If you move house please hand them over to the next occupier.
United Kingdom
en
User Guide
High Efficiency Wall Hung Condensing Gas Boiler
Baxi Combi
624 — 630
Page 2
Dear Customer,
Thank you very much for buying this appliance.
Please read through the manual carefully before using the product, and keep it in a safe place for later reference. In order to
ensure continued safe and efficient operation we recommend that the product is serviced regularly. Our service and customer
service organisation can assist with this.
We hope you enjoy years of problem-free operation with the product.
Danger
This boiler can be used by children aged 8 years and above and
by persons with reduced physical, sensory or mental capabilities
or lack of experience and knowledge when they have been given
supervision or instruction concerning the safe use of the device
and understand the resulting risks. Children must not be allowed
to play with the appliance. Cleaning and user maintenance must
not be carried out by children without supervision.
Danger
If you smell gas:
1. Turn off the gas supply at the meter.
2. Open windows and doors in the hazardous area.
3. Do not operate light switches.
4. Do not operate any electrical equipment.
5. Do not use a telephone in the hazardous area.
6. Extinguish any naked flame and do not smoke.
7. Warn any other occupants and vacate the premises.
8. Telephone the National Gas Emergency Service on:- 0800
111 999.
Fig.1Taps ON and OFF
Note
If a water or gas leak occurs or is suspected, the boiler can be iso
1
lated at the inlet valves by turning their taps through 90° (
/4 turn)
downwards.
AON
BOFF
For advice please contact your Installer, Annual Service Provider
or Baxi Customer Support - The Service Division of Baxi. You can
contact Baxi Customer Support on telephone number 0344 871
1545.
When contacting Baxi Customer Support it will be useful to have
the "Benchmark Checklist " at the back of the Installation & Serv
ice Manual to hand as it includes details relevant to the boiler and
installation.
Warning
Do not touch flue/chimney pipes. Depending on the settings of the
appliance, the temperature of flue/chimney pipes may exceed
60 °C.
Do not touch radiators for long periods. Depending on the settings
of the appliance, the temperature of radiators may reach 85 °C.
Take precautions with domestic hot water. Depending on the set
tings of the appliance, domestic hot water temperature may reach
65 °C.
Caution
Do not neglect to service the appliance. Contact a qualified pro
fessional or take out a maintenance contract for the annual servic
ing of the appliance.
Page 6
1 Safety
67679305 - 1 - 14082017
1.2 Recommendations
Caution
Only qualified professionals are authorised to work on the boiler
and the installation.
The appliance has an integral frost protection mode as long as
there is power to the boiler.
Important
Regularly check the water pressure in the system (recommen
ded pressure is 1.5 bar).
Keep the appliance accessible at all times.
Do not remove or cover the user information and serial number
labels affixed to the boiler control flap. They must remain legible
throughout the lifetime of the boiler.
1.2.1
Baxi Heating UK Ltd is a licensed member of the Benchmark Scheme
which aims to improve the standards of installation and commissioning of
domestic heating and hot water systems in the UK and to encourage regu
lar servicing to optimise safety, efficiency and performance.
Benchmark is managed and promoted by Heating and Hotwater Industry
Council. For more information visit www.centralheating.co.uk
1.2.2
Please ensure that the installer has fully completed the Benchmark Check
list on the inside back pages of the installation instructions supplied with
the product and that you have signed it to say that you have received a full
and clear explanation of its operation. The installer is legally required to
complete a commissioning checklist as a means of complying with the ap
propriate Building Regulations (England and Wales).
All installations must be notified, by the installer, to Local Area Building
Control either directly or through a Competent Persons Scheme. A Build
ing Regulations Compliance Certificate will then be issued to the customer
who should, on receipt, write the Notification Number on the Benchmark
Checklist.
This product should be serviced annually to optimise its safety, efficiency
and performance. The service engineer should complete the relevant sec
tion of the Benchmark Service Record in the Installation & Service manual
after each service.
The completed Benchmark Checklist & proof of annual servicing (where
applicable) will be required in the event of any warranty work.
The Benchmark Scheme
Benchmark Commissioning Checklist
1.3
Liabilities
1.3.1 User's liability
To guarantee optimum operation of the system, you must abide by the fol
lowing instructions:
Read and follow the instructions given in the manuals provided with the
appliance.
Call on a qualified professional to carry out installation and initial com
missioning.
Get your installer to explain your installation to you.
Have the required inspections and maintenance carried out by a quali
fied installer.
