Baumer ED711 User Manual

Cleaning and maintenance
There is no need cleaning the pressure trans­mitter. However, in order to avoid any damage, please do not direct high pressure cleaning “jets of water” directly at the diaphragm. In particular, never clean the diaphragm with tools or other mechanical objects. Do not insert hard objects into the pressure gauge opening.
Operation / procedure in case of malfunction
The admissible range acc. to technical datash­eet must be respected in any case. In case of malfunction, please check the follow­ing points :
– Check the data on the label plate and compare
with the installed confi guration. – Check wiring. – Check the power supply and load. – Check if the diaphragm is ok or damage. – Check the possibilities of EMC infl uences.
Connecting diagram
For 4 … 20 mA current loop
a
b
I
A
d
Load RL + R
1500
Line
1200
900
+R
L
600 300
Load R
:
Line
Prohibited zone
0
0 5 10 15 20 25 30 35
Supply voltage
Pressure Transmitter ED 711
U
B
R
L
Repair
Please send the pressure transmitter (if pos­sible with the original packing) to the nearest representation. Detailed information regarding the malfunction helps us in obtaining a faster anal y sis.
www.baumerprocess.com Application Manual G45214.1 Design and specifi cations subject to change without notice
Pin assignment
Contact DIN 43650 plug
4…20 mA a 1 b 2 c – d GND
View soldering side cable socket
Installation and Operating Instructions
E-2004-05-01
Thank you for having chosen our product. These instructions should allow you an easy installa­tion. Please study this documentation carefully and retain for further reference. Information about the materials used and general technical data can be obtained from the relevant technical data sheet.
1. General points
This pressure transmitter is a precision measur­ing device. The highly sensitive diaphragm is protected with a cap which should only be re­moved just prior to the installation. Take special care to avoid abrasive media, solid bodies and other mechanical damage (thumb-mark). Please follow these instructions carefully so that the pressure transmitter works perfectly. The admissible storage temperature is –10 °C ... +100 °C (dry air). The pressure transmitter corresponds – under the condition that the installation has been properly effected – to the EMC standards EN 50081-1 and 2, as well as EN 50082-2 and EN
61326.
2. Installation / Removal
2.1 Pressure transmitter with thread
Screw the pressure transmitter in the corre­sponding threaded hole and tighten with the following torque :
Pressure range (bar) Torque (Nm) 0,1 – 10 30
It is advisable to grease the threads lightly with a molybdenum disulfi de grease such as Molykote or Molymagus. In food applications, use Vaseline.
2.2
Do not install the pressure transmitter close to any fast closing valves or pumps (for example in hydraulic systems), however the sensitive sen­sor is protected against pressure peaks. Before removals, make sure that the tube carry­ing the medium is completely de pres su rized.
Attention: Serious injury can result if the line is still pressurized! After removal, the diaphragm resp. the pressure connection, must be protected with the original cap immediately.
3. Electrical connection
We recommend a shielded cable in order to obtain the best possible EMC pro tec tion. The shield has to be connected to the GND of the plug. In addition, we rec om mend not to install the cable in a chan nel where al ready cables of controlling pumps, motors, etc. have been in stalled. The cable shield has to be earthed at the side “Power supply/con trol”.
3.1 Plug version
Fix the socket on the corresponding wires of the cable. Assignement of contacts – please refer to the labelling plate or to the corresponding list. Fix the cable shield to the socket in such a way that there will be a good contact between shield and housing. Plug in and fi x the cable socket connector.
3.2
For pin assignment, cable colors, electrical dia­grams and load, please refer to the reverse page of this manual. The pressure transmitter is protected against reverse polarity of the suply volt age, as well as against over voltage.
4. New – Calibration of the Zero point
The function for the new calibration of the Zero point is accessible on the device. This function allows you to make a correction of the output signal drift, for example caused by the installa­tion. Any long term drifts can be corrected like­wise. Caution: Usually, the pressure transmitter
must be free of any pressure, when adjusting the Zero point. An exception, if for example you
want to adjust a level transmitter and you want to set a new Zero point. If you need to set the pressure transmitter with a negative range (-1 … X bar ) or with an absolute range, it can only be achieved if the defi ned pressure is applied on the pressure transmitter. This can be done by means of using a calibrator.
white wire
Zero point push button
So the Zero point can be found, the device must be connected to a power supply. The New-Cali­bration of the Zero point is achieved with a single push on the push button. The Zero point switch can be reached in different way depending on the model:
The model with the plug unit connector: Unplug the device plug, then loosen the plug unit from the pressure transmitter, turn it anticlockwise.
Caution: The plug unit is connected with the electronic system. Try to avoid to pull out the cable to much, because you can possible pull out the plug. Although using all your caution and you unplug the connection, you take the white wire and plug it in the right top hand corner (see picture). Now you can apply the power supply
by plugging in the plug of the device. Press the Zero point switch. Detach the plug of the device. To assemble the plug unit, turning it clockwise onto the device. Caution: Watch out and take the
necessary caution not to have the wires twisted between the plug unit and the electronic, before assembling. Fasten the plug unit on the device.
Your pressure transmitter is now reset with a new Zero point and is ready to be used.
www.baumerprocess.com Application Manual G45214.1 Design and specifi cations subject to change without notice
Loading...