Baxi Bahama 100 Installation And Servicing Instructions

Baxi Bahama 100
Gas Fired Wall Mounted Combination Boiler
Installation and Servicing Instructions
BAXI
Page 2
Baxi Bahama 100
G.C.Nº 47 075 02 Baxi Limited is one of the leading manufacturers of domestic
heating products in the UK. Our first priority is to give a high quality service to our
customers. Quality is designed into every Baxi product ­products which fulfil the demands and needs of customers, offering choice, efficiency and reliability.
The boiler meets the requirements of Statutory Instrument “The Boiler (Efficiency) Regulations 1993 Nº 3083” and is deemed to meet the requirements of Directive 92/42/EEC on the energy efficiency requirements for new hot water boilers fired with liquid or gaseous fuels:-
Type test for purpose of Regulation 5 certified by: Notified Body 0086.
To keep ahead of changing trends, we have made a commitment to develop new ideas using the latest technology - with the aim of continuing to make the products that customers want to buy.
Baxi is also the largest manufacturing partnership in the country. Everyone who works at the company has a commitment to quality because, as shareholders, we know that satisfied customers mean continued success.
We hope you get a satisfactory service from Baxi. If not, please let us know.
Baxi is a BS-EN ISO 9001
Accredited Company
Product/Production certified by: Notified Body 0086.
For GB/IE only.
Contents – page 3
Section
Page
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
Introduction
General Layout
Appliance Operation
Technical Data
Dimensions and Fixings
System Details
Site Requirements
installation
Electrical
Commissioning the Boiler
Fitting the Outer Case
4
5
6
7
8
9
12
17
24
26
28
12.0
13.0
14.0
15.0
16.0
17.0
18.0
Servicing the Boiler
Changing Components
Short Parts List
Fault Finding
Operational Flow Chart
Ignition Flow Chart
Notes
30
28
41
42
46
48
49
1.0 Introduction – page 4
Fig. 1
Fig. 2
NOTE: This appliance must be installed in accordance with the
manufacturer’s instructions and the regulations in force. Read the instructions fully before installing or using the appliance.
1.1 Description
1. The Baxi Bahama 100 is a fully automatic gas fired wall mounted combination boiler. It is room sealed and fan assisted, and will serve central heating and mains fed domestic hot water.
2. The boiler is preset to give a maximum output of 29.3 kW (100,000 Btu/h) for hot water. The central heating is factory set to 80,000 Btu/h, but can be rated as required from 50,000 to 100,000 Btu/h.
3. It is designed for use on Natural Gas (G20) and can be converted to use Propane.
4. The boiler is suitable for use only on fully pumped sealed heating systems. Priority is given to domestic hot water.
5. A label giving details of the model, serial number and Gas Council number is situated on the rear of the outer case lower door panel (Fig. 1).
6. The boiler data badge is positioned on the back face of the facia box (Fig. 2).
7. The boiler is intended to be installed in residential / commercial / light industrial E.M.C. environments on a governed meter supply only.
8. The boiler must be installed with one of the purpose designed flues such as the standard horizontal flue kit, part nº 241028.
9. All systems must be thoroughly flushed and treated with
inhibitor (see section 6.2).
“Benchmark” Log Book
As part of the industry-wide “Benchmark” initiative all Baxi boilers now include an Installation, Commissioning and Service Record Log Book. Please read the Log Book carefully and complete all sections relevant to the appliance and installation. These include sections on the type of controls employed, flushing the system, burner operating pressure etc. The details of the Log Book will be required in the event of any warranty work. Also, there is a section to be completed at each subsequent regular service visit.
1.2 Installation
1. The appliance is suitable for installation only in G.B. and I.E. and should be installed in accordance with the rules in force. For Ireland install in accordance with l.S.813 “INSTALLATION OF GAS APPLIANCES”. The installation must be carried out by a CORGI Registered Installer or other competent person and be in accordance with the relevant requirements of GAS
SAFETY (Installation and Use) REGULATIONS, the BUILDING REGULATIONS (Scotland) (Consolidation), the LOCAL BUILDING REGULATIONS, the CURRENT I.E.E. WIRING REGULATIONS and the bye laws of the Local Water
Undertaking. Where no specific instructions are given, reference should be made to the relevant BRITISH
STANDARD CODES OF PRACTICE.
