In the following you will find the explanations of the symbols used
in this operating manual.
This symbol indicates activities to be carried out.
●This symbol indicates supplementary technical information.
This symbol is located before texts to which particular
attention is to be paid to ensure proper use of the
NE215.
This symbol is located before texts that provide important
additional information.
Important terms in the left text column are printed in italics
to help you find information more quickly.
1Safety Instructions
1.1 General information
The products has been developed and built in accordance with the
recognized rules of technology. The units have left the
manufacturing plant ready to operate and in safe condition.
To keep the units in this condition, it is necessary that the
units be installed and operated
– properly,
– in a safety and hazard-conscious manner,
– under observance of this operating manual and in particular of
these safety precautions!
Make sure that the personnel has read and understood the
operating manual, and in particular the "Safety Instructions" chapter.
In addition to the operating manual, the generally applicable legal
and other binding regulations for accident prevention and
environmental protection must be observed and ensured.
1.2 Proper use
The application of the units consists of controlling and monitoring
industrial processes in the metal, wood, plastics, paper, glass and
textile industry etc.
The units may only be operated
– in the properly installed state and
– in accordance with the specifications of the technical data!
Operation not covered by the specified
descriptions/parameters is improper and can lead to
– fatal injuries,
– serious damage to health,
– property damage or
– damage to the units
in conjunction with the systems/machines/processes
to be controlled/monitored!
2
NE215Safety Instructions
The overvoltages to which the units are subjected at the connection
terminals must be limited to the value of the overvoltage category II
(see Technical Data)!
The units may not be operated
– in hazardous areas,
– as medical units,
– in applications expressly named in EN 61010!
If the units are used to control/monitor machines or processes with
which, as the result of a failure/malfunction or incorrect operation
of the units
– a life-threatening danger,
– health risks or
– a danger of property or environmental damage
could result, then appropriate safety precautions
must be taken!
Do not open the housing of the units or make any
changes to it!
Tampering with the units can have a negative affect on their
operating safety, resulting in dangers!
Do not make repairs on the units! Return defective units to the
manufacturer!
1.3 Installation/commissioning
In case of changes (including in the operating behavior) that
impair safety, shut-down the units immediately.
Installation may only be carried out in accordance with the
procedure described in Chapter 3 "Connecting".
During installation work on the units, the power supply must
always be disconnected. Installation work may only be carried out
by appropriately trained experts.
Max. voltage 250 V terminal - terminal, ground - terminal.
Following proper assembly and installation, the units are ready for
operation. Following commissioning, familiarize yourself with the
use of the units in Chapter 4 "Operator Level".
1.4 Maintenance/repairs
Always disconnect the power supply of all units involved.
Maintenance and repair work may only be carried out by
appropriately trained experts.
If troubleshooting is unsuccessful, do not continue to use the units.
Please contact the manufacturer in this case.
3
NE215Getting to know the counter
2Getting to know the counter
The counter comprises the following:
– Presetting the counter with 2 preset value, (preliminary testing by PTB)
– Secondary counter with preset value and multiplier,
– Totalizing counter, (preliminary testing by PTB)
– Time meter
Components / LED-display
XP Counter status, main counter
P1 Preset value 1, main counter
P2 Preset value 2, main counter
mMeter display
ΣTotalizing counter
B1 Preset value, sec. counter
Current value, time meter
Control panel
0
...9Numerical keypad
Selector key for function display
Selector key for programming/operating mode
Function key
Druck
The counter is a micro-processor controlled electronic device with
serial interface for counting, controlling and monitoring. The device is
approved by the German Physical Technical Authorities (PTB) as
calibrated for the use as: “measured value transfer device for
application in calibrated machines for length measurement”.
Key for printing
Reset key
Function display
LEDs- Symbol display
Selector key/Function display
PTB-Number
Reset key C
Selector key for programming/operating mode
Function key
Key for printing
Numerical keypad
Address for printer:
DATAMEGA Mikrodatent. GmbH
Landsberger Str. 318-320
80687 München
Tel.: +49 (0)89 56017-300
4
RegistrationFromReference number
NE21523.12.19931.62-3251.11 / IVO-040293
1. addendum 16.03.19951.62-3251.11 / IVO-040293
2. addendum 28.09.19971.62-3251.11 / IVO-040293
3. addendum 24.06.19995.23-99037480
4. addendum 29.03.20015.21-01028291
PTB-Approval:
The counter is only PTB approved in combination with an encoder.
The PTB- approved system for example provides a chart printer
model STAR SP298.
1. 3
93.15
Getting to know the counter
Example for print
NE215
Main counter systems: (PTB-approved)
1 up/down preset counter with totalizer.
Batch counter systems:1 preset counter, adding.
A key provided at the counter enables switching the display to the
respective countersof the main respectively batch counting
system.
Counter function
Applications
The counter is administrating the inputs of both counting systems
and will react by the programmed output action upon achieving the
set presets respectively limit values.
