We assumes no responsibility or liability for loss or damages, whether direct, indirect,
consequential or incidental, which might arise out of the use of such information. The use of
any such information will be entirely at the user’s risk. Information in this manual is subject to
change without notice. We make no commitment to update or keep current the information in
this manual. If you find information in this manual that is incorrect, misleading, or incomplete,
we would appreciate your comments and suggestions.
Table of Contents
1. SAFETY AND EMC INSTRUCTIONS ................................................................................................. 1
1-1.TRANSPORTATION AND STORAGE ............................................................................................................... 1
All safety instructions in this document must be read, understood and followed.
1-1. Transportation and Storage
Please transport the UPS system only in the original packaging to protect against shock and
damage.
The UPS must be stored in the room where the temperature is well regulated. Ambient
temperature should not exceed 40°C.
1-2. Preparation
Condensation may form if the UPS system is moved immediately from cold to warm environment.
The UPS system must be absolutely dry before being installed. Please allow at least two hours for
the UPS system to acclimate the environment.
Do not install the UPS system near water or in moist environments.
Do not install the UPS system where it would be exposed to direct sunlight or nearby heat source.
Do not block ventilation holes on the UPS housing.
1-3. Installation
Do not connect appliances or devices which would overload the UPS (e.g. big motor-type
equipment)) to the UPS output terminal.
Place cables in such a way that no one can step on or trip over them.
Do not block air vents on the housing of the UPS. Ensure proper unit spacing of ventilation.
UPS came equipped with grounding terminal, in the final installation phase, connect grounding/
earthing wire to the external UPS battery cabinets or appropriate grounding terminals.
The UPS can be installed only by qualified maintenance personnel.
An appropriate disconnect device such as short-circuit backup protection should be incorporated
during installation.
An integral emergency shutoff switch which prevents additional load from the UPS in any mode
of operation should be implemented during the installation.
Secure the grounding/earthing wire before connecting to any live wire terminal.
Installation and Wiring must be in accordance with the local electrical laws and regulations.
1
1-4. Connection Warnings
Main
Input
Input Rly
UPS
L1
L2
L3
N
Main
Input
Input Rly
UPS
L1
L2
L3
N
Bypass
Input
Input Rly
L1
L2
L3
N
Before working on this circuit
- Isolate Uninterruptible Power Supply (UPS)
- Then check for Hazardous Voltage between all terminals including the protected
earth
Risk of Voltage Backfeed
WARNING
HIGH LEAKAGE CURRENT
EARTH CONNECTION ESSENTIAL
BEFORE CONNECTING SUPPLY
•In accordance with safety standard, installation has to be provided with a《Backfeed Protection》 system,
as for example a contactor, which will prevent the appearance of voltage or dangerous energy in the
input mains during a mains fault. There is no standard backfeed protection inside of the UPS. However,
there are relays on the Input to cut off line voltage and while the neutral is still connect to UPS.
Input relay diagram Input relay diagram for dual-input model
There can be no derivation in the line that goes from the «Backfeed Protection» to the UPS, as
the standard safety would be infringed.
• Warning labels should be placed on all primary power switches installed in places away from the unit to
alert the electrical maintenance personnel of the presence of a UPS in the circuit. The label will bear the
following or an equivalent text:
• The power input for this unit must be three-phase rated in accordance with the equipment nameplate. It
also must be suitably grounded.
• This UPS should be connected with TN grounding/earthing system.
• Use of this equipment in medical instrument of any life-sustaining equipment where failure of this
equipment can reasonably be expected to cause the failure of the life-sustaining equipment or to
significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the
presence of a flammable mixture with air, oxygen or nitrous oxide.
• Connect grounding terminal of UPS to a grounding electrode conductor.
2
1-5. Operation
* Safety
UL 1778, CSA C22.2 No.107.3-14
* EMI
Conducted Emission...............................: FCC Part 15, Subpart B
Class A
Radiated Emission..................................: FCC Part 15, Subpart B
Class A
Do not disconnect the grounding/earthing conductor cable on the UPS or the building wiring
terminals under any circumstance.
The UPS system features its own, internal current source (batteries). The UPS output sockets or
output terminal blocks may be electrically live even if the UPS system is not connected to the building
mains/live wires. (only for standard models)
In order to fully disconnect the UPS system, first press the “OFF” button and then disconnect the
mains/live wires.
Ensure that no liquid or other foreign objects can enter into the UPS system.
The UPS can be operated by any individuals with no previous experience.
1-6. Standards
NOTE:
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial environment. This equipment generates, uses,
and can radiate radio frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in which case the user will be required to correct the
interference at his own expense.
3
2. Installation and Operation
We offer optional parallel function upon request. The UPS with parallel function is called the “Parallel model”.
We have detail installation and operation procedure of the Parallel Model in the following chapter.
2-1. Unpacking and Inspection
Unpack the package and check the package contents. The shipping package should contain:
● One UPS
● One user manual
● One monitoring software CD
● One RS-232 cable (option)
● One USB cable
● One parallel cable (only available for parallel model)
● One shared current cable (only available for parallel model)
NOTE: Before the installation, please inspect the unit. Be sure that there is no physical damage to the unit.
Do not turn on the unit and notify the carrier and dealer immediately if there is any damage or missing parts
and accessories. Please keep the original packaging for future use. It is recommended to keep each
equipment and battery set in their original packaging because they have been designed to provide maximum
protection during transportation and storage.
1. RS-232 communication port (only for firmware updates)
2. USB communication port
3. Emergency power off function connector (EPO connector)
4. Share current port (only available for parallel model)
5. Parallel port (only available for parallel model)
6. Intelligent slot
7. External battery connector (Only available for long-run model)
8. Line input circuit breaker/switch
5
9. Maintenance bypass switch
Model
Wiring spec (AWG)
Input(Ph)
Output(Ph)
Neutral
Ground
LV 15K(L) DUAL
6 6 6 6 LV 20K(L) DUAL
4 4 4
4
10. Input/Output terminal (Refer to diagram 3 for the details)
11. Line input terminal
12. Output terminal
13. Input grounding terminal
14. Output grounding terminal
15. Bypass input circuit breaker/switch
16. Bypass input terminal
17. Grounding terminal
18. Output circuit breaker
2-3. Single UPS Installation
Installation and wiring must be carried out in accordance with the local electric laws and regulations by
trained professionals.
1) Make sure that the mains wire and breakers of the building are rated for the capacity of the UPS to
prevent electric shock or risk of fire.
NOTE: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than
the UPS’s maximum input current. The receptacle may be damaged and destroyed.
2) Switch off the mains switch in the building before installation.
3) Turn off all the connected devices before connecting to the UPS.
4) Prepare wires based on the following table:
NOTE : The selections for color of wires should be followed by the local electrical laws and regulations.
5) Remove the terminal block cover at the rear panel of UPS. Then connect the wires according to the
following terminal block diagrams: (Connect the grounding/earthing wire first when making other wire
connections. Remove the grounding/earthing wire last when connecting the UPS!)
NOTE 1: Make sure that the wires are connected securely with the terminals.
NOTE 2: Please install the output breaker between the output terminal and the load, and the breaker
Terminal block wiring diagram
6
should have leakage current protective function if necessary.
6) Put the terminal block cover back at the rear panel of the UPS.
Warning: (Only for standard model)
● Make sure the UPS is off before the installation. The UPS should not be turned on during wiring
connection.
● Do not attempt to modify the standard model into the long-run model. In particular, do not try to
connect the standard internal battery to the external battery. The battery type and voltage may be
different, risk of electric shock or fire may occurred!
Warning: (Only for long-run model)
● Make sure a DC breaker or other protective device between UPS and the external battery pack is
installed for added safety. If not, please install it carefully. Switch off the battery breaker before
installation.
NOTE: Set the battery pack breaker in “OFF” position and then install the battery pack.
● Pay special attention to the rated battery voltage marked on the rear panel. If you want to change the
numbers of the battery in a chain, make sure you modify the UPS setting accordingly. Connection with
wrong battery voltage may cause irreversible damage of the UPS.
● Pay special attention to the polarity marking on external battery terminal block. Connection with wrong
battery voltage may cause irreversible damage of the UPS.
● Make sure the protective grounding/earthing wiring is adequate. The current spec, color, position,
connection and conductance reliability of the wire should be verified.
● Make sure the utility input & output wiring is rated correctly. The current spec, color, position, connection
and conductance reliability of the wire should be verified. Make sure the L/N side is correct, not reverse
or short-circuited.