1.3 Optional Extras
KIT PART Nº HORIZONTAL FLUE KITS Flue Extension 0.25M 241102 Flue Extension 0.5M 241101 Flue Extension 1M (Use two kits for 2M etc.) 241100 Flue Bend – 45º (Reduce overall length of flue by 0.5m when fitting this bend) 241104 Flue Bend – 90º (Reduce overall length of flue by 1m when fitting this bend) 241103 Wall Liner/Internal Fixing 236441
VERTICAL FLUE KITS Flue - 125/80mm Dia Concentric 241107 Twin Flue - 80mm Dia 241123
CONTROL ACCESSORIES Programmable Room Thermostat (24 hour) 236254 Programmable Room Thermostat (7 day) 238326 Integral Electronic Timer Kit (7 day) 241550 Integral Electro-Mechanical Timer Kit (12 hour am/pm) 241087
FUEL KIT
2.0 General Layout – page 5
2.1 Layout
1. Backplate
2. Airbox
3. Fan Assembly
4. Primary Heat Exchanger
5. Combustion Chamber
6. Burner Assembly & Electrodes
7. Gas Valve Assembly
8. Automatic Air Vent
9. Flow Switch Heating Circuit
10. Flow Switch DHW Circuit
11. Circulation Pump
12. Facia Box
13. Safety Thermostat
14. CH Thermostat Sensor
15. Three Way Valve
16. DHW Plate Heat Exchanger
17. ON-Off Selector Switch
18. DHW Temperature Adjustment
19. Heating Temperature Adjustment
20. Green Light - Power On
21. Orange Light - Burner On
22. Red Light - Flame Failure
23. Flame Failure Reset Switch
24. Water Pressure Gauge
25. Air Pressure Switch
26. Optional Integral Timers
27. Expansion Vessel
2.2 Nomenclature used in these instructions
DHW - Domestic Hot Water CH - Central Heating CVI Board - Ignition Board ECS Board - Control Board
3.0 Appliance Operation – page 6
NOTE: All delay timers mentioned in 3.1 and 3.2 are
overridden by domestic hot water demand.
3.1 Central Heating Mode
1. With a demand for heating, the pump circulates water through the primary circuit. At a flow rate of approximately 125 I/hr the central heating flow switch operates, initiating the ignition sequence.
2. The main burner ignites at low rate, then the gas valve controls the gas rate to maintain the heating temperature measured by the thermostat sensor.
3. When the flow temperature exceeds the setting temperature, a 3 minute delay occurs before the burner relights automatically (anti-cycling). The pump continues to run during this period.
4. When the demand is satisfied the burner is extinguished and the pump continues to run for a period of 30 seconds (Pump Overrun).
3.2 Domestic Hot Water Mode
1. Priority is given to the domestic hot water supply. A demand at a tap or shower will override any central heating requirement.
2. The flow of water will operate the DHW flow switch which requests the 3 way valve to change position. This will allow the pump to circulate the primary water through the DHW plate heat exchanger.
3. The burner will light automatically and the temperature of the domestic hot water is controlled by the thermostat sensor.
4. When the domestic hot water demand ceases the burner will extinguish and the diverter valve will remain in the domestic hot water mode, unless there is a demand for central heating.
3.3 Frost Protection Mode
1. The frost protection mode is integral to the appliance when left in the domestic hot water and central heating position. If the system temperature falls below 5º C then the boiler will fire on its minimum setting until a flow temperature of 30º C is reached. Further protection can be incorporated by using a system frost thermostat.
3.4 Pump Protection
1. The control system continually monitors the time since the pump last operates. This will result in the pump being run for 10 seconds every so often to prevent seizure.
4.0 Technical Data – page 7
5.0 Dimensions and Fixings – page 8
6.0 System Details – page 9
6.1 Information
1. The Baxi Bahama 100 Combination Boiler is a ‘Water Byelaws Scheme - Approved Product’. To comply with the Water Byelaws your attention is drawn to the following installation requirements and notes (IRN). a) IRN 001 - See text of entry for installation requirements and notes. b) IRN 116 - Byelaw 90 and 9l. c) IRN 302 - Byelaw 14.
2. Reference to the WRC publications, ‘Water fittings and materials directory’ and ‘Water supply byelaws guide’ give full details of byelaws and the IRNs.
6.2 Central Heating Circuit
1. The appliance is suitable for fully pumped SEALED SYSTEMS ONLY.
Treatment of Water Circulating Systems
All recirculatory water systems will be subject to corrosion unless an appropriate water treatment is applied. This means
that the efficiency of the system will deteriorate as corrosion sludge accumulates within the system, risking damage to pump and valves, boiler noise and circulation problems.
