Baumer DFON User Manual

Operators instructions CombiView™, type DFON
DFON graphical displays are used as separate units, but also used in complete instruments, e.g. CombiPress™, CombiTemp™
Safety instructions
This instrument is built and tested according to the current EU­directives and packed in a technically safe condition. In order to main­tain this condition and to ensure safe operation, the user must follow the hints and warnings given in this instruction.
During the installation the valid national rules have to be observed. Ig­noring the warnings may lead to severe personal injury or substantial damage to property.
The product must be operated by trained staff. Correct and safe opera­tion of this equipment is dependent on proper transport, storage, instal­lation and operation.
All electrical wiring must conform to local standards. In order to prevent stray electrical radiation, we recommend twisted and shielded input cables, as also to keep power supply cables separated from the input cables. The connection must be made according to the connection dia­grams.
Before switching on or off the power supply take care that other equip­ment is not effected. Ensure that the supply voltage and the conditions in the environment comply with the specification of the device.
Description
The DFON is powered by the 4…20 mA loop and need no additional power supply. When mounted on new instrument series like the CombiPress™ PFMx it is via the internal UnitCom ribbon cable supplied with power and a digital signal, instead of integrated in the 4…20 mA loop. In instruments with UnitCom both the transmitter and display can be programmed at the same time alternative­ly separate programming of each device can be selected.
The DFON has an unique background colour setting. Three colours are available – White / Red / Green and further the red and green colour can be set as flashing in warning mode.
The DFON has two integrated galvanic separated relays. The instrument can be delivered with or without activated relays. If sup­plied without activated relays, those can be activated by purchasing a license code from Baumer. By entering the code to the in­strument via the FlexProgrammer the relays are enabled.
The DFON can be programmed by the touch screen on the display or by the FlexProgrammer 9701 Baumer programming unit with the Baumer FlexProgram installed on a PC. (Free download from www.baumer.com > Services > Downloads > Software < Flex…)
The DFON can be delivered as a loose display or as an integrated part of an instrument e.g. PFMx, TFRx.
Alternatively it can be delivered as a loop-powered local display for any instrument in a SS case for wall mounting, panel mounting or tube mounting.
www.baumer.com
Operators instructions: 11112759 Page 1 / 8
EN/20131116 Design and specifications subject to change without notice
Operators instructions CombiView™, type DFON
Display mode
There are 9 different display modes available
Digital Analogue Bar graph Tank small analogue horizontal tank illustration large same w. bar graph vertical bottle illustration same w. value
Electrical connection
Electrical connection Pin 1 + 4…20 mA Pin 2 - 4…20 mA
Pin 3 Relay 1 Pin 4 Relay 1
Pin 5 Relay 2 Pin 6 Relay 2
Com 1 FlexProgrammer ① red Com 2 FlexProgrammer ① black
Pin 3 and 5 can be jumpered together if common supply is used for the two relays, e.g. via a M12 5-pin connector.
When instruments like PFMx are delivered with DFON display terminal 1 and 2 are not connected. In this case the DFON is pow­ered and will have data through a special ribbon cable (UnitCom). When connected via UnitCom the DFON and transmitter can be programmed together.
UnitCom
Dimensions for mounting of stand alone instrument
Wall mounting Panel mounting Tube mounting
PCD for holes: Ø95 mm Panel cut out: 80 mm Tube diameter: Ø38 mm
PCD for holes: 82 mm Ø51 mm Ø64 mm
www.baumer.com
Operators instructions: 11112759 Page 2 / 8
Operators instructions CombiView™, type DFON
Touch screen programming the CombiView™ , type DFON
Programming CombiView™, type DFON using the touch screen on the display
Tap on the display screen and the button will appear in the bottom.
Press and the display may start with one out of two possible selections.
With traditional 4…20 mA loop configuration (connected to pin 1 and 2 on the display)
Display menu
With a transmitter communicating with the DFON via UnitCom ribbon cable
Display menu
Instrument name> menu
Display menu
Data display mode
Data display mode will communicate with the transmitter digitally, which is more accurate than using the 4…20 mA communica-
tion.
