BASO BGC258 User Manual

Page 1
Installation Instructions BGC258 Issue Date October 04, 2011
BGC258 Series BASOTROL®
Installation
IMPORTANT: These instructions are intended as a
guide for qualified personnel installing or servicing BASO Gas Products. Carefully follow all instructions in this bulletin and all instructions on the appliance. Limit repairs, adjustments, and servicing to the operations listed in this bulletin or on the appliance.
To install the BGC258 valve:
1. Shut off power to the appliance.
2. Shut off the gas at the main manual shutoff valve.
3. Label each wire with the correct terminal designation prior to disconnection.
!
WARNING: Risk of Fire or Explosion.
The system must meet all applicable local, national, and regional regulations. Improper installation may cause gas leaks, explosions, property damage, and injuries.
!
WARNING: Risk of Fire or Explosion.
To prevent leakage of upstream gas, shut off the gas supply at the main manual shutoff valve before installing or servicing the BGC258 valve. Failure to shut off the gas supply can result in the release of gas during installation or servicing, which can lead to an explosion or fire, and may result in severe personal injury or death.
Mounting
!
CAUTION: Risk of Equipment Damage. To prevent damage to the valve when mounting to pipework, do not use a wrench on any surface other than the casting flats provided at the inlet and outlet ends of the valve body.
4. Compare the voltage on the valve with the power source voltage to ensure the correct unit is being installed.
5. Mount the valve. The BGC258 valve may be mounted on a horizontal manifold with the magnetic operators (solenoid coils) pointed up (vertical) or in any position not exceeding 90° from the vertical (see Figure 1). The valve may also be mounted on a vertical manifold in any position around its axis. Do not install the solenoid coils upside down.
90° Maximum
from Vertical
Limited Horizontal and Vertical
90° Maximum from Vertical
Figure 1: BGC258 Mounting Positions
© 2011 BASO Gas Products 1
Part No. BASO-INS-BGC258B, Rev. - www.baso.com
Vertical mounting may be 360º ar ound its axis with the gas flow either
up or dow n, but always in the direction of the arrow.
Page 2
6. If you desire to measure the outlet pressure, use the bottom cast pressure test fitting or use the Y99AX pressure test fitting (see
Figure 2) and an
approved pip joint compound on the male threads and screw the fitting into dither side of the valve, which ever side is convenient, replacing the pressure tap plug.
Figure 2: Y99AX-1 (1/8-27 NPT) Pressure Test Fitting
Y99AX -2 (1/8-28 BSPT) Pressure Test Fitting
7. Install the valve on the manifold; ensure the gas flows through the valve body in the direction indicated by the arrow on the body. If the valve is installed with the gas flow in the opposite direction of the arrow, leakage can occur.
Note: If installing a valve with threaded
connections, use an approved pipe joint sealing compound on the male threads before assembly. An optional thread lubricant may have been factory applied to the first two or three threads of the inlet and outlet to avoid galling. Make sure that excess compound is removed after mounting. Threads of pipe and nipples must be smooth and free of tears and burrs. Steam clean all piping to remove foreign substances such as cutting oil or thread chips.
8. Connect the pilot tubing (when necessary) to the threaded pilot connection on the underside of the valve body (Figure 3) and run the tube to the pilot burner within the appliance. Connect the pilot tube to the valve with an optional compression fitting.
9. Check for leakage before making any valve adjustments.
a. Shut off the gas at the main manual shutoff
valve and open the pressure connection between the manual shutoff valve and the BGC258 valve.
b. Connect air tubing with a maximum pressure of
1-1/2 times the valve’s maximum operating pressure (as indicated on the valve) to the opened pressure connection.
c. Paint all valve body connections with a rich
soap and water solution. If bubbles occur, this is an indication of a leak.
To stop a leak, tighten joints and connections. Replace the part if the leak cannot be stopped.
If bubbles do not occur, remove the air tubing and close the pressure connection.
10. Make wiring connections. See the Wiring section for specific wiring instructions.
11. To measure the outlet pressure, apply power to the valve and energizing both valve solenoids. Use the outlet pressure tap connection on the underside of the valve body to monitor the outlet pressure. The outlet pressure tap is a bleed hole with a cast spigot, sealed with a threaded brass needle screw (Figure 3). To measure the outlet pressure, turn the screw in a counterclockwise direction one or two turns and fit a 9 mm diameter flexible tube over the cast spigot. After all valve adjustments have been made and the desired outlet pressure has been obtained, remove the flexible tube. Tighten the needle screw by turning it clockwise with a slotted screwdriver until hand tight, sealing the bleed hole.
