Date of purchase: _________________________________
Date of installation: _______________________________
Installer: ________________________________________
Model number: ___________________________________
Serial number: ___________________________________
W10309063B
W10309065B-SP
1
DRYER SAFETY
INSTALLATION REQUIREMENTS
TOOLS AND PARTS
Gather the required tools and parts before starting installation.
Tools needed:
Flat-blade screwdriver#2 Phillips screwdriver
2
Wire stripper
(direct wire installations)
1/4" nut driver
(recommended)
Tin snips
(new vent installations)
Vent clamps
Adjustable wrench that
opens to 1" (25 mm) or
hex-head socket wrench
Utility knife
Parts needed: (Not supplied with dryer)
Check local codes. Check existing electrical supply and venting.
See “Electrical Requirements” and “Venting Requirements”
before purchasing parts.
Check code requirements. Some codes limit, or do not permit,
installing dryer in garages, closets, mobile homes, or sleeping
quarters. Contact your local building inspector.
LOCATION REQUIREMENTS
Tape measure
Level
Parts supplied:
Leveling legs (4)
Short inlet hose
Pliers
Caulking gun and
compound (for installing
new exhaust vent)
“Y” connector
Long inlet hose
You will need:
A location allowing for proper exhaust installation. See ■
“Venting Requirements.”
A separate 30 amp circuit.■
If using power supply cord, a grounded electrical outlet ■
located within 2 ft. (610 mm) of either side of dryer. See
“Electrical Requirements.”
Floor must support dryer weight of 200 lbs. (90.7 kg). Also ■
consider weight of companion appliance.
Cold water faucets located within 4 ft. (1.2 m) of the water ll ■
valves, and water pressure of 20-100 psi (137.9-689.6 kPa).
You may use the water supply for your washer using the
“Y” connector and short hose (if needed) which are provided.
20-100 psi (138-690 kPa) for best performance.■
Level oor with maximum slope of 1" (25 mm) under entire ■
dryer. If slope is greater than 1" (25 mm), install Extended
Dryer Feet Kit, Part Number 279810. If not level, clothes
may not tumble properly and automatic sensor cycles may
not operate correctly.
Rubber washer
Parts package is located in dryer drum. Check that all parts
are included.
NOTE: If installing dryer on pedestal, do not use leveling legs.
Optional Equipment: (Not supplied with dryer)
Refer to your Use and Care Guide for information about
accessories available for your dryer.
For each arrangement, consider allowing more space for ease
of installation and servicing; spacing for companion appliances
and clearances for walls, doors, and oor moldings. Space
must be large enough to allow door to fully open. Add spacing
on all sides of dryer to reduce noise transfer. If a closet door
or louvered door is installed, top and bottom air openings
in door are required.
3
DRYER DIMENSIONS
27"
(686 mm)
3
/4"
(18 mm)
42 3/8"
(899 mm)
30 7/8 "
(783 mm)
9"
(228 mm)
351/2"
(902 mm)
3 1/2"
(89 mm)
14
1
/2"
(368 mm)
1 1/2"
(36 mm)
5 3/4"
(149 mm)
3 1/4"
(88 mm)
6 1/4"
(156 mm)
Front view:
Back view:
* Approx. measurement
Side view:
NOTE: Most installations require a minimum of 5" (102 mm)
clearance behind dryer for exhaust vent with elbow. See
“Venting Requirements.”
IMPORTANT: Do not operate, install, or store dryer where
it will be exposed to water, weather, or at temperatures below
45° F (7° C). Lower temperatures may cause dryer not to shut
off at end of automatic sensor cycles, resulting in longer
drying times.
Installation spacing for recessed area or closet:
All dimensions show recommended spacing allowed, with
tested spacing of 0" (0 mm) clearance on sides and rear.
Additional spacing should be considered for ease ■
of installation and servicing.
Additional clearances might be required for wall, door, ■
and oor moldings.