2-4. UPS Installation for Parallel System
If the UPS is only for single operation, you may skip this section.
1) Install and wired the UPS according to the section 2-3.
2) Connect the output wires of each UPS to an output breaker.
3) Connect all output breakers to a centralize breaker. This centralize output breaker will then connect
directly to the loads.
4) Either common battery packs or independent battery packs for each UPS are allowed.
5) Refer to the following wiring diagram:
7
Wiring diagram of parallel system
2-5. Software Installation
For optimal computer system protection, install UPS monitoring software to configure UPS shutdown
operation.
8
3. Operation
LCD模組
Mode LED
Bypass
Line
Battery
Fault
UPS On
● ● ●
●
Standby mode
○ ○ ○
○
Bypass mode
●
○○○
Line mode
○ ● ○
○
Battery mode
○
○ ● ○
CVCF mode
○ ● ○
○
Battery Test
●●●
○
ECO mode
●
●
○
○
Fault
○○○
●
LED indicators
LCD panel
3-1. Initial Operation
1) Before operation, make sure that the two strings of batteries are connected correctly in order
of ”+,GND,-” terminals and the breaker of the battery pack is at “ON” position (only for long-run
model).
2) Press the “” button to set up the power supply for the UPS. UPS will enter to power on
mode. After initialization, UPS will enter to “No Output mode”.
3-2. LED Indicators and LCD Panel
LED Indicators:
There are 4 LEDs on front panel to show the UPS working status:
Note: ● means LED is lighting, and ○ means LED is faded.
3-3. Screen Description
After initialization, the LCD will display main screen. There are five sub-menus: Control, measure, setting,
information and data log. Touch any sub-menu icon to enter into the sub-screen.
9
MAINInitializing
CONTROL
DATA LOG
MEASURE
ON/OFF UPS
BATTERY TEST
MUTE ALL
MEASURE1
MEASURE2
MEASURE3
GENERAL
ADVANCE:
Maintainer
BASIC1
BASIC2
SETTING
INFO
ON/OFF CHARGER
ADVANCE:
User
DATALOG
PARAMETERS
CALIBRATION
EEPROM
TOUCH
SYS PARAMETER
PASSWORD:****
INSTALL INFO
VOL CALI
CURR CALI
INITIAL
ELECTRICAL
BATTERY
MISCELLANEOUS
UPS SELFTEST
ELECTRICAL
BATTERY
MISCELLANEOUS
PASSWORD:0000
PARAMETER INFO
RATED INFO
BASIC INFO
Menu tree
9672.07
3-3-1. Main screen
Upon powering on, the LCD will start initialization approximately few seconds as shown below.
After initialization, the main screen will display as shown below. On the bottom, there are five icons to
represent five sub-menus: CONTROL, MEASURE, SETTING, INFO, DATALOG.
10
DATALOG
INFOSETTING
MEASURECONTROLHOME
20KVA
Bypass Mode
120.0V
120.0V
120.0V
120.0V
120.0V
120.0V
60.0Hz
60.0Hz
19:52:36
2018-11-07
120.0V
120.0V
60.0Hz
120.0V
50%
125.0V
9AH
0%
DATALOG
INFOSETTING
MEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
ON/OFF UPS
BATT TEST
MUTE ALL
ON/OFF CHARGER
HOMECONTROL
ON/OFF UPS
MUTE ALL
Confirm YES Turn ON /OFF UPS
Confirm YES Do Battery Test
Confirm YES Do MUTE ALL
Enter No Or Back
Enter No Or Back
Enter No Or Back
ON/OFF CHARGER
BATTERY TEST
Confirm YES Turn ON/OFF CHARGER
Enter No Or Back
3-3-2. Control screen
Touch the icon to enter control sub-menu.
Touch icon to return back to main screen no matter it’s in any screen of any submenu.
On/Off UPS
It will show “Turn on UPS?” when UPS is off.
It will show “Turn off UPS?” when UPS is on.
Screen 1.0 «Control» and its sub-menus
11
Touch “YES” to turn on or off the UPS. Then, the screen will return to main screen.
DATALOG
INFOSETTING
MEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
ON/OFF UPS
BATT TEST
MUTE ALL
ON/OFF CHARGER
Turn On UPS?
YESNO
DATALOG
INFOSETTING
MEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
ON/OFF UPS
BATT TEST
MUTE ALL
ON/OFF CHARGER
Turn Off UPS?
YESNO
DATALOG
INFOSETTING
MEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
ON/OFF UPS
BATT TEST
MUTE ALL
ON/OFF CHARGER
BATT Test?
YESNO
DATALOG
INFOSETTING
MEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
ON/OFF UPS
BATT TEST
MUTE ALL
ON/OFF CHARGER
Cancel BATT Test?
YESNO
Touch “Back” to return to main screen immediately or “No” to cancel this operation and back to main
screen.
TURN ON UPS TURN OFF UPS
Battery Test
It will show “Battery Test” if the UPS is not in test. Touch “Yes” to start battery test. Then, it will show
“Battery testing……“ during battery test period. After few seconds, battery test result will show on the
screen. Touch “Back” to return to main screen immediately or “No” to cancel this operation and back to
main screen.
It will show “Cancel battery test” if the UPS is in test.
Battery Test Cancel Battery Test
Audio mute
It will show “Mute all” if the audio is active. Touch “Yes” to activate mute. If “Mute all” is active, it will
show icon on the top left corner of the main screen. Touch “Back” to return to CONTROL screen
immediately or “No” to cancel this operation and back to CONTROL screen.
It will show “Cancel mute” if the UPS is mute already. Touch “Yes” to activate audio function or “No”
keep mute. Touch “Back” to return to CONTROL screen.
12
DATALOG
INFOSETTING
MEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
ON/OFF UPS
BATT TEST
MUTE ALL
ON/OFF CHARGER
Mute All?
YESNO
DATALOG
INFOSETTING
MEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
ON/OFF UPS
BATT TEST
MUTE ALL
ON/OFF CHARGER
Cancel Mute All?
YESNO
DATALOG
INFOSETTING
MEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
ON/OFF UPS
BATT TEST
MUTE ALL
ON/OFF CHARGER
Turn On Charger?
YESNO
DATALOG
INFOSETTING
MEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
ON/OFF UPS
BATT TEST
MUTE ALL
ON/OFF CHARGER
Turn Off Charger?
YESNO
DATALOG
INFOSETTING
MEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
LINE VOLINVERTER VOLBYPASS VOLOUTPUT VOL
L1:
L2:
L3:
L12:
L23:
L13:
60.0Hz
120.0V
120.0V
120.0V
207.8V
207.8V
207.8V
120.0V
120.0V
120.0V
207.8V
207.8V
207.8V
60.0Hz
120.0V
120.0V
120.0V
207.8V
207.8V
207.8V
60.0Hz
0.3V
0.3V
0.3V
0.4V
0.4V
0.4V
0.0Hz
Mute All Cancel Mute all
On/Off CHARGER
It will show “Turn on Charger?” when Charger is off.
It will show “Turn off Charger?” when Charger is on.
Touch “YES” to turn on or off the Charger. Then, the screen will return to main screen.
Touch “Back” to return to CONTROL screen immediately or “No” to cancel this operation and back to
CONTROL screen.
TURN ON CHARGER TURN OFF CHARGER
3-3-3. Measure screen
Touch the icon to enter measure page. Touch the icon or to browse information.
Touch the icon to return to main screen. Touch the icon to go back to previous menu.
LINE VOL: The real time value of L1, L2, and L3 phase voltage, input power in VA and input frequency.
INVERTER VOL: The real time value of L1, L2 and L3 inverter voltage and frequency.
BYPASS VOL: The real time value of L1, L2 and L3 bypass voltage and frequency.
Measure screen page 1
13
OUTPUT VOL: The real time value of L1, L2 and L3 output voltage and frequency.