MENU
Configuration
Enabling the user to set up the connected transmitter
Enabling the user to program the DFON display
Enabling the user to program the connected transmitter. The programmed values will also be valid for the DFON display. (Ignoring whatever setup already set on the display) Only programming of background colours and relays must be done under “Display menu” / “Configuration”.
Display setup
Instrument name menu
MENU
Diagnostics
Display setup
Data display mode
Instrument name menu
Instrument name menu
Instrument name menu
Instrument name menu
Instrument name menu
Programming the CombiView™, type DFON with the FlexProgram and FlexProgrammer
For programming configuration please see page 4
Guidance on programming of DFON display using FlexProgram on your PC and the FlexProgrammer hardware tool will not be
described here. A full manual for this is available on Baumer home page. Please see or download the instruction from below internet address:
www.baumer.com → download → product documentation → assembly instructions/Operation instructions/Manuals → Programming the DFON
Operators instructions: 11112759 Page 3 / 8
www.baumer.com
Operators instructions CombiView™, type DFON
Touch screen programming the CombiView™, type DFON
www.baumer.com
Operators instructions: 11112759 Page 4 / 8
Operators instructions CombiView™, type DFON
CombiView™, type DFON - ATEX specifications and instruction
Zone 0/1 Gas: II 1 G, Ex ia IIC T5 Gas
Zone 20/21 Dust: II 1 D, Ex ia IIIC T100°C Da
Zone 2 Gas: II 3 G, Ex nA II T5
Please ensure the special requirements for installation in the specific environment is followed, as described below.
ATEX approval requires the CombiView™, type DFON to be installed in IP67 certified housing, such as Baumer FlexHousing.
Safety instructions
This instrument is constructed and tested according to the current EU directives and packed in a technically safe condition. In order to ensure safe conditions and operation, the user must follow the instructions and warnings given in this instruction and the standard operation instruction. See: www.baumer.com/downloads/product documents/manuals - DFON - Operators instructions
During the installation the valid national rules have to be observed. Ignoring the instructions may lead to severe personal injury or substantial damage to property.
The product must be installed and operated by trained staff. Correct and safe operation of this equipment is dependent on proper installation and operation.
All electrical wiring must conform to local standards and the connection must be made according to the connection diagrams on the following pages.
Before switching on the power supply take care that other equipment is not affected. Ensure that the supply voltage and condi­tions in the environment comply with the specification of the device.
Before switching off the supply voltage check the possible effects on other equipment and processing system.
To obtain the specified ingress protection degree, the CombiView™, type DFON must be mounted with a compliant cable.
Warning
This product is allowed to be operated in an explosion hazardous atmosphere of zone 0 only if atmospheric conditions exists (temperature –20°C…+60°C and pressure from 0,8...1,1 bar). Under other atmospheric conditions the certificate may be used as a guide.
Use of FlexProgrammer 9701 is only allowed in the safe area, not in the hazardous area.
Impact test of the display cover is performed according to EN 60079-0, with low impact energy of 2J and does not create a crack or other intrusion into the housing. However the display, which is mounted close to the front cover may be damaged, but this will not create any external sparking. The housing is impact texted also according to EN 60079-0, with low impact energy of 4J on housing, connectors and cable gland.
This product contains no replaceable parts. In case of malfunction the products must be shipped to Baumer for repair.
www.baumer.com
Operators instructions: 11112759 Page 5 / 8
Operators instructions CombiView™, type DFON
ATEX Gas ia and for ATEX Dust ia
For ATEX ia Gas zone 0 and ATEX ia Dust zone 20 a zener barrier must separate the hazardous and safe area and must be in­stalled in accordance with prevailing guidelines for zone 0 / zone 20.