For optimum performance after installation this boiler and its associated central heating system must be flushed in
accordance with the guidelines given in BS 7593:1992 “Treatment of water in domestic hot water central heating systems”.
This must involve the use of a proprietary cleanser, such as BetzDearborn Sentinel X300 or X400, or Fernox Superfloc.
Full instructions are supplied with the products, but for immediate information please contact BetzDearborn (0151 420
9563) or Fernox (01799 550 811) directly.
For long term protection against corrosion and scale, after flushing it is recommended that an inhibitor such as
BetzDearborn Sentinel X100, or Fernox MB-1 or Copal is dosed in accordance with the guidelines given in BS 7593:1992.
Failure to flush and add inhibitor to the system may invalidate the appliance warranty.
It is important to check the inhibitor concentration after installation, system modification and at every service in
accordance with the manufacturer’s instructions. (Test kits are available from inhibitor stockists.)
For information or advice regarding any of the above contact the Baxi Helpline.
6.3 Bypass
1. The boiler has an integral pre-set bypass and in most cases this should suffice. However in certain circumstances, e.g. on systems where there is a high resistance and TRV’s are fitted to all the radiators it may be necessary to fit an external by-pass. This should be of the automatic type and not a gate valve or ball type valve. The valve must be fitted between the heating flow and return to the boiler before any other part of the system, i.e. Radiators, Diverter valves etc. If there are any doubts, contact the technical help line. (see page 7 for flow rates).
6.4 System Control
1. The boiler is designed for use in a heating system that incorporates external controls, i.e. a minimum of a timer device.
2. Suitable timer kits are available as optional extras.
3. For optimum operating conditions and maximum economy the fitting of a programmable thermostat, such as one of the Baxi Bahama 100 Controllers, is recommended.
6.0 System Details – page 10
Fig. 3
Fig. 4
6.5 System Filling and Pressurising
1. A filling point connection on the central heating return pipework must be provided to facilitate initial filling and pressurising and also any subsequent water loss replacement/refilling.
2. The filling method adopted must be in accordance with all relevant water supply bye-laws and use approved equipment.
3. Your attention is drawn to: IRN 302 and Byelaw 14.
4. The sealed primary circuits may be filled or replenished by means of a temporary connection between the circuit and a supply pipe, provided a ‘Listed’ double check valve or some other no less effective backflow prevention device is permanently connected at the inlet to the circuit and the temporary connection is removed after use (Fig. 3).
6.6 Expansion Vessel
(Central Heating only)
1. The appliance expansion vessel is pre-charged to 1 bar (10 lb/in²). Therefore, the minimum cold fill pressure is 1 bar. The vessel is suitable for correct operation for system capacities up to 125 litres (27.5gal). For greater system capacities an additional expansion vessel must be fitted - refer to BS 7074 Pt 1.
6.7 Pressure Relief Valve (Fig. 4)
1. The pressure relief valve is set at 3 bar, therefore all pipework, fittings, etc. should be suitable for pressures in excess of 3 bar.
2. The pressure relief discharge pipe should be not less than 15mm dia, run continuously downward, and discharge outside the building, preferably over a drain. It should be routed in such a manner that no hazard occurs to occupants or causes damage to wiring or electrical components. The end of the pipe should terminate facing down and towards the wall.
3. The discharge must not be above a window, entrance or other public access. Consideration must be given to the possibility that boiling water/steam could discharge from the pipe.
6.0 System Details – page 11
6.8 Domestic Hot Water Circuit
1. All DHW circuits, connections, fittings, etc. should be fully in accordance with relevant standards and water supply bye-laws.
2. Your attention is drawn to: IRN 116 and Byelaw 90 and 91. Sealed primary circuits and/or secondary hot water systems shall incorporate a means for accommodating the thermal expansion of water to prevent any discharge from the circuit and/or system, except in an emergency situation.
3. When the system includes any device which prevents water expanding back towards the supply (check valve, loose jumpered stopcock, water meter, water treatment device), then an expansion vessel must be fitted (e.g. Zilmet 160ml, R½ 15bar). To comply with Byelaw 91, a check valve must also be fitted on the supply as shown, to ensure efficient operation and also to prevent the reverse flow of hot water into the supply pipe.
4. If the hot water expansion is not provided for, then high pressures can develop which may result in damage to fittings and devices on the system.