DATALOG
INFOSETTING
MEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
OUTPUT WOUTPUT VABATT P VOL125.0V
L1:
L2:
L3:
TOTAL W(%)
4W
5W
1W
0%
0%
0%
BUS P VOL
BUS N VOL
CHARG CURR
DISCHG CURR
TEMP L1
125.0V
231.3V
229.5V
3.9A
0.0A
27
46VA
46VA
46VA
0%
0%
0%
TOTAL VA(%)
OUTPUT W(%)
OUTPUT VA(%)
L1:
L2:
L3:
0%
0%
BATT N VOL
TEMP L2
TEMP L3
27
27
DATALOG
INFOSETTING
MEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
INPUT WINPUT VAINPUT CURRINPUT PF
L1:
L2:
L3:
TOTAL W(%)
4W
4W
4W
0%
0%
0%
L2: 0.3A
L3: 0.3A
OUTPUT CURR
L1: 0.3A
0.08
0.08
0.08
OUTPUT PF
0.08
46VA
46VA
46VA
0%
0%
0%
TOTAL VA(%)
INPUT W(%)
INPUT VA(%)
L1:
L2:
L3:
0%
0%
L1: 0.3A
L2: 0.3A
L3: 0.3A
0.08
0.08
Measure screen page 2
OUTPUT W: L1, L2 and L3 output power in watt.
OUTPUT VA: L1, L2 and L3 output power in VA.
OUTPUT W (%):L1, L2 and L3 output power watt in percentage.
OUTPUT VA (%):L1, L2 and L3 output power VA in percentage.
Total watt and VA: Total output load in watt and VA.
BATT Voltage/Bus Voltage/Charging Current/Discharging Current: The real time value of DC related
information.
Temperature: Temperature of L1, L2 and L3 phases.
Measure screen page 3
Input current: The real-time value of input current in L1/L2/L3 and L12/L23/L13.
Output current: The real-time value of output current in L1/L2/L3 and L12/L23/L13.
3-3-4. Setting screen
This sub-menu is used to set the parameters of UPS. Touch the icon to enter setting menu page.
There are 2 options: Basic and Advanced. Touch the icon to return to main screen. Touch the icon
to go back to previous menu.
NOTE: Not all settings are available in every operation mode. If the setting is not available in present mode,
the LCD will keep its original setting parameter showed instead of changing the parameters.
14
DATALOGINFOSETTINGMEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
GENERAL
ADVANCE
UPS operation
Mode
Setting item
Standby
Mode
Bypass
Mode
Line
Mode
Battery
Mode
Battery
Test
Mode
Fault
Mode
Converter
Mode
ECO
Mode
Authorization
No Password
User
Maintainer
GENERAL
Date/Time
Y Y Y Y Y Y Y Y Y
Language
Y Y Y Y Y Y Y Y Y
Input Source
Y Y Y
Contact
Y Y Y Y Y Y Y Y Y
Phone
Y Y Y Y Y Y Y Y Y
Mail
Y Y Y Y Y Y Y Y Y
Audible Alarm
Y Y Y Y Y Y Y Y Y
ADVANCE
Output Voltage
Y Y Y Y
Output Frequency
Y Y Y Y
CVCF Mode
Y Y Y Y
Bypass Forbid
Y Y Y Y Y Y Y Y Y
Bypass Mode
Y Y Y Y Y Y Y Y Y
Bypass Voltage
Range
Y Y Y Y
Bypass Frequency
Range
Y Y Y Y
ECO Mode
Y Y Y Y
ECO Voltage
Range
Y Y Y Y
ECO Frequency
Range
Y Y Y Y
Battery
Warning
Voltage
Y Y Y Y Y Y Y Y Y
Shutdown
Voltage
Y Y Y Y Y Y Y Y Y
Age Alert
Y Y Y Y Y Y Y Y Y
Capacity in Ah
Y Y Y Y Y Y Y Y Y
Auto-Restart
(this function is
reserved for
future)
Y Y Y Y Y Y Y Y Y Y
System Shutdown
Time
Y Y Y Y Y Y Y Y Y Y
Setting screen
GENERAL: It’s to set up basic information of the UPS. It’s not related to any function parameter.
ADVANCE: It’s required to enter password to access to the “ADVANCE” setting. There are two types of
authority, User and Maintainer.
The authority list:
15
System Restore
Time
Y Y Y Y Y Y Y Y Y Y
Password setting
Y Y Y Y Y Y Y Y Y Y
Default User
password
Y Y Y Y Y Y Y Y Y
Model Name
Y Y Y Y Y Y Y Y Y
Serial Number
Y Y Y Y Y Y Y Y Y
Manufacturer
Y Y Y Y Y Y Y Y Y
Max charging
current
Y Y Y Y Y Y Y Y
Battery Number
Y Y Y Y Y Y Y Y
Charge Voltage
Y Y Y Y Y Y Y Y
Charger Number
Y Y Y Y Y Y Y Y
System Install
Date
Y Y Y Y Y Y Y Y Y
Battery Install
Date
Y Y Y Y Y Y Y Y Y
Voltage Calibration
Y Y Y
Current Calibration
Y Y Y Y
Clean Data log
Y Y Y Y Y Y Y Y Y
Reset parameters
Y Y Y
Reset Calibration
Y Y Y
Reset EEPROM
Y Y Y
Touch Calibration
Y Y Y Y Y Y Y Y Y
UPS Selftest
Y Y
“Y” meansthat this setting item can be set in this operation mode.
DATALOGINFOSETTINGMEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
GENERAL
ADVANCE
Date/Time
Language
Input Source
Contact
Phone
Mail
English
Line
0
0
0
2018-11-08 15:47:30
GENERAL
General screen page 1
Date/Time: Set the date and time. The format is YYYY-MM-DD HH:MM:SS. The calendar day will be
automatically changed when the year, month and date are set.
Language: Set the LCD language. Only English is available.
Input Source: Select the input source. There are two options: Line (utility) and generator. Line is
default setting. This setting value will show on the main page. When “generator” is selected, the
acceptable input frequency will be fixed at the range of 40~75Hz. This setting value will show on the
status bar.
Service Contact: Set the name of contact person and the maximum length is 18 characters.
Service Phone: Set the service phone number. Only 0~9, + and – are accepted. The maximum length
is 14 characters.
16
Service Mail: Set the service email accounts up to two and the maximum length is 36 characters.
DATALOGINFOSETTINGMEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
GENERAL
ADVANCE
Audio Alarm
All Mute
Mode Mute
Disable
Disable
DATALOGINFOSETTINGMEASURECONTROL
HOME
20KVA
Bypass Mode
19:52:36
2018-11-07
GENERAL
ADVANCE
PASSWORD
Password remain timeMins
0
General screen page 2
Audio Alarm: There are two events available to mute. You may choose “Enable” or “Disable” alarm
when related events occur.
Enable: When selected, alarm will be mute when related events occur.
Disable: When selected, UPS will alarm when related events occur.
All Mute: When “enable” is selected, all the faults and warnings will be mute. It will show
icon on the top right corner of the main screen.
Mode Mute: UPS status mode alarm enable/disable. If “Mode Mute” is activated, it will show
icon on the top right corner of the main screen.
ADVANCE
Advance Password Page
It’s required to enter password (4 digits) to access to the “ADVANCE” page.
ADVANCE User
To access to the “AdvanceUser” Setting menu page, the default password is “0000”.
If entered password is right, the page will jump to setting screen. If the password is wrong, it will ask to
enter again.
17
DATALOGINFOSETTINGMEASURE
CONTROL
HOME
20KVA
Bypass Mode
19:52:36
2018-11-07
GENERAL
ADVANCE
PASSWORD
Password Error!!
DATALOG
INFOSETTINGMEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
ELECTRONIC
BATTERY
MISCELLANEOUS
DATALOGINFOSETTINGMEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
ELECTRONIC
BATTERY
MISCELLANEOUS
OUTPUT VOL
OUTPUT FRE
CVCF Mode
Bypass Forbid
120V
60Hz
Disable
Disable
Password error page
Advance Setting Menu Page
There are three sub-menus under “AdvanceUser” setting: ELECTRONIC, BATTERY and MISCELLANEOUS.
ELECTRICAL
Electrical Setting Page 1
Output Voltage: Select the output rated voltage.
There are two options, 120V and 127V. 120Vac is default setting.
50Hz: The output frequency is setting for 50Hz.
60Hz: The output frequency is setting for 60Hz.
CVCF Mode (constant voltage and constant frequency function)
Enable: CVCF function is enabled. The output frequency will be fixed at 50Hz or 60Hz according to
setting of “OP Freq.”. The input frequency could be from 40Hz to 70Hz.
Disable: CVCF function is disabled. The output frequency will synchronize with the bypass
frequency within 45~55 Hz for 50Hz system or within 55~65 Hz for 60Hz system. Disable is the
18
default setting.
DATALOGINFOSETTINGMEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
ELECTRONIC
BATTERY
MISCELLANEOUS
Bypass UPS Off
Bypass VOL Range
Bypass FRE Range
ECO Mode
96V
Enable
Disable
ECO VOL Range
ECO FRE Range
146V
64.0Hz56.0Hz
115V125V
58Hz62Hz
Bypass Forbid:
Allow: Bypass allowed. When selected, UPS will run in Bypass mode depending on “Byp.at off”
setting. It is the default setting.
Forbid: Bypass is not allowed. When selected, it’s not allowed for running in Bypass mode under
any situations.
Electrical Setting Page 2
Bypass at UPS off: Select the bypass status when manually turning off the UPS. This setting is only
available when “Bypass forbid.” is set to “Disable”.
Enable: Bypass enabled. When selected, bypass mode is activated.
Disable: Bypass disabled. When selected, no output through bypass when manually turning off
the UPS.
Bypass Voltage Range: Set the bypass voltage range.
L: Low voltage point for bypass. The setting range is 96V ~ 110V. 96V is default setting.
H: High voltage point for bypass. The setting range is 130V ~ 146V. 146V is default setting.
Bypass FRE Range: Set the bypass frequency range.
The acceptable bypass frequency range from 46Hz to 54Hz when UPS is 50Hz system and from 56Hz to
64Hz when UPS is 60Hz system.
ECO mode: Enable/Disable ECO mode. Default setting is “Disable”.
ECO Voltage Range: Set the ECO voltage range.
L: Low voltage point for ECO mode. The setting range is from “Rated output voltage – 5V” to
“Rated output voltage - 11V”. “Rated output voltage – 5V” is default setting.
H: High voltage point for ECO mode. The setting range is from “Rated output voltage + 5V” to
“Rated output voltage + 11V”. “Rated output voltage + 5V” is default setting.
ECO FRE Range: Set the ECO frequency range. The setting range is from 46Hz to 54Hz when the UPS
is 50Hz system and from 56Hz to 64Hz when the UPS is 60Hz system.
19
BATTERY
DATALOG
INFOSETTING
MEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
ELECTRONIC
BATTERY
MISCELLANEOUS
BATT Warning VOL
Shutdown VOL
BATT Age
BATT Parameters
10.7V
14.4V
BATT AH
HIGH
LOW
24
9
11.5V
DATALOGINFOSETTINGMEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
ELECTRONIC
BATTERY
MISCELLANEOUS
Auto Restart
Shutdown Delay
Restore Delay
New Password
0min
Enable
0min
****
Battery setting page
Battery Warning Voltage:
HIGH: High battery warning voltage. The setting range is 14.0V ~ 15.0V. 14.4V is default setting.
LOW: Low battery warning voltage. The setting range is 10.1V ~ 14.0V. 11.4V is default setting.
This parameter setting is related to “Shutdown Voltage” setting. This setting value should be
higher than “Shutdown Voltage” setting.
Shutdown Voltage: If battery voltage is lower than this point in battery mode, UPS will automatically
shut down. The setting range is 10.0V ~ 12.0V. 10.7V is default setting. (The setting is only available
for long-run model)
Battery Parameter:
Battery AH: setting battery capacity. 9Ah is default setting.
MISCELLANEOUS
Auto Restart: (This function is reserved for future use)
Shutdown Delay Min: UPS will shut down in setting minutes. The countdown will start after confirming
Restore Delay Min: UPS will automatically restart in setting minutes after the UPS shuts down.
Miscellaneous setting page
Enable: After “Enable” is set, once UPS shutdown occurs due to low battery and then utility
restores, the UPS will return to line mode.
Disable: After “Disable” is set, once UPS shutdown occurs and the utility restores, the UPS will
not automatically turn on.
the pop-up screen.
20
New Password: Set up new password to enter “ADVANCEUser” menu.
DATALOG
INFOSETTING
MEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
SYS PARAMETER
INSTALL INFO
VOL CALI
CURR CALI
INITIAL
DATALOGINFOSETTINGMEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
ELECTRONIC
BATT
MISCELLANEOUS
UPS SELFTEST
DATALOGINFOSETTINGMEASURECONTROLHOME
20KVA
StanbyMode
19:52:36
2018-11-07
SYS PARAMETER
INSTALL INFO
VOL CALI
CURR CALI
85211810100018000
----------------
Mode Name
INITIAL
Serial Number
10
13.6V
12A
Manufacturer
Charge MaxCURR
BATT Number
Charge VOL
ADVANCE Maintainer
Advance: Maintainer Setting Menu Page1
To access the “AdvanceMaintainer” Setting menu page, it’s required to enter password. Please contact
your local dealer to get maintainer password.
CAUTION: This setting menu is only for qualified technician. Otherwise, mis-operation will cause UPS
damage.
There are five sub-menus under “AdvanceMaintainer” setting: SYS PARAMETER, INSTALL INFO, VOL CALI,
CURR CALI, INITIAL, ELECTRONIC, BATT, MISCELLANEOUS and UPS SELFTEST.
SYS PARAMETER
Advance: Maintainer Setting Menu Page2
SYS PARAMETER Page1
21
Mode Name: Set the UPS model name.
DATALOGINFOSETTINGMEASURECONTROLHOME
20KVA
StanbyMode
19:52:36
2018-11-07
SYS PARAMETER
INSTALL INFO
VOL CALI
CURR CALI
LV
Charger Number
INITIAL
UPS Type
3PCS
DATALOGINFOSETTINGMEASURECONTROLHOME
20KVA
StanbyMode
19:52:36
2018-11-07
SYS PARAMETER
INSTALL INFO
VOL CALI
CURR CALI
20181
SYS Install Date
INITIAL
BAT Install Date
201811
1
Serial Number: Set the serial number.
Manufacturer: Set the UPS manufacturer.
Charge MaxCURR: The maximum of battery charging current. This parameter setting is related to
“Charger Number” setting (check next page for the details).
One piece of charger: There are four options, 1A, 2A, 3A, 4A. 4A is default setting.
Two pieces of charger: There are two options, 4A, 8A. 8A is default setting.
Three pieces of charger: There are three options, 4A, 8A, 12A. 12A is default setting.
BATT Number: The total number of installed battery. (It should be restart UPS after setting.) The setting
range is 8 ~ 10. 10 is default setting.
Charge VOL: The setting point of battery float voltage. 13.6V is default setting.
SYS PARAMETER Page 2
Charger Number: The number of charging boards installed on the UPS.
NOTE:It’s required to restart the UPS after setting.
One piece of charger: When selected, there are four options available for “Charger MaxCURR”.
Two pieces of charger: When selected, there are two options available for “Charger MaxCURR”.
Three pieces of charger: When selected, there are three options available for “Charger
MaxCURR”.
UPS Type: There are two options, HV and LV. This change is only allowed for qualified technician.
NOTE: It’s required to restart the UPS after setting.
INSTALL INFO
SYS Install Date: Set the date of UPS installation.
BAT Install Date: Set the date of Battery installation.
INSTALL INFO Page
22
VOL CALI
DATALOGINFOSETTINGMEASURECONTROLHOME
20KVA
StanbyMode
19:52:36
2018-11-07
SYS PARAMETER
INSTALL INFO
VOL CALI
CURR CALI
231.3V
229.5V
Bus VOL
INITIAL
P
7.9V
6.2V
0.0%N
BATT VOL
P
N
0.0%
0.0%
0.0%
DATALOGINFOSETTINGMEASURECONTROLHOME
20KVA
StanbyMode
19:52:36
2018-11-07
SYS PARAMETER
INSTALL INFO
VOL CALI
CURR CALI
120.0V
120.0V
Line VOL
INITIAL
R
120.0V
120.0V
0.0%S
Output VOL
R
S
0.0%
0.0%
0.0%
T
T
0.0%
0.0%
120.0V
120.0V
VOL CALI Page1
Bus VOL: BUS voltage calibration. Increment of each click is 0.1% no matter it’s pressing up or down key
. Press “up” key to increase 0.1% and press “down” key to decrease 0.1%. Press “OK” key to confirm
the modification.
BATT VOL: Battery voltage calibration. Increment of each click is 0.1% no matter it’s pressing up or down
key . Press “up” key to increase 0.1% and press “down” key to decrease 0.1%. Press “OK” key to
confirm the modification.
VOL CALI Page2
Line VOL: Line voltage calibration. Increment of each click is 0.1% no matter it’s pressing up or down key
. Press “up” key to increase 0.1% and press “down” key to decrease 0.1%. Press “OK” key to confirm
the modification.
