Baxi 100 He Installation And Servicing Instructions

Baxi 100 HE
Wall Mounted Powered Flue Condensing Boiler
Gas Fired Central Heating Unit
Installation and Servicing Instructions
Please leave these instructions with the user
Baxi UK Limited is one of the leading manufacturers
of domestic heating products in the UK.
Our first priority is to give a high quality service to our
customers. Quality is designed into every Baxi product
- products which fulfil the demands and needs of
customers, offering choice, efficiency and reliability.
To keep ahead of changing trends, we have made a
commitment to develop new ideas using the
latest technology - with the aim of continuing to make
the products that customers want to buy.
Everyone who works at Baxi has a commitment to
quality because we know that satisfied customers
mean continued success.
We hope you get a satisfactory service from Baxi. If
not, please let us know.
Natural Gas
Baxi 100 HE
G.C.No41 075 32
Baxi is a BS-EN ISO 9001 Accredited Company
The boiler meets the requirements of Statutory Instrument “ The Boiler (Efficiency) Regulations 1993 N
o
3083” and is deemed to meet the requirements of Directive 92/42/EEC on the energy efficiency requirements for new hot water boilers fired with liquid or gaseous fuels:-
Type test for purpose of Regulation 5 certified by: Notified Body 0086.
Product/Production certified by: Notified Body 0086.
For GB/IE only.
1.0 Introduction 4
2.0 General Layout 5
3.0 Appliance Operation 6
4.0 Technical Data 7
5.0 Dimensions and Fixings 8
6.0 System Details 9
7.0 Site Requirements 12
8.0 Installation 17
9.0 Electrical 23
10.0 Commissioning the Boiler 25
11.0 Fitting the Outer Case 26
12.0 Servicing the Boiler 27
13.0 Changing Components 29
14.0 Fault Finding 36
15.0 Short Parts List 44
Section Page
Contents
Baxi UK Limited declare that no substances harmful to health are contained in the appliance or used during appliance manufacture.
NOTE: This appliance must be installed in
accordance with the manufacturers instructions and the regulations in force, and only used in a suitably ventilated location.
All systems must be thoroughly flushed and treated with inhibitor (see Section 6.2).
Read the instructions fully before installing or using the appliance.
1.1 Description
1. The Baxi 100 HE is a gas fired room sealed fan assisted condensing central heating boiler.
2. The maximum output of the boiler is preset at 75,000 Btu/hr. The boiler will automatically adjust down to 30,000 Btu/hr according to the system load. If required, the output can be set to 100,000 Btu/hr. Please refer to section 8.8.
3. It is designed for use on Natural Gas (G20).
4. The boiler is suitable for fully pumped open vented central heating and domestic hot water systems and sealed systems.
5. A label giving details of the model, serial number and Gas Council number is situated on the rear of the lower door panel (Fig. 1).
6. The boiler data badge is positioned on the air box door (Fig. 2).
7. The boiler is intended to be installed in residential / commercial / light industrial E.M.C. environments on a governed meter supply only.
8. The boiler must be installed with one of the purpose designed flues such as the standard horizontal flue kit, part n
o
236921.
1.2 Important Information
This product contains Refractory Ceramic Fibres (R.C.F.) which are man-made vitreous silicate fibres. Excessive exposure to these materials may cause temporary irritation to eyes, skin and respiratory tract. Care must be taken when handling these articles to ensure the release of dust or fibres is kept to a minimum. To ensure that the release of fibres from these articles is kept to a minimum, during installation and servicing it is recommended that a H.E.P.A. filtered vacuum is used to remove any dust, soot or other debris accumulated in and around the appliance. This should be performed before and after working on the installation. It is recommended that any replaced item(s) are not broken up but sealed within heavy duty polythene bags and clearly labelled R.C.F. waste. This is not classified as hazardous waste and may be disposed of at a tipping site licensed for the disposal of industrial waste. Protective clothing is not required when handling these articles but it is recommended that gloves are worn and the normal hygiene rules of not smoking, eating or drinking in the work area are followed and always wash hands before eating or drinking.
