38
© Baxi Heating UK 2012
Commissioning record
The following chart should be completed during Commissioning of the system.
Installer: _______________________________
Contact details: _______________________________
Original commissioning date: _______________________________
General Commissioning
All pipework correctly installed, identified and ❑
earth bonded
Solar expansion vessel charge pressure checked ❑
and set before filling the system bar
Solar primary system filled with heat transfer ❑
fluid supplied
System pressure test carried out ❑
Air vented from system ❑
Exposed pipework insulated using high-temp and ❑
weather resistant insulation (bird/rodent-proof)
collector installation weatherproof ❑
Collector fixings checked and secure ❑
Hydraulic Station
System pressure when cold bar
Solar primary flow when cold l/min
Isolating/non-return valves (flow and return) in ❑
operating position
Solar Collectors
Collector visually inspected for defects ❑
Collector temperature sensors correctly installed ❑
and secured
Pipe entry points to building weatherproof ❑
Solar Differential Temperature Controller
Record all operational parameters set ❑
(see separate table)
Pump operation tested in automatic and manual ❑
modes
All cables correctly installed and secured ❑
Suitably fused isolating device installed ❑
Controller earthed ❑
Solar Cylinder
Cylinder installed and commissioned in ❑
accordance with cylinder installation instructions
Adjustable in menu Typical Current
"Programming" adjustment adjustment
Storage tank1: 65°C *
Maximum storage temperature
Storage tank1: 7 K
switch-on difference (dTon)
Storage tank1: 3 K
switch-off difference (dToff)
Storage tank2: 90°C *
Maximum storage temperature
Storage tank2: 7 K
switch-on difference (dTon)
Storage tank2: 3 K
switch-off difference (dToff)
Minimum pump power on 100%
rotational speed regulation
Switch-on temperature of 40°C
thermostat function
Hysteresis of thermostat function 10 K
2nd temperature differential 65°C
controller maximum temperature Tmax
2nd temperature differential controller 7 K
hysteresis dTmax
Adjustable in menu Typical Current
"Basic adjustments" adjustment adjustment
Switching on or off the function 0 = off *
collector protection
Temperature at which the collector 120°C *
protection function is active
Switching on or off the function 0 = off *
recooling (only when the collector
protection is on)
Temperature to which the storage 40°C *
tank is recooled when collector
protection function is on
Function for time-controlled 0 = off
circulation in operation with
tube collectors
Switching on or off the function 2 = on
energy productivity measurement
Choice of glycol types used 0 = Anro
Mixture ratio of coolants 50%
Litres per min 10 l/m
Switching on or off the function 0 = off
antifreezing
Temperature at which the antifreezing 3°C
is active
Alternative choice of the cooling, 2
thermostat function or the 2nd
temperature differential controller
System type type 0
Time control in secs 240
Storage priority 1
Solar differential temperature controller - operational parameters
If any factory values are changed please enter the new values in the
table below.
BPEC No.: _______________________________
Serial Nos. Cylinder _______________________________
Collector _________________
Pump Station Serial Number: ___________________________
* Baxi recommends these settings are left at the default value.