rst to be removed.
3.8 FAULT WARNINGS AND RESETTING THE BOILER
Page 11
11
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE USER
(*) Auotoreset when fault disappears.
All the faults are displayed in order of importance; if several faults occur simultaneously, the rst to be displayed is the one with highest priority. After the cause of the rst fault has been removed, the second one will be
displayed, and so on. If any given fault occurs frequently, contact the authorised Service Centre.
3.9 TABLE OF FAULTS AND ERROR MESSAGES
Corrective action
Call an authorised service centre (*).
Call an authorised service centre (*).
Call an authorised service centre (*).
Press the reset key (for about 2 seconds: if this device is triggered repeatedly, call the authorised service centre)
Call an authorised service centre.
Call an authorised service centre.
Call an authorised service centre to check the gas pressure.
Press the reset key (for about 2 seconds); if the fault persists, call the authorised
service centre to check polarity of ignition electrodes, ionisation current.
If symbol is displayed, press the reset button otherwise switch off the
electricity supply to the boiler for at least 10 seconds; if the fault persists, call the
authorised service centre.
Check the positioning of the ignition and ame sensing electrode (see section 16).
Press the key again (about 2 seconds)
Press and hold reset button (2 seconds approx.) then press again when warning E153 appears
Call an authorised service centre.
Check that the system is at the rated pressure. (Refer to the section on lling the
system). If the fault persists, call the authorised service centre.
Description of fault
Outdoor temperature sensor fault
NTC output sensor failure
Hot water NTC sensor failure
Safety or ue gas thermostat tripped
Loss of ame during operation (the
ionization current has fallen below the limit)
Minimum fan speed limit not reached
Gas pressure switch tripped / external thermostat tripped
No ame detected
Boiler circuit board error
The reset key h as been pressed inappropriately
Internal error on boiler circuit module
Fan speed threshold not reached
Low water pressure
Error code
E10
E20
E50
E110
E128
E129
E132
E133
E151
E153
E154
E160
E164
Page 12
12
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE USER
To shut down the boiler switch off the electrical supply to the appliance.
IMPORTANT: Regularly check that the pressure displayed by the pressure gauge is 1 ÷ 4 bar when the central
heating system is cold. Open the boiler drain cock to reduce pressure if it is too high. Open the lling cock to
increase pressure if it is too low.
Always open the lling cock very slowly to allow any air to bleed off.
If the pressure in the system drops frequently, contact an authorised service centre to have the system chec­ked.
We recommend you avoid draining the whole system as raw water makeup will lead to harmful limestone de­posits inside the boiler and on the heating elements. In case the boiler is not operated during wintertime and is therefore exposed to danger of frost we suggest you
add some specic-purpose anti-freeze to the water contained in the system (e.g.: propylene glycole coupled
with corrosion and scaling inhibitors). The electronic management of the boilers includes a “frost protection” function in the central heating system which operates the burner to reach a heating ow temperature of 30° C when the system heating ow tempe­rature drops below 5°C.
The frost protection function is enabled if:
* electrical supply to the boiler is on; * the gas service cock is open; * the system pressure is as required;
* the boiler is not isolated.
To maintain efcient and safe operation of your boiler have it checked by a Qualied Service Engineer at the
end of every heating season. Careful servicing will ensure economical operation of the system.
Do not clean the outer casing of the appliance with abrasive, aggressive and/or easily ammable cleaners
(i.e.: gasoline, alcohol, and so on). Always isolate the electrical supply to the appliance before cleaning it (see section 5 Turning off the boiler).
These boilers are produced for natural gas and can be converted to work with LPG (G 31). Any gas change must be effected by a Qualified Service Engineer.
4. FILLING THE SYSTEM
5. SWITCHING THE BOILER OFF
6. PROLONGED STANDSTILL OF THE SYSTEM. FROST PROTECTION
7. SERVICING INSTRUCTIONS AND GAS CHANGE
Page 13
13
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
This boiler is designed to heat water at a lower than boiling temperature at atmospheric pressure. The boiler must be connected to a central heating system and/or to a domestic hot water supply system in compliance with its performances and output power.
IMPORTANT! The following components are not installed in the boiler as supplied. It is the installer’s responsibility to provide them:
• Expansion vessel;
• Pressure safety valve;
• Circulation pump;
• Filling system cock.
Before connecting the boiler ensure the following operations have been completed:
a) Check that the boiler is t for operation with the type of gas available. For more details see the notice on the
packaging and the label on the appliance itself.
b) Check that the ue terminal draft is appropriate; that the terminal is not obstructed and that no other applian-
ce exhaust gases are expelled through the same ue duct, unless the ue is especially designed to collect
the exhaust gas coming from more than one appliance, in conformity with the standards and regulations in force.
c) Check that, in case the ue has been connected to pre-existing ue ducts, thorough cleaning has been carried
out in that residual combustion products may come off during operation of the boiler and obstruct the ue
duct.
The following remarks and instructions are addressed to Service Engineers to help them carry out a faultless installation. Instructions regarding lighting and operation of the boiler are contained in the ‘Instructions pertai­ning to the user’ section. Note that installation, maintenance and operation of the gas appliances must be performed exclusively by
qualied personnel in compliance with current standards.
Please note the following:
• Install the boiler in a permanent ventilated central heating boiler room.
• This boiler can be connected to any type of convector plates, radiators, thermoconvectors. Design the system
sections as usual though taking into account the available output / pump head performances, as shown in chapter 10.4.
• Do not leave any packaging components (plastic bags, polystyrene, etc.) within children’s reach as they are
a potential source of danger.
• Initial lighting of the boiler must be effected by a Qualied Service Engineer.
• Make sure that the room where the boiler is installed has a sufcient supply of air to ensure complete combu-
stion of the gas consumed by the appliance. Install unblockable ventilation grilles as necessary in accordance with the Rules in force.
