BASI BULT200 User Manual

Page 1
ULTRASONIC LEVELMETER
BULT200 MANUAL
Used for process control in the liquid/solid level and other objects position measurement
V 1.0 -2018
Page 2
Safety instructions
The instrument for low voltage DC power supply (DC24V), power supply should meet the technical requirements
The metal housing should be connected with the earth
Please read the manual of this instrument carefully before putting the instrument into operation
All operations described in this manual must be carried out only by trained specialist personnel
All rights reserved
Page 3
This manual is for products that have the appearance of the following electronic units:
Page 4
Table of contents
Page 5
1
1. Introduction
Uses:
Liquid level, solid level or object position measurement.
Application:
The liquid level surface , material surface or solid surface that the ultrasonic can transmission effectively. Such as: storage tanks, troughs, measuring boxes, ponds, tanks, wells, drains, granaries, silos, moving objects.
Features: Two-wire connection, strong ultrasonic emission, stable and
reliable measurement
Optional HART output function, HART7.5 version, and
backward compatible
Without HART hand-held Communicator, HART parameters
can be simply set by the instrument itself
Large LCD display, easy to debug and observe Over-voltage and over-current protection, lightning
protection
Intelligent signal processing technology to ensure that the
instrument to adapt to a variety of working conditions
All plastic probe,good acid and alkali anti-corrosion, to
adapt to harsh environments
The measuring range:
The meter has the following range specifications: Liquid level: 4m、6m、8m、12m、15m、20m、30m Solid Level: 3m、5m、7m、10m、15m
Note:
1. The above range is only for relatively calm liquid level measurement, for the liquid level fluctuations, liquid volatile easy to make the ultrasonic probe surface condensation,solid level measurement and other conditions, the effective range of about 50% of the above data, it is recommended to select a larger range (higher power) .
2. Outdoor installation in cold areas, should prevent the probe surface frost or icing.Probe lengthened type is optional, the probe can enter into the container inside.Or select the four-wire with probe heating function type.
Page 6
2
2. Structure:
4m、6m、8m 12m、20m、30m
20m、30m Horn Type (Small beam angle)
Page 7
3
3. Measuring principle
Level meter consists of an ultrasonic probe and an electronic unit.Level meter is mounted on top of the container, under the control of the electronic unit, the ultrasonic probe transmitting ultrasonic pulses to the measured object.Sound waves are reflected by the surface of the object, part of the echo received by the probe and converted to electrical signals.The meter measures the time between pulse transmission and reception. The time is proportional to the distance from the probe to the measured object. The electronic unit detects this time and calculates the measured distance based on the known sound velocity. Level value can be obtained by the subtraction.
The speed of ultrasonic wave in the air is affected by the air temperature, therefore, the Ambient temperature needs to be detected when the level meter works, and the sound speed is compensated to ensure the measurement accuracy .Blind zone: Span F may not extend into the blind zone B. Level echo from the blind zone cannot be evaluated due to the transient characteristics of the sensor.
Page 8
4
4. Technical data
The measuring range:
The blacking distance:(From the sensor surface)
Type
Condition
4m
6m
8m
12m
20m
30m
Relatively calm
liquid, flat solid
4.00m
6.00m
8.00m
12.00m
20.00m
30.00m
Drastic fluctuation,
strong volatile liquid
3.00m
4.00m
6.00m
9.00m
16.00m
25.00m
Blocky, particles
solid
4.00m
6.00m
12.00m
20.00m
MODEL
4m
6m
8m
12m
20m
30m
Blacking distance
0.20m
0.25m
0.30m
0.50m
0.80m
1.00m
Accuracy
0.2% of full span (in air,stationary plane, standard signal strength)
Display resolution
1mm (Less than 10m type) 1cm (more than 10m type)
Display
4 digit LCD
Output current
4-20mA (HART function is optional)
Output load
0-500Ω
Parameter set up
3 Membrane buttons
Temperature range
Electronic unit : -40℃~+75℃ ( LCD: -20℃~+70℃ ) Sensor(PVC/ABS): -40℃~+75℃ Sensor(PTFE/PVDF): -40℃~+100℃
Temperature compensation
Full range automatically.