1.0 Introduction
Fig. 1
H IG
H
L O
W
H I G
H
L O
W
Data Badge
Air Box Door
Lower Door Panel
Position of Label
Fig. 2
“Benchmark” Log Book
As part of the industry-wide Benchmark initiative all Baxi boilers now include an Installation, Commissioning and Service Record Log Book. Please read the Log Book carefully and complete all sections relevant to the appliance and installation. These include sections on the type of controls employed, flushing the system, burner operating pressure etc. The details of the Log Book will be required in the event of any warranty work. Also, there is a section to be completed at each subsequent regular sevice visit.
2.0 General Layout
2.1 Layout (Figs. 3,4 & 5)
1. Wall Plate
2. Flue Elbow
3. Heat Exchanger
4. Burner
5. Air Box
6. Fan Protection Thermostat
7. Fan Assembly
8. Condensate Trap
9. User Interface (optional timer available)
10. Gas Tap
11. Gas / Air Ratio Valve
12. Electronics Housing
13. Transformer
14. Flow Pipe Connection
15. Return Pipe Connection
16. Flow Temperature Safety Thermostat - Black
17. Flow Temperature Thermistor - Red
18. Flow Switch (dry fire protection)
H
I G
H
L
O
W
1
2
3
4
5
6
7
9
8
10
11
12
13
17 16
14
15
18
Fig. 4
Fig. 3
Fig. 5
2.2 Optional Extras
KIT PART N
o
FLUE EXTENSION KITS (110/70)
Flue Extension 0.25M 241692
Flue Extension 0.5M 241694
Flue Extension 1M
(Use two kits for 2M etc.) 241695
Flue Bend x 2 - 45°
(Reduce overall length of flue
by 0.5m when fitting this bend)
241689
Flue Bend - 90° (
Reduce overall length of flue
by 1m when fitting each bend)
241687
VERTICAL FLUE (110/70)
Vertical Flue Terminal 242802
Vertical Boiler Connection 242886
CONTROL ACCESSORIES
Integral Electronic Twin Channel Timer Kit 242834
3.0 Appliance Operation
3.1
1. Switched Live On: When the switched live switches on pump overrun occurs.
2. Pump Overrun: The pump is on while the fan, spark generator and gas valve are off. If at any stage during pump overrun the flow temperature is less than the set point and the flow switch is made then fan purge occurs. After 1 minute of pump overrun anti-cycle occurs.
3. Fan Purge: The pump and fan are on while the spark generator and gas valve are off. After 5 seconds ignition occurs.
4. Ignition: The pump, fan, spark generator and gas valve are on. If a flame is detected then burner on occurs. If a flame is not detected within 5 seconds and less than 5 ignition attempts have been made then fan purge occurs. If a flame is not detected within 5 seconds and 5 ignition attempts have been made the ignition lockout occurs.
5. Burner On: The pump, fan and gas valve are on while the spark generator is off. Flow temperature is controlled by varying the fan speed (and thereby the gas rate) to achieve optimum operation. If the flow temperature is greater than the set point then pump overrun occurs. If the TRVs all shut down then anti-cycle occurs.
6. Anti-cycle: The pump, fan, spark generator and gas valve are switched off. After 3 minutes pump overrun occurs.
7. Ignition Lockout: The pump, fan, spark generator and gas valve are switched off. The boiler can only be reset by manually using the thermostat knob.
Mains On.
Flow
temperature less
than set point and flow
switch made ?
YES
5 second
Fan Purge.
Flame Detected ?
Burner On.
Ignition
Lockout.
5 second
Ignition Period.
All TRVs
shut down ?
Flow temperature
greater than set
point ?
Ignition done and
5 attempts made ?
Ignition done
and less than 5
attempts made ?
Pump Overrun
Anti-cycle.
Pump Overrun
for 1 minute ?