• Connect the boiler directly to an efcient ue to vent all fumes and combustion gases outdoors. Make sure that the pipe connecting the boiler to the ue is not smaller in diameter than the boiler’s ue outlet. Make sure that the ue is in good condition and free from holes or cracks that could reduce draw.
Failure to observe the above will render the warranty null and void.
8. GENERAL INFORMATION
9. INSTRUCTIONS PRIOR TO INSTALLATION
Page 14
14
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
10. BOILER INSTALLATION AND DIMENSIONS
Install the boiler in a position that ensures easy maintenance. You must be able to fully open the front access door and have adequate access to the rear of the boiler.
If possible, install the boiler on a raised base of 200 mm in height to facilitate drainage of ue condensate. When calculating the weight of the boiler on the oor, bear in mind the weight of the water in the heat exchanger
(see table 1).
Adjust the levelling feet to compensate for any unevenness in the oor.
Install the necessary utility connections starting from the water and gas connections on the rear of the boiler
(see table 1 for tting type and size).
These appliances do not have any circulation pump, expansion tank or safety valve. These devices must therefore be provided elsewhere in the system, and must be sized to suit the system’s thermal capacity.
Connect the ue condensate drain pipe to a suitable water drain, ensuring an adequate slope.
To drain the boiler, use the drain tap at the rear.
To ensure correct operation of the appliance and avoid invalidating the warranty, observe the following precautions:
1. Heating circuit
1.1. New system Before proceeding with installation of the boiler, the system must be cleaned and ushed out thoroughly to
eliminate residual thread-cutting swarf, solder and solvents if any, using suitable proprietary products.
To avoid damaging metal, plastic and rubber parts, use only neutral cleaners, i.e. non-acid and non
alkaline. The recommended products for cleaning are:
SENTINEL X300 or X400 and FERNOX heating circuit restore. The use of this product must be strictly
in accordance with the maker’s directions. Finally the system must be dosed with a suitable inhibitor at 1% system volume.
1.2. Existing system
Before proceeding with installation of the boiler, the system must be cleaned and ushed out to remove
sludge and contaminants, using suitable proprietary products as described in section 1.1.
To avoid damaging metal, plastic and rubber parts, use only neutral cleaners, i.e. non-acid and non-
alkaline such us SENTINEL X100 and FERNOX heating circuit protective. To use this product proceeding strictly in accordance with the maker’s directions.
Remember that the presence of foreign matter in the heating system can adversely affect the operation
of the boiler (e.g. overheating and noisy operation of the heat exchanger). Dose with inhibitor.
Failure to observe the above will render the warranty null and void.
Page 15
15
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
Figure 5
Table 1
Model Depth Height Width Gas Fitting Fitting Water contents
(mm) (mm) (mm) tting F R ( l )
A (CH) (CH)
FS 90 801 850 450 G 3/4” G 1 1/4’’ G 1 1/4’’ 13,7
FS 105 871 850 450 G 1” G 1 1/2” G 1 1/2” 21
FS 130 1024 850 450 G 1” G 1 1/2” G 1 1/2” 23,3
FS 160 1132 850 450 G 1” G 1 1/2” G 1 1/2” 25,3
Insert the flue-gas union and fasten the connector to the flue-gas thermo­stat
CT_0804 / 0906_2501
F CH: heating ow
R CH: heating return GAS: gas inlet to the boiler
SC: condensate drain SIZE = EXTERNAL 25 mm INTERNAL 18 mm
CLEARANCE FRONT = 700 mm REAR = allow room to make
connections SIDE = 10 mm TOP = 500 mm
Page 16
16
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
Figure 6
10.1 HYDRAULIC SYSTEM 1
(Pumped heating circuits with remote control QAA73 or Room Thermostat, including hot-water tank, with primary loop)
Applications and Installation Details
- TS: Tank Sensor (QAZ36)*
- B3: Room Control Module (QAA73)*
- B1: Room Thermostat*
- B9: Outdoor Temperature Sensor (QAC34) supplied with the boiler
- P1: Heating Pump
- PDHW: Hot Water Pump
- PLP: Primary Pump
(*) Available Optional Extra
- Pumps, Hot Water Cylinder, Low Loss Header , Non return valve (Not supplied)
- Installer Wiring ---------------
Applications (pumps, sensor, remote control ...) have to be connected to terminal as follows (see also section 12):
WITH QAA73 WITH REMOTE CONTROL ROOM THERMOSTAT APPLICATION
TERMINAL BOARD TERMINAL BOARD PRIMARY PUMP PLP M1: A – B M1: A – B DHW PUMP PDHW M3: 13 – 14 M3: 13 – 14 HEATING PUMP P1 M3: 11 – 12 M3: 11 – 12 DHW SENSOR TS M2: 7 – 8 M2: 7 – 8 REMOTE CONTROL QAA73 M2: 1 – 2 NO ROOM THERMOSTAT M2: 3 – 4 OPEN M2: 3 – 4
CT_0664 / 0906_2202
Page 17
17
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
Parameter changes requires (see also section 14):
PCB Description Setting Parameter PARAMETER
H552 Hydraulic system H552 = 2 (*)
H553 KongHKS H553 = 21 (*)
H615 KongAusgang H615 = 9 (*)
H632 WANFO Q8 H632 = 00001100 (*)
(*) factory set
10.2 HYDRAULIC SYSTEM 2
(Pumped heating circuits with Room Thermostats and compensated circuit with remote control QAA73, including hot-water tank, with primary loop)
Applications and Installation Details
- TS:Tank Sensor (QAZ36)*
- B3: Room Control Module (QAA73)*
