Baxi Barcelona Installation And Servicing Instructions

Baxi Barcelona
Wall Mounted Powered Flue Condensing Boiler Gas Fired Central Heating Unit
Installation and Servicing Instructions
BAXI
Natural Gas
Baxi Barcelona
G.C.Nº 41 075 02 Baxi Limited is one of the leading manufacturers of domestic
heating products in the UK. Our first priority is to give a high quality service to our
customers. Quality is designed into every Baxi product ­products which fulfil the demands and needs of customers, offering choice, efficiency and reliability.
To keep ahead of changing trends, we have made a commitment to develop new ideas using the latest technology - with the aim of continuing to make the products that customers want to buy.
The boiler meets the requirements of Statutory Instrument “The Boiler (Efficiency) Regulations 1993 Nº 3083” and is deemed to meet the requirements of Directive 92/42/EEC on the energy efficiency requirements for new hot water boilers fired with liquid or gaseous fuels:-
Baxi is also the largest manufacturing partnership in the country. Everyone who works at the company has a commitment to quality because, as shareholders, we know that satisfied customers mean continued success.
We hope you get a satisfactory service from Baxi. If not, please let us know.
Baxi is a BS-EN ISO 9001 Accredited Company
Type test for purpose of Regulation 5 certified by: Notified Body 0086.
Product/Production certified by: Notified Body 0086.
For GB/IE only.
Contents – page 3
Section
Page
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
Introduction
General Layout
Appliance Operation
Technical Data
Dimensions and Fixings
System Details
Site Requirements
Installation
Electrical
Commissioning the Boiler
Fitting the Outer Case
4
5
6
7
8
9
12
16
22
24
25
12.0
13.0
14.0
15.0
Servicing the Boiler
Changing Components
Short Parts List
Fault Finding
26
28
35
36
1.0 Introduction – page 4
Fig.1
Fig. 2
Baxi Limited declare that no substances harmful to health are contained in the appliance or used during appliance manufacture.
NOTE: This appliance must be installed in accordance with the manufacturer’s instructions and the regulations in force, and only used in a suitably ventilated location.
All systems must be thoroughly flushed and treated with inhibitor (see Section 6.2).
Read the instructions fully before installing or using the appliance
1.1 Description
1. The Baxi Barcelona is a gas fired room sealed fan assisted condensing central heating boiler.
2. The maximum output of the boiler is preset at 80,000 Btu/hr. The boiler will automatically adjust down to 30,000 Btu/hr according to the system load. If required, the output can be set to 100,000 Btu/hr. Please refer to section 8.8.
3. It is designed for use on Natural Gas (G20).
4. The boiler is suitable for fully pumped open vented central heating and domestic hot water systems and sealed systems.
5. A label giving details of the model, serial number and Gas Council number is situated on the rear of the lower door panel (Fig. 1).
6. The boiler data badge is positioned on the air box door (Fig. 2).
7. The boiler is intended to be installed in residential / commercial / light industrial E.M.C. environments on a governed meter supply only.
8. The boiler must be installed with one of the purpose designed flues such as the standard horizontal flue kit, part nº 236921.
“Benchmark” Log Book
As part of the industry-wide “Benchmark” initiative all Baxi boilers now include an Installation, Commissioning and Service Record Log Book. Please read the Log Book carefully and complete all sections relevant to the appliance and installation. These include sections on the type of controls employed, flushing the system, burner operating pressure etc. The details of the Log Book will be required in the event of any warranty work. Also, there is a section to be completed at each subsequent regular service visit.
1.2 Important Information
This product contains Refractory Ceramic Fibres (R.C.F.) which are man-made vitreous silicate fibres. Excessive exposure to these materials may cause temporary irritation to eyes, skin and respiratory tract. Care must be taken when handling these articles to ensure the release of dust or fibres is kept to a minimum.
To ensure that the release of fibres from these articles is kept to a minimum, during installation and servicing it is recommended that a HEPA. filtered vacuum is used to remove any dust, soot or other debris accumulated in and around the appliance. This should be performed before and after working on the installation.