Pressure range
-0.04~+0.1MP(Except for the following models) 4m/6m/8m,4m/6m/8m-F:-0.04~+0.2MP
Page 9
5
Mounting dimensions
4m-S、6m-S 4m 、6m 、8m、
12m(Standard) 12m-D(Small beam
angle)20m、30m
Power supply
DC24V(±10%),30mA
Cable diameter
6~12mm
Single wire diameter
0.5~1.78mm
Cable gland
PG13.5/M20
Measure cycle
1.5 second (changeable )
Beam angle
5º(3db) for range :12m-D and 20m,30m horn probe 8º(3db) for any other range probe
Housing material
Aluminium,Plastic(ABS)、
Sensor material
ABS/PVC/PTFE/PVDF
Protect grade
IP67
Fix
Thread ,flange or bracket
ABS/PVC Probe
Page 10
6
4m-F、6m-F
4m-S-F、6m-S-F 8m-F、12m-F 20m-F、30m-F
20m、30m Horn type
Horn probe with a smaller beam angle, suitable for narrow space level measurement
PTFE/PVDF Probe
Horn Probe
Page 11
7
Probe launch surface dimensions:
PTFE/PVDF probe is a flat probe, the front of other materials probe structure is horn.
Note: The detection distance and the dead zone value should be calculated from the launch surface of the probe.
Page 12
8
Panel layout of the electronics unit
Wiring diagram
Note: The power supply for the level meter is DC24v, please note the wiring marked, and the actual wiring marking on the level meter. The external loop should have a current supply capability of 30mA. Outdoor use, the metal housing should be connected to the earth, in order to ensure the instrument lightning protection capability.
Use a small slotted
screwdriver
Insert the wire as
shown above
Page 13
9
HART Communications and Settings (Optional).
Comply with the HART 7.5 standard ,backward compatible. Have been tested by the HART Foundation accredited
laboratory.
Part of HART settings can be setup by the instrument’s
button.
Support the common functions of the HART Communicator. Support all HART 7 Universal Command and some
Common Practice Command.
Common features:
Read and Write Identifier,Tags or Messages. Read Primary Variable(Level Value),Loop Current and
Percent Of Range.
Read Secondary Variable (Distance Value). Read Tertiary Variable (temperature Value ) . Write Polling Address(0~63). Set Range Value. Trim Loop Current.
Connection with the HART Communicator.
Page 14
10
Operation
Display and keys
The series is displayed with 4 digit LCD.
The series has 3 keys, with its functions as follow:
SEL
Selection of the display content or parameter
INC
Changing the value of the certain digit from 0 to 9
in turn
MOV
Selection of the digit to be changed
Two working mode
The instrument has two working mode:
Measurement mode Program mode.
Press SEL and MOV simultaneously to switch between these two mode. After entering the Program mode, the corresponding indicator will change.
Measurement mode
The level value、the distance value and the temperature value will be shown in turn by pressing the SEL key in measurement mode. Please pay attention to the indicate symbol:
Display Value
LCD
Description
Level Value
Flashing arrows point to L(Level)
Distance
Value
Flashing arrows point to D (Distance)
Temperature
Flashing arrows point to T (Temperature)
Page 15
11
POWER ON Power on the instrument shows the boot symbol. After a few seconds, the level or distance value is displayed.
The▲symbol flashes on the left of the screen, indicating that an echo is received.At the same time, the symbol ▲ point to
the variable abbreviation (L, D, T) on the panel to indicate the corresponding current display value.
When the meter is powered on, reset or exited from the parameter setting status, the level or distance value is first displayed, which is determined by the currently selected measurement variable (selected in the parameter setting).
KEYS Press the SEL ,the level meter can switch to select the display level value, distance value, temperature value.
Press the button should be released immediately.
In running state, INC/MOV key is invalid.