- B1: Room Thermostat*
- B9: Outdoor Temp Sensor (QAC34) supplied with the boiler
- AGU2.500: Zone controller (Clip-in AGU2.500)*
- FS: Flow Sensor (QAD36: supplied with the AGU2.500)*
- P1: CTC Heating Pump
- P DHW: Hot Water pump
- PLP: Primary Pump
- 3WV: 3-Way Valve (power open / power close)
- P2: VTC Pump
(*) Available Optional Extra
- Pumps , Hot Water Cylinder, Low Loss Header, Non return valve (Not supplied)
- Installer Wiring --------------
Figure 7
CT_0663 / 0906_2203
Page 18
18
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
Applications (pumps, sensor, remote control ...) have to be connected to terminal as follows (see also section 12):
APPLICATION
TERMINAL BOARD
PRIMARY PUMP PLP M1: A – B
DHW PUMP PDHW M3: 13 – 14
HEATING PUMP P1 M3: 11 – 12
DHW SENSOR SB M2: 7 – 8
REMOTE CONTROL QAA73 (LOW TEMPERATURE) M2: 1 – 2
ROOM THERMOSTAT M2: 3 – 4
HEATING PUMP P2 CLIP IN AGU 2.500
3 WAY VALVE 3WV CLIP IN AGU 2.500
FLOW SENSOR FS CLIP IN AGU 2.500
Parameter changes requires
(see also section 14)
:
PCB PARAMETER Description Setting Parameter
H552 Hydraulic system H552 = 50
H553 KongHKS H553 = 12
H615 KongAusgang H615 = 9
H632 WANFO Q8 00001111
10.3 HYDRAULIC SYSTEM 3
(Cascade with pumped heating circuits, Room Thermostats, primary loop)
Applications and Installation Details
- RT: Room Thermostat*
- B9: Outdoor Temperature Sensor (QAC34) supplied with the boiler
- OCI 420: Cascade interface controller (Clip-in OCI 420)*
- RVA 47: Cascade controller (RVA 47)*
- FS: Flow/return Sensor (QAD21)*
- P1: Heating Pump
- PLP: Primary Pump
(*) Available Optional Extra
- Pumps , Hot Water Cylinder, Low Loss Header, Non return valve (Not supplied)
- Installer Wiring --------------
Page 19
19
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
Figure 8
Applications (pumps, sensor, remote control ...) have to be connected to terminal as follows (see also section 12):
APPLICATION
TERMINAL BOARD
PRIMARY PUMP PLP M1: A – B
HEATING PUMP P1 RVA 47
ROOM THERMOSTAT RVA 47
FLOW/ RETURN SENSOR QAD 21 RVA 47
Parameter changes requires
(see also section 14)
:
PCB PARAMETER Description Setting Parameter
H552 Hydraulic system H552 = 80
H553 KongHKS H553 = 21
H615 KongAusgang H615 = 9
H632 WANFO Q8 00001111
If DHW circuit is required then DHW pump and DHW sensor have to be connected to terminal of RVA 47 Cascade Controller.
For more details refer to the instruction provided with the accessories RVA 47 and RVA 46 (compensated circuit).
CT_0665 / 0906_2204
Page 20
20
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
10.4 EXCHANGERS PRESSURE DROP
Exchanger pressure drop (mH
2
O)
WATER FLOW RATE (l/h)
Graph 1
Exchanger pressure drop (mH
2
O)
WATER FLOW RATE (l/h)
Graph 1.1
FS 90 - 105 EXCHANGER PRESSURE DROP.
FS 130 - 160 EXCHANGER PRESSURE DROP.
0512_19010512_1902
90
105
130
160
kPa Lit/sec kPa Lit/sec kPa Lit/sec kPa Lit/sec
FS 90 76,49 1,85 36,29 1,35 23,54 1,02 10,79 0,68
FS 105 74,53 2,17 40,21 1,59 22,56 1,19 12,75 0,80
FS 130 53,94 2,61 31,38 1,91 22,56 1,43 10,79 0,96
FS 160 49,03 3,26 31,38 2,39 19,61 1,79 10,79 1,19
Boiler Hydraulic Resistance and Water Flow Rates 11°K ∆T 15°K ∆T 20°K ∆T 30°K ∆T
FS 90 0,52
FS 105 0,58
FS 130 0,72
FS 160 0,91
Boiler Minimum Water Flow Rates Lit/sec
Page 21
21
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
Connect the boiler to the ue using a pipe made of stainless steel or plastic material with an internal diameter of 100 mm, capable of resisting normal mechanical stresses over time, as well as high temperatures (<120°C) and the chemical effects of fuel gases and their condensates. Insert the flue-gas union and fasten the
connector to the flue-gas thermostat before hooking up to the flue.
Whenever possible use a ue connection that can be disconnected for maintenance.
Important! Horizontal flue sections must have a minimum slope of 3° towards the boiler.
Flue accessories made of plastic material for cascade or single installations are available.
11. CHIMNEY FLUE CONNECTION
Figure 7a
CT_0809 / 0902_2705
CT0667 / 0903_1601
In case exhaust and intake flues not supplied by POTTERTON COMMERCIAL have been installed, these must be certified for the type of use and must have a maximum pressure drop in according to the values reported in the table.
To ensure the correct rated heat input to the maximum and minimum heat input, it is necessary to update the speed (rpm) of the fan, it depends on the lenght of the pipes, in accordance with the installation of ue and air pipes as indicated in the tables below. The factory-set value is referred to the minimum length of ue pipe (0÷10 m). To carry such updating, changing the speed of the fan at the (rpm and pwm%) , refer to par. 13-14.
Max. length of ue duct (L) : 20 m Each 90° bend reduces the duct max. length by : 1 m Each 45° bend reduces the duct max. length by : 0.5 m
FLUE PRESSURE TABLE AVAILABLE
Cascade solution
∆P available
ue duct B23 Ø 100
∆P available with
single non-return valve
Ø 110/110
∆P available with
double non-return valve
Ø 110/110
FS 90 110 110 -
FS 105 150 110 -
FS 130 170 - 80
FS 160 280 - 120
Page 22
22
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
The kit is used to introduce combustion air from outside the installation area and comprises a hose to be installed in the mixer body.