Keep the instruction manuals in good condition close to the appliance.
Page 7
1 Safety
7679305 - 1 - 140820177
1.3.2 Installer's liability
The installer is responsible for the installation and initial commissioning of
the appliance. The installer must observe the following instructions:
Read and follow the instructions given in the manuals provided with the
appliance.
Install the appliance in compliance with prevailing legislation and stand
ards.
Carry out initial commissioning and any checks necessary.
Explain the installation to the user.
If maintenance is necessary, warn the user of the obligation to check the
appliance and keep it in good working order.
Give all the instruction manuals to the user.
1.3.3 Manufacturer's liability
Our products are manufactured in compliance with the requirements of the
various Directives applicable. They are therefore delivered with the
marking and any documents necessary. In the interests of the quality of
our products, we strive constantly to improve them. We therefore reserve
the right to modify the specifications given in this document.
Our liability as manufacturer may not be invoked in the following cases:
Failure to abide by the instructions on installing the appliance.
Failure to abide by the instructions on using the appliance.
Faulty or insufficient maintenance of the appliance.
Page 8
2 About this manual
87679305 - 1 - 14082017
2 About this manual
2.1 General
Warning
Installation, repair and maintenance must only be carried out only
by a competent person.
All Gas Safe registered engineers carry an ID card with their licence num
ber and a photograph. You can check your engineer is registered by tele
phoning 0800 408 5500 or online at www.gassaferegister.co.uk
This manual is intended for the user of the Baxi Combi boiler. If the appli
ance is sold or transferred, or if the owner moves leaving the appliance
behind you should ensure that the manual is kept with the appliance for
consultation by the new owner and their installer.
The appliance is designed as a boiler for use in residential domestic envi
ronments on a governed meter supply only. The selection of this boiler is
entirely at the owner’s risk. If the appliance is used for purposes other than
or in excess of these specifications, the manufacturer will not accept any
liability for resulting loss, damage or injury.
The manufacturer will not accept any liability whatsoever for loss, damage
or injury arising as a result of failure to observe the instructions for use,
maintenance and installation of the appliance.
2.2 Additional documentation
2.3 Symbols used
Various timers, external controls, etc. are available as optional extras. Full
details are contained in the relevant sales literature.
2.3.1 Symbols used in the manual
This manual uses various danger levels to draw attention to special in
structions. We do this to improve user safety, to prevent problems and to
guarantee correct operation of the appliance.
Danger
Risk of dangerous situations that may result in serious personal
injury.
Danger of electric shock
Risk of electric shock.
Warning
Risk of dangerous situations that may result in minor personal in
jury.
Caution
Risk of material damage.
Important
Please note: important information.
See
Reference to other manuals or pages in this manual.
2.4
Abbreviations/glossary
CHCentral heating
Page 9
DHWDomestic hot water
7679305 - 1 - 140820179
PCUPCB for managing burner operation
PncCondensing output
SUSafety PCB
2 About this manual
Page 10
3 Technical specifications
107679305 - 1 - 14082017
3 Technical specifications
3.1 Homologations
3.1.1 Certifications
Tab.1Certifications
CE certificate number
NOx class5
Boiler typeC13, C
3.2
Technical data
33
3.2.1 Technical information
Tab.2General
Baxi Combi624630
Gas council numbers47 077 2847 077 29
Tab.3Central heating circuit specifications
Baxi Combi624630
Maximum pressurebar33
Minimum pressurebar0.50.5
Central heating temperature adjustment°C25/80 ± 5°25/80 ± 5°
Tab.4Domestic hot water circuit specifications
Baxi Combi624630
Maximum pressurebar88
Dynamic minimum pressurebar0.50.5
Minimum working water flow ratel/min2.02.0
Domestic hot water temperature range adjust
ment
Specific flow rate (D)l/min1012.5
Important
Where low flow taps or fittings are intended to be used in the DHW system connected, it is strongly
recommended that the DHW flow rate DOES NOT fall below 2.5 l/min. This will ensure reliable op
eration of the DHW function.
Clearances (above/below casing)
front (for servicing)/(in operation)
side (left hand/right hand)
mm
mm
mm
178 / 200
450 / 5
5 / 5
178 / 200
450 / 5
5 / 5
These are MINIMUM recommended dimensions. Greater clearance will aid installation and maintenance.
Important
All data in this section are nominal values and subject to normal
production tolerances.
