BASI BPT50-A Operation Manual

Page 1
BASI Instrument AB, P.O.Box 53, SE-275 06 VOLLSJÖ, SWEDEN tel: +46 (0)40 88009, fax: +46 (0)40 929877, e-mail: [email protected]
PRESSURE TRANSMITTER WITH DISPLAY
v1-2-03.13
OPERATION MANUAL
Please read this Operation Manual before mounting and operating!
Save the Manual for future references!
Page 2
Overview
2
BPT50-A is a combination of a pressure sensor and a programmable loop­powered 5-digit LCD display that allows visualization of the measured pressure from -9999 to 9999 units. BPT50-A is also equipped with a programmable pressure alarm driving a low-power electronic relay output which can also be used to activate various electric actuators for ON/OFF pressure control.
Mounting and Wiring
Important note:
If the medium temperature is higher than the maximum, specified for your transmitter, mount an additional cooling spiral tube between the object and the transmitter in order to decrease the medium temperature at the transmitter input.
Mounting
Screw the BPT50-A transmitter to its
exact place using a preinstalled bush with a female thread matching the transmitter's one (¼", ½", etc.).
To ensure hermetical mounting,
use a proper gasket (e.g. DIN16258).
The right tightening torque depends
on the gasket material and shape as well as on the mounting thread.
For mounting, use ONLY a proper
hexagonal wrench applying the torque ONLY to the hexahedral transmitter head!
The installation site must be
protected from deep-freezing and high-temperature sources, and all environmental conditions must be within those, specified for your transmitter type (see 'Specifications').
Wiring
Connect the transmitter via detachable connector Mini-HIRSCHMAN by following the markings as shown on the left.
Important note:
The supply voltage must be greater than the required minimum (marked on the label) plus the load voltage drop at 20 mA!
Page 3
Parameter Programming
3
Some parameters
are accessible only when the respective functionality is installed. (see 'Specifications').
- Changing
Point Position value reflects on the real value of all parameters with ISU!
E.g.: changing
Point Position value from (0) to (0.0) would change a Set-point value of 100 to 10.0!!!
Device parameters
BPT50-A is a programmable device whose service behavior is determined by a set of parameters. All the parameters, along with their names, symbols, and value ranges, are given in Table 1.
Setting numerical parameter value
Enter parameter value adjustment mode
(see 'Program Levels').
The whole part of the value together with
the left zeroes appears on the display, and the rightmost digit blinks.
To select another digit, press . The 4 rightmost digits can accept values
from 0 to 9, and the leftmost digit can accept the value - or none.
To increase or decrease the blinking digit
value, use respectively or .
Confirm the adjusted value by pressing
simultaneously + .
If the new value has not been confirmed
and no key has been pressed for a certain period of time, value adjustment automatically ceases, and the parameter retains its initial value.
Setting symbolic parameter value
Enter parameter value adjustment mode
(see 'Program Levels').
Read the blinking parameter value. To change the value, use or ,
and to confirm, press + .
If the new value has not been confirmed
and no key has been pressed for a certain period of time, value adjustment automatically ceases, and the parameter retains its initial value.
Page 4
Table 1
Notes
Configuration Parameters
when indicating values
with the input-signal measurement unit (ISU)
display offset value
higher value for better filtration
For authorized personnel ONLY!
DO NOT SET to YES!
++L_ - activates under set point,
_V++- activates over set point
Keyboard Locking Parameter (parameter of Hidden level)
d"EY (keyboard disabled),
ESP (only set-point adjustment enabled),
E"EY (keyboard enabled)
Unit
-
ISU
ISU
ISU
- - ­ISU
-
-
Value
0, 0.0, 0.00, 0.000
-9999 ... 9999
-9999 ... 9999
-9999 ... 9999
0…255
0…3000
no, YES
-9999 ... 9999
++L_, _V++
d"EY,
ESP,
E"EY
Description
Display decimal point position
Display value at low limit of the input range
Display value at high limit of the input range
Constant to be added to the measured input value
Relative time constant of the input filter
Zone around the measured value,
within which the filter is active
Enables / disables calibration mode.