Key
1 Expansion Vessel 2 Primary Heat Exchanger 3 Safety Thermostat 4 CH Thermostat Sensor 5 3 Way valve 6 DHW Plate Heat Exchanger 7 CH Flow Switch 8 Pump 9 Pressure Gauge 10 CH Flow Valve 11 Gas Inlet 12 DHW Mains Inlet 13 DHW Flow Switch 14 CH Return Valve 15 Pressure Relief Valve 16 Filling Loop 17 Flow Regulator 18 Filter 19 Gas Valve
5. The boiler’s maximum working mains pressure is 10 bar (150 lb/in²), therefore all pipework, connections, fittings, etc. should be suitable for pressures in excess of 10 bar. A pressure reducing valve must be fitted for pressures in excess of 10 bar. The manufacturer of any outlet fittings, such as a shower valve, may require a lower maximum pressure. The pressure reduction must take account of all fittings connected to the DHW system.
6.9 Showers
1. If a shower control is supplied from the appliance it should be of the thermostatic or pressure balanced type. Thermostatic type shower valves provide the best comfort and guard against water at too high a temperature. Existing controls may not be suitable ­refer to the shower valve manufacturer.
6.10 Hard Water Areas
1. If the area of the installation is recognised as a HARD WATER AREA then a suitable device should be fitted to treat the mains water supply to the boiler.
7.0 Site Requirements – page 12
Fig. 5
Fig. 6
7.1 Information
1. The installation must be carried out by a CORGI Registered Installer or other registered competent person and be in accordance with the relevant requirements of the current GAS SAFETY (Installation and Use) REGULATIONS, the BUILDING
REGULATIONS (Scotland) (Consolidation), the LOCAL BUILDING REGULATIONS, the current I.E.E. WIRING REGULATIONS and the bye laws of the LOCAL WATER UNDERTAKING. Where no specific
instruction is given reference should be made to the relevant BRITISH STANDARD CODES OF PRACTICE. For Ireland install in accordance with IS 813 “INSTALLATION OF GAS APPLIANCES”.
7.2 B.S. Codes of Practice
Standard Scope BS 6891 Gas Installation. BS 5546 Installation of hot water supplies for
domestic purposes. BS 5449 Part 1 Forced circulation hot water systems. BS 6798 Installation of gas fired hot water boilers. BS 5440 Part 1 Flues. BS 5440 Part 2 Ventilation. BS 7074 Expansion vessels and ancillary equipment
for sealed water systems. BS 7593 Treatment of water in domestic hot water
central heating systems.
WARNING - The addition of anything that may interfere with the normal operation of the appliance without the express written permission of Baxi Limited could invalidate the appliance warranty and infringe the GAS
SAFETY (Installation and Use) REGULATIONS.
7.3 Clearances (Fig. 5 & 6)
1. A flat vertical area is required for the installation of the
boiler.
2. These dimensions include the necessary clearances
around the boiler for case removal, spanner access and air movement. Additional clearances may be required for the passage of pipes around local obstructions such as joists running parallel to the front face of the boiler.
7.4 Location
1. The boiler may be fitted to any suitable wall with the
flue passing through an outside wall or roof and discharging to atmosphere in a position permitting satisfactory removal of combustion products and providing an adequate air supply. The boiler should be fitted within the building unless otherwise protected by a suitable enclosure i.e. garage or outhouse. (The boiler may be fitted inside a cupboard - see Section 7.5 ).
2. If the boiler is sited in an unheated enclosure then it is
recommended to leave the ON/OFF Selector Switch in the domestic hot water and central heating position to give frost protection.
3. If the boiler is fitted in a room containing a bath or
shower reference must be made to the current I.E.E.
WIRING REGULATIONS and BUILDING REGULATIONS. If the boiler is to be fitted into a
building of timber frame construction then reference must be made to British Gas document DM2.
7.0 Site Requirements – page 13
7.5 Ventilation of Compartments
1. Where the appliance is installed in a cupboard or
compartment, no air vents are required.
NOTE: The ventilation label on the front of the outer case MUST NOT BE REMOVED when the appliance is
installed in a compartment or cupboard.
2. BS 5440: Part 2 Clause 4.2 refers to room sealed
appliances installed in compartments. The appliance will run sufficiently cool without ventilation.
Fig. 8
7.6 Gas Supply
1. The gas installation should be in accordance with
BS6891.
2. The connection to the appliance is a 22mm copper tail
located at the rear of the gas service cock (Fig. 8).
3. Ensure that the pipework from the meter to the
appliance is of adequate size. Do not use pipes of a smaller diameter than the boiler gas connection (22mm).
7.7 Electrical Supply
1. External wiring must be correctly earthed, polarised and
in accordance with current I.E.E. WIRING REGULATIONS.