3.2.2 Dimensions and connections/clearances
Fig.2
Dimensions and connections / clearances
1
Condensate trap sump
2
Condensate drain
3
Heating circuit water flow
4
Hot water outlet
5
Gas inlet
6
Pressure relief pipe
7
Cold water inlet
8
Heating circuit water return
9
Pump drain point
10
Boiler drain point on flow isolation tap
11
Cable entry points
The clearances shown in the diagram are minimum requirements to allow
for case removal, spanner access and air movement. These should be ob
served at all times and kept clear of obstructions.
Page 12
PN-0000606
A
R
Reset
bar
0
1
2
3
4
1
2
3
4
56
PN-0000607
M
i
n
M
a
x
M
a
x
M
i
n
4 Description of the product
127679305 - 1 - 14082017
4 Description of the product
4.1 General description
Fig.3
Information label
4.2 Operating principle
The Baxi Combi range of fully automatic gas fired wall hung condensing
combination boilers are room sealed and fan assisted, and will serve cen
tral heating and mains fed domestic hot water.
AInformation label
Tab.7The boiler is set to give a maximum output of :-
624 model25 kW DHW
21.16 kW CH Pnc (Condensing)
630 model30 kW DHW
21.16 kW CH Pnc (Condensing)
The boiler is factory set for use only on Natural Gas (G20).
Priority is given to domestic hot water.
The boiler model, serial number and Gas Council number are also shown
on the information label. This is for user reference.
4.2.1 In operation
Whilst the boiler is in operation cooled flue gases are discharged through
the flue gas discharge pipe. This may appear as a cloud of steam which is
normal.
Condensed water is discharged from the boiler heat exchanger into a pipe
(the condensate drain). This pipe must never be altered or re-routed ex
cept by a qualified professional.
4.3 Control panel description
Fig.4Control panel
4.3.1 Description of the control panel
1Display
2Reset button
3Central heating temperature control
4Service diagnostic port
5DHW temperature control
6System water pressure gauge
Page 13
R
R
PN-0000336
4 Description of the product
7679305 - 1 - 1408201713
Fig.5
4.4
Display screen
Accessories and options
Display description
The following symbols may be seen on the display
OFF (frost protection still enabled)
Indicates errors that prevent the burner from starting
Error — not resettable by user
Water pressure too low
Indicates a resettable error
Not applicable
Not applicable
Generic error
Burner lit
DHW request
Heating mode
Units for temperature
Units for pressure
4.4.1 Optional accessories
The table shows the accessories available for this boiler range.
Tab.8Optional accessories
Part numberAccessory
7212438Baxi single channel wired programmable room thermostat
720971601Baxi room thermostat
720330001Baxi wired weather sensor
720648301Multifit condensate & PRV combined pump
720644401Multifit 1m condensate drain pipe 'trace heating' element
720664101Multifit 2m Condensate drain pipe 'trace heating' element
720664201Multifit 3m condensate drain pipe 'trace Heating' element
720664401Multifit 5m condensate drain pipe 'trace heating' element
5121379Multifit remote secondary PRV kit
248221Multifit filling loop
7682790Multifit rear pipework kit
7682545Multifit pre-plumbing jig
7209714Multifit wall mounted 24 hour timeclock
720030501RF Single Channel Room Thermostat
7212444Single channel wired timer
For flue accessories (elbows, extensions, clamps etc.) refer to the Flue Ac
cessories Fitting Guide supplied in the literature pack.
Any of the above MUST be fitted ONLY by a qualified competent person.
Further details can be found in the relevant sales literature and at
www.baxi.co.uk
Page 14
START
Make sure the gas
supply is turned ON
and check if other
gas appliances are
operating (e.g. fire,
cooker). If the
property has a
prepayment meter
ensure it has
sufficient credit.
NO
If no gas, consult
your supplier.
Is there electricity to the
boiler ? Is the display lit ?
T: Where Low Flow Taps or Fittings
are intended to be used in the DHW system
connected it is strongly recommended that the
DHW flow rate DOES NOT fall below 2.5 l/min.
This will ensure reliable operation of the DHW
function.
Is the Timer ON and
calling for heat ?
Is the Room Thermostat
(if fitted) set high enough ?
12
1
2
3
4
5
6
7
8
9
10
11
Typical
examples of
external timer
Ensure timer is set for
Central Heating ON (see
any instructions supplied
with timer)
NO
YES
YES
NO
15
10
5
20
25
15
10
5
20
25
Turn Room Thermostat
to maximum setting
(typical example shown)
CH ON
CH OFF
bar
0
1
2
3
4
Is the Central Heating
System Pressure
between 1.0 and 2.5 bar ?
