baxi 624 Combi, 630 Combi User guide

Page 1
Please keep these instructions in a safe place.
If you move house please hand them over to the next occupier.
United Kingdom
en
User Guide
High Efficiency Wall Hung Condensing Gas Boiler
Baxi Combi
Page 2
Dear Customer,
Thank you very much for buying this appliance.
Please read through the manual carefully before using the product, and keep it in a safe place for later reference. In order to ensure continued safe and efficient operation we recommend that the product is serviced regularly. Our service and customer service organisation can assist with this.
We hope you enjoy years of problem-free operation with the product.
Page 3

Contents

7679305 - 1 - 14082017 3
Contents
1 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1 General safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2.1 The Benchmark Scheme . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2.2 Benchmark Commissioning Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3 Liabilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3.1 User's liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
1.3.2 Installer's liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.3.3 Manufacturer's liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2 About this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.2 Additional documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.3 Symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.3.1 Symbols used in the manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.4 Abbreviations/glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3 Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.1 Homologations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.1.1 Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.2 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
3.2.1 Technical information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
3.2.2 Dimensions and connections/clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4 Description of the product . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.1 General description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
4.2 Operating principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.2.1 In operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.3 Control panel description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.3.1 Description of the control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.4 Accessories and options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.4.1 Optional accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
5.1 Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.1.1 Operation checking procedure & basic fault identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.2 Use of the control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.2.1 Using the control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.3 Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.4 Frost protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6.2 Maintenance instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6.2.1 Re-pressurising the system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6.3 Venting the installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6.4 Draining the installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
7 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
7.1 Error codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
7.1.1 List of error codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
7.2 Fault finding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
8 Decommissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
8.1 Decommissioning procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
9 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
9.1 Disposal and recycling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
10 Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
10.1 Energy saving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
10.2 Room thermostats and settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
11 Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Page 4
Contents
4 7679305 - 1 - 14082017
11.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
11.2 Standard warranty terms and conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
12 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
12.1 Product fiche - Combination boilers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
12.2 Package fiche - boilers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
12.3 Package fiche - Combination heaters (boilers or heat pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Page 5
1 Safety
PN-0000367
A
B
7679305 - 1 - 14082017 5

1.1 General safety instructions

1 Safety

Danger This boiler can be used by children aged 8 years and above and by persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge when they have been given supervision or instruction concerning the safe use of the device and understand the resulting risks. Children must not be allowed to play with the appliance. Cleaning and user maintenance must not be carried out by children without supervision.
Danger If you smell gas:
1. Turn off the gas supply at the meter.
2. Open windows and doors in the hazardous area.
3. Do not operate light switches.
4. Do not operate any electrical equipment.
5. Do not use a telephone in the hazardous area.
6. Extinguish any naked flame and do not smoke.
7. Warn any other occupants and vacate the premises.
8. Telephone the National Gas Emergency Service on:- 0800 111 999.
Fig.1 Taps ON and OFF
Note If a water or gas leak occurs or is suspected, the boiler can be iso
1
lated at the inlet valves by turning their taps through 90° (
/4 turn)
downwards.
A ON B OFF
For advice please contact your Installer, Annual Service Provider or Baxi Customer Support - The Service Division of Baxi. You can contact Baxi Customer Support on telephone number 0344 871
1545. When contacting Baxi Customer Support it will be useful to have the "Benchmark Checklist " at the back of the Installation & Serv ice Manual to hand as it includes details relevant to the boiler and installation.
Warning Do not touch flue/chimney pipes. Depending on the settings of the appliance, the temperature of flue/chimney pipes may exceed 60 °C. Do not touch radiators for long periods. Depending on the settings of the appliance, the temperature of radiators may reach 85 °C. Take precautions with domestic hot water. Depending on the set tings of the appliance, domestic hot water temperature may reach 65 °C.
Caution Do not neglect to service the appliance. Contact a qualified pro fessional or take out a maintenance contract for the annual servic ing of the appliance.
Page 6
1 Safety
6 7679305 - 1 - 14082017

1.2 Recommendations

Caution
Only qualified professionals are authorised to work on the boiler and the installation. The appliance has an integral frost protection mode as long as there is power to the boiler.
Important
Regularly check the water pressure in the system (recommen ded pressure is 1.5 bar). Keep the appliance accessible at all times. Do not remove or cover the user information and serial number labels affixed to the boiler control flap. They must remain legible throughout the lifetime of the boiler.
1.2.1
Baxi Heating UK Ltd is a licensed member of the Benchmark Scheme which aims to improve the standards of installation and commissioning of domestic heating and hot water systems in the UK and to encourage regu lar servicing to optimise safety, efficiency and performance.
Benchmark is managed and promoted by Heating and Hotwater Industry Council. For more information visit www.centralheating.co.uk
1.2.2
Please ensure that the installer has fully completed the Benchmark Check list on the inside back pages of the installation instructions supplied with the product and that you have signed it to say that you have received a full and clear explanation of its operation. The installer is legally required to complete a commissioning checklist as a means of complying with the ap propriate Building Regulations (England and Wales).
All installations must be notified, by the installer, to Local Area Building Control either directly or through a Competent Persons Scheme. A Build ing Regulations Compliance Certificate will then be issued to the customer who should, on receipt, write the Notification Number on the Benchmark Checklist.
This product should be serviced annually to optimise its safety, efficiency and performance. The service engineer should complete the relevant sec tion of the Benchmark Service Record in the Installation & Service manual after each service.
The completed Benchmark Checklist & proof of annual servicing (where applicable) will be required in the event of any warranty work.

