TankScan™ W-Series
WL2 Level Monitor
Installation Manual
Version 99L16wz
ID#11683
PRELIMINARY
The TankScan Wireless Level System WL2 Monitor consists of an
electronics housing and a "waveguide" probe for measuring tank fluid level.
System Installation Steps
A. Install controller (distance & line-of-sight location predetermined).
B. Install monitor(s) on the tank(s)
C. Install fill indicator(s) at a accessible location near the fill point.
D. Install software on host PC
E. Power up and configure the controller
F. Power up the monitor(s) and fill unit(s).
Monitor Installation
Precautions
A. Ensure the bottom of the probe (weight) does not rest
on the bottom of the tank, because the waveguide wire
may become slack — resulting in measurement errors.
B. Ensure the probe waveguide wire does not
touch anything inside the tank (e.g., riser) —
if it does, it could cause false readings.
C. DO NOT install the monitor in a riser unless it has a
blank length (optional non-active coax probe extension) greater than the riser height.
1. Unpack Monitor assembly (carefully un-wind the probe's waveguide wire/
weight), then carefully hand-straighten the wire — making sure not to kink
or damage the wire.
2. Install Monitor — screw bottom of monitor into a 1-1/2 or 2 inch female
NPT connection — hand tighten only.
3. After installing and configuring the TankScan Controller, install Monitor's
Battery Pack (included). Remove the Monitor's compartment cover by
unscrewing the (2) screws (w/small bladed
screwdriver). Insert battery pack into compartment and plug keyed connector into the socket
(on right). Finally, position the wires to prevent
damage, then reattach the cover.
NPT
Connector
4/2001
Battery
Compartment
Socket
1
Specifications
WL2x Level Monitor
Measurement Method .............. Micropower Impulse Radar (MIR)
Measured Value ...................... Level
Accuracy ................................ ±0.25" or 0.5% of probe length
(whichever is greater)
(1)
Output ................................... Transmits ID, level data, and diagnostics
Radio Communications ........... Transmits and receives up to 500' (150 m),
line-of-sight, in 902-928 MHz band (North
America) or 869.7-870 MHz band (Europe)
Operating Temperature ........... -40°F/°C to +140°F (+60°C)
Power Requirements ............... Battery Pack [4-AA Alkaline]
Construction ........................... Weatherproof, non-corrosive, NEMA-4/IP65
enclosure
Pressure Rating....................... 15 PSI (1 bar) maximum
Construction Materials ............. Teflon/Brass or Teflon/SST, Plastic (20% glass
filled Polybutylene Terephthalate polyester
(PBT), and Epoxy
Approvals............................... Intrinsically Safe;
CSA (Class I, Div. 1, Groups C & D);
EEx ia IIB T4; UL Pending
Mounting ............................... 2 inch and 1-1/2 inch NPT (standard)
Shipping Weight (approx.) ....... Monitor and Probe — 2.4 lbs (1.1 kg)
Notes: (1) Active probe length does not include top 3" (75 mm) or bottom 3" (75 mm) of
specified probe length. See dimension drawing below.
(2) Probe length should be selected so no portion will contact the tank bottom.
Dimensions
Replacement Parts List
Part Description Part Number
Battery Pack ........................... 0130-1043T (Standard, non-hazardous)
0130-1044T (Cenelec, intrinsically safe)
2