Set-point value of the alarm output
Control action direction of the alarm output
Keyboard locking mode
Symbol
Pnt
ILo
IHi oFFS
\t
\b
cALE
SP1
dir1 Loc"
Parameter
Point Position
Display Low
Display High
Display Offset
Filter Time
Filter Band
Calibration
Set Point
Direction
Lock
Keyboard
Page 5
Program Levels
5
Programming order
Unlock the keyboard. Adjust the configuration parameters. If needed, restrict the access again
by adjusting the Lock Keyboard parameter.
Access control (Hidden level)
Hold
depressed while turning
the power supply on and until Loc" appears.
Set keyboard locking mode
according to Table 1.
Basic level
At power-on, BPT50-A enters Basic level. At this level, the device indicates the measured pressure with a resolution, according to the Point Position parameter.
If the measured value is greater than
Display High + 10, the display shows blinking error message {++}.
When the measured value is less than
Display Low - 10, L__V is displayed.
Either error message may appear
on the display also as a result of a damaged sensor.
Configuration level
Enter from Basic level by pressing
and holding until conF appears on the display.
Choose a parameter using or
.
To enter parameter value
adjustment mode, press .
If no key has been pressed for a while,
the device automatically returns to Basic level, storing all confirmed changes.
For quick exiting and saving,
use key combination + or select rtn and press .
Page 6
Output Control
6
Alarm output operation
The alarm output operates
according to the control algorithm parameters.
The sign in the upper left
display corner indicates activated alarm output.
ON/OFF control algorithm
The static characteristic of an alarm relay controlled by an ON/OFF algorithm is shown on the left drawing.
Input Filtration
Low-pass filter
This first-order filter acts ONLY within a certain band around filter output value. This has been designed to cut periodic noises outside the communication signal spectrum.
Filter operation is defined
by two parameters:
Filter Time (defines filter time
constant) and Filter Band (defines filter active band around filter output value).
If the newly measured value
differs from the filter output by more than Filter Band, the filter resets with a new initial output value (newly measured value).
Page 7
Waste Disposal
7
Do not dispose of electronic devices together with household waste material!
If disposed of within European Union, this product should be treated and recycled in accordance with the laws of your jurisdiction implementing the WEEE Directive 2002/96 on the Waste Electrical and Electronic Equipment.
Page 8
Specifications
8
Pressure Range Output Signal Alarm Output
Power Supply UB Voltage Deviation Loop Voltage Drop Maximum Line Load Medium Temperature Ambient Temperature Sensor Accuracy Display Error Sensor Temperature Drift Display Temperature Drift Response Time Overload Process Connection
Protection Class: sensor / display
.......................... bar
4…20 mA, 2-wire
SSR 0.12A/240V,  MOS gate 0.1A/60V
16…32 VDC,  ...............................
2% at 50/60 Hz max. 6 V RA[] = (UB[V] - 14 V) / 0.02 A
-30…85 °C
-20…70 °C
1.0% (at medium temperature 10...40 °C) 0.1% from span
0.02% from span for 1 °C
0.01% from span for 1 °C 10 ms (0...99% of span)
1.5 x full span
G¼", G½", ¼" NPT, ½" NPT,
 ....................................
IP65 / IP44
Warranty and Support
………………………….
serial number
………………………….
manufacturing date
QC check mark …….……(passed)
(stamp)
BASI Instrument AB p.o.box 53 SE-275 06 VOLLSJÖ, SWEDEN
tel: +46 (0)40 88009 fax: +46 (0)40 929877 e-mail: [email protected]
QD-8.2.4-WC
Warranty
BASI Instrument AB warrants this product to be free from defects in materials and workmanship for 2 years. If your unit is found to be defective within that time, we will promptly repair or replace it. This warranty does not cover accidental damage, wear or tear, or consequential or incidental loss. This warranty does not cover any defects caused by wrong transportation, storage, installation, or operating (see 'Specifications').
Technical support
In the unlikely event that you encounter a problem with your BASI device, please call your local dealer or contact directly our support team.
Loading...