Press the SEL, MOV key together and instantly release the key to enter or exit the parameter setting state. RESET Press SEL and MOV at the same time and hold for more than 4s can reset the meter and enter into the parameter setting state, press the SEL, MOV key at the same time and instantly release to exit.
DISPLAY AND CURRENT OUTPUT
Level and distance unit is the meter(foot can be set in the inner setting), the temperature is °C.
The distance value is directly obtained by the level meter, level value is the installation height value to subtract the measured distance value obtained. Therefore, the distance value must be accurate, the installation height must be accurately set.
Ambient temperature affects the accuracy of sound velocity, temperature values should be displayed correctly.
Without HART function, the current output corresponds to the measured variable (level or distance) selected in the parameter. With HART function, the current corresponds to the level only.
Installation height must be accurate and should be greater than or equal to the distance measurement value.If it
Page 16
12
is less than the distance measurement value, then the left two symbols flashing at the same time,the level value and the corresponding current value does not change, but the distance value changes(If the PV is set as the distance value, the current output changes).
If the level meter displays only the boot symbol for a long time after power on, or if the SEL key is pressed, the instrument level and distance measurement display 0.000 while the symbol do not flashing that the level meter fails to work normally.
Program mode
When SEL and MOV keys are pressed simultaneously, the instrument can enter or exit of the mode.
Press SEL key to select the content in turn in program mode, please pay attention to the symbol in the following examples.
Parameters
Significance
Installation
height
The distance from the surface of the probe to the bottom of the container;unit is m(ft can be choose from the inner setting).
Full span
The 20mA output corresponding to the maximum value of the PV. Can also be programmed by the hart hand-held programmer.
Zero span
The 4mA output corresponding to the minimum value of the PV. Can also be programmed by the hart hand-held programmer.
PV select
Select the 4-20mA corresponding to the level or the distance value.When the setting is HL99 the current corresponding to the distance value. The any other value the current corresponding to the level value.(This parameter is not available with
Page 17
13
With HART function Without HART function
SET PARAMETERS
1. In Measurement mode, press SEL、MOV simultaneously
into program mode。 The LCD displays the value of Installation height:
2. press MOV,to select a certain bit, the bit will be dark, then
press INC to change the digit:
HART function, the current output corresponds to the level value.)
Address
select
Setting the local HART polling address (00~63) (This parameter is only available with HART function)
Inner
password
The password for inner parameters setting. Users do not need to set up this parameter.
Parameters
LCD
Installation
height
Full span
Zero span
Address
select
Inner
password
Parameters
LCD
Installation
height
Full span
Zero span
PV Select
Inner
password
Page 18
14
3. press MOV,to selcet other bits, and press INC to change
the digits:
4. press SEL to save the value and select next parameter, full
span:
5. as the same way, to change the value of full span.
6. press SEL to save the value and select next parameter,
zero span:
7. as the same way, to change the value of full span.
8. press SEL to save the value and select next parameter,
pv select or address select:(If there is no HART function, the parameters is pv select.)
9. as the same way, to change the value of pv selet.
10. the last parameter is inner password, it needn’t to be
change.
11. press SEL back to preceding parameters, check the
values.
12. press SEL and MOV simultaneously, the instrument can
exit of the operating mode.
Page 19
15
The current output correspondence
Current = [(PV(Primary Variable)-Zero span) / (Full span- Zero
span)] *16mA + 4mA e.g: ①The Primary variable is Level (the variable is selected as
HL00), the Level value is 3.626m, the Full scale is set to
6.000m, the Zero scale is set to 0.000m, the current output is: [(3.626-0.00)/(6.000-0.000)] *16mA +4mA = 13.67mA
PV is level value (HL00)
② The Primary variable is distance (the variable is selected as HL99), the distance value is 2.365m, the Full scale is set to
6.000m, the Zero scale is set to 0.500m, the current output is: [(2.365-0.500)/(6.000-0.500)] *16mA +4mA = 9.43mA
Page 20
16
PV is distance value (HL99)
Instrument inspection
1.Power supply should be correctly connected by the identification . The voltage of Level meter is DC24V. External power supply should have a 30mA current supply capability to meet the startup current requirements.