The Benchmark Scheme

Benchmark Commissioning Checklist

1.3

Liabilities

1.3.1 User's liability

To guarantee optimum operation of the system, you must abide by the fol lowing instructions:
Read and follow the instructions given in the manuals provided with the appliance. Call on a qualified professional to carry out installation and initial com missioning. Get your installer to explain your installation to you. Have the required inspections and maintenance carried out by a quali fied installer. Keep the instruction manuals in good condition close to the appliance.
Page 7
1 Safety
7679305 - 1 - 14082017 7

1.3.2 Installer's liability

The installer is responsible for the installation and initial commissioning of the appliance. The installer must observe the following instructions:
Read and follow the instructions given in the manuals provided with the appliance. Install the appliance in compliance with prevailing legislation and stand ards. Carry out initial commissioning and any checks necessary. Explain the installation to the user. If maintenance is necessary, warn the user of the obligation to check the appliance and keep it in good working order. Give all the instruction manuals to the user.

1.3.3 Manufacturer's liability

Our products are manufactured in compliance with the requirements of the various Directives applicable. They are therefore delivered with the marking and any documents necessary. In the interests of the quality of our products, we strive constantly to improve them. We therefore reserve the right to modify the specifications given in this document.
Our liability as manufacturer may not be invoked in the following cases:
Failure to abide by the instructions on installing the appliance. Failure to abide by the instructions on using the appliance. Faulty or insufficient maintenance of the appliance.
Page 8

2 About this manual

8 7679305 - 1 - 14082017
2 About this manual

2.1 General

Warning Installation, repair and maintenance must only be carried out only by a competent person.
All Gas Safe registered engineers carry an ID card with their licence num ber and a photograph. You can check your engineer is registered by tele phoning 0800 408 5500 or online at www.gassaferegister.co.uk
This manual is intended for the user of the Baxi Combi boiler. If the appli ance is sold or transferred, or if the owner moves leaving the appliance behind you should ensure that the manual is kept with the appliance for consultation by the new owner and their installer.
The appliance is designed as a boiler for use in residential domestic envi ronments on a governed meter supply only. The selection of this boiler is entirely at the owner’s risk. If the appliance is used for purposes other than or in excess of these specifications, the manufacturer will not accept any liability for resulting loss, damage or injury.
The manufacturer will not accept any liability whatsoever for loss, damage or injury arising as a result of failure to observe the instructions for use, maintenance and installation of the appliance.

2.2 Additional documentation

2.3 Symbols used

Various timers, external controls, etc. are available as optional extras. Full details are contained in the relevant sales literature.

2.3.1 Symbols used in the manual

This manual uses various danger levels to draw attention to special in structions. We do this to improve user safety, to prevent problems and to guarantee correct operation of the appliance.
Danger Risk of dangerous situations that may result in serious personal injury.
Danger of electric shock Risk of electric shock.
Warning Risk of dangerous situations that may result in minor personal in jury.
Caution Risk of material damage.
Important Please note: important information.
See Reference to other manuals or pages in this manual.
2.4

Abbreviations/glossary

CH Central heating
Page 9
DHW Domestic hot water
7679305 - 1 - 14082017 9
PCU PCB for managing burner operation Pnc Condensing output SU Safety PCB
2 About this manual
Page 10