Outlet P ressure T ap Connection
Pilot Tube
Connection
Figure 3: Underside of Valve with
Direct-Acting Regulator
2 BGC258 Series CE Approved Gas Valve Installation Instructions
Page 3
12. Check for leakage at the bleed hole. Paint the bleed hole with a rich soap and water solution (or use acceptable gas leak detection equipment). If bubbles occur, this is an indication of a gas leak. To stop a leak, tighten the needle screw. Replace the valve if the leak cannot be stopped.
Note: If installing a valve with a pressure
regulator, set the valve to the desired outlet pressure. See the Regulator Adjustment section for specific adjustment procedures. After setting the valve outlet pressure, ensure that the leak-limiting seal cap is replaced (Figure 4).
13. Observe at least three complete operating cycles to ensure that all components are functioning correctly before leaving the installation.
Wiring
!
CAUTION: Risk of Electric Shock. Disconnect power supply before making electrical connection to avoid electric shock or equipment damage. Ensure that the operating voltage is identical to the information on the product identification label.
The BGC258 valve is supplied with 3-tab or 2-tab electrical connections. The solenoid coils are male tabs and electrical connections should be made using
6.35 x 0.8 mm (1/4 in.) female, fully insulated push-on terminals. The earth ground is clearly labeled.
The electrical wiring to a twin solenoid valve from an electronic intermittent proven pilot ignition system is comprised of two lines; a common and an independent earth ground. Wiring can be done using a single 4-wire cable. The wiring connections for a 4-wire cable are shown in Figure 4.
Route the electrical cable for the valve solenoid actuators from the burner sequence control to the valve and make wiring connections in accordance with (see Figure 4).
Note: Electrical connections can also be made using pre-wired electrical plugs (DIN 43650 Form B [ISO 4400]).
Note: All wiring must be in accordance with national and local electrical codes and regulations.
Setup and Adjustments
Checkout
!
WARNING: Risk of Explosion or Fire.
Follow this or an equivalent checkout procedure after installation. Before leaving the installation, verify that the gas valve functions properly and that the system has no gas leaks. Gas leaks can lead to an explosion or fire, and may result in severe personal injury or death.
Make sure all components are functioning properly by performing the following test:
1. Test all joints and connections for leaks with a soap solution.
2. Close the main upstream shutoff valve and wait at least 5 minutes for unburned gas to escape from the appliance, and then reopen the shutoff valve.
3. Turn on the main electrical power switch and close the thermostat contacts. The appliance should operate in accordance with the manufacturer’s specified sequence of operation.
4. Turn the thermostat to a low dial setting to open the contacts. All burner flames should be extinguished. Repeat Steps 3 and 4 at least three times.
5. Return the thermostat to a normal setting before leaving the installation.
BGC258 Series CE Approved Gas Valve Installation Instructions 3
Page 4
Regulator Adjustment
IMPORTANT: All adjustments must be made in
conjunction with the gas appliance and in accordance with the appliance manufacturer’s instructions. Only authorized personnel should make adjustments.
!
WARNING: Risk of Explosion or Fire. The minimum flow rate of the valve must not be adjusted below the minimum safe working rate of the appliance. this may cause gas leads, which can lead to an explosion or fire and may result in severe personal injury or death.
The BGC258 can have a bottom adjust, right or left-handed top adjust spring pressure regulator. Right of left-hand orientation is determined by the position of the adjustment when looking into the inlet connection of the valve.
The regulator controls the gas pressure at the valve outlet by positioning the regulator poppet for selected throughput flow and pressure. This is achieved by the valve outlet pressure acting on the regulator diaphragm, which balances against the preset regulator spring. Adjustment of the spring compression determines the valve outlet pressure and the throughput flow rate.
To adjust the outlet pressure, remove the leak-limiting seal cap to expose the adjusting screw (see Figure 4). Turn the screw (using a suitable screwdriver) in a clockwise direction to increase or in a counterclockwise direction to decrease the outlet pressure of the valve.
Table 1: Replacement Solenoid Coil
Part Number Description
RSDA95A-12
RSDA95A-25V
RSDA95A-25 RSDA95A-25A RSDA95A-120 RSDA95A-240
12 VDC; 2-tab 10.5 VA Coil
25 VDC; 3-tab 11.5 VA Coil 25 VAC; 50/60 Hz; 3-tab 10.5 VA Coil 25 VAC; 50/60 Hz; 2-tab 10.5 VA Coil
120 VAC; 60/60 Hz; 3-tab 10.5 VA Coil
240VAC; 50/60 Hz; 3-tab 10.5 VA Coil
Do not make field repairs except for the replacement of the solenoid coil.
Any attempt to repair this assembly voids the manufacturer’s warranty. For a replacement coil or gas valve, contact the original equipment manufacturer or the nearest BASO Gas Products distributor.
