Baseline BHM Series Hydrometers
with Incorporated Flow biCoders
Installation Instructions
1. Power off the two-wire when installing any two-wire device. Leave 24 to 36 inches of slack in
the two-wire at the connection point to allow for easy installation and maintenance.
2. Follow the instructions in the Netafim installation manual to install the flow meter.
3. Connect the red and black wires from the flow biCoder to the corresponding red and black
wires from the two-wire path. Make certain to maintain polarity. All two-wire connections
must have DBR/Y or equivalent moisture-resistant connectors.
4. Follow the instructions in the controller’s user manual to configure each device. For normally
open master valves, configure the master valve as normally open in the controller as
instructed in the controller’s user manual.
Flow biCoder that is aached
to the ow meter
Always use appropriate
moisture-resistant connectors
Connect the red wire from the
biCoder to the red wire on the
two-wire path. Do the same
for the black wires.
1-866-294-5847 Rev 1.3.2013 www.baselinesystems.com
Baseline BHM Series Hydrometers
with Incorporated Flow biCoders
K-Value and Oset Table for Each Model
Model Gallons per Pulse Pulses per Gallon K-Value Offset Suggested Operating
Range (GPM)
BL-BHM150 0.0053 188.68 0.318 0 1.8-55
BL-BHM150-NO 0.0053 188.68 0.318 0 1.8-55
BL-BHM200 0.0085 117.65 0.51 0 5.3-95
BL-BHM200-NO 0.0085 117.65 0.51 0 5.3-95
BL-BHM300 0.0205 48.78 1.23 0 14-220
BL-BHM300-NO 0.0205 48.78 1.23 0 14-220
BL-BHM400 0.0556 17.993 3.335 0 21-380
BL-BHM400-NO 0.0556 17.993 3.335 0 21-380
1-866-294-5847 Rev 1.3.2013 www.baselinesystems.com