If the reading falls below 1.0 bar
repressurise the system as described
in Maintenance
NO
Error Code 118 showing
low pressure.
YES
If you don’t know what you need to do
to get the boiler to light, or need help with
the system and controls, contact your
installer as soon as possible
PN-0000634
R
R
7679305 - 1 - 1408201715
5 Operation
Page 16
Reset
PN-0000636
R
R
R
Reset
bar
0
1
2
3
4
M
i
n
M
a
x
M
a
x
M
i
n
5 Operation
167679305 - 1 - 14082017
5.2 Use of the control panel
5.2.1 Using the control panel
Fig.8Using the control panel
Important
OpenTherm controller.Your installer will advise you when this type
of control is connected to the boiler. If so, any change to the boiler
settings (e.g. heating temperature) must be made using the Open
Therm controller not the boiler control panel. Please consult the
user manual for the OpenTherm controller.
To increase or decrease boiler temperature and/or the domestic hot water
(DHW) temperature:
1. Turn the control knob with the symbol over it clockwise to in
crease the boiler set temperature. The set temperature will be
shown on the display screen.
2. Turn the control knob with the symbol over it anticlockwise to de
crease the boiler temperature. The temperature will be shown on the
display screen.
3. Turn the control knob with the symbol over it clockwise to in
crease the DHW temperature. The temperature will be shown on the
display screen.
4. Turn the control knob with the symbol over it anticlockwise to de
crease the DHW temperature. The temperature will be shown on the
display screen.
To reset the boiler:
1. Press the
button for approximately 1 second, holding the button
for more than 2 seconds the boiler will not reset. (see List of error co
des, page 21.)
5.3 Shutdown
5.4
Frost protection
Isolate the mains power supply at the fused spur unit.
Isolate the gas supply at the boiler valve.
Protect the boiler from frost.
Important
The boiler is not protected against frost once it has been shut
down.
Important
If it is anticipated that the boiler will not be used for a long period
or the property is to be unoccupied it is recommended that the
system be drained if the electricity and gas supplies are to be
turned off. Your installer will be able to offer advice.
Where possible, draining the system should be avoided. If the system is to
be unused during winter months several precautions must be taken:
Any parts of the system that are in unheated areas of the dwelling
should be fitted with a device such as a pipe thermostat or frost thermo
stat.
Power must remain supplied to the boiler and controls.
Gas must remain supplied to the boiler.
The boiler pump will operate if the system temperature drops below 7°C. If
the temperature falls to 4°C the burner will ignite and remain lit until the
temperature reaches 10°C. At this temperature the burner will extinguish
but the pump will continue to operate for 15 minutes. This feature will pro
tect the boiler and to some extent adjacent parts of the system but addi
tional devices must be incorporated to guarantee frost protection.
Page 17
6 Maintenance
7679305 - 1 - 1408201717
6.1 General
6 Maintenance
The boiler does not require any special maintenance. However, the boiler
must be serviced annually in accordance with the Installation and Service
Manual and the relevant section of the Benchmark Service Record com
pleted in order to maintain the warranty.
Important
Taking out a maintenance contract is recommended.
Caution
Maintenance operations must be performed by a qualified compe
tent person.
Use only Baxi genuine spare parts.
The painted panels should be wiped with a damp cloth and then dried
completely. DO NOT USE ABRASIVE CLEANING AGENTS.
6.2
Maintenance instructions
The central heating system should be checked regularly. Proceed as fol
lows:
1. Check the water pressure in the central heating system.
Important
If the water pressure is lower than 0.7 bar, the system must be
topped up.
See
Re-pressurising the system.
Important
If the water pressure drops below 0.5 bar the boiler will not work.
2. Check radiators for leaks and (especially in damp areas) for rust.
3. Open and close the radiator valves several times a year to ensure
they can still be rotated.
Caution
Only a qualified installer may clean the inside of the boiler.
6.2.1 Re-pressurising the system
If the water pressure is too low, the system must be re-pressurised.
The normal operating water pressure is between 1 and 2 bar. If the pres
sure exceeds 3 bar the safety pressure valve will operate and a fault is in
dicated. Ensure that the filling loop is disconnected if it is of a temporary
type. Contact your installer.