Additional spacing should be considered on all sides ■
of the dryer to reduce noise transfer.
For closet installation, with a door, minimum ventilation ■
openings in the top and bottom of the door are required.
Louvered doors with equivalent ventilitation openings
are acceptable.
Companion appliance spacing should also be considered.■
4
Closet installation (dryer only):
24 in.
2
(155 cm2)
48 in.
2
(310 cm2)
1"
(25 mm)
1"
(25 mm)
5"
(102 mm)
3"
(76 mm)
34" recommended
(864 mm)
18" min.
(457 mm)
3"
(76 mm)
Mobile home - Additional installation requirements:
This dryer is suitable for mobile home installations. The
installation must conform to the Manufactured Home
Construction and Safety Standard, Title 24 CFR, Part 3280
(formerly the Federal Standard for Mobile home construction
and Safety, Title 24, HUD Part 280) or Standard CAN/CSA-Z240
MH.
Mobile home installations require:
Metal exhaust system hardware, available for purchase ■
from your dealer. For further information, see “Assistance
or Service” section in your Use and Care Guide.
Special provisions must be made in mobile homes ■
to introduce outside air into dryer. Openings (such
as a nearby window) should be at least twice as large
as dryer exhaust opening.
ELECTRICAL REQUIREMENTS
It is your responsibility:
To contact a qualied electrical installer.■
To be sue that the electrical connection is adequate and ■
in conformance with the National Electrical Code, ANSI/NFPA
70 - latest edition and all local codes and ordinances.
The National Electrical Code requires a 4-wire power supply
connection for homes built after 1996, dryer circuits involved
in remodeling after 1996, and all mobile home installations.
A copy of the above code standards can be obtained from:
National Fire Protection Association, One Batterymarch Park,
Quincy, MA 02269.
To supply the required 3 or 4 wire, single phase, 120/240 ■
volt, 60 Hz, AC only electrical supply (or 3 or 4 wire, 120/208
volt electrical supply, if specied on the serial/rating plate)
on a separate 30-amp circuit, fused on both sides of the line.
Connect to an individual branch circuit. Do not have a fuse
in the neutral or grounding circuit.
Do not use an extension cord.■
If codes permit and a separate ground wire is used, ■
it is recommended that a qualied electrician determine
that the ground path is adequate.
Electrical Connection
To properly install your dryer, you must determine the type
of electrical connection you will be using and follow
the instructions provided for it here.
This dryer is manufactured ready to install with a 3-wire ■
electrical supply connection. The neutral ground conductor
is permanently connected to the neutral conductor (white
wire) within the dryer. If the dryer is installed with a 4-wire
electrical supply connection, the neutral ground conductor
must be removed from the external ground connector (green
screw), and secured under the neutral terminal (center
or white wire) of the terminal block. When the neutral ground
conductor is secured under the neutral terminal (center
or white wire) of the terminal block, the dryer cabinet
is isolated from the neutral conductor.
If local codes do not permit the connection of a neutral ■
ground wire to the neutral wire, see “Optional 3-wire
connection” section.
A 4-wire power supply connection must be used when ■
the appliance is installed in a location where grounding
through the neutral conductor is prohibited. Grounding
through the neutral is prohibited for (1) new branch-circuit
installations, (2) mobile homes, (3) recreational vehicles,
and (4) areas where local codes prohibit grounding through
the neutral conductors.
If using a power supply cord:
Use a UL listed power supply cord kit marked for use with
clothes dryers. The kit should contain:
A UL listed 30-amp power supply cord, rated 120/240 volt ■
minimum. The cord should be type SRD or SRDT
and be at least 4 ft. (1.22 m) long. The wires that connect
to the dryer must end in ring terminals or spade terminals
with upturned ends.