2. Place the the level meter perpendicular to the wall, the measured distance must not within the blind distance and there should no obstacles. Power up the level meter.
3. The level meter first shows the boot symbol and then shows the level value.
4. Press the SEL key, the meter can switch display distance value, temperature value and level value.
5. Slowly move the level meter, the level or distance value displayed on the meter should be changed accordingly.
When moving within close range (1m), speed should not exceed 0.1m / s. There is a detection window inside the level meter. The target beyond the detection window needs to have a judgment time of about 5s. The measurement window below 10m is usually ± 0.5m, and the window above 10m is ± 1.2m. Due to the detection window, the distance sudden change from far to near about 1/2 of the distance , errors may be occur. The sudden change of distance usually does not exist in the actual measurement.
6. Press SEL and MOV keys simultaneously to enter the program mode, set the installation height, full scale, zero scale and other parameters
Page 21
17
The installation height must be greater than or equal to the maximum distance value of the level meter. If the distance value is greater than the installation height, the left symbol flashes, the level value does not change, and the current output does not change if PV is set as the level value. But if the PV is set as the distance value ,the current will change.
7. Use ammeter to measure 4-20mA current output.
8. Connect the HART hand-held communicator to the level meter to test the functions related to HART communication. The full scale , zero scale and POLLING address via the
HART hand-held communicator is the same as the result set by the keys on the meter. Installation height can not be set by the HART hand-held communicator.
Page 22
18
5. Installation
Reasonable installation is critical factor of the
instrument’s normal working.
Level meter installed in the top of the container. Probe launch surface perpendicular to the liquid or material surface. If a sealed container mounting flange should be used. Other cases can be mounted bracket.
Flange mounting, plastic flange recommendations formulated according to the size of the thread on the level meter. 20m, 30m horn type level gauge has been directly equipped with flange (DN200).
Flange mounting Bracket mounting Mounting measures
■ Ultrasonic emission, having a small spread angle. If other objects within the spread angle obstruct and form equal to or less than 90°reflection angle, reflection will occur. If the reflection is very strong, measurement errors will result. The smooth and flat side of the container does not reflect the ultrasonic waves coming from above. The installation
distance between the meter and the side wall should be
Page 23
19
more than 10% of the measuring range and not less than
0.4m.
■ When flange mounting,plastic material flange is recommended. It is best to specify the size of the installation flange when ordering, direct preparation by the manufacturer.
If installed on metal flange or metal thread, please install
as above. To avoid resonance, resulting in measurement errors (large measure liquid level than actual value)
■ In the case of a closed container, the flanges and short tube on the container shall meet the following requirements:
■Install the installation as far away from the uneven container wall, away from the ladder in the container, sprue, mixing
Type
4m、6m、8m
12m、20m、30m
20m、30m Horn
Requirement
Flange diameter should not be less than 65mm,short socket of the inner wall is smooth and large diameter,the length should be short, < 400mm.
Flange diameter should not be less than 100mm, flange socket length should be less than 150mm and the inner wall is smooth. The probe should extend from the mounting opening.
Flange diameter should not be less than 200mm, flange socket length should be less than 200mm, the probe should be extended from the mounting opening.
Page 24
20
blades and other things that can block the sound waves.
■Installation port, flange socket too long, will affect the sound wave propagation,reduced effective range. The probe should be extended from the mounting opening or close to it
■ If there is fluctuation in liquid level, or if there are float balls, foam, strong liquid volatility, probe easy condensation, objects that block sound waves, etc., which can be solved by adding a plastic tube to the container,so that the sound waves spread only in the plastic pipe,to ensure the stable and reliable of the measurement .It requires plastic pipe wall is smooth, flat, seamless.The pipe should from the flange to the bottom of the container. Two small holes must open in upper and lower ends of each side of the tube , to ensure consistent level of inner and outer tube. If the plastic tube can not be down to the bottom of the container, a oblique truncated short tube can be used to shield false signal .