Page 18
PN-0000373
PN-0000635
6 Maintenance
187679305 - 1 - 14082017
Fig.9Water pressure
Fig.10"Easy-Fill" - operate green lever as
shown to add water
It may be necessary to repressurise the system occasionally (when the
water pressure falls below 0.7). A filling device (the filling loop) will be fitted
on the system. This may be on the boiler itself, or on pipework near to the
boiler.
Important
If the water pressure requires regular re-pressurising a fault or
leak is indicated. Seek advice from your installer.
The Baxi 600 Combi is supplied with a special device, the "Easy-Fill" per
manent filling link.
1. Operate the spring loaded green lever to add water to the system.
Important
The system pressure is shown at all times on the pressure gauge
and can be viewed on the display when there is power to the boil
er.
2. When the figures on the display or needle on the pressure gauge in
dicate between 1 and 1.5 bar release the lever.
3. It is not necessary to remove any part of the permanent link.
4. When the correct pressure is restored the boiler will reset automati
cally.
See
Go to the "How to videos" section of the "Information & advice"
page at www.baxi.co.uk for further details.
Page 19
6.3 Venting the installation
76
A
C
B
5
4
3
2
1
2
3
4
1
10
PN-0000468
M
a
x
M
i
n
R
M
a
x
M
i
n
R
x 2
PN-0000608
R
Reset
bar
0
1
2
3
4
M
i
n
M
a
x
M
a
x
M
i
n
7679305 - 1 - 1408201719
6 Maintenance
Fig.11Venting the radiators
If any air is present in the appliance or system it must be removed in order
to prevent nuisance noises that may occur during heating or when drawing
off hot water. Proceed as follows:
1. Open the valves of all the radiators connected to the system.
2. Set the room thermostat to the highest possible temperature and
any timers to ‘ON’.
3. Wait until the radiators are warm.
4. Switch off the boiler.
5. Vent the radiators. Work from the lowest radiator in the property.
6. Open the bleed vent with the key, keeping a cloth pressed against
the vent.
7. Wait until water comes out of the bleed vent and then close.
Warning
The CH water in the radiators will still be hot.
8. Switch the boiler on.
9. After venting, check that the water pressure in the system is still ad
equate.
Important
If the water pressure is lower than 0.7 bar, the water must be top
ped up. If necessary repressurise the system (recommended
pressure between 1 and 1.5 bar when cold).
10. Reset the room thermostat to the desired temperature.
Fig.12Enabling de-aeration function
The purpose of the function is to remove as much air as possible from the
heating system.
1. Turn off the power to the boiler and rotate the CH control knob fully
anticlockwise.
2. Turn on the power to the boiler. The display shows "000" .
3. Turn the CH control knob ( ) 1/4 turn clockwise twice in quick suc
cession (within 2 seconds).
4. Display shows "312" while de-aeration is taking place (approximately
7 minutes).
5. When de-aeration has completed, the display will show the primary
flow temperature and both the CH ( ) and DHW ( ) symbols.
Page 20
AD-3000730-01
5
3
2
1
2
3
4
1
4
6 Maintenance
207679305 - 1 - 14082017
Caution
If the system is drained (even partly, when replacing a radiator for
example) the de-aeration function must be repeated. Also the in
hibitor concentration must be checked and replenished if necessa
ry.
6.4
Draining the installation
Fig.13Draining the installation
It may be necessary to drain the central heating system if radiators need
to be replaced, if there is a major water leak or if there is a risk of freezing.
Proceed as follows:
1. Open the valves of all the radiators connected to the system.
2. Switch off the boiler's electrical connection.
3. Wait approximately ten minutes, until the radiators feel cold.
4. Connect a drain hose to the lowest draining point. Place the end of
the hose in a drain or at a place where drained pipe water will not
cause any damage.
5. Open the central heating system fill/drain valve. Drain the installa
tion.
Warning
The water may still be hot.
6. Close the drain valve when no more water comes from the draining
point.
Important
After draining the system, the concentration of corrosion inhibitor
and antifreeze agent may be extremely diluted - check with your
installer.