A UL listed strain relief.■
If your outlet looks like this:
Then choose a 4-wire power supply cord
with ring or spade terminals and UL listed
strain relief. The 4-wire power supply cord,
at least 4 ft. (1.22 m) long, must have four
10-gauge copper wires and match a 4-wire
receptacle of NEMA Type 14-30R. The ground
4-wire receptacle
(14-30R)
wire (ground conductor) may be either green
or bare. The neutral conductor must be
identied by a white cover.
If your outlet looks like this:
Then choose a 3-wire power supply cord
with ring or spade terminals and UL listed
strain relief. The 3-wire power supply cord,
at least 4 ft. (1.22 m) long, must have three
10-gauge copper wires and match a 3-wire
3-wire receptacle
(10-30R)
receptacle of NEMA Type 10-30R.
Choose a standard power supply cord connector:
Flanged spade connectors Ring connectors
5
If connecting by direct wire:
diamond
m
arking
Power supply cable must match power supply (4-wire or 3-wire)
and be:
Flexible armored cable or nonmetallic sheathed copper cable ■
(with ground wire), protected with exible metallic conduit. All
current-carrying wires must be insulated.
10-gauge solid copper wire (do not use aluminum) at least ■
5 ft. (1.52 m) long.
2.
Screw in leveling legs
Examine leveling legs, nd diamond marking. Screw legs into leg
holes by hand, use a wrench to nish turning legs until diamond
marking is no longer visible.
Now stand the dryer on its feet. Slide the dryer until it is close
to its nal location. Leave enough room for electrical connection
and to connect the exhaust vent.
ELECTRICAL CONNECTION
OPTIONS
1.Choose electrical connection type
Power supply cord 4-wire receptacle
(NEMA Type 14-30R):
Follow only steps for 4-wire power
supply cord connection.
Then, go to Venting Requirements.
INSTALL LEVELING LEGS
Prepare dryer for leveling legs
1.
Power supply cord 3-wire receptacle
(NEMA Type 10-30R):
Follow only steps for 3-wire power
supply cord connection.
Then go to Venting Requirements.
4-wire direct connection:
Follow only steps for 4-wire direct
connection.
Then go to Venting Requirements.
3-wire direct connection:
Follow only steps for 3-wire direct
connection.
Then go to Venting Requirements.
NOTE: If local codes do not permit connection of a
cabinet-ground conductor to neutral wire, go to “Optional 3-wire
connection” and follow the required steps. This connection may
be used with either a power supply cord or a direct wire
connection.
To avoid damaging oor, use a large at piece of cardboard from
dryer carton; place under entire back edge of dryer. Firmly grasp
dryer body (not console panel) and gently lay dryer down on
cardboard.
6
2.Remove terminal block cover
A
B
C
D
Power supply cord strain relief:
Attach power supply cord
1.
strain relief
Before you start, disconnect power. Remove hold-down screw
and terminal block cover.
ELECTRICAL CONNECTION
Power Supply Cord
A. Strain relief tab pointing up
B. Hole below terminal block opening
C. Clamp section
D. Strain relief tab pointing down
Remove screws from 3/4" (19 mm) UL listed strain relief (UL
marking on strain relief). Put two clamp section tabs into hole
below terminal block opening with one tab pointing up and one
pointing down. Hold in place and tighten strain relief screws
enough to hold two clamp sections together.
Attach power supply cord
2.
to strain relief
Put power supply cord through strain relief. Be sure that wire
insulation on power cord is inside strain relief. Strain relief should
be a tight t with dryer cabinet and be in a horizontal position.
Do not tighten strain relief screws at this point.
Now go to step 1 for 4-wire power supply cord connection
or step 1 for 3-wire power supply cord connection.
7
4-WIRE POWER SUPPLY CORD
A
BF
E
G
D
C
A
B
D
C
E
F
G
CONNECTION
IMPORTANT:A 4-wire connection is required for mobile
homes and where local codes do not permit the use of 3-wire
connections.