YES
YES
YES
YES
YES
YES
Appliance Category CAT I
2H
4.0 Technical Data
Horizontal Flue Terminal Diameter 110mm Dimensions Projection 150mm
Outercase Dimensions
Overall Height Inc Flue Elbow - 750mm Casing Height - 600mm Casing Width - 390mm Casing Depth - 320mm
Weights kg lb Packaged Boiler Carton 40.7 89.6 Packaged Flue Kit 3.6 8.0 Weight Empty 38.2 84.1 Installation Lift Weight 31.5 69.3
Connections
Gas Supply -1/2in BSPT Central Heating Flow - 28mm Central Heating Return - 28mm Condensate Drain - 1 in BSP
Recommended System Temperature Drop
Normal 11°C20°F Condensing 20°C36°F
Heat Input Max Min
(see note) kW 33.76 10.2
Btu/h 115,200 34,840
Heat Output
(Non Condensing 70° C Mean Water Temp)
Max Min
kW 30.18 9.14
Btu/h 102,980 31,180
Electrical Supply 230V~ 50Hz
(Appliance must be connected to an earthed supply)
Power Consumption 80W
External Fuse Rating 3A
Internal Fuse Rating (BS 4265)
Fuse (2) 4 AT (Control Board) Fuse (3) 2 AT (Ignition Board)
Max Gas Rate (Natural Gas)
(After 10 Mins)
Btu/hr 102,980 75,000
m3/h 2.95 2.31
ft3/h 104.2 81.6
Inlet Pressure at Gas Valve (Natural Gas)
Min 18.1 mbar
Max 22.5 mbar
(see Section 10.1)
Injector (Natural Gas)
6.3mm Diameter
Clearances
(For unventilated compartments see Section 7.5)
Both Sides 5mm Min Above Casing 200mm Min Below Casing 50mm Min Front (For Servicing) 500mm Min Front (In Operation) 5mm Min
0 10203040
20
40
60
80
100
120
140
160
180
200
220
Water Flow Rate (litres/min)
Pressure Drop (mbar)
0.8
1.7
2.5
3.3
4.2
5.0
5.8
6.6
7.5
8.3
9.1
Pressure Drop (in wg)
Hydraulic Resistance Chart
Appliance Type C
13
C
33
Nox Class 5
Heat Output
(Condensing 40° C Mean Water Temp)
Max Min
kW 32.61 10.1
Btu/h 111,280 34,520
Water Content
litres 2.6
pints 4.6
Static Head
max 30 metres (100 ft)
min 1 metre (3.25 ft)
Low Head 0.2m (8 in) min
System Detail
fully pumped open vented & sealed systems
Gas Connection
RC1/2(1/2in BSPT)
Controls
boiler thermostat, safety thermostat, flow switch, electronic flame sensing, temperature protection thermostat & condensate blockage sensor
NOTE: The maximum output of the boiler is factory set at 22.0kW (75,000 Btu/hr). This can be altered to 30.18kW (102,980 Btu/hr)
- see section 8.8.
The efficiency is 90.9%
This value is used in the UK Government’s
Standard Assessment Procedure (SAP) for
energy rating of dwellings. The test data from
which it has been calculated has been
certified by 0086.
SEDBUK Declaration For 100 HE
5.0 Dimensions and Fixings
DIMENSIONS
A 600mm
B 320mm
C 390mm
D 125mm Ø Min.
E 150mm
F 125mm
SIDE FLUE (left and right)
For every 1m of horizontal flue length, the clearance above the top of the flue elbow should be 55mm to incorporate the 3° (1 in 20) fall in the flue from the terminal to the elbow.
The 3° (1 in 20) fall provided by the elbow is to allow condensate to run back to the boiler, for disposal through the condensate discharge pipe.
Flue length (Y)
up to 1m
1m - 2m
2m - 3m
Clearance (X)
55mm
110mm
165mm
360° Orientation
Tube Ø 110mm
D
C
B
A
E
F
Y
3°
(1 in 20)
X
3°
(1 in 20)
Fig. 6
Fig. 7
6.0 System Details
6.1 Water Circulating Systems
1. The appliance is suitable for use with open vent fully pumped systems and sealed systems .
The following conditions should be observed on all systems:
The static head must not exceed 30m (100ft) of water.
The boiler must not be used with a direct cylinder.
Drain cocks should be fitted to all system low points.
All gas and water pipes and electrical wiring must be installed in a way which would not restrict the servicing of the boiler.
Position isolating valves as close to circulating pump as possible.
It is recommended that the return pipe is fitted with an automatic air vent as close to the boiler as is practical.
NOTE: Full TRV Systems (refer to section 6.4) Where all the radiators are controlled by TRV’s then pump protection will be required. This can be done by either of the options opposite (see Fig A & B). The option shown in Fig. A should only be
used on a full TRV system without a bypass. Fig. B shows a system with a bypass that must be capable of allowing a flow of at least 3 l/min.