Page 21
7 Troubleshooting
R
Reset
PN-0000637
R
R
Reset
bar
0
1
2
3
4
M
i
n
M
a
x
M
a
x
M
i
n
7679305 - 1 - 1408201721
7.1 Error codes
7 Troubleshooting
7.1.1 List of error codes
Fig.14Control panel error display
Tab.9Table of error codes
Error codeDescription of fault
09
15
20
28
40
83
109
110
118
125
128
130
133
135
Gas valve connection cable
Gas valve fault
Central heating NTC fault
Flue NTC fault
Central heating return NTC fault
Communication error
Pre-circulation fault
Safety thermostat operated
Primary system water pressure too low
Circulation fault (primary)
Flame failure
Flue NTC operated
Interruption of gas supply or flame failure
Interruption of gas supply (internal error)
154
160
270
321
384
Flow / return sensor temperature test
Fan or fan wiring fault
Circulation fault (Dry fire)
Hot water NTC fault
False flame
The display shows two types of signals: and R. In both cases the
display shows symbol and the numeric value of the error (see the table
of error codes above).
The spanner symbol appears it cannot be reset by the user. Please
contact your Installer, Annual Service Provider or Baxi Customer Support.
You can contact Baxi Customer Support on 0344 871 1545.
fault errors can be reset by pressing the
button.
For 103, 104, 107 & "Bat" please contact your installer, annual service
provider or Baxi Customer Support
Important
If a different error code from those described in the "Table of error
codes" appears on the display contact Baxi Customer Support.
Page 22
7 Troubleshooting
227679305 - 1 - 14082017
7.2 Fault finding
Tab.10Problems and solutions
ProblemPossible causesSolution
Check that the boiler is being supplied with power.
Check fuses and the switches.
The boiler is not working.
There is no domestic hot wa
ter.
The DHW function is switched off.Activate the DHW mode.
The water pressure is too low (< 0.5 bar). Re-pressurise the system.
Insufficient flow.Flow must be at least 2.5 litres per minute.
Check whether the gas isolation cock is properly
open.
If the property has a prepayment meter ensure it
has sufficient credit.
The radiators are cold.
The boiler is not working.
The temperature set point for the heating
is too low.
The heating mode is deactivated.Activate the heating mode.
The radiator valves are not open.Open the valves of all radiators connected to the
The boiler is not working.Check that the boiler is being supplied with power.
The water pressure is too low (< 0.5 bar). Re-pressurise the system.
The temperature set point for the heating
is too low.
No demand for heating.Ensure that timers & thermostats are calling for
No power supply.Check that the boiler is being supplied with power.
The water pressure is too low (< 0.5 bar). Re-pressurise the system.
The boiler is indicating an error.Press the Reset button.
Increase the value with the CH temperature knob
or if a room thermostat is connected, increase the
temperature on the room thermostat.
system.
Check fuses and switches.
Check whether the gas isolation cock is properly
open.
If the property has a prepayment meter ensure it
has sufficient credit.
Increase the value with the CH temperature knob
or if a room thermostat is connected, increase the
temperature on the room thermostat.
heat.
Check the fuses and switches.
Correct the error, if possible.
The gas pressure is too low.Check whether the gas isolation cock is fully open.
Open the gas isolation cock.
Condensate drain blocked.Check drain, especially any external runs in freez
ing temperatures.
If the boiler is not working also check section "Operation checking proce
dure and basic fault identification" or contact your Installer.
Page 23
8 Decommissioning
7679305 - 1 - 1408201723
8.1 Decommissioning procedure
8 Decommissioning
Caution
Only qualified persons are authorised to work on the appliance
and system to decommission.
If your boiler needs to be decommissioned either temporarily or perma
nently the following should be performed:
1. Switch off the boiler’s electrical connection.
2. Close the gas isolation tap.
3. Drain the central heating system.
Seek the advice of your installer.
Page 24
9 Disposal
247679305 - 1 - 14082017
9 Disposal
9.1 Disposal and recycling
Caution
Removal and disposal of the boiler must be carried out by a quali
fied person in accordance with local and national regulations.
Page 25
10 Environmental
7679305 - 1 - 1408201725
10.1 Energy saving
10 Environmental
Tips on saving energy:
Do not cover radiators. Do not hang curtains in front of radiators.
Install reflective panels behind the radiators to prevent heat loss.
Insulate the pipes in rooms that are not heated (cellars and lofts).
Install loft insulation & double glazing.
Use draught excluders where necessary.
Upgrade any older boiler external controls.
Turn down room thermostats by 1°.
Turn off radiators in rooms not in use.
Do not run hot (or cold) water pointlessly.
Fit a water-saving shower head to save up to 40 % energy.
Take showers rather than baths. A bath consumes twice as much water
and energy.
10.2
Room thermostats and settings
Various models of room thermostat are available. The thermostat type and
setting affect the total energy consumption.