A. 4-wire receptacle (NEMA type 14-30R)
B. 4-prong plug
C. Ground prong
D. Neutral prong
E. Spade terminals with upturned ends
F. 3/4" (19 mm) UL listed strain relief
G. Ring terminals
Prepare to connect neutral
1.
ground wire and neutral wire.
E
B
3.Connect ground wire
F
A
Connect ground wire (F) (green or bare) of power supply cord
to external ground conductor screw (A). Tighten screw.
4.
Connect remaining wires
A
Remove center, silver-colored terminal block screw (B).Remove
neutral ground wire (E) from external ground conductor screw (A).
2.
Connect neutral ground wire
and neutral wire
C
B
E
Connect neutral ground wire (E) and neutral wire (white or center
wire) (C) of power supply cord under center, silver-colored
terminal block screw (B). Tighten screw.
Connect remaining wires to outer terminal block screws. Tighten
screws. Finally, reinsert tab of terminal block cover into slot of
dryer rear panel. Secure cover with hold-down screw. Now, go to
Venting Requirements.
3-WIRE POWER SUPPLY CORD
CONNECTION
Use where local codes permit connecting cabinet-ground
conductor to neutral wire.
A. 3-wire receptacle (NEMA type 10-30R)
B. 3-wire plug
C. Neutral prong
D. Spade terminals with upturned ends
E. 3/4" (19 mm) UL listed strain relief
F. Ring terminals
G. Neutral (white or center wire)
1.Remove center screw
B
8
Remove center, silver-colored terminal block screw (B).
2.Connect neutral wire
Direct wire strain relief:
1.Attach direct wire strain relief
C
Connect neutral wire (white or center wire) (C) of power supply
cord to center, silver-colored terminal block screw (B). Tighten
screw.
B
3.Connect remaining wires
Unscrew removable conduit connector and any screws from
a 3/4" (19 mm) UL listed strain relief (UL marking on strain relief).
Put threaded section of strain relief through hole below terminal
block opening, screw removable conduit connector onto strain
relief threads.
2.Attach direct wire cable
to strain relief
Connect remaining wires to outer terminal block screws. Tighten
screws. Finally, reinsert tab of terminal block cover into slot of
dryer rear panel. Secure cover with hold-down screw. Now, go
to Venting Requirements.
Direct Wire
Put direct wire cable through strain relief. Strain relief should be a
tight t with dryer cabinet and be in a horizontal position. Tighten
strain relief screw against direct wire cable. Now go to step 1
for 4-wire direct wire connection, step 1 for 3-wire direct wire
connection, or step 1 for optional 3-wire connection.
9
4-WIRE DIRECT WIRE
1"
(25 mm)
5"
(127 mm)
CONNECTION
Prepare your 4-wire cable for direct connection:
IMPORTANT: A 4-wire connection is required for mobile
homes and where local codes do not permit 3-wire
connections.
1.Prepare your 4-wire cable for
direct connection
Direct wire cable must have 5 ft. (1.52 m) of extra length so dryer
may be moved if needed.
Strip 5" (127 mm) of outer covering from end of cable, leaving
bare ground wire at 5" (127 mm). Cut 11/2" (38 mm) from
remaining 3 wires. Strip insulation back 1" (25 mm). Shape
ends of wires into hooks.
4.Connect neutral ground wire
and neutral wire
C
Connect neutral ground wire (E) and place hooked end (hook
facing right) of neutral wire (white or center wire) (C) of direct wire
cable under center screw of terminal block (B). Squeeze hooked
ends together and tighten screw.
B
E
5.Connect ground wire
F
2.Connect wires to terminal block
To connect wires to terminal block, place hooked end of wire
under terminal block screw, facing to the right, squeeze hooked
end together and tighten screw.
3.Prepare to connect neutral
ground wire and neutral wire
E
B
A
A
Connect ground wire (green or bare) (F) of direct wire cable to
external ground conductor screw (A). Tighten screw.