3 Technical specifications

10 7679305 - 1 - 14082017
3 Technical specifications

3.1 Homologations

3.1.1 Certifications

Tab.1 Certifications
CE certificate number
NOx class 5
Boiler type C13, C
3.2

Technical data

33

3.2.1 Technical information

Tab.2 General
Baxi Combi 624 630
Gas council numbers 47 077 28 47 077 29
Tab.3 Central heating circuit specifications
Baxi Combi 624 630
Maximum pressure bar 3 3
Minimum pressure bar 0.5 0.5
Central heating temperature adjustment °C 25/80 ± 5° 25/80 ± 5°
Tab.4 Domestic hot water circuit specifications
Baxi Combi 624 630
Maximum pressure bar 8 8
Dynamic minimum pressure bar 0.5 0.5
Minimum working water flow rate l/min 2.0 2.0
Domestic hot water temperature range adjust ment
Specific flow rate (D) l/min 10 12.5
Important Where low flow taps or fittings are intended to be used in the DHW system connected, it is strongly recommended that the DHW flow rate DOES NOT fall below 2.5 l/min. This will ensure reliable op eration of the DHW function.
Tab.5 Electrical specifications
Baxi Combi 624 630
Nominal electrical power supply voltage V 230 230
Nominal electrical power supply frequency Hz 50 50
Nominal power consumption when firing W 100 100
External fuse rating Amp 3 3
°C 35/60 ± 5° 35/60 ± 5°
Page 11
Tab.6 Other specifications
PN-0000605
700
285
390
5
5
178
200
450
5
1
2
3
4
5
6
7
8
9
11
10
7679305 - 1 - 14082017 11
Baxi Combi 624 630
3 Technical specifications
Degree of protection against humidity (EN
IP IPX5D IPX5D
60529)
Boiler lift weight (dry) kg 30.16 30.16
Dimensions (height/width/depth) mm H 700/W 390/D 285 H 700/W 390/D 285
Clearances (above/below casing) front (for servicing)/(in operation) side (left hand/right hand)
mm mm mm
178 / 200 450 / 5 5 / 5
178 / 200 450 / 5 5 / 5
These are MINIMUM recommended dimensions. Greater clearance will aid installation and maintenance.
Important All data in this section are nominal values and subject to normal production tolerances.

3.2.2 Dimensions and connections/clearances

Fig.2
Dimensions and connections / clearances
1
Condensate trap sump
2
Condensate drain
3
Heating circuit water flow
4
Hot water outlet
5
Gas inlet
6
Pressure relief pipe
7
Cold water inlet
8
Heating circuit water return
9
Pump drain point
10
Boiler drain point on flow isolation tap
11
Cable entry points
The clearances shown in the diagram are minimum requirements to allow for case removal, spanner access and air movement. These should be ob served at all times and kept clear of obstructions.
Page 12
PN-0000606
A
R
Reset
bar
0
1
2
3
4
1
2
3
4
5 6
PN-0000607
M
i
n
M
a
x
M
a
x
M
i
n

4 Description of the product

12 7679305 - 1 - 14082017
4 Description of the product

4.1 General description

Fig.3
Information label

4.2 Operating principle

The Baxi Combi range of fully automatic gas fired wall hung condensing combination boilers are room sealed and fan assisted, and will serve cen tral heating and mains fed domestic hot water.
A Information label
Tab.7 The boiler is set to give a maximum output of :-
624 model 25 kW DHW
21.16 kW CH Pnc (Condensing)
630 model 30 kW DHW
21.16 kW CH Pnc (Condensing)
The boiler is factory set for use only on Natural Gas (G20).
Priority is given to domestic hot water.
The boiler model, serial number and Gas Council number are also shown on the information label. This is for user reference.

4.2.1 In operation

Whilst the boiler is in operation cooled flue gases are discharged through the flue gas discharge pipe. This may appear as a cloud of steam which is normal.
Condensed water is discharged from the boiler heat exchanger into a pipe (the condensate drain). This pipe must never be altered or re-routed ex cept by a qualified professional.

4.3 Control panel description

Fig.4 Control panel

4.3.1 Description of the control panel

1 Display 2 Reset button 3 Central heating temperature control 4 Service diagnostic port 5 DHW temperature control 6 System water pressure gauge
Page 13
R
R
PN-0000336
4 Description of the product
7679305 - 1 - 14082017 13
Fig.5
4.4
Display screen

Accessories and options

Display description
The following symbols may be seen on the display
OFF (frost protection still enabled)
Indicates errors that prevent the burner from starting Error — not resettable by user Water pressure too low Indicates a resettable error
Not applicable Not applicable Generic error Burner lit DHW request Heating mode Units for temperature Units for pressure