It is recommended that any replaced item(s) are not broken up but sealed within heavy duty polythene bags and clearly labelled “R.C.F. waste”. This is not classified as “hazardous waste” and may be disposed of at a tipping site licensed for the disposal of industrial waste.
Protective clothing is not required when handling these articles but it is recommended that gloves are worn and the normal hygiene rules of not smoking, eating or drinking in the work area are followed and always wash hands before eating or drinking.
2.0 General Layout – page 5
2.1 Layout (Figs. 3,4 & 5)
1. Wall Plate
2. Flue Elbow
3. Heat Exchanger
4. Burner
5. Air Box
6. Fan Protection Thermostat
7. Fan Assembly
8. Condensate Trap
9. User Interface (optional timer available)
10. Gas Tap
11. Gas / Air Ratio Valve
12. Electronics Housing
13. Transformer
14. Flow Pipe Connection
15. Return Pipe Connection
16. Flow Temperature Safety Thermostat - Black
17. Flow Temperature Thermistor - Red
18. Flow Switch (dry fire protection)
2.2 Optional Extras
KIT PART Nº FLUE EXTENSION KITS (110/70) Flue Extension 0.25M 241692 Flue Extension 0.5M 241694 Flue Extension 1 M (Use two kits for 2M etc.) 241695 Flue Bend x 2 – 45º (Reduce overall length
of flue by 0.5m when fitting this bend) 241689 Flue Bend – 90º (Reduce Overall length of
flue by 1m when fitting each bend) 241687 VERTICAL FLUE (110/70)
Vertical Flue Terminal 242802 Vertical Boiler Connection 242886 CONTROL ACCESSORIES
Integral Electronic Twin Channel Timer Kit 242834
3.0 Appliance Operation – page 6
3.1
1. Pump Overrun: When the switched live to the boiler switches on or the flow temperature is greater than the set point or anti-cycle finishes then Pump Overrun occurs for 10 seconds (cold) or 60 seconds (hot). The pump is on while the fan, spark generator and gas valve are off.
2. Fan Purge: When pump overrun has finished if the flow temperature is less than that set on the thermostat knob then Fan Purge occurs. The pump and fan are on while the spark generator and gas valve are off.
3. Ignition: When fan purge has finished Ignition occurs. The pump, fan, spark generator and gas valve are on. The burner ignites at mid rate.
4. Burner On: When a flame is detected during the ignition period then Burner On occurs. The pump, fan and gas valve are on while the spark generator is off. Flow temperature is controlled by varying the fan speed (and thereby the gas rate) to achieve optimum operation.
5. Anti-cycle: When all the TRVs shut down during Burner On or Pump Overrun finishes and flow temperature is greater than set point then Anti-cycle occurs. The pump, fan, spark generator and gas valve are switched off.
6. Ignition Lockout: When 5 ignition attempts have been made without a flame being detected then Ignition Lockout occurs. The pump, fan, spark generator and gas valve are switched off. The lockout light flashes once a second. The boiler can only be reset manually using the thermostat knob.
7. No Water Flow: When there is No Water Flow through the boiler (indicated by the flow switch) then a continuous cycle of Pump Overrun and Anti-cycle occurs.
4.0 Technical Data – page 7
5.0 Dimensions and Fixings – page 8
Fig. 6
DIMENSIONS A 600mm B 320mm C 390mm D l25mm Ø Min. E 150mm F 125mm
The 3º (1 in 20) fall provided by the elbow is to allow condensate to run back to the boiler, for disposal through the condensate discharge pipe.
Fig 7
SIDE FLUE (left and right)
For every 1 m of horizontal flue length, the clearance above the top of the flue elbow should be 55mm to incorporate the 3º (1 in 20) fall in the flue from the terminal to the elbow.
Flue length (Y) Clearance (X)
Up to1m 55mm 1m-2m 110mm 2m-3m 165mm
6.0 System Details – page 9
Fig. A Wiring to the pump feed connection of boiler
6.1 Water Circulating Systems
1. The appliance is suitable for use with open vent fully pumped systems and sealed systems.
The following conditions should be observed on all systems:
The static head must not exceed 30m (100ft) of water.
The boiler must not be used with a direct cylinder.
