Installation Instructions Issue Date June 26, 2014
BG1100M Direct Spark Ignition Control
Application
The BG1100M is a microprocessor based ignition
control. The microprocessor provides reliable software
control of all timings and operates a diagnostic red
Light-Emitting Diode (LED). It is designed for direct
burner supervision and can be used with all gases. It
provides ignition sequence, flame monitoring, and
safety shutoff for direct spark ignition boilers, furnaces
and other heating appliances. For a complete listing of
specifications, refer to the Technical Specifications
section.
Installation
IMPORTANT: Only qualified personnel should
install or service BASO Gas Products®. These
instructions are a guide for such personnel. Carefully
follow all instructions for the appliance.
IMPORTANT:Make all gas installations in
accordance with applicable local, national, and
regional regulations.
Instructions for installing the burner/igniter-sensor are
typically provided by the appliance manufacturer. It is
important to follow those instructions. If such
information is not included, refer to the Mounting
section.
Mounting
!
CAUTION:Risk of Electric Shock.
Disconnect power supply before making electrical
connections to avoid electric shock.
!
WARNING:Risk of Explosion or Fire.
Shut off the gas supply at the main manual shutoff
valve before installing or servicing the control.
Failure to shut off the gas supply can result in the
release of gas during installation or servicing, which
can lead to an explosion or fire, and may result in
severe personal injury or death.
!
WARNING:Risk of Explosion or Fire.
Do not install the control in an area that is exposed
to water (for example, dripping, spraying, rain). Do
not use the control if it has been exposed to water.
Exposure to water may cause malfunction and can
lead to an explosion or fire and may result in severe
personal injury or death.
IMPORTANT:This control is approved for use
with only noise suppression (resistive) spark wires. If
the application has copper wire, it must be replaced.
IMPORTANT:Do not mount the control where
it can be exposed to direct infrared radiation from the
main burner or to temperatures in excess of the
maximum product temperature rating.
Location Considerations
Choose a location that provides the shortest, direct
cable route to the spark electrode, pilot burner/ignitersensor assembly. Easy access to the terminals is
desired for wiring and servicing. The control may be
mounted in any position. Mount the control on a
grounded metal surface with #6 sheet metal or
machine screws through the mounting holes provided
in the enclosure.
The pilot burner/igniter sensor must be securely
mounted to the main burner to ensure that the pilot
burner flame remains properly positioned with respect
to the main burner flame. The pilot burner must be
located such that the flame receives an ample supply
of air, free from the products of combustion, the flame
must not be exposed to draft conditions, the full force
must not be exposed to draft conditions, the full force
of main burner ignition, or falling scale, which could
otherwise impede ignition of main burner flame.
Securely mount the pilot burner/igniter-sensor to the
main burner with metal screws at a distance
approximately 3/8 in. (9.52 mm) above and 1/4 in.
(6.35 mm) away from the center of the nearest main
burner port. Ensure that the main burner flames do not
impinge on any part of the pilot burner.
The spark electrode, flame sensor, and BG1100M
must share a common ground with the burner to
operate correctly. Thermoplastic insulated wire with a
minimum rate of 221˚F (105˚C) is recommended for
the ground wire. Ensure that the flame sensor wire and
the high voltage spark transformer wire are separated
from one another by a minimum distance of 1/4 in.
(6.35 mm) and are not wrapped around any pipe, other
wiring, or accessory.
Wiring
!
WARNING:Risk of Explosion or Fire.
Locate all safety, limit, and operating controls in
series with the thermostat terminal (TH) on the
ignition control. Improper installation may cause gas
leaks, which can lead to an explosion or fire and
may result in severe personal injury or death.
Refer to Figure 1 and Figure 2 for wiring diagrams. All
wiring should be in accordance with the National
Electrical Code (NEC) and all other local codes and
regulations.
Check the voltage rating marked on the control and
make sure it is suited to the application. Use a Class 2
transformer capable of providing 24 VAC under
maximum load, including valves. A transformer having
excessive primary impedance due to poor coupling
affects the ignition potential.