4.4.1 Optional accessories

The table shows the accessories available for this boiler range.
Tab.8 Optional accessories
Part number Accessory
7212438 Baxi single channel wired programmable room thermostat
720971601 Baxi room thermostat
720330001 Baxi wired weather sensor
720648301 Multifit condensate & PRV combined pump
720644401 Multifit 1m condensate drain pipe 'trace heating' element
720664101 Multifit 2m Condensate drain pipe 'trace heating' element
720664201 Multifit 3m condensate drain pipe 'trace Heating' element
720664401 Multifit 5m condensate drain pipe 'trace heating' element
5121379 Multifit remote secondary PRV kit
248221 Multifit filling loop
7682790 Multifit rear pipework kit
7682545 Multifit pre-plumbing jig
7209714 Multifit wall mounted 24 hour timeclock
720030501 RF Single Channel Room Thermostat
7212444 Single channel wired timer
For flue accessories (elbows, extensions, clamps etc.) refer to the Flue Ac cessories Fitting Guide supplied in the literature pack.
Any of the above MUST be fitted ONLY by a qualified competent person. Further details can be found in the relevant sales literature and at www.baxi.co.uk
Page 14
START
Make sure the gas supply is turned ON and check if other gas appliances are operating (e.g. fire, cooker). If the property has a prepayment meter ensure it has sufficient credit.
NO
If no gas, consult your supplier.
Is there electricity to the boiler ? Is the display lit ?
Check electrical supply to boiler is switched on.
NO
YES
Is the Burner Flame showing.
Burner Flame (Indicates burner is on)
Boiler operating satisfactorily.
NO
YES
YES
YES
Is the E and R symbol illuminated or flashing ?
YES
Press the Reset Button
(e.g. press and hold for 5 seconds)
If it does not reset
CONTACT YOUR
INSTALLER OR
SERVICE ENGINEER.
Reset Symbol
Is the Spanner symbol illuminated or flashing ?
YES
Spanner Symbol
Error Code
Flame Failure
OR
PN-0000638
R R
RR
Boiler Temperature
Error Symbol
Central Heating
Reset Button
R
Reset
bar
0
1
2
3
4
M
i
n
M
a
x
M
a
x
M
i
n

5 Operation

14 7679305 - 1 - 14082017
5 Operation

5.1 Start-up

Fig.6 Start-up and checking

5.1.1 Operation checking procedure & basic fault identification

Page 15
Fig.7 Start-up and checking (continued)
IMPOR
T
AN
T: Where Low Flow Taps or Fittings are intended to be used in the DHW system connected it is strongly recommended that the DHW flow rate DOES NOT fall below 2.5 l/min. This will ensure reliable operation of the DHW function.
Is the Timer ON and calling for heat ?
Is the Room Thermostat (if fitted) set high enough ?
12
1
2
3
4
5
6
7
8
9
10
11
Typical examples of external timer
Ensure timer is set for Central Heating ON (see any instructions supplied with timer)
NO
YES
YES
NO
15
10
5
20
25
15
10
5
20
25
Turn Room Thermostat to maximum setting (typical example shown)
CH ON
CH OFF
bar
0
1
2
3
4
Is the Central Heating System Pressure between 1.0 and 2.5 bar ?
If the reading falls below 1.0 bar repressurise the system as described in Maintenance
NO
Error Code 118 showing low pressure.
YES
If you don’t know what you need to do
to get the boiler to light, or need help with
the system and controls, contact your
installer as soon as possible
PN-0000634
R
R
7679305 - 1 - 14082017 15
5 Operation
Page 16
Reset
PN-0000636
R
R
R
Reset
bar
0
1
2
3
4
M
i
n
M
a
x
M
a
x
M
i
n
5 Operation
16 7679305 - 1 - 14082017

5.2 Use of the control panel

5.2.1 Using the control panel

Fig.8 Using the control panel
Important OpenTherm controller.Your installer will advise you when this type of control is connected to the boiler. If so, any change to the boiler settings (e.g. heating temperature) must be made using the Open Therm controller not the boiler control panel. Please consult the user manual for the OpenTherm controller.
To increase or decrease boiler temperature and/or the domestic hot water (DHW) temperature:
1. Turn the control knob with the symbol over it clockwise to in crease the boiler set temperature. The set temperature will be shown on the display screen.
2. Turn the control knob with the symbol over it anticlockwise to de crease the boiler temperature. The temperature will be shown on the display screen.
3. Turn the control knob with the symbol over it clockwise to in crease the DHW temperature. The temperature will be shown on the display screen.
4. Turn the control knob with the symbol over it anticlockwise to de crease the DHW temperature. The temperature will be shown on the display screen.
To reset the boiler:
1. Press the
button for approximately 1 second, holding the button for more than 2 seconds the boiler will not reset. (see List of error co des, page 21.)

5.3 Shutdown

5.4

Frost protection

Isolate the mains power supply at the fused spur unit. Isolate the gas supply at the boiler valve. Protect the boiler from frost.
Important The boiler is not protected against frost once it has been shut down.
Important If it is anticipated that the boiler will not be used for a long period or the property is to be unoccupied it is recommended that the system be drained if the electricity and gas supplies are to be turned off. Your installer will be able to offer advice.
Where possible, draining the system should be avoided. If the system is to be unused during winter months several precautions must be taken:
Any parts of the system that are in unheated areas of the dwelling should be fitted with a device such as a pipe thermostat or frost thermo stat. Power must remain supplied to the boiler and controls. Gas must remain supplied to the boiler.
The boiler pump will operate if the system temperature drops below 7°C. If the temperature falls to 4°C the burner will ignite and remain lit until the temperature reaches 10°C. At this temperature the burner will extinguish but the pump will continue to operate for 15 minutes. This feature will pro tect the boiler and to some extent adjacent parts of the system but addi tional devices must be incorporated to guarantee frost protection.
Page 17
6 Maintenance
7679305 - 1 - 14082017 17