Drain cocks should be fitted to all system low points.
All gas and water pipes and electrical wiring must be
installed in a way which would not restrict the servicing of the boiler.
Position isolating valves as close to circulating pump as possible.
It is recommended that the return pipe is fitted with an automatic air vent as close to the boiler as is practical.
NOTE: Full TRV Systems (refer to section 6.4) Where all the radiators are controlled by TRV’s then pump protection will be required. This can be done by either of the options opposite (see Fig A & B). The option shown in Fig. A
should only be used on a full TRV system without a bypass. Fig. B shows a system with a bypass that must be capable of allowing a flow of at least 3 l/mm.
Fig. B Providing a 3 l/mm bypass
6.2 Treatment of Water Circulating Systems
All recirculatory water systems will be subject to corrosion unless an appropriate water treatment is applied. This means that the efficiency of the system will deteriorate as corrosion sludge accumulates within the system, risking damage to pump and valves, boiler noise and circulation problems.
When upgrading existing systems that exhibit evidence of sludging, it is advisable to clean the system prior to treatment in order to remove any sludge and reduce the likelihood of these deposits damaging new components.
When fitting new systems flux will be evident within the system, which can lead to damage of system components.
All systems must be thoroughly drained and flushed out. The recommended flushing and cleansing agents are Betz-Dearborn Sentinel X300 or X400 and Fernox Superfloc Universal Cleanser which should be used following the flushing agent manufacturer’s instructions.
System additives - corrosion inhibitors and flushing agents/descalers should be suitable for aluminium and comply to BS7593 requirements. The only system additives recommended are Betz-Dearborn Sentinel X100 and Fernox-Copal which should be used following the inhibitor manufacturer’s instructions.
Failure to flush and add inhibitor to the system will invalidate the appliance warranty.
It is important to check the inhibitor concentration after installation, system modification and at every service in accordance with the manufacturer’s instructions. (Test kits are available from inhibitor stockists.)
For information or advice regarding any of the above contact the Baxi Helpline.
6.0 System Details – page 10
Fig. 7a
Fig. 8 Typical Low Head Installation
Fig. 9 If Conditions Require,
This System Possible
6.3 Pipework
1. The sizes of flow and return pipes from the boiler should be determined by normal methods, according to the requirements of the system. The connection to the boiler is 28mm (compression).
2. Due to space requirements within the boiler outercase, pipework should comprise of solder fittings.
3. A 20ºC (36ºF) drop in temperature across the system is recommended for condensing boilers. Existing radiators may be oversized and so allow this, but where radiator sizing is marginal it may be advisable to retain a system temperature drop of 11ºC (20ºF).
4. In systems using non-metallic pipework it is necessary to use copper pipe for the boiler Flow and Return. The copper must extend at least 1 metre from the boiler and include any branches (Fig. 7a).
6.4 System Controls
1. For optimum operating conditions, the heating system into which the boiler is installed should include a control system.
2. Such a system will comprise of a timer control and separate room or cylinder thermostats as appropriate. (An integral twin channel programmer is available as an optional extra).
3. The boiler should be controlled so that it operates on demand only.
4. Operation of the system under control of the boiler thermostat & TRV’s only does not produce the best results.
Fig. 10 Alternative Low Head Installation
6.5 Low Head Installation
1. Using a close couple arrangement the minimum head is as shown in the diagrams (Figs. 8 & 9) subject to the following conditions:
a) The pump being adjusted to give an 20ºC drop across
the boiler.
b) The pump must be fitted on the flow. c) The pump must be fitted in accordance with the pump
manufacturers instructions.
d) The open vent pipe must be taken up from a tee in a
horizontal section of the flow pipe. An alternative Low Head Installation (Fig. 10)
2. For heads below 400mm then a combined vent and feed pipe may be connected. This must be a minimum of 22mm diameter. It is recommended that an air separator is fitted when using a combined feed and vent pipe.
