Baseline Systems Baseline BFM User Manual

Baseline BFM Series Flow Meters
Installation Guide
Installation Instructions
1. Power off the two-wire when installing any two-wire device. Leave 24 to 36 inches of slack in the two-wire at the connection point to allow for easy installation and maintenance.
2. Follow the instructions in the Netafim installation manual to install the flow meter.
3. Connect the red and black wires from the flow biCoder to the corresponding red and black wires from the two-wire path. Make certain to maintain polarity. All two-wire connections must have DBR/Y or equivalent moisture-resistant connectors.
4. Follow the instructions in the controller’s user manual to configure each device.
Always use appropriate
moisture-resistant connectors
Connect the red wire from the
biCoder to the red wire on the
two-wire path. Do the same
Flow biCoder that is aached
to the ow meter
K Value and Offset Table
Model Gallons per Pulse Pulses per Gallon K-Value Oset Suggested Operang Range (GPM)
BL-BFM075 0.015 666.67 0.09 0 0.2-11
BL-BFM100 0.0021 476.19 0.126 0 0.3-15.4
BL-BFM150 0.0074 135.14 0.444 0 0.9-44
for the black wires.
1-866-294-5847 Rev 11042013 www.baselinesystems.com