Output VOL: Output voltage calibration. Increment of each click is 0.1% no matter it’s pressing up or
down key . Press “up” key to increase 0.1% and press “down” key to decrease 0.1%. Press “OK” key to
confirm the modification.
23
DATALOGINFOSETTINGMEASURECONTROLHOME
20KVA
StanbyMode
19:52:36
2018-11-07
SYS PARAMETER
INSTALL INFO
VOL CALI
CURR CALI
0.0V
0.0V
Inverter VOL
INITIAL
R
120.0V
120.0V
0.0%
T
Bypass VOL
R
S
0.0%
0.0%
0.0%
S
T
0.0%
0.0%
0.0V
120.0V
DATALOGINFOSETTINGMEASURECONTROLHOME
20KVA
StanbyMode
19:52:36
2018-11-07
SYS PARAMETER
INSTALL INFO
VOL CALI
CURR CALI
0.0A
0.0%
Output CURR
S
T
INITIAL
R
0.0A
0.0A
0.0%
0.0%
VOL CALI Page3
Inverter VOL: Inverter voltage calibration. Increment of each click is 0.1% no matter it’s pressing up or
down key . Press “up” key to increase 0.1% and press “down” key to decrease 0.1%. Press “OK” key to
confirm the modification.
Bypass VOL: Bypass voltage calibration. Increment of each click is 0.1% no matter it’s pressing up or
down key . Press “up” key to increase 0.1% and press “down” key to decrease 0.1%. Press “OK” key to
confirm the modification.
CURR CALI
CURR CALI Page
Output CURR: Output current calibration. Increment of each click is 0.1% no matter it’s pressing up or
down key . Press “up” key to increase 0.1% and press “down” key to decrease 0.1%. Press “OK” key to
confirm the modification.
24
INITIAL
DATALOGINFOSETTINGMEASURECONTROLHOME
20KVA
StanbyMode
19:52:36
2018-11-07
SYS PARAMETER
INSTALL INFO
VOL CALI
CURR CALI
DATA LOG
INITIAL
PARAMETERS
EEPROM
TOUCH CALI
CALI
DATALOGINFOSETTINGMEASURECONTROLHOME
20KVA
StanbyMode
19:52:36
2018-11-07
SYS PARAMETER
INSTALL INFO
VOL CALI
CURR CALI
DATA LOG
INITIAL
PARAMETERS
EEPROM
TOUCH CALI
CALI
Initial the Datalog?
YES
NO
DATALOGINFOSETTINGMEASURECONTROLHOME
20KVA
StanbyMode
19:52:36
2018-11-07
SYS PARAMETER
INSTALL INFO
VOL CALI
CURR CALI
DATA LOG
INITIAL
PARAMETERS
EEPROM
TOUCH CALI
CALI
Initial the Parameters?
YES
NO
INITIAL menu Page
INITIAL DATALOG Page
DATALOG: After pressing, the confirmation window will pop up as shown in above screen. Touch “YES”
to clean the DATALOG page. Touch “Back” or “No” to cancel this operation and back to INITIAL menu
page。
INITIAL PARAMETERS Page
PARAMETERS: Touch “YES” to restore default value. Touch “Back” or “No” to cancel this operation and
back to INITIAL menu page.
25
DATALOGINFOSETTINGMEASURECONTROLHOME
20KVA
StanbyMode
19:52:36
2018-11-07
SYS PARAMETER
INSTALL INFO
VOL CALI
CURR CALI
DATA LOG
INITIAL
PARAMETERS
EEPROM
TOUCH CALI
CALI
Initial the CALI?
YES
NO
DATALOGINFOSETTINGMEASURECONTROLHOME
20KVA
StanbyMode
19:52:36
2018-11-07
SYS PARAMETER
INSTALL INFO
VOL CALI
CURR CALI
DATA LOG
INITIAL
PARAMETERS
EEPROM
TOUCH CALI
CALI
Initial the EEPROM?
YES
NO
+
INITIAL CALI Page
CALI: After pressing, the confirmation window will pop up. Touch “YES” to restore default calibration
value. Touch “Back”or “No” to cancel this operation and back to INITIAL menu page.
INITIAL EEPROM Page
EEPROM: Touch “YES” to clean all setting value in EEPROM. Touch “Back”or “No” to cancel this
operation and back to INITIAL menu page.
INITIAL TOUCH Page
TOUCH CALI: Touch screen to recalibrate. Then, the blue screen appears and please click on the place
of the cross with your mouse.
26
ELECTRICAL
DATALOGINFOSETTINGMEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
ELECTRONIC
BATTERY
MISCELLANEOUS
OUTPUT VOL
OUTPUT FRE
CVCF Mode
Bypass Forbid
120V
60Hz
Disable
Disable
UPS SELFTEST
DATALOGINFOSETTINGMEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
ELECTRONIC
BATTERY
MISCELLANEOUS
Bypass UPS Off
Bypass VOL Range
Bypass FRE Range
ECO Mode
96V
Enable
Disable
ECO VOL Range
ECO FRE Range
146V
64.0Hz56.0Hz
115V125V
58Hz62Hz
UPS SELFTEST
Electrical Setting Page 1
Output Voltage: Select the output rated voltage.
There are two options, 120V and 127V. 120Vac is default setting.
50Hz: The output frequency is setting for 50Hz.
60Hz: The output frequency is setting for 60Hz.
CVCF Mode (constant voltage and constant frequency function)
Enable: CVCF function is enabled. The output frequency will be fixed at 50Hz or 60Hz according to
setting of “Output Freq.”. The input frequency could be from 40Hz to 70Hz.
Disable: CVCF function is disabled. The output frequency will synchronize with the bypass
frequency within 45~55 Hz for 50Hz system or within 55~65 Hz for 60Hz system. Disable is the
default setting.
Bypass Forbid:
Enable: Bypass Forbid is enabled. It’s not allowed for running in Bypass mode under any
situations.
Disable: Bypass Forbid is disabled. UPS will run in Bypass mode. It is the default setting.
Electrical Setting Page 2
Bypass at UPS off: Select the bypass status when manually turning off the UPS. This setting is only
Bypass Voltage Range: Set the bypass voltage range.
available when “Bypass forbid” is set to “Disable”.
Enable: Bypass enabled. When selected, bypass mode is activated.
Disable: Bypass disabled. When selected, no output through bypass when manually turning off
the UPS.
L: Low voltage point for bypass. The setting range is 96V ~ 110V. 96V is default setting.
27
H: High voltage point for bypass. The setting range is 130V ~ 146V. 146V is default setting.
DATALOG
INFOSETTING
MEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
ELECTRONIC
BATTERY
MISCELLANEOUS
BATT Warning VOL
Shutdown VOL
BATT Age
BATT Parameters
10.7V
14.4V
BATT AH
HIGH
LOW
24
9
11.5V
UPS SELFTEST
DATALOGINFOSETTINGMEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
ELECTRONIC
BATTERY
MISCELLANEOUS
Auto Restart
Shutdown Delay
Restore Delay
New Password
0min
Enable
0min
****
DefaultUserPassword NO
UPS SELFTEST
Bypass FRE Range: Set the bypass frequency range.
The acceptable bypass frequency range from 46Hz to 54Hz when UPS is 50Hz system and from 56Hz to
64Hz when UPS is 60Hz system.
ECO mode: Enable/Disable ECO mode. Default setting is “Disable”.
ECO Voltage Range: Set the ECO voltage range.
L: Low voltage point for ECO mode. The setting range is from “Rated output voltage – 5V” to
“Rated output voltage - 11V”. “Rated output voltage – 5V” is default setting.
H: High voltage point for ECO mode. The setting range is from “Rated output voltage + 5V” to
“Rated output voltage + 11V”. “Rated output voltage + 5V” is default setting.
ECO FRE Range: Set the ECO frequency range. The setting range is from 48Hz to 52Hz when the UPS
is 50Hz system and from 58Hz to 62Hz when the UPS is 60Hz system.
BATTERY
Battery Warning Voltage:
Shutdown Voltage: If battery voltage is lower than this point in battery mode, UPS will automatically
Battery Parameter:
MISCELLANEOUS
Battery setting page
HIGH: High battery warning voltage. The setting range is 14.0V ~ 15.0V. 14.4V is default setting.