Please consult the instructions supplied with the kit.
For air ducts (diameter and length), see the kit manual.
11.2 CONNECTOR WITH C53 TYPE
CT_0813 / 0903_0601
Page 23
23
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
12. MAKING THE ELECTRICAL CONNECTIONS
Electrical safety of the appliance is only guaranteed by correct earthing, in accordance with the current stan­dards and regulations. Connect the boiler to a 230V by means of the three-pin cable supplied with it make sure that the polarities are correctly connected.
Use a double-pole switch with a contact separation of at least 3mm in both poles.
In case you replace the power supply cable t a HAR H05 VV-F’ 3x0.75mm2 cable with an 8mm diameter
maximum outer sheath.
IMPORTANT: Check that the overall current drawn by accessories connected to the appliance is less than 2 amp. If the value is greater, a relay must be wired between the boiler control circuit board and the accessories drawing the higher current.
12.1 TERMINAL BLOCKS ACCESS
• Isolate power to the boiler with the two-pole switch.
• Remove the top facia panel cover (which is held by magnets).
• Unscrew the two screws holding the facia panel in place.
• Swing the facia panel forwards.
Main terminal block M1
• Remove the clip-on cover from terminal strip M1.
• The main terminal block incorporates a fast blow 3.15 A fuse (gure 10). Remove the black fuse holder to
check and/or replace the fuse.
Terminal block M2
• Unscrew the xing screw and remove the cover from terminal block M2.
Terminal block M3
• Unscrew the xing screws and remove the main cover.
Figure 10
020523_0400
Terminal Block M1
Terminal Block M2
Cover
Cover
Facia panel
Page 24
24
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
12.2 CONNECTING THE PUMPS
Figure 11
Turn the control box downward to access terminal boards M1 and M3 used for the electrical connections by removing the protective covers (see gure 11).
Terminals M1 a – b: connection of the Primary loop pump for the heating system (Plp)
Check the correct size and rating of the pump by referring to graph n° 1, which shows the boiler pressure losses.
Terminals M3 11 – 12: connection for heating pump (P1) Terminals M3 13 – 14: connection for hot water tank pump (PDHW)
The electrical specications of the pump must be as follows: 230 V AC; 50 Hz; 1 A max; cos f > 0.8.
If the specications of the installed pump are different, a relay must be wired between the boiler control circuit board and the pump. It is advisable not to adopt any electrical connection other than those described.
Connect earth to earth strip
Remove the resistor from terminals 9-10 of terminal strip M2 (gure 12), and connect the hot water priority NTC sensor, which is supplied as an accessory. The sensing element of the NTC device must be located in the recess provided on the storage tank (gure 12). The temperature and on-off programming of the domestic hot water supply are selected directly from the boiler control panel, as described in this manual under the user instruction headings.
12.3 CONNECTING THE HOT WATER TANK SENSOR
CG_1763 / 0906_2205
Page 25
25
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
Figure 12
Figure 13
0602_0707/CG1764
0602_0708/CG1765
safety contact
room thermostat
Page 26
26
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
Turn the control box downward to access terminal blocks M1 and M2 used for the electrical connections by
removing the two protective covers (see gure 10).
Terminals 1-2: connections for the optional SIEMENS QAA73 (optional extra) room temperature regulator.
These connections do not have any specic polarity.
Remove the bridge between terminals 1-2 “TA” on terminal block M1. Read the instructions provided with the temperature regulator to ensure correct installation and program­ming. Terminals 3-4: room temperature thermostat “TA”. Thermostats with integral accelerator resistor must not be used. Check that there is no voltage across the ends of the two thermostat connection wires.
Terminals 5-6: external safety contact (commercially available device). Terminals 7-8: connections for the optional SIEMENS QAC34 outdoor temperature sensor supplied with the
boiler. Read the instructions provided with the outdoor temperature sensor to ensure correct installation. Terminals 9-10: connections for the optional domestic hot water priority sensor, for connecting single system boilers to external DHW boilers.
CLIP-IN AGU 2.511 Terminals 3-4 L-N OUT: connection to signal lamp (230 V - 0,5 A max) for lockout alarm. Terminals 5-6 L-N OUT: connection to signal lamp (230 V - 0,5 A max) for run mode.
For low voltage signal lamp remove the internal wiring and feed with an external low voltage power supply.
12.4 DESCRIPTION OF THE ELECTRICAL CONNECTIONS TO THE BOILER
12.5 CONNECTING THE QAA73 ROOM TEMPERATURE REGULATOR
The SIEMENS model QAA73 room temperature regulator, if required (optional accessory) must be connected
to terminals 1-2 of terminal block M2 in gure 12.
The link across terminals 3-4, provided for connection of a room temperature thermostat, must be removed. The settings of the domestic hot water temperature and domestic hot water production schedule must be made using this device. The timed program of the central heating circuit must be set on the QAA73 if there is a single zone, or in relation to the zone controlled by the QAA73 device. The timed program for the central heating circuit of the other zones can be set directly on the boiler control panel.
See the instructions provided with the QAA73 temperature regulator for the user parameter programming procedure.
QAA73: parameters which can be set by the installer (service)
By pressing the two PROG buttons together for at least three seconds it is possible to access the list of para­meters that the installer can display and/or set. Press either of these buttons to change the parameter to display or change. Press the [+] or [-] key to change the value displayed. Press either of the PROG buttons again to save the change. Press the information button (i) to quit programming.
Here follows a list of the most commonly used parameters:
Page 27
27
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
- Fault messages
In the event of fault, the display panel on the QAA73 shows the ashing symbol . Press the information key ( ) to display the error code and a description of the fault (see table on paragraph 3.9).