The high-voltage spark transformer cable is noise
suppression (resistive) type, rated for at least 15kVA
and must not be in continuous contact with a metal
surface. Use standoff insulators. Ensure that the flame
sensor wire and high voltage spark transformer cable
are separated from one another by a minimum of 1/4
in. (6.35 mm) and are not wrapped around any pipe,
other wiring, or accessories.
!
WARNING:Risk of Electric Shock.
Before applying power to the control, connect the
high voltage cable to the spark transformer terminal
and spark electrode (pilot burner assembly). Verify
the ground wire is attached to the pilot burner and
the control ground terminal strip. Failure to follow
this procedure can cause electric shock and may
result in severe personal injury or death.
2 BG1100M Direct Spark Ignition Control Installation Instructions
VALVE
2
GND
(COM)
VALVE
3456810
24V
GND
BURNER
SENSE
SPARK
Thermostat
Combination
Gas Valve
5
Burner/ignitor
1
Power Supply. Provides disconnect means and overload protection as required.
Maximum cable length 48 inches (1,220 mm). (Resistive wire recommended.)
2
3
Alternate location for limit controller.
4
Controls in 24V circuit must not be in ground leg to transformer.
5
Sensor rod must be 3/8” (9.53 mm) to 1/2” (12.7 mm) of the sensor tip should
3
4
24VAC
Class 2
Transformer
Chassis or Frame
Ground
High
Tem p
Limit
1
L1 (Hot)
L2 (Neu)
2
be in the flame for proper sensing signal.
Figure 1: Wiring for 1 Rod Flame Sense
VALVE
(COM)
234
GND
VALVE
GND
BURNER
56
24V
SENSE
8
SPARK
10
Thermostat
Combination
Gas Valve
6
Burner/Ignitor
1
Power Supply. Provides disconnect means and overload protection as required.
Maximum cable length 48 inches (1,220 mm). (Resistive wire recommended.)
2
3
Alternate location for limit controller.
4
Controls in 24V circuit must not be in ground le g to transform er.
5
Maximum cabl e le ngth 48 inches (1, 220 mm).
Sensor rod m ust be 3/8” (9.53 m m ) t o 1/ 2” (12.7 mm) o f the sensor tip should
6
be in the flam e for proper sensin g si gnal.
Flame
Sensor
3
4
24VAC
Class 2
Transformer
Chassis or Frame
Ground
High
Temp
Limit
5
1
L1 (Hot)
L2 (Neu)
Figure 2: Wiring for 2 Rod Flame Sense
BG1100M Direct Spark Ignition Control Installation Instructions 3
2
Setup and Adjustments
Operation
Checkout
!
WARNING:Risk of Explosion or Fire. Verify
that there are no gas leaks by testing with appropriate
equipment. Never use a match or lighter to test for the
presence of gas. Failure to test properly can lead to an
explosion or fire and may result in severe personal injury
or death.
Make sure all components function properly by performing
the following test.
1. Before starting the appliance, perform a safety
inspection of piping, burners and venting. Check for
water leaks, etc. Check all wiring for proper
connections. Be sure the system is properly
grounded, including ground connection to the pilot
burner.
2. With the gas and thermostat off, turn on power to the
appliance.
3. Turn the thermostat to a high setting and verify that
the control goes through the operating sequence to a
shutoff condition.
Note: The burner does not light because the gas is
off.
4. Turn off the thermostat.
5. Turn on the gas and purge gas lines of all air.
6. Check for gas leaks on all pipe joints upstream of the
gas valve with a soap solution.
7. Turn the thermostat to the highest setting and verify
successful ignition and a normal run condition for at
least 5 minutes. If the appliance fails to run, see the
Troubleshooting section.
8. Check for gas leaks on all pipe joints downstream of
the gas valve with a soap solution.