6.2 Treatment of Water Circulating
Systems
All recirculatory water systems will be subject to corrosion unless an appropriate water treatment is applied. This means that the efficiency of the system will deteriorate as corrosion sludge accumulates within the system, risking damage to pump and valves, boiler noise and circulation problems.
When upgrading existing systems that exhibit evidence of sludging, it is advisable to clean the system prior to treatment in order to remove any sludge and reduce the likelihood of these deposits damaging new components.
When fitting new systems flux will be evident within the system, which can lead to damage of system components.
All systems must be thoroughly drained and flushed out. The recommended flushing and cleansing agents are Betz-Dearborn Sentinel X300 or X400 and Fernox Superfloc Universal Cleanser which should be used following the flushing agent manufacturers instructions.
System additives - corrosion inhibitors and flushing agents/descalers should be suitable for aluminium and comply to BS7593 requirements. The only system additives recommended are Betz-Dearborn Sentinel X100 and Fernox-Copal which should be used followng the inhibitor manufacturers instructions.
Failure to flush and add inhibitor to the system will invalidate the appliance warranty.
It is important to check the inhibitor concentration after installation, system modification and at every service in accordance with the manufacturers instructions. (Test kits are available from inhibitor stockists.)
For information or advice regarding any of the above contact the Baxi Helpline.
Boiler
No demand for hot water
Central heating load
All TRVs shut down (boiler flow switch causes pump to stop)
Live feed to pump
Switch live from programmer, etc.
S/L N
P/F
Fig. A Wiring to the pump feed connection of boiler
Fig. B Providing a 3 l/min bypass
Boiler
No demand for hot water
Central heating load
All TRVs shut down (pump continues around bypass)
Switch live from programmer, room stat, etc.
S/L junction
S/L N
P/F
3 l/min bypass
Boiler Connections
Boiler Connections
NOTE: This boiler does not require a bypass.
This boiler does not require a permanent live. These diagrams only refer to pump protection for fully TRVd systems.
6.0 System Details
10
6.3 Pipework
1. The sizes of flow and return pipes from the boiler should be determined by normal methods, according to the requirements of the system. The connection to the boiler is 28mm (compression).
2. Due to space requirements within the boiler outercase, pipework should comprise of solder fittings.
3. A 20 °C (36°F) drop in temperature across the system is recommended for condensing boilers. Existing radiators may be oversized and so allow this, but where radiator sizing is marginal it may be advisable to retain a system temperature drop of 11°C (20°F).
4. In systems using non-metallic pipework it is necessary to use copper pipe for the boiler Flow and Return. The copper must extend at least 1 metre from the boiler and include any branches (Fig. 7a).
6.4 System Controls
1. For optimum operating conditions, the heating system into which the boiler is installed should include a control system.
2. Such a system will comprise of a timer control and separate room or cylinder thermostats as appropriate. (An integral twin channel programmer is available as an optional extra).
3. The boiler should be controlled so that it operates on demand only.
4. Operation of the system under control of the boiler thermostat & TRVs only does not produce the best results.
6.5 Low Head Installation
1. Using a close couple arrangement the minimum head is as shown in the diagrams (Figs. 8 & 9) subject to the following conditions:
a) The pump being adjusted to give an 20
o
C
drop across the boiler. b) The pump must be fitted on the flow. c) The pump must be fitted in accordance with
the pump manufacturer's instructions. d) The open vent pipe must be taken up from a
tee in a horizontal section of the flow pipe.
An alternative Low Head Installation (Fig. 10)
2. For heads below 400mm then a combined vent and feed pipe may be connected. This must be a minimum of 22mm diameter. It is recommended that an air separator is fitted when using a combined feed and vent pipe.
6.6 Thermal Stores
1. When the 100 HE is fitted in conjunction with a thermal store, jumper 2 must be removed from the Control PCB, see Fig. 32a Section 8.8.