Line no.
70
72
74
75
77
78
79
80
90
91
Default value
15
85
Light
On HC1
On
0
0
—.-
10
24 h/day
Range
2.5…40
25…85
Light, Heavy
on HC1 on HC2 on HC1+HC2 nil
On - off
0…360 min
0…360 min
2.5…40 —.- = not active
10…58
24 h/day TSP HC-1h TSP HC TSP DHW
Parameter
HC1 gradient heating curve Selection of central heating circuit temperature curve “kt”
HC1 max. output Central heating system maximum output temperature
Type of building
Room compensation
Activation/deactivation of the inuence of the room temperature. If it is
deactivated, the outdoor temperature sensor must be installed.
Automatic adaptation of the temperature curve “kt” in relation to the room temperature.
Opt Start Max Maximum time the boiler is switched on ahead of the timed program to optimise the temperature in the premises.
Opt Stop Max Maximum time the boiler is switched off ahead of the timed program to optimise the temperature in the premises.
HC2 gradient heating curve
DHW Red Setp Minimum temperature of the domestic domestic hot water
DHW program Selection of the type of timed program for domestic hot water. 24 h/day = always on PROG HC-1h = as HC1 central heating program less one hour PROG HC = as central heating program
PROG DHW = specic domestic hot water program
(see also program lines 30-36)
Page 28
28
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
The SIEMENS model QAC34 outdoor temperature sensor must be connected to terminals 7-8 of terminal board
M2 in gure 12.
The procedures for setting the gradient of the temperature curve “kt” vary depending on the accessories con­nected to the boiler.
a) Without QAA73 room temperature regulator:
The temperature curve “kt” must be selected by setting parameter H532 as described in section 14 “setting the boiler parameters”. See graph 2 for selecting the curve referred to a room temperature of 20°C.
The chosen curve can be shifted by pressing the (2), button (2) on the boiler control panel, and modifying
the value displayed by pressing the and . keys. See graph 3 for curve selection. (The example show in graph 3 refers to the curve Kt=15). Increase the value displayed if the room temperature required is not reached inside the premises for central heating.
b) With QAA73 room temperature regulator:
The temperature curve “kt” must be selected by setting parameter 70 “HC1 curve” of the QAA73 room tem­perature control device as described in section 12.4 “QAA73: parameters which can be set by the installation (service) engineer”. See graph 4 for selecting the curve referred to a room temperature of 20°C. The curve is shifted automatically on the basis of the room temperature set using the QAA73 climate control. If the system is divided into zones, the temperature curve “kt” relating to the part of the system not controlled by the QAA73 must be selected by setting parameter H532 as described in section 14 “setting the boiler parameters”.
Graph 2 Graph 3
TM = Flow temperature Te = Composite outside temperature Sth = Kt Curve
TM = Flow temperature Te = Composite outside temperature
020523_0600
020523_1000
12.6 CONNECTING THE OUTDOOR TEMPERATURE SENSOR PROBE
Graph 4
c) With AGU2.500 for control of a low temperature system:
Refer to the instructions provided with the AGU2.500 accessories for connection and control of a variable
temperature zone.
Page 29
29
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
0502_2108
Figure 14a
LEGEND: Pi: Gas supply pressure
connection point
P out: Pressure connection point for
measurement of the OFFSET
Pl: Air signal input from fan
V: Gas ow adjuster screw (high) K: OFFSET adjuster screw (low)
13. ADJUSTING THE GAS VALVES
0502_2109
Figure 14b
FS 90 - 105 models have a single gas valve (gure 14 a). FS 130 - 160 models have a double gas valve (gure 14 b).
Gas nozzle
Gas nozzle
Page 30
30
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
13.1 SINGLE GAS VALVE MODELS (FS 90 - 105) FIGURE 14a
Proceed as follows to adjust the single gas valve:
• Insert the ue analysis probe into the ue sampling hole as instructed in section 17 (gure 17).
• Press and hold the and keys on the control panel simultaneously for 7 seconds until the symbols
appear on the display in the position shown in gures 15a and 15b . You are now in ‘calibration
mode’.
• Press the key to set the maximum heat output, with the display showing 100% (gure 15a).
Caution: in the event of the boiler failing to ignite, or when replacing the gas valve, the recommended procedure is to tighten the adjuster screw (V) fully and then back off 3 turns, repeating the steps described above.
• Turn the adjuster screw V on the gas valve until you achieve the CO2 levels shown in
table 2.1 for natural
gas (G20) and in table 2.2 for propane (LPG):
- Turn the screw anti-clockwise to increase the CO2 level.
- Turn the screw clockwise to decrease the CO2 level.
• Press the key to set the minimum heat output, with the display showing 0% (gure 13b).
• Turn the adjuster screw K on the gas valve until you achieve the CO2 levels shown in table 2:
- Turn the screw clockwise to increase the CO2 level.
- Turn the screw anti-clockwise to decrease the CO2 level.
Proceed as follows to adjust the double gas valve:
Connect a pressure gauge to the P1OUT pressure measurement hole on valve 1.
• Insert the probe of the ue gas analyzer in the sampling port as indicated in heading 17 - gure 17.
• Switch on the boiler, activating the “setting function” from the control panel by pressing and holding the
and keys simultaneously until the symbols are displayed, positioned as illustrated in gures
15a and 15b . You are now in ‘calibration mode’.
Press the key to set the maximum heat output, with the display showing 100% (gure 15a).
Caution: in the event of the boiler failing to ignite, or when replacing the gas valves, the recommended procedure is to tighten the adjuster screws (V1) and (V2) fully and then, depending on the model, back off 2¼ turns (FS 130) or 2½ turns (FS 160), repeating the steps described above.
