BASO GM7000 User Manual

Installation Instructions GM-7000 Issue Date November 9, 2012
GM-7000 Series CE Approved Gas Control Valve
IMPORTANT: These instructions are intended as a
guide for qualified personnel installing or servicing BASO Gas Products. Carefully follow all instructions in this bulletin and all instructions on the appliance. Limit repairs, adjustments, and servicing to the operations listed in this bulletin or on the appliance.
!
WARNING: Risk of Fire or Explosion.
The system must meet all applicable local, national, and regional regulations. Improper installation may cause gas leaks, explosions, property damage, and injuries.
4. Compare the voltage on the valve with the power source voltage to ensure the correct unit is being installed.
5. Mount the valve. The GM-7000 valve may be mounted on a horizontal manifold with the magnetic operators (solenoid coils) pointed up (vertical) or in any position not exceeding 90° from the vertical (Figure 1). The valve may also be mounted on a vertical manifold in any position around its axis. Do not install the solenoid coils upside
down. Install vertically wherever possible.
6. If you desire to measure the outlet pressure, use the bottom cast pressure test fitting.
90° Maximum
from Vertical
90° Maximum from Vertical
!
WARNING: Risk of Fire or Explosion.
To prevent leakage of upstream gas, shut off the gas supply at the main manual shutoff valve before installing or servicing the GM-7000 valve. Failure to shut off the gas supply can result in the release of gas during installation or servicing, which can lead to an explosion or fire, and may result in severe personal injury or death.
Mounting
!
CAUTION: Risk of Equipment Damage.
To prevent damage to the valve when mounting to pipework, do not use a wrench on any surface other than the casting flats provided at the inlet and outlet ends of the valve body.
To install the GM-7000 valve:
1. Shut off power to the appliance.
2. Shut off the gas at the main manual shutoff valve.
3. Label each wire with the correct terminal designation prior to disconnection.
Limited Horizontal and Vertical
Vertical mounting may be 360º ar ound its axis with the gas flow either
up or dow n, but always in the direction of the arrow.
Figure 1: GM-7000 Mounting Positions
7. Install the valve on the manifold; ensure the gas flows through the valve body in the direction indicated by the arrow on the body. If the valve is installed with the gas flow in the opposite direction of the arrow, leakage can occur.
© 2012 BASO Gas Products 1
Part No. BASO-INS-GM7000, Rev. F www.baso.com
Note: If installing a valve with threaded
connections, use an approved pipe joint sealing compound on the male threads before assembly. An optional thread lubricant may have been factory applied to the first two or three threads of the inlet and outlet to avoid galling. Make sure that excess compound is removed after mounting. Threads of pipe and nipples must be smooth and free of tears and burrs. Steam clean all piping to remove foreign substances such as cutting oil or thread chips.
8. Connect the pilot tubing (when necessary) to the threaded pilot connection on the underside of the valve body (Figure 2) and run the tube to the pilot burner within the appliance. Connect the pilot tube to the valve with an optional compression fitting.
Outlet P r essure T ap Connection
Pilot Tube
Connection
Figure 2: Underside of Valve with
Direct-Acting Regulator
9. Check for leakage before making any valve adjustments.
a. Shut off the gas at the main manual shutoff
valve and open the pressure connection between the manual shutoff valve and the GM-7000 valve.
b. Connect air tubing with a maximum pressure
of 1-1/2 times the valve’s maximum operating pressure (as indicated on the valve) to the opened pressure connection.
c. Paint all valve body connections with a rich
soap and water solution.
If bubbles occur, this is an indication of a leak. To stop a leak, tighten joints and connections. Replace the part if the leak cannot be stopped.
If bubbles do not occur, remove the air tubing and close the pressure connection.
10. Make wiring connections. See the Wiring section for specific wiring instructions.
11. To measure the outlet pressure, by apply power to the valve and energizing both valve solenoids. Use the outlet pressure tap connection on the underside of the valve body to monitor the outlet pressure. The outlet pressure tap is a bleed hole with a cast spigot, sealed with a threaded brass needle screw (Figure 2). To measure the outlet pressure, turn the screw in a counterclockwise direction one or two turns and fit a 9 mm diameter flexible tube over the cast spigot. After all valve adjustments have been made and the desired outlet pressure has been obtained, remove the flexible tube. Tighten the needle screw by turning it clockwise with a slotted screwdriver until hand tight, sealing the bleed hole.