6.1 General

6 Maintenance

The boiler does not require any special maintenance. However, the boiler must be serviced annually in accordance with the Installation and Service Manual and the relevant section of the Benchmark Service Record com pleted in order to maintain the warranty.
Important Taking out a maintenance contract is recommended.
Caution Maintenance operations must be performed by a qualified compe tent person. Use only Baxi genuine spare parts.
The painted panels should be wiped with a damp cloth and then dried completely. DO NOT USE ABRASIVE CLEANING AGENTS.
6.2

Maintenance instructions

The central heating system should be checked regularly. Proceed as fol lows:
1. Check the water pressure in the central heating system.
Important If the water pressure is lower than 0.7 bar, the system must be topped up.
See Re-pressurising the system.
Important If the water pressure drops below 0.5 bar the boiler will not work.
2. Check radiators for leaks and (especially in damp areas) for rust.
3. Open and close the radiator valves several times a year to ensure they can still be rotated.
Caution Only a qualified installer may clean the inside of the boiler.

6.2.1 Re-pressurising the system

If the water pressure is too low, the system must be re-pressurised.
The normal operating water pressure is between 1 and 2 bar. If the pres sure exceeds 3 bar the safety pressure valve will operate and a fault is in dicated. Ensure that the filling loop is disconnected if it is of a temporary type. Contact your installer.
Page 18
PN-0000373
PN-0000635
6 Maintenance
18 7679305 - 1 - 14082017
Fig.9 Water pressure
Fig.10 "Easy-Fill" - operate green lever as
shown to add water
It may be necessary to repressurise the system occasionally (when the water pressure falls below 0.7). A filling device (the filling loop) will be fitted on the system. This may be on the boiler itself, or on pipework near to the boiler.
Important If the water pressure requires regular re-pressurising a fault or leak is indicated. Seek advice from your installer.
The Baxi 600 Combi is supplied with a special device, the "Easy-Fill" per manent filling link.
1. Operate the spring loaded green lever to add water to the system.
Important The system pressure is shown at all times on the pressure gauge and can be viewed on the display when there is power to the boil er.
2. When the figures on the display or needle on the pressure gauge in dicate between 1 and 1.5 bar release the lever.
3. It is not necessary to remove any part of the permanent link.
4. When the correct pressure is restored the boiler will reset automati cally.
See Go to the "How to videos" section of the "Information & advice" page at www.baxi.co.uk for further details.
Page 19

6.3 Venting the installation

76
A
C
B
5
4
3
2
1
2
3
4
1
10
PN-0000468
M
a
x
M
i
n
R
M
a
x
M
i
n
R
x 2
PN-0000608
R
Reset
bar
0
1
2
3
4
M
i
n
M
a
x
M
a
x
M
i
n
7679305 - 1 - 14082017 19
6 Maintenance
Fig.11 Venting the radiators
If any air is present in the appliance or system it must be removed in order to prevent nuisance noises that may occur during heating or when drawing off hot water. Proceed as follows:
1. Open the valves of all the radiators connected to the system.
2. Set the room thermostat to the highest possible temperature and any timers to ‘ON’.
3. Wait until the radiators are warm.
4. Switch off the boiler.
5. Vent the radiators. Work from the lowest radiator in the property.
6. Open the bleed vent with the key, keeping a cloth pressed against the vent.
7. Wait until water comes out of the bleed vent and then close.
Warning The CH water in the radiators will still be hot.
8. Switch the boiler on.
9. After venting, check that the water pressure in the system is still ad equate.
Important If the water pressure is lower than 0.7 bar, the water must be top ped up. If necessary repressurise the system (recommended pressure between 1 and 1.5 bar when cold).
10. Reset the room thermostat to the desired temperature.
Fig.12 Enabling de-aeration function
The purpose of the function is to remove as much air as possible from the heating system.
1. Turn off the power to the boiler and rotate the CH control knob fully anticlockwise.
2. Turn on the power to the boiler. The display shows "000" .
3. Turn the CH control knob ( ) 1/4 turn clockwise twice in quick suc cession (within 2 seconds).
4. Display shows "312" while de-aeration is taking place (approximately 7 minutes).
5. When de-aeration has completed, the display will show the primary flow temperature and both the CH ( ) and DHW ( ) symbols.
Page 20
AD-3000730-01
5
3
2
1
2
3
4
1
4
6 Maintenance
20 7679305 - 1 - 14082017
Caution If the system is drained (even partly, when replacing a radiator for example) the de-aeration function must be repeated. Also the in hibitor concentration must be checked and replenished if necessa ry.
6.4