6.Connect remaining wires
Place hooked ends of remaining direct wire cable wires under
outer terminal block screws (hooks facing right). Squeeze hooked
ends together and tighten screws. Finally, reinsert tab of terminal
block cover into slot of dryer rear panel. Secure cover with
hold-down screw. Now, go to Venting Requirements.
Remove center, silver-colored terminal block screw (B). Remove
neutral ground wire (E) from external ground conductor screw (A).
10
3-WIRE DIRECT WIRE
1"
(25 mm)
3½"
(89 mm)
CONNECTION
Use where local codes permit connecting cabinet-ground
conductor to neutral wire.
1.Prepare your 3-wire cable for
direct connection
4.Connect neutral wire
C
Place hooked end of neutral wire (white or center wire) (C) of
direct wire cable under center terminal block screw (B). Squeeze
hooked end together. Tighten screw.
B
Direct wire cable must have 5 ft. (1.52 m) of extra length so dryer
may be moved if needed.
Strip 31/2" (89 mm) of outer covering from end of cable. Strip
insulation back 1" (25 mm). If using 3-wire cable with ground
wire, cut bare wire even with outer covering. Shape wire ends
into hooks.
2.Connect wires to terminal block
To connect wires to terminal block, place hooked end of wire
under terminal block screw, facing to the right, squeeze hooked
end together and tighten screw.
3.Remove center screw
5. Connect remaining wires
Place hooked ends of remaining direct wire cable wires under
outer terminal block screws (hooks facing right). Squeeze hooked
ends together and tighten screws. Finally, reinsert tab of terminal
block cover into slot of dryer rear panel. Secure cover with
hold-down screw. Now, go to Venting Requirements.
OPTIONAL 3-WIRE CONNECTION
You must verify with a qualied electrician that this
grounding method is acceptable before connecting.
1.Prepare to connect neutral
ground wire and neutral wire
Remove center, silver-colored terminal block screw (B).
B
B
E
A
Remove center, silver-colored terminal block screw (B).
Remove neutral ground wire (E) from external ground
conductor screw (A).
11
2.
4"
(102 mm)
4"
(102 mm)
B
A
4"
(102 mm)
2½"
(64 mm)
Connect neutral ground wire
and neutral wire
C
B
E
Connect neutral ground wire (E) and neutral wire (white
or center wire) (C) of power supply cord or cable under center,
silver-colored terminal block screw (B). Tighten screw.
3.
Connect remaining wires
VENTING REQUIREMENTS
WARNING: To reduce the risk of re, this dryer MUST BE
EXHAUSTED OUTDOORS.
IMPORTANT: Observe all governing codes and ordinances.
Dryer exhaust must not be connected into any gas vent,
chimney, wall, ceiling, attic, crawlspace, or a concealed space
of a building. Only rigid or exible metal vent shall be used
for exhausting.
Place hooked ends of remaining wires under outer terminal
block screws (hooks facing right). Tighten screws.
4.
Connect a separate copper ground wire (G) from the external
ground conductor screw (A) to an adequate ground. Finally,
reinsert tab of terminal block cover into slot of dryer rear panel.
Secure cover with hold-down screw. Now, go to Venting
Requirements.
Connect external ground wire
A
G
■
Only a 4" (102 mm) heavy metal exhaust
vent and clamps may be used.
■
Do not use plastic or metal foil vent.
Rigid metal vent:
Recommended for best drying performance and to avoid ■
crushing and kinking.
Flexible metal vent: (Acceptable only if accessible to clean)
Must be fully extended and supported in nal dryer location.■
Remove excess to avoid sagging and kinking that may result ■
in reduced airow and poor performance.
Do not install in enclosed walls, ceilings, or oors.■
The total length should not exceed 7■
3
/4 ft. (2.4 m).