9. Turn the thermostat down for at least 30 seconds
and then back up again. Verify successful ignition at
least five times.
10. Return the thermostat to a normal temperature
setting before leaving the installation.
IMPORTANT:Only qualified personnel should
install or service BASO Gas Products®. If any faults are
detected, see Troubleshooting Table 2. If control
module has been opened or any attempts to repair are
done, the warranty is void.
Table 1: Red LED Indications, Normal Operation
Flash Code Flash Code Indication
Steady On Flame detected, main burner on
0.1 Second On
0.1 Second Off
0.5 Second On
0.5 Second Off
1.0 Second On
4.0 Second Off
Sequence of Operation
The heating cycle starts when a call for heat from the
thermostat supplies 24VAC to the 24V/TH terminal. After
a 1 second maximum diagnostic period, the control enters
pre-purge mode, after pre-purge time, the spark starts
and the gas valve opens, starting with the trial for ignition
period. If no pre-purge, trial for ignition mode begins
immediately (see Table 1 for red LED normal operation).
During the trial for ignition period, the control sparks while
rapidly flashing red LED. It then turns off the spark and
red LED while checking pilot flame sense. This cycle will
repeat until pilot flame is detected or trial time is over.
When pilot flame is detected, the spark stops, the gas
valve remains open and the red LED stays on
continuously. The control will remain in this state until the
pilot flame is lost or the call for heat ends. Model with no inter-purge, if the pilot flame is lost, the gas valve
remains open and a new trial for ignition will start. Model with inter-purge, if flame is lost within 5 seconds of an
established flame, the gas valve remains open; the control
initiates sparking, and begins a trial for ignition period
immediately. If flame is lost after 5 seconds of an
established flame, the gas valve will close, and the control
initiates the inter-purge time delay before beginning
another trial for ignition period. Model with no retry and one trial, if pilot flame is not detected during the trial for
ignition period, the gas valve will close. Lockout will occur
and a red LED will flash indicating an error (see Table 2
for proper diagnostics of the error). Remove power to end
lockout. Model with retry and three trials, if flame is not
sensed by the end of the trial for ignition time period, the
gas valve will close and the control module will initiate an
inter-purge time delay, followed by another trial for ignition
period (this occurs up to three trials). After the third trial,
the control will initiate a 5 minute retry period. If flame is
not sensed, the ignition sequence will repeat, until flame is
sensed. If flame still is not sensed, remove power to reset
the ignition.
Trial time spark on trying to light
pilot burner
Pre-Purge or Inter-Purge Time
Retry or Recycle Time
4 BG1100M Direct Spark Ignition Control Installation Instructions
Troubleshooting
If the system does not function properly, determine the
cause using the procedures in this section.
Before proceeding with troubleshooting the system, check
the following.
Preliminary Checks
Are you using resistive wire between the module
spark (10) and the pilot connection?
Are all mechanical and electrical connections tight?
Is the system wired and ground correctly?
Is gas inlet pressure per manufacturer’s
specifications?
Is the system powered?
Is the thermostat calling for heat?
!
WARNING:Risk of Personal Injury.
Do not place face, hands, or other parts of the body in
or near the burner area when the red LED is flashing
(retry mode). When the red LED is flashing, the control
may at any time (while in the retry mode) re-energize
the burner control system and ignite the burner which
may result in electric shock from contact with the
electrode or severe burn injury from firing of the burner.
Red LED Error Indications
If the control module’s internal diagnostics detect a fault it
will go into lockout. Spark and both valves will be turned
off. The red LED will flash an error code .25 seconds on
and .25 seconds off for each count of the error code with
1 second off between codes. The control will remain in
this condition until power is removed by turning off the call
for heat. A flashing red LED error code indicates either a
problem with wiring, or a component not working, or the
control module is faulty. Try to cycle the control again. If
the error repeats then see Table 2 for troubleshooting.
BG1100M Direct Spark Ignition Control Installation Instructions 5
Loading...
+ 10 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.