Typical Low Head Installation
If Conditions Require, This System Possible
Alternative Low Head Installation
Boiler
500mm
45°
22mm Open Vent
1000mm
Min
150mm
Max
15mm Cold Feed
400mm
Min Head
Return
Pump
Flow
Boiler
500mm
45°
22mm Open Vent
400mm
Min Head
1000mm
Min
Automatic
Air Vent
15mm Cold Feed
150mm
Max
Return
Pump
Flow
Return
Pump
Flow
Boiler
200mm
Min
Air
Separator
22mm Feed & Vent Pipe
Fig. 8
Fig. 9
Fig. 10
Boiler
Flow
Return
Copper
0.5m
Copper
1m
Copper
0.5m
Fig. 7a
6.0 System Details
11
6.7 Sealed Systems
(Fig. 11)
1. SAFETY VALVE - A safety valve complying with the requirements of BS 6750 Part 1 must be fitted close to the boiler on the flow pipe by means of a horizontal or vertically upward connection with no intervening valve or restrictions and should be positioned to facilitate testing. The valve should be pre-set and non-adjustable to operate at a pressure of 3 bar (45 Ibf/in
2
). It must be arranged to discharge any water or steam through a pipe to a safe outlet position.
2. PRESSURE GAUGE - A pressure gauge of minimum range 0-4 bar (0-60 Ibf/in2) with a fill pressure indicator must be fitted to the system, preferably at the same point as the expansion vessel in an easily visible position.
3. EXPANSION VESSEL - An expansion vessel complying with the requirements of BS 4814 must be fitted to the system by means of a connection close to the inlet side of the circulating pump in accordance with the manufacturers instructions, the connecting pipe being unrestricted and not less than 15mm (
1
/2in) nominal size. The volume of the vessel should be suitable for the system water content and the nitrogen or air charge pressure should not be less than the system static head (See Table. 1).
Further details of sealed system design can be obtained from BS 5449 and the British Gas publication entitled 'Specifications for Domestic Wet Central Heating Systems'.
4. FILLING POINT - A filling point connection on the central heating return pipework must be provided to facilitate initial filling and pressurising and also any subsequent water loss replacement / refilling. The filling method adopted must be in accordance with the Water Supply (Water Fittings) regulations and the Water Bylaws (Scotland). Your attention is drawn to: Paragraph 24 of Schedule 2 Section 8 of the publication Water Regulations Guide which gives recommendations and guidance on approved methods for filling sealed systems. The sealed primary circuits may be filled or replenished by means of a temporary connection between the primary circuit and a supply pipe provided the arrangement in accordance with Diagram R24.2a of the Water Regulations Guide. The temporary hose must be completely removed at both ends after use.
5. MAKE UP SYSTEM - A method of replacing water lost from the system should be provided either by means of a make up vessel of not more than 3 litres (5 pints) capacity, mounted above the highest point of the system, or by re-pressurisation of the system.
6. VENTING - A method of venting the system during filling and commissioning must be provided by fitting automatic air vents or by venting manually.
7. HOT WATER STORAGE - The hot water storage vessel must be of the indirect coil type. All components used in the system must be suitable for operation at 110°C (230°F) and at the pressure allowed by the safety valve.
Safety
Valve
Pressure
Gauge
Pump
Filling
Point
Air
Vent
3 Litre Top Up Bottle (if required)
Radiator Circuit
Expansion Vessel
System Drains at Low Point
Max Boiler Flow
Temp = 82° C
Boiler
Fig. 11
Table. 1
Vessel Charge Pressure (Bar)
0.5
1.0
1.5
Initial System
Pressure (Bar)
0.5
1.0
1.5
2.0
1.0
1.5
2.0
1.5
2.0
Multiply Total
Water Content
Of System By
(Litres)
0.067
0.112
0.207
0.441
0.087
0.152
0.330
0.125
0.265
Method of determining minimum valve of
expansion vessel volume for sealed
systems using Baxi Boilers
System Volume = 75 litres Vessel Charge Pressure = 1.0 bar Initial System Pressure = 1.5 bar 75 x 0.152 = 11.4 litres Expansion Vessel Volume
Example :-
Then :-
NOTE
Where a vessel of the calculated size is not obtainable
then the next available larger size should be used.
Stop Valve
Double Check Valve
DHW Mains Inlet
CH Return
Temporary Hose
Stop Valve
Fig. 11a
7.0 Site Requirements
12
7.1 Information
WARNING - Check the information on the data
plate is compatible with local supply conditions.