LOW: Low battery warning voltage. The setting range is 10.8V ~ 12.7V. 10.1V ~ 14.0V. 11.4V is
default setting. This parameter setting is related to “Shutdown Voltage” setting. The setting value
should be higher than “Shutdown Voltage” setting.
shut down. The setting range is 10.0V ~ 12.0V. 10.7V is default setting (The setting is only available for
long-run model)
Battery AH: setting battery capacity. 9Ah is default setting.
Miscellaneous setting page
28
Auto Restart:
unknown
R-Phase
PFC Test Step:
00
INV Test Step:
S-Phase
T-Phase
unknown
unknown
unknown
unknown
unknown
R-Phase
S-Phase
T-Phase
Enable: After “Enable” is set, once UPS shutdown occurs due to low battery and then utility
restores, the UPS will return to line mode.
Disable: After “Disable” is set, once UPS shutdown occurs and the utility restores, the UPS will
not automatically turn on.
Shutdown Delay Min: UPS will shut down in setting minutes. The countdown will start after confirming
the pop-up screen.
Restore Delay Min: UPS will automatically restart in setting minutes after the UPS shuts down.
New Password: Set up User new password to enter ADVANCE User?? menu page.
DefaultUserPassword:
YES: After “YES” is set, User password will restore default setting value.
NO: After “NO” is set, the UPS will cancel this operation.
UPS SELFTEST
This function is only effective when UPS type setting is “HV”. Therefore, please disconnect all loads and
utility first before executing this function. Then, please change UPS type to “HV”. For the detailed operation,
please check “System Parameter” menu under Advance Maintainer directory.
After changing UPS type to “HV”, you have to restart the UPS. After the UPS is restarted, please enter
Advance screen and enter Maintainer password. It will show “UPS SELFTEST” selection in the screen. In the
screen, all tested items are shown “unknown”. Simply click “UPS SELFTEST” button, the UPS will start
self-test. If the UPS is normal, it will show “Normal” in all columns. Otherwise, “Unknown” will be displayed
in the columns.
29
3-3-5. Information screen
DATALOGINFOSETTINGMEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
BASIC
RATED
PARAMETER
MCU Version
DSP Version
Serial NO.
Manufacturer
9666.04
9673.03
0
-----------------------
Service Contact
Service Phone
Service Mail
INV:
PFC:
9667.06
-----------------------
-----------------------
-----------------------
COMM:LCD: 9672.07
DATALOGINFOSETTINGMEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
BASIC
RATED
PARAMETER
Output VOL
Output FRE
CVCF Mode
Bypass Forbid
60Hz
120V
Disable
Bypass UPS Off
Auto Restart
ECO Mode
Disable
Enable
Enable
Disable
Touch the icon to enter information page. Touch the icon or to browse information.
Touch the icon to return to main screen. Touch the icon to go back to previous menu.
Basic Information Page
Basic Information
MCU Version: MCU version.
DSP Version: DSP version.
Serial NO.: The serial number of UPS.
Manufacturer: The information about manufacturer.
Service Contact: The contact name is set in “Basic Setting”.
Service Phone: The listed numbers are set in “Basic Setting”.
Service Mail: The service email account is set in “Basic Setting”.
Rated Information Page
Rated Information
Output Voltage: It shows output rated voltage.
Output FRE: It shows output rated frequency.
CVCF Mode: Enable/Disable CVCF mode.
Bypass Forbid: Enable/disable bypass function.
Bypass UPS Off: Enable/disable auto bypass function when UPS is off.
Auto Restart: Enable/disable auto-restart function.
ECO Mode: Enable/disable ECO function.
30
DATALOGINFOSETTINGMEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
BASIC
RATED
PARAMETER
Line VOL Range
Line FRE Range
Bypass VOL Range
Bypass FRE Range
56.0Hz
80V
96V
ECO VOL Range
ECO FRE Range
56.0Hz
115V
58.0Hz
156V
64.0Hz
146V
64.0Hz
125V
62.0Hz
Parameter Information Page 1
DATALOG
INFOSETTING
MEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
BASIC
RATED
PARAMETER
BATTMode Work Time
BATT Warning VOLHIGH
Shutdown VOL
990Min
Shutdown Delay
Restore Delay
10.7V
0min
0min
14.4V
11.5V
10
LOW
BATT Number
Parameter Information
Line Voltage Range: The acceptable line input voltage range.
Line FRE Range: The acceptable line input frequency range.
Bypass Voltage Range: The acceptable input voltage range for bypass mode.
Bypass FRE Range: The acceptable input frequency range for bypass mode.
ECO Voltage Range: The acceptable input voltage range for ECO mode.
ECO FRE Range: The acceptable input frequency range for ECO mode.
Parameter Information Page 2
BATT Mode Work Time: The maximum discharge time in battery mode.
BATT Warning Voltage:
HIGH: High battery warning voltage.
LOW: Low battery warning voltage.
Shutdown Voltage: If battery voltage is lower this point, UPS will automatically shut down.
Shutdown Delay: UPS will shut down in setting minutes. The countdown will start after confirming the
pop-up screen.
Restore Delay: UPS will automatically restart in setting minutes after the UPS shuts down.
Battery Number: It shows battery number.
3-3-6. Data Log screen
Touch the icon to enter date log page. Data log is used to record the warning and fault information of
the UPS. The record contains date & time, code, type and description. Touch the icon or to
page up or down if there are more than one page in the date log. Touch the icon to return to main
screen. Press the icon to go back to main menu. Please refer to Section 3-7 and 3-8 for warning and
31
fault code list.
DATALOG
INFOSETTING
MEASURECONTROLHOME
20KVA
Bypass Mode
19:52:36
2018-11-07
Date TimeDescription
2018/11/8
2018/11/8
17:02:30
TYPE
Bypass Mode
Mode
01
02
17:02:30
CODE
Mode Standby Mode
Description
Buzzer status
Muted
UPS status
Bypass mode
Beeping once every 2 minutes
Yes
Battery mode
Beeping once every 4 seconds
Fault mode
Beeping continuously
Warning
Overload
Beeping twice every second
No
Others
Beeping once every second
Fault
All
Beeping continuously
Yes
3-4. Audible Alarm
Data Log Page
3-5. Single UPS Operation
1. Turn on the UPS with utility power (in AC mode)
1) After power mains is connected correctly, set the breaker of the battery pack to “ON” position (this
step only necessary for long-run model). Then set the line input breaker to “ON” position. At the
same time the fan will start running and the UPS will start initialization. In just a few seconds, the
UPS will supply power to the loads via the Bypass mode.
NOTE: When UPS is in Bypass mode, the output voltage will be directed from mains after you switch
on the input breaker. In Bypass mode, the load is not protected by the UPS. To protect your precious
devices, you should turn on the UPS. Refer to next step.
2) Touch “CONTROL” and select “UPS on/off” icon. It will show “Turn on UPS?” in screen and select “Yes”. Refer to On/Off UPS screen.
3) In just a few seconds, the UPS will enter into AC mode. If the mains is abnormal, the UPS will
operate in Battery mode without interruption.
NOTE: When the UPS runs out battery, it will shut down automatically in Battery mode. When the mains
2. Turn on the UPS without utility power supply (in Battery mode)
is normalized, the UPS will auto restart in AC mode.
1) Make sure that the two strings of batteries are connected correctly in order of ”+,GND,-” terminals
and the breaker of the battery pack is at “ON” position (only for long-run model).
2) Press the “” button to set up the power supply for the UPS. UPS will enter to power on mode. After initialization, UPS will enter to “No Output mode”.
3) In just a few seconds, the UPS will be turned on and enter into Battery mode.
32
3. Connect devices to UPS
After the UPS is turned on, you can connect devices to the UPS.
1) Turn on the UPS first and then switch on the devices one by one. The LCD panel will display total
load level.
2) If it is necessary to connect the inductive loads such as a printer, the in-rush current of the load
should be calculated carefully to see if it meets the overload capability of the UPS. Any load more
than 150% over designed capacity the runtime will be less than 60ms
3) If the UPS is overload, the buzzer will beep twice every second.
4) When the UPS is overload, please remove some loads immediately. It is recommended to have the
total loads connected to the UPS less than 80% of its nominal power capacity to prevent overload
for system safety.
5) If the overload time is over acceptable time listed in spec in AC mode, the UPS will automatically
transfer to Bypass mode. After the overloading was resolved, it will return back to AC mode. If the
overload time is over acceptable time listed in spec in Battery mode, the UPS will enter fault status.