12. Check for leakage at the bleed hole. Paint the bleed hole with a rich soap and water solution (or use acceptable gas leak detection equipment). If bubbles occur, this is an indication of a gas leak. To stop a leak, tighten the needle screw. Replace the valve if the leak cannot be stopped.
Note: If installing a valve with a pressure
regulator, set the valve to the desired outlet pressure. See the Regulator Adjustment section for specific adjustment procedures. After setting the valve outlet pressure, ensure that the leak-limiting seal cap is replaced (Figure 3).
13. Observe at least three complete operating cycles to ensure that all components are functioning correctly before leaving the installation.
2 GM-7000 Series CE Approved Gas Control Valve Installation Instructions
Earth Ground
Line 2 Neutral
L2
N2
Coil 2 Main Valve
Non-Polarity Sensitive
Line and N eutral
Connections
Ground Tab (Op tional)
Line 1
Twin Solenoid Wiring Using 4-Wire Cable
N1
L1
Coil 1 Pilot Valve
Non-Polarity Sensitive Line and N eutral Connections
Ground Tab (Op tional)
Leak-Limiting
Seal Cap
To Main SolenoidTo Pilot Solenoid
L
N
LN
Figure 3: GM-7532 Model with Direct-Acting Regulator
GM-7000 Series CE Approved Gas Control Valve Installation Instructions 3
Wiring
!
CAUTION: Risk of Electric Shock. Disconnect power supply before making electrical connections to avoid electric shock or equipment damage. Ensure that the operating voltage is identical to the information on the product identification label.
The GM-753_ is supplied with 6.35 x 0.8 mm (1/4 in.) male tabs, and connections should be made using
6.35 x 0.8 mm (1/4 in.) female, fully insulated push-on terminals.
Route the electrical connection for the valve solenoid actuators from the burner sequence control to the valve (see Figure 3).
Note: Electrical connections can also be made using pre-wired electrical plugs (DIN 43650 Form B [ISO 4400]).
Note: All wiring must be in accordance with national and local codes and regulations.
4. Turn the thermostat to a low dial setting to open the contacts. All burner flames should be extinguished. Repeat Steps 3 and 4 at least three times.
5. Return the thermostat to a normal setting before leaving the installation.
Regulator Adjustment
IMPORTANT: All adjustments must be made
in conjunction with the gas appliance and in accordance with the appliance manufacturer’s instructions. Only authorized personnel should make adjustments.
!
WARNING: Risk of Explosion or Fire. The minimum flow rate of the valve must not be adjusted below the minimum safe working rate of the appliance. This may cause gas leaks, which can lead to an explosion or fire and may result in severe personal injury or death.
Setup and Adjustments
Checkout
!
WARNING: Risk of Explosion or Fire. Follow this or an equivalent checkout procedure after installation. Before leaving the installation, verify that the gas valve functions properly and that the system has no gas leaks. Gas leaks can lead to an explosion or fire, and may result in severe personal injury or death.
Make sure all components are functioning properly by performing the following test:
1. Test all joints and connections for leaks with a soap solution.
2. Close the main upstream shutoff valve and wait at least 5 minutes for unburned gas to escape from the appliance, and then reopen the shutoff valve.
3. Turn on the main electrical power switch and close the thermostat contacts. The appliance should operate in accordance with the manufacturer’s specified sequence of operation.
The GM-753_ model has a bottom adjust pressure regulator. To adjust the regulator, turn the adjusting screw to determine the compression of the regulator spring against the regulator diaphragm.
To adjust the outlet pressure, remove the leak-limiting seal cap to expose the adjusting screw (Figure 3). Turn the screw (using a suitable screwdriver) in a clockwise direction to increase or in a counterclockwise direction to decrease the outlet pressure of the valve.
Repairs and Replacement
Table 1: Replacement Solenoid Coil
Part Number Description
RSDA95A-25
RSDA95A-25A
Do not make field repairs except for the replacement of the solenoid coil.
Any attempt to repair this assembly voids the manufacturer’s warranty. For a replacement coil or gas valve, contact the original equipment manufacturer or the nearest BASO Gas Products distributor.