A few tips:
A modulating thermostat in combination with thermostatic radiator valves
saves energy and offers considerable comfort. This combination gives
you flexibility with the temperatures. Do not fit thermostatic radiator
valves in the room in which the room thermostat is installed.
Completely closing and opening thermostatic valve radiators causes un
desirable temperature fluctuations. Open and close thermostatic valves
in small steps.
Lower the thermostat to around 20°C. This reduces heating costs and
energy consumption.
Lower the room thermostat temperature temporarily if opening windows
to air the rooms.
If you are using an ON/OFF type thermostat, reduce the water tempera
ture value in summer (e.g. 60°C in summer and 80°C in winter).
When setting an hourly programmable thermostat, consider days when
you are absent or on holiday. Electricity production and energy savings
reach their optimum level with a programmed and activated timer pro
gramme.
Page 26
11 Warranty
267679305 - 1 - 14082017
11 Warranty
11.1 General
To make sure your boiler warranty is activated and maintained, it is essen
tial that the:
1. Benchmark checklist is completed by your installer
2. Warranty is registered within 30 days
3. Boiler has an annual service
Important
Please note that failure to adhere to terms and conditions will in
validate your warranty.
11.2
Standard warranty terms and conditions
Warranty registration, service & repair
For full terms and conditions, visit www.baxi.co.uk/terms.
Benchmark checklist
The Benchmark Checklist will be completed by your installer and records
that the boiler has been installed and commissioned correctly. It can be
found at the back of the installation and service manual and should be
kept in a safe place for the life of the boiler. We will check that the Bench
mark Checklist has been completed on an in-warranty visit.
Ways to register your warranty
If your boiler is eligible for an extended warranty, your installer may regis
ter the product on your behalf and provide you with the relevant documen
tation. Please check with your installer.
Should this not be the case, you can register your warranty online at
www.baxi.co.uk/registration
Annual service
A service must be completed every 12 months from the date of installation
to maintain your warranty.
This service must be completed by one of the following:
A Gas Safe registered installer/engineer
Baxi Customer Support; call us 0344 871 1545
Please make sure that your engineer has logged the service information at
the back of the installation and service manual. You will be asked for your
service history on any in-warranty repair visit.
If you experience a problem with your boiler
For any in or out of warranty repair, Baxi Customer Support is on hand to
help you. Call our award-winning team to arrange for one of our nation
wide team of Gas Safe registered engineers to visit.
If your product is in warranty, everything is free of charge, subject to our
warranty terms and conditions. If it is out of warranty, we can still help and
offer a range of options you can choose from to suit your needs.
Contact Baxi Customer Support 0344 871 1545
Opening hours
Monday - Friday, 8.00am - 6.00pm
Weekends and Bank Holidays, 8.30am - 2.00pm
Please note calls may be recorded for training and monitoring purposes.
When contacting Baxi Customer Support, please have the following infor
mation to hand:
Boiler serial number.
Page 27
11 Warranty
7679305 - 1 - 1408201727
Proof of purchase if you do not have the boiler serial number
Please note that for in-warranty repairs, our engineers will ask to see your
service history record, completed Benchmark Checklist and details of your
installer. These can all be found in the Installation and Service manual.
Page 28
A
A
A
A
12 Appendix
287679305 - 1 - 14082017
12 Appendix
12.1 Product fiche - Combination boilers
Tab.11Product fiche for combination boilers
Baxi Combi624630
Space heating - Temperature applicationMediumMedium
Water heating - Declared load profileXLXL
Seasonal space heating energy efficiency class
Water heating energy efficiency class
Rated heat output
(Prated or Psup)
kW2020
Space heating - Annual energy consumptionGJ6274
Water heating - Annual energy consumption
kWh
GJ
(1)
(2)
33
17
33
17
Seasonal space heating energy efficiency%9393
Water heating energy efficiency%8685
Sound power level LWA indoorsdB5154
(1) Electricity
(2) Fuel
See
For specific precautions about assembling, installing and main
taining: Safety, page 5
Page 29
12.2 Package fiche - boilers
AD-3000743-01
%
1
‘I’
2
%+
3
%( - ‘I’ ) x 0.1 = ±
4
%(‘III’ x + ‘IV’ x ) x 0.9 x ( /100) x = +
(1)
A* = 0.95, A = 0.91,
B = 0.86, C = 0.83,
D - G = 0.81
5
%( - ‘I’ ) x ‘II’ = +
6
%0.5 x 0.5 x = -
54
<30%
GFEDCBAA
+
A
++
A
+++
%+ (50 x ‘II’) =
7
7
%
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building, as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics.