Page 25
21
Add plastic tube effectively eliminate Add inclined plastic tube shielding all kinds of interference and improve produce false signal location detection ability
Add plastic tube to make level Level measurement instrument measurement stable installation position and angle signal position
■Make sure the distance between the probe surface and the maximum level exceeds the blind distance. Instrument can be properly increased the height of installation. When using the closed container, the inner wall of the the tube should be smooth, and its inner diameter should not be larger than the inner diameter of the flange of the container. The increased height installation will reduce the effective range.
Page 26
22
Level meter higher installation, Probe lengthened, to avoid
eliminate blind effect frosting, icing
■ When install to the cold area, such as measuring the
level of liquid in a closed container, should choose the lengthen probe of the level meter ,make the sensor extend
into the container to avoid frosting or freezing.
Or select a four-wire level meter with electric heating function.
■ level meter probe launch surface should be as vertical
as possible
to the liquid or material surface.
Page 27
23
Level meter installation is not vertical, the measurement level value may be smaller than the actual value or impossible to measure
Irregular openings, easy to produce false signals, plastic short tube can be mounted or choose the lengthen probe type.
Power work
The meter will first appear the boot logo after it is powered on. The level value will be displayed after a few seconds, while
the ▲ symbol on the left side of the display flashes, indicating
that an echo has been received.
The actual measurement of the level meter is the distance from the probe to the liquid surface or material surface, then converted to the level value, which is very important principle.
Press the SEL key to view the distance value and temperature values. If the distance value is the same as the actual value, it indicates that the level meter status is good state and the relevant parameters can be set.
Page 28
24
Press SEL and MOV keys simultaneously to enter the program mode, set the installation height, full scale, zero scale and other parameters, then press the SEL button to save. Then press MOV, SEL simultaneously to return to measurement status. The meter will display the correct level value while outputting the correct current signal.
The relevant HART communication parameters can also be set via the Hart hand-held Communicator.
If there is a measurement error, please refer to the section "Troubleshooting" below and read through the " Installation" section again to identify the problem and resolve it, or consult the manufacturer.
Instrument seal
After the instrument setting is completed and working , Tighten the water proof cable gland, the cable is preferably to bend downwardly , to prevent water infiltration.
Incorrect Correct
Page 29
25
6. Troubleshooting
The failure of the meter should be judged from the following aspects:
1.First of all, to determine whether the instrument power
supply is normal.
2. After that, confirm that the instrument itself has no
trouble.
Align the meter with the ground or wall to see if the meter can be properly tested.
3. Check the parameter settings to confirm that the
parameters are set correctly.
4. Compare the mounting requirements, check the
mounting.
5. Check the application environment, whether there are
adverse factors affecting the measurement.
6. Check whether the level metre had been water
damaged, causing corrosion of the electronic circuit.
7. Refer to the next page of the symptoms and solve the
problem.
8. Consult the the level meter supplier or manufacturer.
Page 30
26
Trouble-shooting
Trouble Phenomenon
Trouble Reason
Solution
The level meter does not display
Power supply error.
Wiring error.
Instrument water, corrosion of the corridor line
Check the power supply and the current output
Check the wiring.
Return to factory maintenance
The meter is display but it does not work
Or sometimes impossible to measure
The sensor doesn’t aim at the liquid or the material.
The surface has great fluctuations or large volatile liquid
Liquid surface with lots of foam.
The container is empty and the bottom is not flat.
Over the range.
Adjust the sensor and aim at the material.
Add a tube to the container or switch to a larger
range of level meter
Add a tube to the container or use radar level meter
Use instrument with a lager range. Use instrument with a lager range.
The instrument shows unstable or the
measured value has a great deviation.
The level enters the blanking distance.
There is strong electromagnetic interference
There is Obstruction of the ultrasonic wave.
Increase the installation height of the instrument. or
prevent the level too high.
Increase shielding to the instrument.
Change the installation site or using a plastic tube.