Thanks to various programming options the device is capable of
many machine monitoring and controlling tasks. Running values and
the set parameters remain even after power failure.
The serial interface allows printout of counter values.
●Interior use for monitoring and control of production machines
and systems.
●In any branches of industry where length measurement is
subject to calibration.
The device must not be used in: explosive areas, medical appliances
as well as in applications explicitly mentioned in the standards of
VDE 0411 part 100.
2.1 Block diagram
The block diagram shows the components together with its contacts
and connections.
Supply
voltage
count
XP-Reset
h counter
B1 counter
B1 reset
2
3
12
A
B
A 90° B
13
14
15
16
17
Totalizer
Main counter
Batch counter
or
Tachometer
4
5
P1
6
7
8
P2
9
10
B1
11
Coding
Interface
19
18
T
23
R
25
GND
26
Time Meter
Interface
RS232
Sensor
supply
20
5
Counter connect
NE215
3Counter connect
This chapter will explain how the contacts are assigned.
Under chapters 3.1 to 3.5 you will find actual tips and technical data
for the various connections.
The electrical inputs and outputs are assigned to two 12-pole plug-in
screw terminals, coded to prevent reversed polarity.
Assignment
22 2 1 20 19 18 17 16 15 14 13 12
+24V 0V
Sensor
supply
NPN Br. 18-20
PNP Br. 18-19
B1 reset
11 10 9 8 7 6 5 4 3 2 1
B1P2P1
Output
max. 250 VTerminal - Terminal- Terminal
* Models with scaling
26 25 24 23
RxD
TxD
GND
RS232
B1 counter
22 21
T, R +
RS485
(Scaling on)*
XP reset
h counter
T, R -
BA
Count
ContactFunction
1Not assigned
2Supply voltage
3Supply voltage
4
5
6
1 Relay contact output P1
7
Supply
8
9
10
11
1 Relay contact output P2
1 Relay contact output B1
12Signal input, track A
13Signal input, track B
14Reset XP
15Time meter
16Signal input, track B1
17Reset B1
18Coding input for input logic
19Encoder supply 0 Volt
20Encoder supply +24 Volt
21Option RS485 T,R22Option RS485 T,R+
Litz contact only by means of connector sleeves with insulating
enclosures for reasons of shock protection according to VDE 0411
part 100. Do not otherwise assign contacts that have been left
unassigned ex factory. We recommend to screen all encoder
terminal leads and to ground the shield on one side. Shields on
both sides are recommended in case of RF interference or in case
of equipotential bonding over long distances. The encoder leads
should not be in the same phase winding as the MAINS supply and
the output contact leads.
6
Counter connect
115 VAC 230 VAC
6 5 47 8 9
NE215
3.1 Connecting the power supply
For power supply following voltage ranges are available:
AC 115/230 VAC (50/60 Hz)
DC 24 VDC ±10%
Voltage supply Recommended external fuse
115/230 VAC M 125 mA
24 VDC M 400 mA
➜ Assign voltage supply to terminals 2 and 3 according to
diagramm.
DC-voltage 24 VDC:
Connect voltage supply that is free from any interference. Do not utilize the voltage supply for parallel supply of drives, shields, magnetic
valves, etc. Supplying lines must be separated from lines providing
load current.
Fire protection: Operate the instrument using the recommended
external fusing indicated in the terminal diagram. EN 61010 specifies
that 8 A/150 VA (W) must never be exceeded in the event of a fault.
3.2 Assignment signal output „relay contact“
Terminals 4, 5, 6 and 7, 8, 9 are no-potential changeover contacts.
Terminals 10 and 11 are configured as NC or NO contacts in accordance with the purchase order specification. The signal outputs
can be assigned in accordance with the adjoining wiring diagram.
Implementation as a pulse or continuous signal, together with the
pulse time, is effected in the programming mode (lines 31, 32, 33).
11 10
Max. ratingMax. voltageMax. current
150 VA/30 W265 V1 A
The user is responsible for ensuring that a switching load of 8 A/150
VA (W) is not exceeded in the event of a fault. Internal spark suppression by means of two zinc oxide varistors (275 V).
Terminals 12 to 17 are AC optocoupler inputs. Terminals 12 (track A)
and 13 (track B) are pulse inputs for the main counter (XP) counting
function.
Terminal 14 is an external reset input for the main counter.
Depending on what is set in the programming mode (line 40),
terminal 15 serves as a starting input for the operating hours counter.
Terminal 16 (track B1) is the pulse input for the secondary counter
(XB). Terminal 17 is the input for resetting the secodary counter.