Boiler and supplementary heat pump installed with low temperature heat emitters at 35°C ?
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in %)
Supplementary heat pump
Tank rating
Collector effi ciency (in
%)
Tank volume (in m³) Collector size (in m²)
Seasonal space heating energy effi ciency (in %)
Supplementary boiler
Class I = 1%, Class II = 2%, Class III = 1.5%,
Class IV = 2%, Class V = 3%, Class VI = 4%,
Class VII = 3.5%, Class VIII = 5%
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A, use 0.95
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
7679305 - 1 - 1408201729
Fig.15Package fiche for boilers indicating the space heating energy efficiency of the package
12 Appendix
IThe value of the seasonal space heating energy efficiency of the
preferential space heater, expressed in %.
Page 30
12 Appendix
307679305 - 1 - 14082017
IIThe factor for weighting the heat output of preferential and supple
mentary heaters of a package as set out in the following table.
IIIThe value of the mathematical expression: 294/(11 · Prated),
whereby ‘Prated’ is related to the preferential space heater.
IVThe value of the mathematical expression 115/(11 · Prated),
whereby ‘Prated’ is related to the preferential space heater.
Tab.12Weighting of boilers
Psup / (Prated + Psup)
(1)(2)
II, package without hot water storage tankII, package with hot water storage tank
000
0.10.30.37
0.20.550.70
0.30.750.85
0.40.850.94
0.50.950.98
0.60.981.00
≥ 0.71.001.00
(1) The intermediate values are calculated by linear interpolation between the two adjacent values.
(2) Prated is related to the preferential space heater or combination heater.
Tab.13Package efficiency
Baxi Combi624630
Temperature control X%
Temperature control Y%
Page 31
AD-3000747-01
%
1
‘I’
2
%(1.1 x ‘I’ - 10%) x ‘II’ - - ‘I’ = +
‘III’
<28%
XXL
XL
L
M
GFEDCBAA
+
A
++
A
+++
3
%
%+ 0.4 x =
23
%- 0.2 x =
23
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building, as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics.
Water heating energy effi ciency class of package under average climate
Water heating energy effi ciency of package under average climate
Auxiliary electricity
Solar contribution
Water heating energy effi ciency of combination heater
from fi che of solar device
Colder:
Warmer:
Water heating energy effi ciency under colder and warmer climate conditions
Declared load profi le:
12 Appendix
7679305 - 1 - 1408201731
12.3 Package fiche - Combination heaters (boilers or heat pumps
Fig.16Package fiche for combination heaters (boilers or heat pumps) indicating the water heating energy efficiency of the
package
IThe value of the water heating energy efficiency of the combination
heater, expressed in %.
IIThe value of the mathematical expression (220 · Q
where Q
15 and Q
is taken from Regulation EU 811/2013, Annex VII Table
ref
from the product fiche of the solar device for the de
nonsol
)/Q
ref
clared load profile M, L, XL or XXL of the combination heater.
IIIThe value of the mathematical expression (Q
expressed in %, where Q
solar device and Q
ref
is taken from the product fiche of the
aux
from Regulation EU 811/2013, Annex VII Ta
· 2,5)/(220 · Q
aux
ble 15 for the declared load profile M, L, XL or XXL.
All technical and technological information contained in these technical instructions, as well as any drawings and technical de
scriptions supplied, remain our property and shall not be multiplied without our prior consent in writing. Subject to alterations.
Page 36
Baxi Customer Support
0344 871 1545
Opening hours
Monday - Friday, 8.00am-6.00pm
Weekends and Bank Holidays, 8.30am-2.00pm
Please note calls may be recorded for training and monitoring purposes
baxi.co.uk
Register now to activate your warranty:
www.baxi.co.uk/registration
For the warranty to be maintained, please make sure...
Benchmark checklist is completed
Warranty is registered within 30 days
The boiler has an annual service
1
2
3
For full terms and conditions, visit www.baxi.co.uk/terms. Failure to adhere to
terms and conditions will void your manufacturer’s warranty.
Please ensure the boiler is installed in accordance with these installation
instructions and that you adhere to the Building Regulations.
e&oe
All descriptions and illustrations provided in this document have been
carefully prepared but we reserve the right to make changes and
improvements in our products which may affect the accuracy of the
information contained in this leaflet. All goods are sold subject to our
standard Conditions of Sale which are available on request.
7679305 - 1 - 14082017
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.