1. The installation must be carried out by a CORGI Registered Installer or other registered competent person and be in accordance with the relevant requirements of the current G
AS SAFETY (Installation
and Use) R
EGULATIONS, the BUILDING REGULATIONS
(Scotland)(Consolidation), the LOCAL BUILDING REGULATIONS, the current I.E.E. WIRING REGULATIONS
and the bye laws of the LOCAL WATER UNDERTAKING. Where no specific instruction is given reference should be made to the relevant BRITISH STANDARD CODES OF PRACTICE. For Ireland install in accordance with IS 813 “I
NSTALLATION OF
GAS APPLIANCES. Reference should also be made to B
RITISH GAS GUIDANCE NOTES FOR THE
INSTALLATION OF DOMESTIC GAS CONDENSING BOILERS.
7.2 B.S. Codes of Practice
Standard Scope
BS 6891 Gas Installation. BS 5546 Installation of hot water supplies for
domestic purposes. BS 5449 Part 1 Forced circulation hot water systems. BS 6798 Installation of gas fired hot water boilers. BS 5440 Part 1 Flues. BS 5440 Part 2 Ventilation. BS 7074 Expansion vessels and ancillary
equipment for sealed water systems. BS 7593 Treatment of water in domestic hot water
central heating systems.
WARNING - The addition of anything that may interfere with the normal operation of the appliance without the express written permission of Baxi UK Limited could invalidate the appliance warranty and infringe the G
AS SAFETY
(Installation and Use) REGULATIONS.
7.3 Clearances (Figs. 12 &13)
1. A flat vertical area is required for the installation of the boiler.
2. These dimensions include the necessary clearances around the boiler for case removal, spanner access and air movement. Additional clearances may be required for the passage of pipes around local obstructions such as joists running parallel to the front face of the boiler.
3. For unventilated compartments see Section 7.5.
7.4 Location
1. The boiler may be fitted to any suitable wall with the flue passing through an outside wall or roof and discharging to atmosphere in a position permitting satisfactory removal of combustion products and providing an adequate air supply. The boiler should be fitted within the building unless otherwise protected by a suitable enclosure i.e. garage or outhouse. (The boiler may be fitted inside a cupboard - see Section 7.5).
2. If the boiler is sited in an unheated enclosure then it is recommended to incorporate in the system controls a suitable device for frost protection.
3. If the boiler is fitted in a room containing a bath or shower reference must be made to the current
I.E.E. W
IRING REGULATIONS and BUILDING
REGULATIONS. If the boiler is to be fitted into a
building of timber frame construction then reference must be made to the Institute of Gas Engineers document UP 7.
50mm
600mm
390mm
200mm
5mm Min
5mm Min
5mm
500mm
For Servicing
Purposes
Fig. 12
Fig. 13
In Operation
3°
(1 in 20)
320mm
7.0 Site Requirements
13
7.5 Ventilation of Compartments
1. Where the boiler is installed in a cupboard or compartment, no air vents are required for cooling purposes providing that the minimum dimensions below are maintained.
Sides 15mm Top 200mm Bottom 50mm Front 30mm
2. If the boiler is installed in a smaller cupboard or compartment it must be ventilated according to BS 5440 Part 2 and the minimum clearances given in section 4.0 Technical Data maintained.
3. Any compartment should be large enough to house the boiler only.
NOTE: The ventilation label on the front of the outer case MUST NOT BE REMOVED when the appliance is installed in a compartment or cupboard.
7.6 Gas Supply
1. The gas installation should be in accordance with BS6891.
2. The connection to the appliance is a
1
/2in BSPT internal threaded connection located at the rear of the gas service cock (Fig. 15).
3. Ensure that the pipework from the meter to the appliance is of adequate size. (22mm pipework must be connected to the appliance gas service cock. This should extend for at least 3 meters back towards the gas meter).
Do not use pipes of a smaller diameter than the boiler gas connection.
7.7 Electrical Supply
1. External wiring must be correctly earthed, polarised and in accordance with current I.E.E.
W
IRING REGULATIONS.
2. The mains supply is 230V ~ 50Hz fused at 3A.
NOTE: The method of connection to the electricity supply must facilitate complete electrical isolation of the appliance. Connection may be via a fused double-pole isolator with a contact separation of at least 3mm in all poles and servicing the boiler and system controls only.
7.8 Condensate Drain
NOTE: Ensure the discharge of condensate
complies with any national or local regulations in force.
1. The condensate outlet terminates in a 1 BSP nut and seal for the connection of 21.5mm (
3
/4in) plastic overflow pipe which should generally discharge internally into the household drainage system. If this is not possible, discharge into an outside drain is acceptable.