Draining the installation

Fig.13 Draining the installation
It may be necessary to drain the central heating system if radiators need to be replaced, if there is a major water leak or if there is a risk of freezing. Proceed as follows:
1. Open the valves of all the radiators connected to the system.
2. Switch off the boiler's electrical connection.
3. Wait approximately ten minutes, until the radiators feel cold.
4. Connect a drain hose to the lowest draining point. Place the end of the hose in a drain or at a place where drained pipe water will not cause any damage.
5. Open the central heating system fill/drain valve. Drain the installa tion.
Warning The water may still be hot.
6. Close the drain valve when no more water comes from the draining point.
Important After draining the system, the concentration of corrosion inhibitor and antifreeze agent may be extremely diluted - check with your installer.
Page 21
7 Troubleshooting
R
Reset
PN-0000637
R
R
Reset
bar
0
1
2
3
4
M
i
n
M
a
x
M
a
x
M
i
n
7679305 - 1 - 14082017 21

7.1 Error codes

7 Troubleshooting

7.1.1 List of error codes

Fig.14 Control panel error display
Tab.9 Table of error codes
Error code Description of fault
09
15
20
28
40
83
109
110
118
125
128
130
133
135
Gas valve connection cable
Gas valve fault
Central heating NTC fault
Flue NTC fault
Central heating return NTC fault
Communication error
Pre-circulation fault
Safety thermostat operated
Primary system water pressure too low
Circulation fault (primary)
Flame failure
Flue NTC operated
Interruption of gas supply or flame failure
Interruption of gas supply (internal error)
154
160
270
321
384
Flow / return sensor temperature test
Fan or fan wiring fault
Circulation fault (Dry fire)
Hot water NTC fault
False flame
The display shows two types of signals: and R. In both cases the display shows symbol and the numeric value of the error (see the table
of error codes above).
The spanner symbol appears it cannot be reset by the user. Please contact your Installer, Annual Service Provider or Baxi Customer Support. You can contact Baxi Customer Support on 0344 871 1545.
fault errors can be reset by pressing the
button.
For 103, 104, 107 & "Bat" please contact your installer, annual service provider or Baxi Customer Support
Important If a different error code from those described in the "Table of error codes" appears on the display contact Baxi Customer Support.
Page 22
7 Troubleshooting
22 7679305 - 1 - 14082017

7.2 Fault finding

Tab.10 Problems and solutions
Problem Possible causes Solution
Check that the boiler is being supplied with power. Check fuses and the switches.
The boiler is not working.
There is no domestic hot wa ter.
The DHW function is switched off. Activate the DHW mode.
The water pressure is too low (< 0.5 bar). Re-pressurise the system.
Insufficient flow. Flow must be at least 2.5 litres per minute.
Check whether the gas isolation cock is properly open. If the property has a prepayment meter ensure it has sufficient credit.
The radiators are cold.
The boiler is not working.
The temperature set point for the heating is too low.
The heating mode is deactivated. Activate the heating mode.
The radiator valves are not open. Open the valves of all radiators connected to the
The boiler is not working. Check that the boiler is being supplied with power.
The water pressure is too low (< 0.5 bar). Re-pressurise the system.
The temperature set point for the heating is too low.
No demand for heating. Ensure that timers & thermostats are calling for
No power supply. Check that the boiler is being supplied with power.
The water pressure is too low (< 0.5 bar). Re-pressurise the system.
The boiler is indicating an error. Press the Reset button.
Increase the value with the CH temperature knob or if a room thermostat is connected, increase the temperature on the room thermostat.
system.
Check fuses and switches. Check whether the gas isolation cock is properly open. If the property has a prepayment meter ensure it has sufficient credit.
Increase the value with the CH temperature knob or if a room thermostat is connected, increase the temperature on the room thermostat.
heat.
Check the fuses and switches.
Correct the error, if possible.
The gas pressure is too low. Check whether the gas isolation cock is fully open.
Open the gas isolation cock.
Condensate drain blocked. Check drain, especially any external runs in freez
ing temperatures.
If the boiler is not working also check section "Operation checking proce dure and basic fault identification" or contact your Installer.
Page 23
8 Decommissioning
7679305 - 1 - 14082017 23

8.1 Decommissioning procedure

8 Decommissioning

Caution Only qualified persons are authorised to work on the appliance and system to decommission.
If your boiler needs to be decommissioned either temporarily or perma nently the following should be performed:
1. Switch off the boiler’s electrical connection.
2. Close the gas isolation tap.
3. Drain the central heating system.
Seek the advice of your installer.
Page 24

9 Disposal

24 7679305 - 1 - 14082017
9 Disposal

9.1 Disposal and recycling

Caution Removal and disposal of the boiler must be carried out by a quali fied person in accordance with local and national regulations.
Page 25

10 Environmental

7679305 - 1 - 14082017 25

10.1 Energy saving

10 Environmental
Tips on saving energy:
Do not cover radiators. Do not hang curtains in front of radiators. Install reflective panels behind the radiators to prevent heat loss. Insulate the pipes in rooms that are not heated (cellars and lofts). Install loft insulation & double glazing. Use draught excluders where necessary. Upgrade any older boiler external controls. Turn down room thermostats by 1°. Turn off radiators in rooms not in use. Do not run hot (or cold) water pointlessly. Fit a water-saving shower head to save up to 40 % energy. Take showers rather than baths. A bath consumes twice as much water and energy.
10.2