ATEX ia Gas / Dust data:
Approval: Gas Zone 0/1 II 1 G, Ex ia IIC T5 Ga
Dust Zone 20/21 II 1 D, Ex ia IIIC T100°C Da
Voltage drop U Temperature class T1…T5 Zone 0 and 20 -20°C…60°C
Zone 1/2 and 21/22 -40°C…65°C
Internal inductivity Li <10 µH Internal capacity Ci <15 nF
Barrier data Ui <30 VDC
Ii <0,1 A Pi <0,75 W
Suitable barrier e.g.: Pepperl+Fuchs, Z728
The display is supplied by the 4…20 mA loop from the transmitter and can thus be placed near the transmitter or near the power supply, as preferred. However to make the display intrinsic safe a zener barrier must be inserted before the DFON. The transmitter may be placed inside or outside the hazardous area.
If the CombiView™, type DFON is attached to a Baumer transmitter using the UnitCom ribbon cable, it is considered to be an inte­grated part of the instrument. Please see the ATEX instruction for the relevant instrument.
If the relays are enabled, each relay must be protected by a zener barrier. Use a barrier for each relay or a barrier with multiple channels. However the two relays must have each a barrier.
Barrier data U <30 VDC
I <75 mA P <0,75 W Suitable barrier e.g.: Pepperl+Fuchs, Z779
4,5 or 6,5 VDC
Disp
Display in the zone, transmitter outside the zone Display and transmitter in the zone
1 +
2 -
Zener barrier
4…20 mA
15…30 VDC
1 +
2 -
With relay output With relay output
Display in the zone/transmitter outside the zone Display and transmitter in the zone
www.baumer.com
1 +
2 -
3
Relay 1
4
5
Relay 2
6
Zener barrier
Zener barrier
Zener barrier
4…20 mA
15…30 VDC
0…30 VDC 75 mA
0…30 VDC 75 mA
1 +
2 -
3
4
5
6
Operators instructions: 11112759 Page 6 / 8
4…20 mA
4…20 mA
Relay 1
Relay 2
Zener barrier
Zener barrier
Zener barrier
Zener barrier
15…30 VDC
15…30 VDC
0…30 VDC 75 mA
0…30 VDC 75 mA
Operators instructions CombiView™, type DFON
ATEX Gas nA
For ATEX nA zone 2 is approved without using zener barrier must separate the hazardous and safe area and must be installed in accordance with prevailing guidelines for zone 0.
ATEX data:
Approval: Gas Zone 2 II 3 G, Ex nA II T5
Voltage drop U Temperature class T1…T5 -30 < T Internal inductivity Li <10 µH Internal capacity Ci <15 nF Maximum voltage U Maximum current I
4,5 or 6,5 VDC
Disp
<35 VDC
max
<0,1 A
max
<65°C
amb
Display without relay output Display with relay output
4…20 mA
Relay 1
Relay 2
1 +
2 -
4…20 mA
1 +
2 -
3
4
5
6
Programming the CombiView™, type DFON in ATEX area
Programming the CombiView™, type DFON in hazardous area with the FlexProgrammer is not allowed, as the FlexProgrammer (and/or the PC) is not ATEX approved.
Follow below procedure to programme the instrument:
a Disconnect mains from the 4…20 mA loop circuit
b Disconnect the instrument from the circuit within the hazardous area
c Uninstall the instrument and bring it to safe area
d Connect the FlexProgrammer and perform the configuration session. (Please see: www.baumer.com/downloads/product documents/manuals - DFON - Programming)
e Re-install the instrument in the hazardous area
f Connect the instrument to the circuit
g Connect mains from the 4…20 mA loop circuit
www.baumer.com
Operators instructions: 11112759 Page 7 / 8
Operators instructions CombiView™, type DFON
Baumer AG
Hummelstrasse 17 8501 Frauenfeld Switzerland
+41 51 / 75 81 122 +41 52 / 72 81 144
sales.ch@baumer.com
www.baumer.com
Baumer A/S
Runetoften 19 8210 Aarhus V Denmark
+45 8931 7611 +45 8931 7610
sales.cc-lct@baumer.com
Contact your local Baumer company or Baumer distributor. Please see:
www.baumer.com/worldwide
Select your country Select your contact
Operators instructions: 11112759 Page 8 / 8