At this time, if bypass is enabled, the UPS will power to the load via bypass. If bypass function is
disabled or the input power is not within bypass acceptable range, it will cut off output entirely.
4. Charge the batteries
1) After the UPS is connected to the mains and turned on in AC mode, the charger will charge the
batteries automatically except in battery mode, during battery self-test, overload or when battery
voltage is high.
2) It’s recommended to charge batteries for at least 10 hours before operation. Otherwise, the backup
time may be shorter than expected.
5. Battery mode operation
1) When the UPS is in Battery mode, the buzzer will sound according to different battery capacity. If
the battery capacity is more than 25%, the buzzer will beep once every 4 seconds. If the battery
voltage drops to the alarm level, the buzzer will beep once every sec to remind users that the
battery is at low level and the UPS will shut down imminently. Users could switch off some
non-critical loads to disable the shutdown alarm and prolong the backup time. If there is no more
load to be switched off, you have to prepare shutdown procedure to preserve working data or
devices. Otherwise, there is a risk of data loss or load failure.
2) In Battery mode, users can touch “SETTING” “Basic” Audio Mute to enable “Mode Mute” to
disable the buzzer.
3) The backup time of the long-run model depends on the external battery capacity.
4) The backup time may vary from different operating temperature and load type.
5) When setting backup time for 16.5 hours (default value from LCD menu), after discharging 16.5
hours, UPS will shut down automatically to protect the battery. This battery discharge protection
can be enabled or disabled through LCD menu.
6. Test the batteries
1) If you need to check the battery status when the UPS is running in AC mode/CVCF mode, you could
touch “CONTROL” and select “Battery Test”. Refer to “Battery Test” screen.
2) Users also can set battery self-test through monitoring software.
7. Turn off the UPS with utility power supply in AC mode
1) Touch “CONTROL” and select “Turn off UPS” icon to turn off the UPS. Refer to “UPS on/off” screen.
NOTE 1: If the UPS has been set to bypass output, it will bypass voltage from the mains to output
terminal even though you have turned off the UPS (inverter).
NOTE 2: After turning off the UPS, please be aware that the UPS is working in Bypass mode, there
will be risk of power loss for connected devices.
2) In Bypass mode, output voltage of the UPS is still present. In order to cut off the output, switch off
the line input breaker. The LCD display will turn off and UPS is now completely off.
33
8. Turn off the UPS without utility power supply in Battery mode
1) Touch “CONTROL” and select “Turn off UPS” icon to turn off the UPS. Refer to “UPS on/off” screen.
2) Then UPS will cut off power to output terminals.
9. Mute the buzzer
1) Touch “SETTING” and select “BASIC” item. There are two events available to mute. Refer to
“SETTING” screen.
2) Some warning alarms can’t be muted unless the error is fixed. Please refer to section 3-3 for details.
10. Operation in warning status
1) When LCD screen shows “Fault Mode” and the buzzer beeps once every second, it indicates that
there are problems for UPS operation. Users can read the warning message(s) from “DATA LOG”
menu. Please refer to the Chapter 4 for details.
2) Some warning alarms can’t be muted unless the error is fixed. Please refer to section 3-3 for details.
11. Operation in Fault mode
1) When the buzzer beeps continuously, it means that there is a fatal error with the UPS. Users can
get the fault code from “DATA LOG” menu. Please refer to the Chapter 4 for details.
2) Please check the loads, wiring, ventilation, mains, battery and so on after the fault occurs. Don’t try
to turn on the UPS again before solving the issues. If the problems persist, contact the distributor or
service personnel immediately.
3) In case of an emergency, shut off connections from mains, external battery, and output immediately
to avoid possible damage to the UPS or equipment.
12. Operation in maintenance mode
This operation should only be performed by maintenance personnel or qualified technicians.
When the UPS needs to repair or service and the load could not be shut off, the UPS needs to be put into
maintenance mode.
1) First, switch off the UPS.
2) Then, remove the cover of maintenance bypass switch on the panel.
3) Turn the maintenance switch to “BPS” position.
3-6. Parallel Operation
1. Parallel system initial startup
Please make sure that all of the running UPSs are parallel models and have the same configuration.
1) Turn on each UPS in AC mode respectively (Refer to section 3-4(1)). Then, measure the inverter
output voltage of each phase for each UPS with a multi-meter. Calibrate the inverter output voltage
by configuring inverter voltage adjustment (Refer to SETTING Miscellaneous screen) in LCD
menu until the inverter output voltage difference of each UPS is within 1V or less.
2) Turn off each UPS (Refer to section 3-4(7.)). Then, follow the wiring procedure in section 2-4.
3) Remove the cover of parallel share current cable port on the UPS, connect each UPS one by one
with the parallel cable and share current cable, and then replace the cover.
4) Turn on the parallel system in AC mode:
a) Turn on the line input breaker of each UPS. If using dual-input unit, please also turn on the
external bypass input breaker. After all UPSs enter into bypass mode, measure the output
voltage between two UPSs for the same phase to make sure the phase sequence is correct. If
these two voltage differences are near to zero, that means all connections are met. Otherwise,
please check if the wirings are connected correctly.
b) Turn on the output breaker of each UPS.
c) Turn on each UPS in turns. After a while, the UPSs should enter into AC mode synchronously
and then, the parallel system is now complete.
34
5) Turn on the parallel system in Battery mode:
a) Turn on the battery breaker (only available in long-run model) and external output breaker of
each UPS.
b) Turn on any UPS. A few seconds later, the UPS will enter into battery mode.
c) Turn on the next UPS in sequence until all the UPSs enter into Battery mode and add to the
parallel system. Now the parallel system is now complete.
If you would like to have more information regarding the parallel operation, please contact
your supplier or service center for detail parallel operation instruction.
2. Add new units into the parallel system
1) You can not add new unit into the parallel system when whole system is running. You must cut off
the load and shutdown the system.
2) Make sure all of the UPS are the parallel models, and follow the wiring reference in section 2-4.
3) Install the new parallel system as per section 3-5.
3. Remove units from the parallel system
There are two methods to remove units from the parallel system:
First method:
1) Touch “CONTROL” “Turn off UPS” and select “Yes” to turn of the UPS. Then, the UPS will enter
into Bypass mode or No Output mode without output.
2) Turn off the external output breaker of this unit, and then turn off the input breaker of this unit.
3) Turn off the battery breaker(only available in long-run model) and remove the parallel and share
current cables. And then remove the unit from the parallel system.
Second method:
1) If the bypass is abnormal, you can not remove the UPS without interruption. You must cut off the
load and shut down the system.
2) Make sure the bypass setting is enabled in each UPS and then turn off the system. All UPSs will
transfer to Bypass mode. Remove all the maintenance bypass covers and set the maintenance
switches from “UPS” to “BPS” position. Turn off all the input breakers and battery breakers in
parallel system.
3) Turn off the output breaker and remove the parallel cable and share current cable of the UPS which
you want to remove. Now, you can remove the UPS from parallel system.
4) Turn on the input breaker of the remaining UPS and the system will transfer to Bypass mode. Set
the maintenance switches from “BPS” to “UPS position and put the maintenance bypass covers back
on.
5) Turn on the remaining UPS according to the previous section.
Warning: (Only for the parallel system)
● Before turning on the parallel system to activate inverter, make sure that all unit’s maintenance
switch at the same position.
● When parallel system is turned on, please do not operate the maintenance switch of any unit.
● The parallel system DOES NOT support ECO mode. Therefore, please DO NOT “enable” ECO mode
in any unit.
35
3-7. Fault Code
Fault code
Fault event
Icon
Fault code
Fault event
Icon
01
Bus start failure
None
42
DSP communication failure
None
02
Bus over
None
43
Overload
None
03
Bus under
None
46
Incorrect UPS setting
None
04
Bus unbalance
None
47
MCU communication failure
None
06
Converter over current
None
48
Two DSP firmware versions
are incompatible in parallel
system.
