Congratulations on selecting the WaterTec™ S100 kit, the industry’s
leading soil-moisture sensing unit for residential and small commercial
applications.
The following manual will guide you step-by-step through the installation
process. Pages 11-17 contain troubleshooting steps to further assist in
your installation. Additional information can be found online at
www.baselinesystems.com
Before You Get Started .............................................................................................3
Before installing your new WaterTec S100, operate the sprinkler system to ensure the system
is functioning properly and all heads are properly adjusted. For best results you will need
to know the distribution rate of your sprinklers as this usually varies greatly from zone to
zone. Ideally each zone would receive the same amount of water (1/2” to 3/4”). Baseline
recommends that, prior to installation, you replace any back-up batteries your timer
requires. You may need to refer to the original owner’s manual.
A Soil Moisture: Water content present in the soil
• Value is displayed by default when no buttons are pressed or held.
• Soil moisture level is displayed as volumetric, ranging from 0.0 to 50.0.
B Sensor Update:
• Brief button press: Causes the biSensor to take a moisture reading.
• Hold button: Displays current Moisture Threshold value. See below for
operation.
C Bypass: Allows the sprinkler timer to operate without interruption from the
S100. Bypass mode is indicated by a periodic flashing of “OFF” on the S100
display.
• Brief button press: Toggle the Bypass function. When enabled the Allow
Water light should turn on.
• Hold button: Holding the Bypass button for 2 seconds displays the current
Cycle Window duration. Use (+)/(-) buttons while holding Bypass to change
the Cycle Window to a value between 0 and 24 hours. Default is 12 hours.
D Moisture Threshold: Soil moisture value at which the S100 will allow watering.
• While “Sensor Update” button is being held, use (+)/(-) buttons to change
the moisture threshold.
E Cycle Window: The cycle window is the time allowed to complete a water
cycle once your soil moisture has reached your soil moisture threshold.
FValve Active: This light indicates that the valve the biSensor is attached to
is currently active (watering).
G Allow Water: This light indicates that the S100 is allowing your sprinkler timer
to water based upon its user defined settings (the system will begin watering
at the next start time programmed on the sprinkler timer).
H Wire Harness: Wires are attached from the sprinkler timer to the S100 here.
Setup Operations: Calibration Cycle
(for initial installation or biSensor repositioning
• Hold the (+)(-) and (Bypass) buttons simultaneously for 3 seconds. The screen
will flash between “CAL” “24 H” and the current moisture reading. The “24
H” will count down on the hour until the calibration is complete. Watering
is paused during this time.
Communication Test: The S100 communicates with the biSensor for about two
minutes, checking for any potential errors
.
• Hold the (+)(-) and (Sensor Update) buttons simultaneously for 3 seconds.
For more information, see Step 1 on page 15 in the Troubleshooting section.
4
WaterTec S100 Manual Aug06 Rev. 1
)
Step 1 biSensor Placement
When planning the biSensor location, take into account variables such as
distribution rate, sun exposure and soil type, or other site specific characteristics
that may affect water holding capacity or the rate at which plants use water.
The location of the biSensor will determine how frequently your sprinkler system
is allowed to water.
than average it will cause your system to operate less frequently, possibly causing
dry spots. If the biSensor is placed in an area that receives less than average
water it will cause the system to operate more frequently.
Baseline biSensor placement recommendations:
• Place the biSensor near the center of a zone (should only receive water
from one zone).
• Place the biSensor in an area that receives average to slightly below average
water.
• Keep away from sidewalks and driveways to avoid water from car washing
or other factors.
If the biSensor is placed in an area that is generally wetter
The illustration to the
right identifies heavy
shadow and runoff
areas in Red and
ideal locations in
Light Green. Avoid
Red areas when
installing your
biSensor. Dark
Green areas with
some shadow can
be used as a
secondary location.
SENSOR
LOCATION
SECONDARY
LOCATION
SENSOR
LOCATION
SENSOR LOCATION
SECONDARY
LOCATION
SENSOR
LOCATION
N
note
WaterTec S100 Manual Aug06 Rev. 1
Note: When installing the biSensor connect it to the most
convenient valve. This connection is used for communication.
5
Step 2
Determining Your Wiring Configuration
Option A: This is the most common option and will work on any timer that has
an accessible 24VAC power source.
Option B: This option is used for systems with zones requiring more frequent
watering than the biSensor controlled zones utilizing Baseline's Drip Bypass.
(DRIP BYPASS SOLD SEPARATELY)
Option A
Connect wires A and B (red and blue) to the 24V connectors on the sprinkler timer
Connect wires C and E (yellow and white) to the common on the sprinkler timer
Connect wire D (brown) to the valve common
Connect wire F (green) to the valve with the sensor
Soil Moisture
Soil Moisture
Soil Moisture
Bypass (allow water)
Bypass (allow water)
Bypass (allow water)
Hold to adjust Cycle Window
Hold to adjust Cycle Window
Hold to adjust Cycle Window
Valve Common Interrupter
www.baselinesystems.com
www.baselinesystems.com
www.baselinesystems.com
+
+
+
Moisture Threshold/
Moisture Threshold/
Moisture Threshold/
Cycle Window
Cycle Window
Cycle Window
-
-
-
A - 24 VAC
A - 24 VAC
A - 24 VAC
B - 24 VAC
B - 24 VAC
B - 24 VAC
A B C D E F
A B C D E F
A B C D E F
C - Interrupt 1
C - Interrupt 1
Sensor Update
Sensor Update
Sensor Update
Hold to adjust Threshold
Hold to adjust Threshold
Hold to adjust Threshold
Valve
Valve
Valve
Active
Active
Active
Allow
Allow
Allow
Water
Water
Water
C - Interrupt 1
D - Interrupt 2
D - Interrupt 2
D - Interrupt 2
E - Common
E - Common
E - Common
F - Sensor
F - Sensor
F - Sensor
SPRINKLER TIMER
24V COM 1 2 3 4 5 6 7 8
Connect sensor wires across valve solenoid.
Option B
Connect wires A and B (red and blue) to the 24V connectors on the sprinkler timer
Connect wires C and E (yellow and white) to the common on the sprinkler timer
Connect wire D (brown) to the valve common
Connect wire F (green) to the valve with the sensor
Soil Moisture
Soil Moisture
Soil Moisture
Sensor Update
Sensor Update
Sensor Update
Hold to adjust Threshold
Hold to adjust Threshold
Hold to adjust Threshold
Bypass (allow water)
Bypass (allow water)
Bypass (allow water)
Hold to adjust Cycle Window
Hold to adjust Cycle Window
Hold to adjust Cycle Window
Drip Bypass
www.baselinesystems.com
www.baselinesystems.com
www.baselinesystems.com
+
+
+
Moisture Threshold/
Moisture Threshold/
Moisture Threshold/
Cycle Window
Cycle Window
Cycle Window
-
-
-
A - 24 VAC
A - 24 VAC
A - 24 VAC
B - 24 VAC
B - 24 VAC
B - 24 VAC
A B C D E F
A B C D E F
A B C D E F
C - Interrupt 1
C - Interrupt 1
Valve
Valve
Valve
Active
Active
Active
Allow
Allow
Allow
Water
Water
Water
C - Interrupt 1
D - Interrupt 2
D - Interrupt 2
D - Interrupt 2
E - Common
E - Common
E - Common
F - Sensor
F - Sensor
F - Sensor
SPRINKLER TIMER
24V COM 1 2 3 4 5 6 7 8
Connect sensor wires across valve solenoid.
6
WaterTec S100 Manual Aug06 Rev. 1
Loading...
+ 14 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.