Programming input logic
TerminalInputStarting currentAbschaltstrom
resistance
121,65 Kohm> 9 mA, < 16 mA< 0,5 mA
131,65 Kohm> 9 mA, < 16 mA< 0,5 mA
143,3 Kohm> 5 mA, < 8 mA< 0,5 mA
153,3 Kohm> 5 mA, < 8 mA< 0,5 mA
161,65 Kohm> 9 mA, < 16 mA< 0,5 mA
173,3 Kohm> 5 mA, < 8 mA< 0,5 mA
The main counter (XP) is reset by pplying an external signal (signal
width ≥ 30 ms) at terminal 14; the secondary counter (XP) at terminal
17. While an external signal is present, no counter take place. The
method of resetting is set in the programming mode (lines 29, 30).
Assign terminals 12 to 17 accordingly. The maximum counter
frequency is selected in the programming mode (line 26).
The signal input logic can be programmed by means of a bridge between terminals 18, 19 and 20, in accordance with the table below.
Apply
- if encoder supply
is not provided by
the counter.
- if the encoder is
featuring push-pull
or PNP output
- if several counters
are triggered in a
parallel way by one
encoder
Encoder signals
PNP, triggered by
positive signals.
E
B
K
Pin assignment
18 and 19
18 and 19
20 19 18 17 16 15 14 13 12
8
- if the encoder is
featuring a NPN
output.
NPN, triggered by
negative signal.
B
K
E
18 and 20
Electrical isolation is provided for instruments with an AC power
supply and a relay output without interface.
Counter connect
NE215
3.4 Connecting the encoder supply
Connect the encoder supply at terminals 19 and 20.
Do not use the encoder supply to supply non-earthed inductive or
capacitive loads.
The encoder power supply is not short-circuit proof.
TerminalVoltageMax.Max. permissible
190V––
20+24 VDCDepending on load80 mA
3.5 Interface connect
The serial interface is capable of executing the following functions:
– Data printout
Interface parameter are as follows:
– Data transmission rate (baud rate),
– Parity bit,
– Number of stop bits,
The interface parameters can be set in the programming
(lines 43, 44, 45 and 46).
The following interfaces can be connected to the counter:
– RS232
Interface characteristics
RS232
Transmission with the following characterisics:
– Asymmetric
– Two leads
– Point-to-Point connection - 1 transmitter and 1 receiver
– Max. data transmission distance: 30 m
+10 %/-50 %
residual ripplecurrent
9
To start test
NE215Counter connecting and operating
3.6 Executing the test routine
The test routine is described below.
Press the 2 and
Switch the counter on.
●All the display segments will be displayes automatically in
sequence and are therby tested for functional capability.
Druck
key simultaneously.
Test extension
Using the key, test the keyboard, the inputs, outputs and
interface in sequence.
No machine fuctions may connected when the outputs are tested.
Keyboard test
Input test
●Inputs can be triggered simultaneously or individually. A display
is only provided when a signal is applied.
Output test
Press keys 1, 2 and 3 .
The outputs are now activated.
Reset the outputs with the key.
Interface test
Display: Model and program number
Display: Program date and version
10
End of test
The test routine is terminated, the counter is now in the operating
mode.
Operating mode
Operating mode
To read
Reset
To read
NE215
4Operating mode
The operation and use of the counter are described in this section.
●As soon as the power supply has been switched on, the
counter is automatically set to the operating mode.
In the operating mode:
– the current main counter status can be read and reset;
– the preset values for the main and secondary counters can be
read;
– the current total can be read and reset;
– the current status of the secondary counter can be read and reset;
– the operating hours counter can be read.
All the parameters can be disabled in the programming mode.
Main counter status
The current counter status is displayed in the operating mode;
no keying is necessary.
Readout running counter value.
Resetting must be enabled in the programming mode.
Press the key.
Main counter preset value
Resetting must be enabled in the programming mode
Press the key.
Read preset value P1.
To change
Other changes
Press the key.
●LED P1 flashes.
Press the key.
●Preset 1 is being deleted.
Input the preset value P1 via the numerical keypad.
Press the key.
●The change is completed.
If a key is not operated within 15 seconds, the preset value will
automatically be re-displayed in the operating mode.
Press the key.
●The following values can also be changed.
11
Operating mode
NE215
If other values are changed, the value at witch the operating level
was left can be re-displayed with thekey after the
programming mode has been left.
Other changes
To change
Other changes
To read
Press thekey.
●Read preset value P2
Press the key.
●LED P2 flashes.
Press thekey.
●Preset 2 is being deleted.
Input the preset value P2 via the numerical keypad.
Press thekey.
●The change is completed.
If a key is not operated within 15 seconds, the preset value will
automatically be re-displayed in the operating mode.
Press the key.
●The following values can also be changed.
If other values are changed, the value at witch the operating level
was left can be re-displayed with thekey after the
programming mode has been left.
Totalizing counter
The totalizing counter can be disabled in the programming mode.
Press thekey.
Read the totalizing counter.
12
Reset
To read
Reset
Press thekey.
Secondary counter status
The secondary counter can be disabled in the programming mode.
Press the key.
Read off the current limit value secondary counter status
Press the key.
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.