6.6 Thermal Stores
1. The Barcelona must not be fitted to thermal stores which override the boiler control system.
6.0 System Details – page 11
Fig 11
6.7 Sealed Systems (Fig. 11)
1. SAFETY VALVE - A safety valve complying with the requirements of BS 6750 Part 1 must be fitted close to the boiler on the flow pipe by means of a horizontal or vertically upward connection with no intervening valve or restrictions and should be positioned to facilitate testing. The valve should be pre-set and non-adjustable to operate at a pressure of 3 bar (45 lbf/in²). It must be arranged to discharge any water or steam through a pipe to a safe outlet position.
2. PRESSURE GAUGE - A pressure gauge of minimum range 0-4 bar (0-60 lbf/in²) with a fill pressure indicator must be fitted to the system, preferably at the same point as the expansion vessel in an easily visible position.
3. EXPANSION VESSEL - An expansion vessel complying with the requirements of BS 4814 must be fitted to the system by means of a connection close to the inlet side of the circulating pump in accordance with the manufacturers instructions, the connecting pipe being unrestricted and not less than 15mm (½ in) nominal size. The volume of the vessel should be suitable for the system water content and the nitrogen or air charge pressure should not be less than the system static head (See Table. 1).
Table 1
NOTE
Where a vessel of the calculated size is not obtainable
then the next available larger size should be used.
Further details of sealed system design can be obtained from BS 5449 and the British Gas publication entitled Specifications for Domestic Wet Central Heating Systems’.
4. FILLING POINT - A filling point and an approved stop valve to BS 1010 must be fitted at low level and the method used for filling the system should be approved by the local water undertaking. For further details see BS 6798.
5. MAKE UP SYSTEM - A method of replacing water lost from the system should be provided either by means of a make up vessel of not more than 3 litres (5 pints) capacity, mounted above the highest point of the system, or by re-pressurisation of the system.
6. VENTING - A method of venting the system during filling and commissioning must be provided by fining automatic air vents or by venting manually.
7. HOT WATER STORAGE - The hot water storage vessel must be of the indirect coil type. All components used in the system must be suitable for operation at 110ºC (230ºF) and at the pressure allowed by the safety valve.
7.0 Site Requirements – page 12
Fig. 12
7.1 Information
WARNING - Check the information on the data plate is compatible
with local supply conditions
1. The installation must be carried out by a CORGI Registered Installer or other registered competent person and be in accordance with the relevant requirements of the current GAS
SAFETY (Installation and Use) REGULATIONS, the BUILDING REGULATIONS (Scotland)(Consolidation), the LOCAL BUILDING REGULATIONS, the current I.E.E. WIRING REGULATIONS and the bye laws of the LOCAL WATER UNDERTAKING. Where no specific instruction is given reference should be made to the relevant BRITISH STANDARD CODES OF PRACTICE. For Ireland install in accordance with IS 813 “INSTALLATION OF GAS APPLIANCES”. Reference should also be made to BRITISH GAS GUIDANCE NOTES FOR THE INSTALLATION OF DOMESTIC GAS CONDENSING BOILERS.
7.2 B.S. Codes of Practice
Standard Scope
BS 6891 Gas Installation BS 5546 Installation of hot water supplies for domestic
purposes. BS 5449 Part 1 Forced circulation hot water systems BS 6798 Installation of gas fired hot water boilers. BS 5440 Part 1 Flues BS 5440 Part 2 Ventilation BS 7074 Expansion vessels and ancillary equipment for
sealed water systems. BS 7593 Treatment of water in domestic hot water
central heating systems
Fig. 13
WARNING - The addition of anything that may interfere with the
normal operation of the appliance without the express written permission of Baxi Limited could invalidate the appliance warranty and infringe the GAS SAFETY (Installation and Use)
REGULATIONS.
7.3 Clearances (Figs. 12 &13)
1. A flat vertical area is required for the installation of the boiler.
2. These dimensions include the necessary clearances around
the boiler for case removal, spanner access and air movement. Additional clearances may be required for the passage of pipes around local obstructions such as joists running parallel to the front face of the boiler.
7.4 Location
1. The boiler may be fitted to any suitable wall with the flue
passing through an outside wall or roof and discharging to atmosphere in a position permitting satisfactory removal of combustion products and providing an adequate air supply. The boiler should be fitted within the building unless otherwise protected by a suitable enclosure i.e. garage or outhouse. (The boiler may be fitted inside a cupboard - see Section 7.5).