NOTE: If using an existing vent system, clean lint from entire
length of the system and make sure exhaust hood is not plugged
with lint. Replace plastic or metal foil vents with rigid metal or
exible metal vents. Review Vent system chart and if necessary,
modify existing vent system to achieve best drying performance.
Exhaust hoods:
Must be at least 12" (305 mm) from ground or any object ■
that may obstruct exhaust (such as owers, rocks, bushes,
or snow).
12
Recommended styles:
A. Louvered hood
B. Box hood
Acceptable styles:
C. Angled hood
An exhaust hood should cap vent to keep rodents ■
and insects from entering home.
Do not use exhaust hood with a magnetic latch.■
Elbows:
45° elbows provide better airow than 90° elbows.■
Alternate exhaust installations (for close clearance):
Vent systems come in many varieties. Select the type best
for your installation. Refer to the manufacturer’s instructions.
Good
Better
Clamps:
Use clamps to seal all joints.■
Exhaust vent must not be connected or secured with screws ■
or other fastening devices that extend into interior of duct
and catch lint. Do not use duct tape.
Vent products can be purchased from your dealer. For further
information, see “Assistance or Service” section in your Use
and Care Guide.
Over-the-top installation
(also available with one offset elbow)
Periscope installation
Special provisions for mobile homes:
Exhaust vent must be securely fastened to a noncombustible
portion of mobile home and must not terminate beneath
the mobile home. Terminate exhaust vent outside.
PLAN VENT SYSTEM
Choose your exhaust installation type
Recommended exhaust installation:
Bottom exhaust installation
13
Determine vent path:
12" min.
(305 mm)
12" min.
(305 mm)
Select route that will provide straightest and most direct ■
path outdoors.
Plan installation to use fewest number of elbows and turns.■
When using elbows or making turns, allow as much room ■
as possible.
Bend vent gradually to avoid kinking.■
Use as few 90° turns as possible.■
Determine vent length and elbows needed for best
drying performance:
Use following Vent system chart to determine type of vent ■
material and hood combinations acceptable to use.
NOTE: Do not use vent runs longer than those specied in
Vent system chart.
Exhaust systems longer than those specied will:
Shorten life of dryer.■
Reduce performance, resulting in longer drying times ■
and increased energy usage.
The Vent system chart provides venting requirements that will
help achieve best drying performance.
NOTE: Side and bottom exhaust installation have a 90° turn
inside the dryer. To determine maximum exhaust length, add on
90° turn to the chart.
NOTE: If exible transition vent is used, the length must be
subtracted from the total exhaust length in the vent system chart.
2.
Vent must t over the exhaust hood. Secure vent to exhaust
hood with 4” (102 mm) clamp. Run vent to dryer location using
straightest path possible. Avoid 90° turns. Use clamps to seal all
joints. Do not use duct tape, screws, or other fastening devices
that extend into interior of vent to secure vent, because they can
catch lint.
Connect vent to exhaust hood
CONNECT INLET HOSE
The dryer must be connected to the cold water faucet using
the new inlet hoses. Do not use old hoses.
Turn cold water off, remove and
1.
replace rubber washer
Vent system chart
Number of
90° elbows
0
1
2
3
4
Type
of vent
Rigid metal
Rigid metal
Rigid metal
Rigid metal
Rigid metal
Box/louvered
hoods
64 ft. (20 m)
54 ft. (16.5 m)
44 ft. (13.4 m)
35 ft. (10.7 m)
27 ft. (8.2 m)
Angled
hoods
58 ft. (17.7 m)
48 ft. (14.6 m)
38 ft. (11.6 m)
29 ft. (8.8 m)
21 ft. (6.4 m)
INSTALL VENT SYSTEM
1.
Install exhaust hood and use caulking compound to seal
exterior wall opening around exhaust hood.
14
Install exhaust hood
Turn cold water faucet off and remove washer inlet hose.
Check and see if rubber washer is in the “Y” connector. Remove
old rubber washer from inlet hose and replace with new rubber
washer provided.