None
11
Inverter soft start failure
None
60
Bypass phase short circuited
None
12
High inverter voltage
None
61
Bypass SCR short circuited
None
15
Inverter B output(line to
neutral) short circuited
None
62
Bypass SCR open circuited
None
16
Inverter C output(line to
neutral) short circuited
None
63
Voltage waveform abnormal
in R phase
None
17
Inverter A-B output (line
to line) short circuited
None
64
Voltage waveform abnormal
in S phase
None
18
Inverter B-C output (line
to line) short circuited
None
65
Voltage waveform abnormal
in T phase
None
19
Inverter C-A output (line
to line) short circuited
None
66
Inverter current sample
abnormal
None
1A
Inverter A negative
power fault
None
67
Bypass O/P short circuited
None
1B
Inverter B negative
power fault
None
68
Bypass O/P line to line short
circuited
None
1C
Inverter C negative
power fault
None
69
Inverter SCR short circuited
None
21
Battery SCR short
circuited
None
6C
BUS voltage drops too fast
None
23
Inverter relay open
circuited
None
6D
Current sampling error value
None
24
Inverter relay short
circuited
None
6E
SPS power error
None
25
Line wiring fault
None
6F
Battery polarity reverse
None
31
Parallel communication
failure
None
71
PFC IGBT over-current in R
phase
None
32
The host signal failure
None
72
PFC IGBT over-current in S
phase
None
33
Synchronous signal
failure
None
73
PFC IGBT over-current in T
phase
None
34
Synchronous trigger
signal failure
None
74
INV IGBT over-current in R
phase
None
35
Parallel communication
loss
None
75
INV IGBT over-current in S
phase
None
36
Parallel output current
unbalance
None
76
INV IGBT over-current in T
phase
None
41
Over temperature
None
77
LCD & MCU communication
failure
None
36
3-8. Warning Code
Warning code
Warning event
Warning code
Warning event
01
Battery unconnected
21
Line situations are different in parallel
system
02
IP Neutral loss
22
Bypass situations are different in
parallel system
04
IP phase abnormal
33
Locked in bypass after overload 3
times in 30 minutes
05
Bypass phase abnormal
34
Converter current unbalanced
07
Over charge
3A
Cover of maintain switch is open
08
Low battery
3C
Utility extremely unbalanced
09
Overload
3D
Bypass is unstable
0A
Fan failure
3E
Battery voltage too high
0B
EPO enable
3F
Battery voltage unbalanced
0D
Over temperature
40
Charger short circuited
0E
Charger failure
37
4. Trouble Shooting
Symptom
Possible cause
Remedy
No indication and alarm in the front
display panel even though the mains is
normal.
The AC input power is not
connected well.
Check if input cable firmly
connected to the mains.
The warning code 0B.
EPO function is activated. At
this time, the EPO switch is in
“OFF” status or the jumper is
open.
Set the circuit in closed
position to disable the EPO
function.
The warning code 01.
The external or internal
battery is incorrectly
connected.
Check if all batteries are
connected well.
The warning code 09.
UPS is overload.
Remove excess loads from UPS
output.
UPS is overloaded. Devices
connected to the UPS are fed
directly by the electrical
network via the Bypass.
Remove excess loads from UPS
output.
After repetitive overloads, the
UPS is locked in the Bypass
mode. Connected devices are
fed directly by the mains.
Remove excess loads from UPS
output first. Then shut down
the UPS and restart it.
Fault code is shown as 43.
UPS is overload too long and
becomes fault. Then UPS shut
down automatically.
Remove excess loads from UPS
output and restart it.
Fault code is shown as 14, 15, 16, 17,
18 or 19,
The UPS shut down
automatically because short
circuit occurs on the UPS
output.
Check output wiring and if
connected devices are in short
circuit status.
Other fault codes are shown on LCD
display and alarm beeps continuously.
A UPS internal fault has
occurred.
Contact your dealer
Battery backup time is shorter than
nominal value.
Batteries are not fully charged.
Charge the batteries for at
least 7 hours and then check
capacity. If the problem still
persists, consult your dealer.
Batteries defect
Contact your dealer to replace
the battery.
The warning code 0A.
Fan is locked or not working.
Or the UPS temperature is too
high.
Check fans and notify dealer.
The warning code 02.
The input neutral wire is
disconnected.
Check and correct the input
neutral connection. If the
connection is ok and the
warning is still displaying,
please refer to the LCD setting
section, to enter the neutral
loss check menu, to see if the
parameter3 is “CHE”. If it is,
please press the “Enter” key
firstly to make the “CHE” flash
and press the “Enter” key
secondly to make the UPS clear
the alarm. If the warning still
exists, please check input fuses
of L2 and L3.
The L2 or L3 input fuse is
broken.
Replace the fuse.
If the UPS system does not operate correctly, please solve the problem by using the table below.
38
5. Storage and Maintenance
Storage Temperature
Recharge Frequency
Charging Duration
-25°C - 40°C
Every 3 months
1-2 hours
40°C - 45°C
Every 2 months
1-2 hours
5-1. Storage
Before storing, charge the UPS at least 7 hours. Store the UPS covered and upright in a cool, dry
location. During storage, recharge the battery in accordance with the following table:
5-2. Maintenance
The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified
maintenance personnel.
Even after the unit is disconnected from the mains, components inside the UPS system are still
connected to the battery packs which are potentially dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that
no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as
BUS-capacitors.
Only persons are adequately familiar with batteries and with the required precautionary measures
may replace batteries and supervise operations. Unauthorized persons must be kept well away from the
batteries.
Verify that no voltage between the battery terminals and the ground is present before maintenance
or repair. In this product, the battery circuit is not isolated from the input voltage. Hazardous voltages may
occur between the battery terminals and the grounding/earthing.
Batteries may cause electric shock and have a high short-circuit current. Please remove all
wristwatches, rings and other conductive objects before maintenance or repair, and only use tools with
insulated grips and handles for maintaining or repairing.
When replace the batteries, install the same number and same type of batteries.
Do not attempt to dispose of batteries by burning them. This could cause battery explosion. The
batteries must be deposed according to local environmental regulations.
Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may
be toxic.
Please replace the fuse only with the same type and amperage in order to avoid fire hazards.
Do not disassemble the UPS system.
39
6. Specifications
MODEL
15K(L)
15K(L) DUAL
20K(L)
20K(L) DUAL
CAPACITY*
15KVA / 15KW
20KVA / 20KW
INPUT
Voltage
Range
Low Line Loss
80 VAC(Ph-N) ± 3 % at 50% Load
100 VAC(Ph-N) ± 3 % at 100% Load
Low Line Comeback
Low Line Loss Voltage + 5V
High Line Loss
156 VAC(L-N) ± 3 % at 50% Load
146 VAC(L-N) ± 3 % at 100% Load
High Line Comeback
High Line Loss Voltage - 5V
Frequency Range
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Phase
3 Phase with Neutral
Power Factor
≧ 0.99 at 100% Load
OUTPUT
Phase
3 Phase with Neutral
Output voltage
208/220VAC (Ph-Ph)
120/127VAC (Ph-N)
AC Voltage Regulation
± 1%
Frequency Range
(Synchronized Range)
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
0 ms (When phase lock fails, <4ms interruption occurs from inverter to bypass)
InverterECO
<10 ms
EFFICIENCY
AC mode
94%
Battery Mode
93.5%
BATTERY
Standard
Model
Type
12 V / 9 Ah
12 V / 9 Ah
Numbers
(10+10)pcs x 2 strings
Recharge Time
9 hours recover to 90% capacity
Charging Current(max.)
4A/8A/12A ± 10% (Adjustable)
Parallelable up to 5 charger boards to reach 20A maximum
Charging Voltage
+/-136.5 VDC ± 1%
Long-run
Model
Type
Depending on applications
Numbers
16 ~ 20 (adjustable)
Charging Current(max.)
4A/8A/12A ± 10% (Adjustable)
Parallelable up to 5 charger boards to reach 20A maximum
Charging Voltage
+/- 13.65 VDC * N ± 1% (N = 8~10)
PHYSICAL
Standard
Model
Dimension, D X W X H
mm
815 x 300 x 1000
815 x 300 x 1000
Net Weight (kgs)
181
231
Long-run
Model
Dimension, D X W X H
mm
815 x 300 x 1000
815 x 300 x 1000
Net Weight (kgs)
81
81
ENVIRONMENT
Operation Temperature
0 ~ 40°C (the battery life will down when > 25°C)
Operation Humidity
<95 % and non-condensing
Operation Altitude**
<1000m**
Acoustic Noise Level
Less than 60dB @ 1 Meter
Less than 70dB @ 1 Meter
MANAGEMENT
Smart RS-232 or USB
Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix, and MAC
Optional SNMP
Power management from SNMP manager and web browser
* If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated 1% per 100m.
**Product specifications are subject to change without further notice.
40
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.