2. The pipe should run internally as much as possible and with a 10° (1 in 6) fall to dispose of condensate quickly to avoid freezing.
H IG
H
L O
W
Gas Service Cock
Fig. 15
7.0 Site Requirements
14
N
I
I
G
F
M
I
A
A
F
H
J,K
D E
H
Likely flue positions requiring a flue terminal guard
C
R
A
I
J,K
I
S
B
7.9 Flue
NOTE: Due to the nature of the boiler a plume
of water vapour will be discharged from the flue. This should be taken into account when siting the flue terminal.
1. The following guidelines indicate the general requirements for siting balanced flue terminals. Recommendations for flues are given in BS 5440 Pt.1.
2. If the terminal discharges onto a pathway or passageway, check that combustion products will not cause a nuisance and that the terminal will not obstruct the passageway.
3. Take into consideration the effect the plume of vapour may have on neighbours when siting the flue.
4. Adjacent surfaces close to the flue terminal may need protection from the effects of condensation. Alternatively a flue deflector kit (part no. 248167) is available.
5. For installation of the flue into an internal corner at the 25mm dimension the flue deflector kit (part no. 248167) must be fitted.
6. * Reduction to the boundary is possible down to 25mm but the flue deflector kit (part no.
248167) must be fitted.
7. For fitting under low sofits and eaves it is acceptable for the flue to project upto 500mm from the face of the wall to the inside of the air intake. This can be painted if required using a suitable external paint.
8. If a terminal is less than 2 metres (78
3
/4in) above a balcony, above ground or above a flat roof to which people have access, then a suitable terminal guard must be provided.
Fig. 17
Fig. 16
300 min
Terminal Assembly
Top View Rear Flue
Property Boundary Line
NOTE: The distance from a fanned draught appliance terminal installed parallel to a boundary may not be less than 300mm in accordance with the diagram below
Table. 2
Terminal Position with Minimum Distance (Fig. 17) (mm)
AaDirectly below an opening, air brick, opening
windows, etc. 300 BaAbove an opening, air brick, opening window etc. 300 CaHorizontally to an opening, air brick, opening window etc. 300 D Below gutters, soil pipes or drain pipes. 25 E Below eaves. 25 F Below balconies or car port roof. 25 G From a vertical drain pipe or soil pipe. 25 H From an internal
(i)
or external
(ii)
corner.
(i)
25
(ii)
115 I Above ground, roof or balcony level. 300 J From a surface facing a terminal. 600 K From a terminal facing a terminal (Horizontal flue). 1200
From a terminal facing a terminal (Vertical flue). 600
L From an opening in carport (e.g. door, window)
into the dwelling. 1200 M Vertically from a terminal on the same wall. 1500 N Horizontally from a terminal on the same wall. 300
R From adjacent wall to flue (vertical only). 300 S From an adjacent opening window (vertical only). 1000
a
In addition, the terminal should be no nearer than 150 mm to an opening in the building fabric formed for the purpose of accommodating a built-in element such as a window frame. See BS 5440 Pt. 1.
*
7.0 Site Requirements
15
7.10 Flue Dimensions
See Section 1.2. The standard horizontal flue kit allows for flue lengths between 270mm (10
5
/8”) and 800mm (32) from elbow to terminal (Fig. 18).
The maximum permissible equivalent flue length is: 4 metres (Fig. 18a).
NOTE: Each additional 45° of flue bend will
account for an equivalent flue length of 0.5m. eg. 45° = 0.5m, 90° = 2 x 45° = 1m etc.
7.11 Terminal Guard (Fig. 19)
1. When codes of practice dictate the use of terminal guards, they can be obtained from most Plumbers and Builders Merchants.
2. When ordering a terminal guard, quote the appliance model number.
3. The flue terminal guard should be positioned centrally over the terminal and fixed as illustrated.
7.12 Vertical Flue
1. Only a flue approved with the Baxi 100 HE can be used.
2. For information on vertical flues consult the Baxi High Efficiency Brochure or Notes for Guidance supplied with the vertical flue pack.
Fig. 18
Fig. 18a
Pictorial examples of flue runs where EQUIVALENT flue length equals 4m
Fig. 19
270mm
800mm
0.5m
1m
0.5m
0.5m
Loading...
+ 33 hidden pages