• Turn both gas valve adjuster screws (V1) and (V2) so as to set the CO2 values as indicated in table 2.1 for
natural gas (G20) and in table 2.2 for propane (LPG):
- Turn the screw clockwise to decrease the CO2 level.
- Turn the screw anti-clockwise to increase the CO2 level.
• Press the key to set the minimum heat output, with the display showing 0% (gure 15b).
• Turn the adjuster screw K1 of gas valve 1 so as to set the pressure value (Pout) as indicated in table 2.1
for natural gas (G20) and in table 2.2 for propane (LPG):
c. Turn the screw clockwise to increase pressure (CO2 increasing).
13.2 DOUBLE GAS VALVE MODELS (FS 130 - 160) FIGURE 14b
Page 31
31
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
d. Turn the screw anti-clockwise to decrease pressure (CO2 decreasing).
• Remove the pressure gauge from the P1OUT port and connect to the P2OUT port of gas valve 2.
• Turn the adjuster screw K2 of gas valve 2 so as to set the pressure value (Pout) as indicated in table 2.1
for natural gas (G20) and in table 2.2 for propane (LPG):
• Check that the CO2 value at minimum heat output is as indicated in table 2.1 or 2.2. The value can be optimized by making the necessary ne adjustment to screw K2.
13.3 GAS CONVERSION
IMPORTANT: in the event of converting the boiler from natural gas (G20) to propane (LPG), the following
operation must be carried out before proceeding to adjust the gas valve as described above:
• For models with one valve, replace the diaphragm on the gas valve outlet (gure 14a).
To replace the diaphragm, disassemble the gas valve by undoing the inlet and outlet ttings, then unscrew
the nozzle with a pair of straight round nose pliers.
Check the uid-tightness of the gas ttings removed previously.
• For models with two gas valves, replace the diaphragm located at the venturi inlet (gure 14b).
To enable this operation, the gas valve manifold must rst be removed. Check the uid-tightness of the gas ttings removed previously.
• Set parameters H536 - H541 - H608 - H609 - H610 - H611 - H612 - H613 by way of the display on the control panel.
The values to be set are given in tables 2.1 and 2.2. The programming methods are described in chapter 14.
Figure 15a
0307_2201
Figure 15b
0502_2110
Page 32
32
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
Table 2.1
Table 2.2
Gas consumption at
15 °C 1013 mbar Gas G31 - 3P - 37 mbar
FS 90 FS 105 FS 130 FS 160
PCI (NET) MJ/Kg 46,34 46,34 46,34 46,34
Consumption at max. heat output
Kg/h 6,77 7,97 9,56 11,95
Consumption at min. heat output
Kg/h 2,57 2,86 3,10 3,22
Gas nozzle
mm 7,8 7,8 7,8 7,8
CO2 max. heat output
% 10,2 10,2 10,2 10,2
CO2 min. heat output
% 9,3 9,8 10,2 10,2
Pout pressure at
minimum power
Pa - - -7 -8
Parameters H536-H613 (rpm) at maximum power
4600 5150 4300 5350
Parameters H541-H610 (
pwm
%)
at maximum power
90 100 55 100
Parameter H612 (rpm) at minimum power
1900 1950 1450 1450
Parameter H609
(pwm)
at minimum power
14,5 14,5 10 9,5
Parameter H611 (rpm) ignition load
4200 4200 2600 2900
Length of exhaust flue : 0 ÷ 10 m
Parameter H608
(pwm)
ignition load
40 40 15 15
Length of exhaust flue : 10 ÷ 20 m
Parameter H608
(pwm)
ignition load
50 50 20 20
Cascade solution with single non-return valve Ø 110/110
Parameters H536-H613 (rpm) at maximum power
5000 5500 - -
Parameter H612 (rpm) at minimum power
2200 2100 - -
Parameter H609
(pwm)
at minimum power
16,5 15 - -
Parameter H608
(pwm)
ignition load
50 50 - -
Gas consumption at
15 °C 1013 mbar
Gas G20 - 2H - 20 mbar
FS 90 FS 105 FS 130 FS 160
PCI (NET) MJ/m
3
34,02 34,02 34,02 34,02
Consumption at max. heat output
m3/h 9,26 10,9 13,08 16,35
Consumption at min. heat output
m3/h 3,50 3,89 4,23 4,39
Gas nozzle
mm 11,5 12 11 11,5
CO2 max. heat output
% 8,7 8,7 8,7 8,7
CO2 min. heat output
% 8,6 8,6 8,4 8,4
Pout pressure at
minimum power
Pa - - -4 -5
Parameters H536-H613 (rpm) at maximum power
5100 5650 4650 6000
Parameters H541-H610 (
pwm
%)
at maximum power
90 100 55 100
Parameter H612 (rpm) at minimum power
1900 2100 1600 1550
Parameter H609
(pwm)
at minimum power
15 15 10 9,5
Parameter H611 (rpm) ignition load
3600 3600 2600 2900
Length of exhaust flue : 0 ÷ 10 m
Parameter H608
(pwm)
ignition load
30 30 15 15
Length of exhaust flue : 10 ÷ 20 m
Parameter H608
(pwm)
ignition load
40 40 20 20
Cascade solution with single non-return valve Ø 110/110
Parameters H536-H613 (rpm) at maximum power
5500 6000 - -
Parameter H612 (rpm) at minimum power
2200 2250 - -
Parameter H609
(pwm)
at minimum power
16,5 16
Parameter H608
(pwm)
ignition load
40 40
Page 33
33
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
( * ) For these parameters see section 10.1 - 10.2 - 10.3 (hydraulic system).
If the electronic circuit board is replaced, make sure that the parameters set are those specic to the boiler
model, as indicated in the documentation available from the authorised Service Centre.
Parameter
N.
Description
Factory setting
H90 Minimum D.H.W. temperature setting (°C).