2. The mains supply is 230V ~ 50HZ fused at 3A.
NOTE: The method of connection to the electricity supply must facilitate complete electrical isolation of the appliance.
Connection may be via a fused double-pole isolator with a contact separation of at least 3mm in all poles and servicing the boiler and system controls only.
7.0 Site Requirements – page 14
Fig. 9
Fig. 10
7.8 Flue
1. An internal fitting kit is available for installations where
the flue terminal is inaccessible from the outside. This is available direct from Baxi Heating. Quote Part Nº 236441 when ordering.
2. The following guidelines indicate the general
requirements for siting balanced flue terminals. Recommendations for flues are given in BS 5440 Pt.1.
3. If the terminal is fitted within 1 metre (39 in) of a plastic
gutter, within 500mm (19½ in) of a painted eave or a painted gutter, an aluminium shield of at least 1 metre (39 in) long should be fitted to the underside of the gutter or painted surface. An air space of 5mm (3/16 in) should be left between shield and gutter (Fig. 9).
4. If the terminal discharges onto a pathway or
passageway, check that combustion products will not cause a nuisance and that the terminal will not obstruct the passageway.
5. If a terminal is less than 2 metres (78¾ in) above a
balcony, above ground or above a flat roof to which people have access, then a suitable terminal guard must be provided.
Terminal Position with Minimum Distance (Fig. 10)
A Directly below an openable window or other opening,
e.g. an air brick. B Below gutters. C Below eaves, soil pipes or drain pipes. D Below balconies or car port roof. E From vertical drain pipes and soil pipes. F From internal or external corners. G Above ground, roof or balcony level. H From a surface facing a terminal. I From a terminal facing a terminal. J Vertically from a terminal on the same wall. K Horizontally from a terminal on the same wall. L For an opening in a car port (e.g. door, window) into
a dwelling.
(mm)
300 25 75 200 75 25 300 600 1200 1500 300
1200
7.0 Site Requirements – page 15
Fig. 11
7.9 Flue Dimensions
See Section 1.2. The standard horizontal flue kit allows for flue lengths between 200mm (7 7/8 in) and 1m (39 3/8 in) from elbow to terminal (Fig. 11).
The maximum permissible equivalent flue length is: 4 metres.
NOTE: Each additional 45º of flue bend will account
for an equivalent flue length of 0.5m. eg. 45º = 0.5m, 90º = 2 x 45º = 1m etc.
7.10 Flue Terminal Trim
1. The trim should be fitted once the flue is secure.
2. Take the three edge clips from the kit and fit equi­spaced onto the inner flange of the trim (Fig. 11b).
3. With the flanges towards the wall pass the trim over the terminal (Fig. 11c). If required a bead of sealant may be applied to the rear face of the trim.
4. Push firmly on the trim to ensure the edge clips engage on the flue.
Fig. 12
7.11 Terminal Guard (Fig. 12)
1. When codes of practice dictate the use of terminal guards, they can be obtained from most Plumbers’ and Builders’ Merchants.
2. When ordering a terminal guard, quote the appliance model number.
3. The guard manufacturers listed below can be contacted for terminal sizes and guard model numbers.
Tower Flue Components Ltd., Tower House, Vale Rise, Tonbridge, Kent. Tel: 01732 351555.
Quinnell, Barrett & Quinnell, 884 Old Kent Road, London, SE15 1NL. Tel: 0171 6391357.
4. The flue terminal guard should be positioned centrally over the terminal and fixed as illustrated.
7.0 Site Requirements – page 16
7.12 Flue Options
1. The Baxi Bahama 100 can be fitted with flue systems as illustrated.
2. The standard flue is suitable only for horizontal applications.
3. Maximum permissible equivalent flue lengths are:-
Horizontal 4.0 metres Vertical 4.0 metres
Vertical (Twin) 22.0 metres
4. Any additional “in line” bends in the flue system must be taken into consideration. Their equivalent lengths are:-
Concentric Pipes:
45º bend 0.5 metres 90º bend 1.0 metres
Twin Flue Pipes
45º bend 0.25 metres 90º bend 0.50 metres
NOTE: The elbow supplied with the standard horizontal flue is not included in any equivalent length calculations.
5. The illustrations opposite show examples of maximum equivalent lengths.
6. Full details of part numbers and descriptions of all optional flue components and kits can be found in Baxi Gas Central Heating Boilers Installers’ Guide.
7. Instructions for guidance and fitting are included in each kit.
Loading...
+ 37 hidden pages