4 BGC258 Series CE Approved Gas Valve Installation Instructions
Page 5
Earth Ground Neutral
Line 1
To Pilot Solenoid
N1
L1
Coil 1 Pilot Valve
Non-Polarity Sensitive Line and N eutral Connections
Ground Tab
25V, 120V and 240V O nl y
Leak-Limiting
Seal Cap
LN
Figure 4: 3-Tab Electrical Connections
BGC258 Series CE Approved Gas Valve Installation Instructions 5
Page 6
Technical Specifications
Product Types of Gas Permissible Ambient (Surface) Temperature Electrical Ratings
Maximum Operating Pressure
Maximum Differential Pressure Reverse Pressure Rating Regulator Classification Regulator Adjustment Range
Body Connections
Valve Torsion Group Pressure Connection
Pilot Connection
Dirt Strainer Operating Time Rating Valve Timings
Power Rating Electrical Connection
Coil Insulation Class Packaging Bulk Pack Quantity Bulk Pack Weight Accessories
BGC258 Series CE Approved Gas Valve 2nd (Natural Gas), and 3rd (LP Gas) Family Gases
-29 to 79°C (-20 to 175°F ) 12 VDC, 0.875A
25 VDC, 0.46A 25 VAC, 50/60 Hz, 0.42A 120 VAC, 50/60 Hz, 0.088A 240 VAC, 50/60 Hz, 0.044A North America: Europe: Australia:
20 mbar (2 kPa [8 in. W.C.]) 50 mbar (5 kPa [20 in. W.C.]) Class B (EN 126 and 161); Class 2 (AG 209 and AG 214)
Class C (EN 126); Adjustable, Class 3, Grade 20 (AG 209) Bottom Adjust Regulators:
Top Adjust Regulators 3/8 or 1/2 NPT, 3/8 or 1/2 BSPP (Thread ISO 7-Rp) or 3/8, 1/2 BSPT (Thread ISO 7-Rc) with
Flange Connection Holes (M4 x 0.7 mm pitch x 6 mm deep) Group 2 (EN 126 and 161) 1/8 BSPP (Thread ISO 7-Rp), 1/8 BSPT (Thread ISO 7-Rc), 1/8 NPT Left-hand and/or Right-hand, or M5 x 0.8 Thread Bottom 1/8 BSPP (Thread ISO 7-Rp), 1/8 BSPT (Thread ISO 7-Rc), 1/8 NPT Left-hand and/or Right-hand, or 1/4 in. cc Fitting Bottom
0.9 mm (0.036 in.) mesh (CE only or upon request) 100% Continuous Closing Time: Opening Time: Dead Time:
10.5 VA per Coil (except 25 VDC, 11.5 VA) 2-Tab Solenoid Coil: 2 x 6.35 mm (1/4 in.) 3-Tab Solenoid Coil: 2 x 6.35 mm (1/4 in.) + 6.35 mm (1/4 in.) Earth Ground Class F Bulk pack supplied to original equipment manufacturer (individual pack option al). 30 per carton 35 kg (77 lb) per carton Conversion Kits Natural gas to LP gas:
1/2 psi 50 mbar 5 kPa
7.5 to 12.5 mbar (0.75 to 1.25 kPa [3 to 5 in. W.C.])
22.5 to 30 mbar (2.25 to 3.0 kPa [9 to 12 in. W.C.])
7.5 to 12.5 mbar (0.75 to 1.25 kPa [3 to 5 in. W.C.])
22.5 to 30 mbar (2.25 to 3.0 kPa [9 to 12 in. W.C.])
1 Second
<
1 Second
< < 1 Second
LP gas to Natural gas: Regulated to non-regulated:
GM-70-CLP GM-70-CNG BG-70-CBP
6 BGC258 Series CE Approved Gas Valve Installation Instructions
Page 7
th
Technical Specifications (continued)
Agency Listings
Specification Standards
CSA (AGA/CGA) Certificate Number Pending EC Certificate Number Pending EN 126 and 161 Standards Complying with the Directive Standards Complying with the Low Voltage Directive Canadian Standards CSA 6.5 and 6.20 ANSI Standards Z21.21 and Z21.78
Performance specifications are nominal and conform to acceptable industry standards. All agency certification of BASO products is performed under dry and controlled indoor environmental conditions. Use of BASO products beyond these conditions is not recommended and may void the warranty. Product must be protected if exposed to water (dripping, spraying, rain, etc.) or other harsh environments. The original equipment manufacturer or end user is responsible for the correct application of BASO products. Consult BASO Gas Products LLC for questionable applications. BASO Gas Products LLC shall not be liable for damages or product malfunctions resulting from misapplication or misuse of its products.
Refer to the BGC258 Series BASOTROL CE Approved Product Bulletin (BASO-PB-BGC258) for necessary information on operating and performance specifications for this product.
1007 South 12 PO Box 170 Watertown, WI 53094 www.baso.com 1-877-227-6427 (1-877-BASOGAS) Published in U.S.A.
Street
BGC258 Series CE Approved Gas Valve Installation Instructions 7
Loading...