10
H91
D.H.W. activation program (0=active; 1=not active)
1
H505
Maximum temperature (°C) of the central heating circuit HC1 corresponding to:
- the main circuit in systems with just one zone;
- the circuit of the zone where the QAA73 room temperature control device is installed in case of systems with more than one high-temperature zone;
- the high temperature zone circuit in mixed systems and if the SIEMENS AGU2.500 accessory is used.
80
H507
Maximum temperature (°C) of the central heating circuit HC2 of a system with more than one zone, corresponding to the circuit of the low-temperature zone if the SIEMENS AGU2.500 accessory is used.
80
H516 Automatic Summer / Winter switching temperature (°C). 20
H532 Selection of temperature curve of central heating circuit HC1 (see Graph 2) 15
H533 Selection of temperature curve of central heating circuit HC2 (see Graph 2) 15
H608 PWM (%) Setting: Ignition load
See table 2
H611 Speed setting (rpm) : Ignition load
H609 PWM Setting (%) : minimum power
H541-H610 PWM Setting (%) : maximum power Central heating / Domestic hot water
H612 Speed setting (rpm) : minimum power
H536-H613 Speed setting (rpm) : maximum power Central heating / Domestic hot water
H544 Pump post-circulation time in central heating mode (min) 10
H545 Burner operating pause time between two start-ups (s) 180
H552
( * )
Hydraulic system setting (see instructions provided with the SIEMENS AGU2.500 accessory) H552 = 50 with AGU2.500 and QAA73 H552 = 80 with RVA 47
2
H553
( * )
Conguration of heating circuits H553 = 12 with AGU2.500
21
H615 Programmable function: 9
H632
( * )
Heat demand to be supported by the system pump H632 = 00001111 with AGU2.500 and RVA 47
00001100
H641 Fan overrun time setting (s) 10
H657
Setpoint of autonomous ANTILEGIONELLA function
60...80 °C = setting temperature range
0 = function inactive
0
Table 3
The boiler parameters may only be modied by professionally qualied staff proceeding as follows:
a) Press the , keys on the boiler’s front panel together for about 3 s until the parameter H90 appears on the display; b) Press the keys to select the parameter for modication;
The boiler parameters may only be modied by professionally qualied staff proceeding as follows:
a) Press the , keys on the boiler’s front panel together for about 3 s until the parameter H90 appears on the display; b) Press the keys to select the parameter for modication; c) Press the and keys to modify the parameter; d) Press the key to exit the programming function.
The following are the parameters generally used:
14. SETTING THE BOILER PARAMETERS
Page 34
34
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
The boiler has been designed in full compliance with European reference standards and in particular is equipped with the following:
• Overheatsafetythermostat
This thermostat interrupts the gas ow to the main burner in case the water contained in the circuit has ove-
rheated. Under these conditions the boiler locks out and can only repeat the ignition procedure by pressing of the reset button on the boiler after the cause of the trip has been rectied.
It is strictly forbidden to disable this safety device.
• Fluethermostat
This device, positioned on the ue inside the boiler, interrupts the ow of gas to the burner if the temperature
exceeds 90 °C. After verifying the cause of the trip, press the reset button positioned on the thermostat itself, then press the reset button on the boiler.
It is forbidden to disenable this safety device
• Flameionizationdetector
The ame sensing electrode guarantees safety of operation in case of gas failure or incomplete interlighting
of the main burner. Under such conditions the boiler is locked out. You must press the reset button on the boiler to restore the normal operating conditions.
• Pumpoverrun
The electronic control system keeps the pump operating for 10 minutes in central heating mode after the
room temperature thermostat has switched off the main burner.
• Frostprotectiondevice
The boilers electronic management includes a “frost protection” function in the central heating system which
operates the burner to reach a heating ow temperature of 30°C when the system heating ow temperature
drops below 5 °C. This function is enabled as long as the boiler is connected to the a.c. power supply gas supplies and the
pressure in the system is as specied.
• Pump-blockingprevention
In case there is no call for heat either from the central heating system or from the DHW system for 24 hours
continous the pump will automatically switch on for 10 seconds.
• Hydraulicpressuresensor
This device enables the main burner only to be switched on if the system pressure is over 0.5 bar.
• Gaspressureswitch
This device enables the burner only to be switched on if the gas pressure is over 12 mbar.
15. CONTROL AND OPERATION DEVICES
Page 35
35
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
Drill a hole in the ue at a distance from the boiler equivalent to twice the diameter of the ue to measure combustion efciency and combustion ue composition in accordance with the rules in force. Use this hole to
measure the following parameters:
• Combustion ue temperature
• Oxygen (O2) or carbon dioxide (CO2) concentration.
• Carbon monoxide (CO) concentration.
Measure the temperature of combustion air near the air inlet to the boiler. The necessary hole must be made by
the technician responsible for the heating system when the system is rst started up, and must then be closed to ensure that the ue remains properly sealed during normal operation.
17. CHECK OF COMBUSTION PARAMETERS
Figure 17
Figure 16
16. POSITIONING OF THE IGNITION AND FLAME SENSING ELECTRODE
0503_2204
Important! Close the ue test point
hole on completion of measurements.
BOILER FLUE TEST POINT HOLE
0811_1703 / CT_0782
Page 36
36
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
To facilitate measurement of the combustion efciency and improve the cleanliness of the production products,
the chimney sweep function can be activated by proceeding as described below:
1) Press the (2-3) together until the pointer “ ” appears on the display alongside the symbol (about 3
seconds but no more than 6 seconds). In these conditions, the boiler operates at the maximum heat output
in central heating mode.