Room thermostats and settings

Various models of room thermostat are available. The thermostat type and setting affect the total energy consumption.
A few tips:
A modulating thermostat in combination with thermostatic radiator valves saves energy and offers considerable comfort. This combination gives you flexibility with the temperatures. Do not fit thermostatic radiator valves in the room in which the room thermostat is installed. Completely closing and opening thermostatic valve radiators causes un desirable temperature fluctuations. Open and close thermostatic valves in small steps. Lower the thermostat to around 20°C. This reduces heating costs and energy consumption. Lower the room thermostat temperature temporarily if opening windows to air the rooms. If you are using an ON/OFF type thermostat, reduce the water tempera ture value in summer (e.g. 60°C in summer and 80°C in winter). When setting an hourly programmable thermostat, consider days when you are absent or on holiday. Electricity production and energy savings reach their optimum level with a programmed and activated timer pro gramme.
Page 26

11 Warranty

26 7679305 - 1 - 14082017
11 Warranty

11.1 General

To make sure your boiler warranty is activated and maintained, it is essen tial that the:
1. Benchmark checklist is completed by your installer
2. Warranty is registered within 30 days
3. Boiler has an annual service
Important Please note that failure to adhere to terms and conditions will in validate your warranty.
11.2

Standard warranty terms and conditions

Warranty registration, service & repair For full terms and conditions, visit www.baxi.co.uk/terms.
Benchmark checklist The Benchmark Checklist will be completed by your installer and records that the boiler has been installed and commissioned correctly. It can be found at the back of the installation and service manual and should be kept in a safe place for the life of the boiler. We will check that the Bench mark Checklist has been completed on an in-warranty visit.
Ways to register your warranty If your boiler is eligible for an extended warranty, your installer may regis ter the product on your behalf and provide you with the relevant documen tation. Please check with your installer.
Should this not be the case, you can register your warranty online at www.baxi.co.uk/registration
Annual service A service must be completed every 12 months from the date of installation to maintain your warranty.
This service must be completed by one of the following:
A Gas Safe registered installer/engineer Baxi Customer Support; call us 0344 871 1545
Please make sure that your engineer has logged the service information at the back of the installation and service manual. You will be asked for your service history on any in-warranty repair visit.
If you experience a problem with your boiler For any in or out of warranty repair, Baxi Customer Support is on hand to help you. Call our award-winning team to arrange for one of our nation wide team of Gas Safe registered engineers to visit.
If your product is in warranty, everything is free of charge, subject to our warranty terms and conditions. If it is out of warranty, we can still help and offer a range of options you can choose from to suit your needs.
Contact Baxi Customer Support 0344 871 1545
Opening hours Monday - Friday, 8.00am - 6.00pm
Weekends and Bank Holidays, 8.30am - 2.00pm
Please note calls may be recorded for training and monitoring purposes.
When contacting Baxi Customer Support, please have the following infor mation to hand:
Boiler serial number.
Page 27
11 Warranty
7679305 - 1 - 14082017 27
Proof of purchase if you do not have the boiler serial number
Please note that for in-warranty repairs, our engineers will ask to see your service history record, completed Benchmark Checklist and details of your installer. These can all be found in the Installation and Service manual.
Page 28
A
A
A
A

12 Appendix

28 7679305 - 1 - 14082017
12 Appendix

12.1 Product fiche - Combination boilers

Tab.11 Product fiche for combination boilers
Baxi Combi 624 630
Space heating - Temperature application Medium Medium
Water heating - Declared load profile XL XL
Seasonal space heating energy efficiency class
Water heating energy efficiency class
Rated heat output
(Prated or Psup)
kW 20 20
Space heating - Annual energy consumption GJ 62 74
Water heating - Annual energy consumption
kWh GJ
(1)
(2)
33 17
33 17
Seasonal space heating energy efficiency % 93 93
Water heating energy efficiency % 86 85
Sound power level LWA indoors dB 51 54
(1) Electricity (2) Fuel
See For specific precautions about assembling, installing and main taining: Safety, page 5
Page 29