25 VAC; 50/60 Hz; 3-tab 10.5 VA Coil 25 VAC; 50/60 Hz; 2-tab 10.5 VA Coil
4 GM-7000 Series CE Approved Gas Control Valve Installation Instructions
Technical Specifications
Product Types of Gas Rated Inlet Pressure
Maximum Working Pressure (CE)
Maximum Differential Pressure
Reverse Pressure Rating Regulator Classification Regulator Setting Direct-Acting Regulator
Pressure Range Permissible Ambient
(Surface) Temperature Body Connections
Valve Torsion Group Pressure Taps Pilot Connection Materials
Dirt Strainer Operating Time Rating Valve Timings
Power Rating Electrical Rating Electrical Connection
Coil Insulation Class Accessories
GM-7000 Series CE Approved Gas Control Valve Natural, Liquefied Petroleum (LP), and LP gas-air mixtures North America:
Europe: Australia:
50 mbar
20 mbar (2 kPa [8 in. W.C.]) 50 mbar (5 kPa [20 in. W.C.]) Class B (EN 126 and 161); Class 2 (AS 4624 and AS 4629)
Class C (EN 126); Adjustable, Class 2, Grade 20 (AS 4624) Factory set to customer’s specification Natural Gas:
LP Gas: 0 to 70°C (32 to 158°F ) 1/2 NPT, 1/2 BSPP (Thread ISO 7-Rp) or 1/2 BSPT (Thread ISO 7-Rc) with Flange Connection Holes
(M4 x 0.7 mm pitch x 6 mm deep) Group 2 (EN 126 and 161) M5 x 0.8 Thread 1/4 in. cc Blank Plug Body:
Diaphragms and Seals:
0.9 mm (0.036 in.) mesh (CE only or upon request) 100% Continuous Closing Time:
Opening Time: Dead Time:
10.5 VA per Coil 25 VAC, 50/60 Hz, 0.42A 2-Tab Solenoid Coil: 2 x 6.35 mm (1/4 in.)
3-Tab Solenoid Coil: 2 x 6.35 mm (1/4 in.) + 6.35 mm (1/4 in.) Earth Ground Class F Conversion Kits Natural gas to LP gas:
1/2 psi 35 mbar
3.5 kPa
7.5 to 12.5 mbar (0.15 to 1.25 kPa [3 to 5 in. W.C.])
22.5 to 30 mbar (2.25 to 3 kPa [9 to 12 in. W.C.])
Die-Cast Aluminum Nitrile Rubber
<
1 Second
<
1 Second
< 1 Second
GM-70-CLP LP gas to Natural gas: Regulated to non-regulated:
GM-70-CNG
BG-70-CBP
GM-7000 Series CE Approved Gas Control Valve Installation Instructions 5
th
Technical Specifications (continued)
Agency Listings
Specification Standards
Performance specifications are nominal and conform to acceptable industry standards. All agency certification of BASO products is performed under dry and controlled indoor environmental conditions. Use of BASO products beyond these conditions is not recommended and may void the warranty. Product must be protected if exposed to water (dripping, spraying, rain, etc.) or other harsh environments. The original equipment manufacturer or end user is responsible for the correct application of BASO products. Consult BASO Gas Products LLC for questionable applications. BASO Gas Products LLC shall not be liable for damages or product malfunctions resulting from misapplication or misuse of its products.
Refer to the GM-7000 Series CE Approved Gas Control Valve Product Bulletin (BASO-PB-GM7000) for necessary information on operating and performance specifications for this product.
CSA (AGA/CGA) Certificate Number 229521-1656041 EC Certificate Number EC-86/11/041 Australian Gas Association Certificate Number 7934
EN 126 and 161 Standards Complying with the Directive Standards Complying with the Low Voltage Directive Australian Standards AS 4624 and AS 4629 Canadian Standard CSA 6.5 and 6.20 ANSI Standards Z21.21 and Z21.78
1007 South 12 PO Box 170 Watertown, WI 53094 www.baso.com 1-877-227-6427 (1-877-BASOGAS) Published in U.S.A.
Street
6 GM-7000 Series CE Approved Gas Control Valve Installation Instructions
Loading...