2) Press either of the buttons to exit the function
020429_0200
Figure 18
To ensure the boiler operates at peak efciency, the following checks must be performed every year:
• Check on the appearance and tightness of the gas and combustion circuit gaskets;
• Check on the condition and position of the ignition and ame sensing electrodes (see section 16);
• Check on the condition of the burner and its xing to the aluminium ange;
• Check for any dirt in the combustion chamber. Use a vacuum-cleaner for this cleaning operation;
• Check that the gas valve is calibrated correctly (see section 13);
• Check that there is no dirt in the siphon;
• Check on the central heating system pressure;
• Check on the central heating expansion vessel pressure.
18. ACTIVATING THE CHIMNEY SWEEP FUNCTION
19. ANNUAL SERVICE
Page 37
37
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
Figure 19
Key: 1 Water pressure gauge 2 Siphon (condensate) 3 Central heating ntc sensor 4 105°C overheat safety thermostat 5 Gas valve 6 Heat exchanger 7 Flame detector electrode (ionisation probe) 8 Burner 9 Ignition electrode 10 Mixer with venturi
11 Gas injector
12 Fan
13 Flue joint
14 Automatic air vent 15 Hydraulic pressure sensor 16 Boiler drain point
17 Joint ue with ue thermostat
18 Flue thermostat 19 Gas pressure switch 20 Seat of air intake pipe
20. BOILER SCHEMATIC
CT_0818 / 0907_0101
Page 38
38
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
21. ILLUSTRATED WIRING DIAGRAM
21.1 FS 90 - 105
CT_0660 / 0907_0102
Page 39
39
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
21.2 FS 130 - 160
CT_0661 / 0907_0103
Page 40
40
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
Boiler model FS 90 105 130 160 Category II
2H3P
II
2H3P
II
2H3P
II
2H3P
Maximum heat input (net/gross) kW 87,2-96,7 102,7-113,8 123,2-136,6 154-170,7 Minimum heat input (net/gross) kW 33,1-36,7 36,8-40,8 40-44,3 41,5-46,02 Maximum heat output 75/60°C kW 85 100 120 150 kcal/h 73100 86000 103200 129000 Maximum heat output 50/30°C kW 91,6 107,8 129,7 162 kcal/h 78776 92708 111542 139320 Minimum heat output 75/60°C kW 32,2 35,8 39 40,4 kcal/h 27692 30788 33540 34744 Minimum heat output 50/30°C kW 34,9 38,8 42,1 43,7 kcal/h 30014 33368 36206 37582
Useful efciency according to 92/42/CEE directive ★★★★ ★★★★ ★★★★ ★★★★
Central heating system max. pressure bar 4 4 4 4
Heating circuit temperature range °C 25÷80 25÷80 25÷80 25÷80 Flue type
B23 - B23P - C53*
Flue duct diameter mm 100 100 100 100
Max. ue mass ow rate kg/s 0,041 0,049 0,058 0,073 Min. ue mass ow rate kg/s 0,016 0,018 0,019 0,020 Max. ue temperature °C 78 80 77 75
NOx class 5 5 5 5
Type of gas used G20 G20 G20 G20 G31 G31 G31 G31 Natural gas feeding pressure 2H mbar 20 20 20 20 Propane gas feeding pressure 3P mbar 37 37 37 37
Gas Consumption (NG) m3/hr 9,26 10,9 13,8 16,35 Minimum Operating Pressure Bar 1 1 1 1 High Level Ventilation to BS6644 boiler room cm2 174,4 205,4 246,4 308 Low Level Ventilation to BS6644 boiler room cm2 348,8 410,8 492,8 616 Mechanical inlet to BS6644 m3/sec 0,067 0,08 0,1 0,12
Water Flow at 20°K Δt lit/sec 1,02 1,19 1,44 1,80 Hydraulic Resistance at 20°K Δt kPa 25 25 22 21
Cold Feed Size to BS6644 mm 25 25 25 32 Safety valve size to BS6644 (open vent) mm 19 19 19 19 Open vent BS6644 mm 32 32 32 32 Maximum Flow Temperature °C 85 85 85 85 Water Content lit 13,7 21 23,3 25,3
Power supply voltage V 230 230 230 230 Power supply frequency Hz 50 50 50 50 Rated power supply W 100 160 135 235
Net weight kg 75 83 95 103 Dimensions height mm 850 850 850 850 width mm 450 450 450 450 depth mm 801 871 1014 1132
* C53 (only with air intake kit)
22. TECHNICAL DATA
Page 41
41
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
Page 42
42
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
Page 43
43
912.823.1 - GB
INSTRUCTIONS PERTAINING TO THE INSTALLER
Page 44
Baxi Commercial Division
Wood Lane, Erdington, Birmingham B24 9QP Email: potterton.commercial@baxigroup.com www.pottertoncommercial.co.uk
Sales:
0845 070 1056
Technical:
0845 070 1057
Commercial sales technical & service enquiries
Tel: 0845 070 1055 Fax: 0845 070 1059 Sales hotline: 0845 070 1056 Technical helpline: 0845 070 1057 Service hotline: 0845 070 1058 e-mail: potterton.commercial@baxigroup.com web: www.pottertoncommercial.co.uk
Spares
Potterton Commercial spares are available nationwide through the interpart network of approved stockists. Alternatively please contact:-
Interpart
Brooks House Coventry Road Warwick CV34 4LL
Tel: 0844 871 1540
Applications & Installations
Our experienced technical support team are available to offer advice on any aspect of heating system design and boiler installation.
Please contact: 0845 070 1057
Commercial service offices
Our service organisation covers the whole of the UK to look after your needs for all Potterton Commercial products.
Our service office offers a wide range of specialised services
including:
• Burner commissioning for all fuels
• Boiler service contracts
• Breakdown and repair services
• Burner and boiler replacement
• Oil/gas conversions
• Water treatment and descaling
• Packaged units
All descriptions and illustrations contained within this leaflet have been carefully prepared, but we reserve the right to make changes and improvements in our products which may affect the accuracy of the information in this leaflet.
Loading...