2. If the boiler is sited in an unheated enclosure then it is
recommended to incorporate an appropriate device for frost protection in the system controls.
3. If the boiler is fitted in a room containing a bath or shower
reference must be made to the current I.E.E.WIRING REGULATIONS and BUILDING REGULATIONS, If the boiler is to be fitted into a building of timber frame construction then reference must be made to the Institute of Gas Engineers document UP 7.
7.0 Site Requirements – page 13
Fig14
7.5 Ventilation of Compartments (Fig. 14)
1. Where the boiler is installed in a cupboard or compartment, air vents are required (for cooling purposes) in the cupboard or compartment at high and low level which may communicate with a room or direct to outside air.
NOTE: Both air vents must communicate with the same room or both be on the same wall to outside air
2. Detailed recommendations for air supply are given in BS 5440: Part 2.
3. An existing cupboard or compartment may be used, provided that it is modified for the purpose. Recommendations for air supplies and details of essential cupboard compartment design are given in BS 5440: Part 2.
7.6 Gas Supply
1. The gas installation should be in accordance with BS6891.
2. The connection to the appliance is a ½in BSPT internal threaded connection located at the rear of the gas service cock (Fig. 15).
3. Ensure that the pipework from the meter to the appliance is of adequate size. (22mm pipework must be connected to the appliance gas service cock. This should extend for at least 3 meters back towards the gas meter).
Do not use pipes of a smaller diameter than the boiler gas connection.
Fig. 15
7.7 Electrical Supply
1. External wiring must be correctly earthed, polarised and in accordance with current l.E.E. WIRING REGULATIONS.
2. The mains supply is 230V ~ 50Hz fused at 3A.
NOTE: The method of connection to the electricity supply must facilitate complete electrical isolation of the appliance. Connection may be via a fused double-pole isolator with a contact separation of at least 3mm in all poles and servicing the boiler and system controls only.
7.8 Condensate Drain
NOTE: Ensure the discharge of condensate complies with
any national or local regulations in force.
1. The condensate outlet terminates in a 1” BSP nut and seal for the connection of 21.5mm (¾in) plastic overflow pipe which should generally discharge internally into the household drainage system. If this is not possible, discharge into an outside drain is acceptable.
2. The pipe should run internally as much as possible and with a 10º (1 in 6) fall to dispose of condensate quickly to avoid freezing.
7.0 Site Requirements – page 14
Fig. 16 7.9 Flue
Fig. 17
NOTE: Due to the nature of the boiler a plume of water
vapour will be discharged from the flue. This should be taken into account when siting the flue terminal.
1. The following guidelines indicate the general requirements for siting balanced flue terminals. Recommendations for flues are given in BS 5440 Pt.1.
2. If the terminal is fitted within 1 metre (39 in) of a plastic gutter, within 500mm (19½ in) of a painted eave or a painted gutter, an aluminium shield of at least 1 metre (39 in) long should be fitted to the underside of the gutter or painted surface. An air space of 5mm (3/16 in) should be left between shield and gutter (Fig. 16).
3. If the terminal discharges onto a pathway or passageway, check that combustion products will not cause a nuisance and that the terminal will not obstruct the passageway.
4. Take into consideration the effect the plume of vapour may have on neighbours when siting the flue.
5. If a terminal is less than 2 metres (78¾ in) above a balcony, above ground or above a flat roof to which people have access, then a suitable terminal guard must be provided.
Terminal Position with Minimum Distance Fig 17 mm
A Directly below an openable window or other opening,
e.g. an air brick. B Below gutters, soil pipes or drain pipes. C Below eaves. D Below balconies or car port roof. E From vertical drain pipes and soil pipes. F From internal or external corners. G Above ground, roof or balcony level. H From a surface facing a terminal. I From a terminal facing a terminal. J Vertically from a terminal on the same wall. K Horizontally from a terminal on the same wall. L For an opening in a car port (e.g. door, window) into a
dwelling.
300
75 200 200
75 300 300 600
1200 1500
300
1200
Loading...
+ 30 hidden pages