Attach short hose and
2.
“Y” connector
A
If space permits, attach the brass female end of the “Y”
connector to the cold water faucet. See gure A.
If “Y” connector cannot be attached directly to the cold water
faucet, the short hose must be used. See gure B. Attach short
hose to cold water faucet. Screw on coupling by hand until it is
seated on faucet. Then attach “Y” connector to brass male end
of the short hose. Screw on coupling by hand until it is seated
on connector.
B
3.
Tighten couplings
Turn on cold water faucet
6.
A
Using pliers, tighten the couplings with additional two-thirds turn.
NOTE: Do not overtighten. Damage to the coupling can result.
Attach long hose to “Y”
4.
B
connector and tighten couplings
One end of the long hose has
a wire mesh strainer inside the
coupling. Attach this end to the “Y” connector. Attach washer
cold inlet hose to other side of “Y” connector. Screw on coupling
by hand until it is seated on connector. Using pliers, tighten the
couplings an additional two-thirds turn.
NOTE: Do not overtighten. Damage to the coupling can result.
Check that the water faucets are turned on.
Check for leaks
7.
Check for leaks around “Y” connector, faucet, and hoses.
CONNECT VENT
1.
Connect vent to exhaust outlet
Attach long hose to dryer ll
5.
valve and tighten coupling
Attach other end of long hose to ll
valve at bottom of dryer back panel.
Screw on coupling by hand until it
is seated on ll valve connector.
Using pliers, tighten the couplings an additional two-thirds turn.
NOTE: Do not overtighten. Damage to the coupling can result.
Using a 4" (102 mm) clamp, connect vent to exhaust outlet in
dryer. If connecting to existing vent, make sure vent is clean.
Dryer vent must t over dryer exhaust outlet and inside exhaust
hood. Check that vent is secured to exhaust hood with a
4" (102 mm) clamp.
15
2.
Move dryer to nal location, taking care not to crush or kink vent.
After dryer is in place, remove corner posts and cardboard from
under dryer.
Move dryer to nal location
LEVEL DRYER
1.
Check levelness of dryer from side to side. Repeat from front
to back.
NOTE: The dryer must be level for the moisture sensing system
to operate correctly.
Not Level LEVEL Not Level
Level Dryer
Place
level here
Place
level here
COMPLETE INSTALLATION
CHECKLIST
Check that all parts are now installed. If there is an extra part,
q
go back through steps to see what was skipped.
Check that you have all of your tools.
q
Dispose of/recycle all packaging materials.
q
Be sure the water faucets are on.
q
Check for leaks around “Y” connector, faucet, and hoses.
q
Check dryer’s nal location. Be sure vent is not crushed or
q
kinked.
Check that dryer is level. See “Level Dryer”.
q
Remove lm on console and any tape remaining on dryer.
q
Wipe dryer drum interior thoroughly with a damp cloth to
q
remove any dust.
Read “Dryer Use” in your Use and Care Guide.
q
For power supply cord installation, plug into a grounded
q
outlet. For direct wire installation, turn on Power.
If you live in a hard water area, use of a water softener is
q
recommended to control the buildup of scale through the
water system in the dryer. Over time, the buildup of lime
scale may clog different parts of the water system, which
will reduce product performance. Excessive scale buildup
may lead to the need for certain part replacement or repair.
Select a Time Dry heated cycle, and start dryer. Do not select
This dryer automatically runs an installation diagnostic routine
at the start of its rst cycle.
NOTE: You may notice an odor when dryer is rst heated. This
odor is common when heating element is rst used. The odor will
go away.
2.
Tighten and adjust leveling legs
TROUBLESHOOTING
See the Use and Care Guide for troubleshooting information.
If dryer is not level, prop up using a wood block, use wrench
to adjust legs up or down, and check again for levelness. Once
legs are level, make sure all four legs are snug against the ground
before tightening them.