12.2 Package fiche - boilers

AD-3000743-01
%
1
‘I’
2
%+
3
%( - ‘I’ ) x 0.1 = ±
4
%(‘III’ x + ‘IV’ x ) x 0.9 x ( /100) x = +
(1)
A* = 0.95, A = 0.91, B = 0.86, C = 0.83, D - G = 0.81
5
%( - ‘I’ ) x ‘II’ = +
6
%0.5 x 0.5 x = -
54
<30%
G F E D C B A A
+
A
++
A
+++
%+ (50 x ‘II’) =
7
7
%
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed in a building, as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the products in relation to building size and characteristics.
Boiler and supplementary heat pump installed with low temperature heat emitters at 35°C ?
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in %)
Supplementary heat pump
Tank rating
Collector effi ciency (in %)
Tank volume (in m³) Collector size (in m²)
Seasonal space heating energy effi ciency (in %)
Supplementary boiler
Class I = 1%, Class II = 2%, Class III = 1.5%, Class IV = 2%, Class V = 3%, Class VI = 4%, Class VII = 3.5%, Class VIII = 5%
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A, use 0.95
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
7679305 - 1 - 14082017 29
Fig.15 Package fiche for boilers indicating the space heating energy efficiency of the package
12 Appendix
I The value of the seasonal space heating energy efficiency of the
preferential space heater, expressed in %.
Page 30
12 Appendix
30 7679305 - 1 - 14082017
II The factor for weighting the heat output of preferential and supple
mentary heaters of a package as set out in the following table.
III The value of the mathematical expression: 294/(11 · Prated),
whereby ‘Prated’ is related to the preferential space heater.
IV The value of the mathematical expression 115/(11 · Prated),
whereby ‘Prated’ is related to the preferential space heater.
Tab.12 Weighting of boilers
Psup / (Prated + Psup)
(1)(2)
II, package without hot water storage tank II, package with hot water storage tank
0 0 0
0.1 0.3 0.37
0.2 0.55 0.70
0.3 0.75 0.85
0.4 0.85 0.94
0.5 0.95 0.98
0.6 0.98 1.00
≥ 0.7 1.00 1.00
(1) The intermediate values are calculated by linear interpolation between the two adjacent values. (2) Prated is related to the preferential space heater or combination heater.
Tab.13 Package efficiency
Baxi Combi 624 630
Temperature control X %
Temperature control Y %
Page 31
AD-3000747-01
%
1
‘I’
2
%(1.1 x ‘I’ - 10%) x ‘II’ - - ‘I’ = +
‘III’
<28%
XXL
XL
L
M
G F E D C B A A
+
A
++
A
+++
3
%
%+ 0.4 x =
23
%- 0.2 x =
23
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed in a building, as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the products in relation to building size and characteristics.
Water heating energy effi ciency class of package under average climate
Water heating energy effi ciency of package under average climate
Auxiliary electricity
Solar contribution
Water heating energy effi ciency of combination heater
from fi che of solar device
Colder:
Warmer:
Water heating energy effi ciency under colder and warmer climate conditions
Declared load profi le:
12 Appendix
7679305 - 1 - 14082017 31

12.3 Package fiche - Combination heaters (boilers or heat pumps

Fig.16 Package fiche for combination heaters (boilers or heat pumps) indicating the water heating energy efficiency of the
package
I The value of the water heating energy efficiency of the combination
heater, expressed in %.
II The value of the mathematical expression (220 · Q
where Q 15 and Q
is taken from Regulation EU 811/2013, Annex VII Table
ref
from the product fiche of the solar device for the de
nonsol
)/Q
ref
clared load profile M, L, XL or XXL of the combination heater.
III The value of the mathematical expression (Q
expressed in %, where Q solar device and Q
ref
is taken from the product fiche of the
aux
from Regulation EU 811/2013, Annex VII Ta
· 2,5)/(220 · Q
aux
ble 15 for the declared load profile M, L, XL or XXL.
nonsol
,
),
ref
Page 32
12 Appendix
32 7679305 - 1 - 14082017
Page 33
12 Appendix
7679305 - 1 - 14082017 33
Page 34
12 Appendix
34 7679305 - 1 - 14082017
Page 35
© Copyright
All technical and technological information contained in these technical instructions, as well as any drawings and technical de scriptions supplied, remain our property and shall not be multiplied without our prior consent in writing. Subject to alterations.
Page 36
Baxi Customer Support
0344 871 1545
Opening hours
Monday - Friday, 8.00am-6.00pm
Weekends and Bank Holidays, 8.30am-2.00pm
Please note calls may be recorded for training and monitoring purposes
baxi.co.uk
Register now to activate your warranty:
www.baxi.co.uk/registration
For the warranty to be maintained, please make sure...
Benchmark checklist is completed Warranty is registered within 30 days The boiler has an annual service
1
2
3
For full terms and conditions, visit www.baxi.co.uk/terms. Failure to adhere to terms and conditions will void your manufacturer’s warranty.
Baxi Brooks House, Coventry Road, Warwick, CV34 4LL
Please ensure the boiler is installed in accordance with these installation instructions and that you adhere to the Building Regulations.
e&oe All descriptions and illustrations provided in this document have been carefully prepared but we reserve the right to make changes and improvements in our products which may affect the accuracy of the information contained in this leaflet. All goods are sold subject to our standard Conditions of Sale which are available on request.
7679305 - 1 - 14082017
Loading...