BARNSTEAD|THERMOLYNE FB1310M, FB1315M, FB1310M-26, FB1318M, FB1310M-33 Operation And Repair Manual And Parts List

...
Page 1
BARNSTEAD|THERMOLYNE CORPORATION
Type FB1300 & FB1400
Furnaces
OPERATION AND REPAIR MANUAL
AND PARTS LIST
SERIES 1256 & 1257
Model Numbers
FB1410M, FB1410M-26, FB1414M, FB1415M, FB1418M, FB1410M-33
LT1256X1 • 8/27/01 Serial Number
Page 2
Table of Contents
Safety Information ..............................................................................................................................................3
Important Information....................................................................................................................................3
Warnings ......................................................................................................................................................4
Introduction..........................................................................................................................................................5
Intended Use ................................................................................................................................................5
General Usage..............................................................................................................................................5
Principles of Operation ................................................................................................................................5
General Specifications ........................................................................................................................................6
Declaration of Conformity ............................................................................................................................7
Unpacking ..........................................................................................................................................................8
Installation ..........................................................................................................................................................9
Site Selection................................................................................................................................................9
Electrical Connections..................................................................................................................................9
Operation ..........................................................................................................................................................10
Power Switch..............................................................................................................................................10
Cycle Light..................................................................................................................................................10
Door Safety Switch ....................................................................................................................................10
Single Setpoint Controller ................................................................................................................................10
Basic Operation ..........................................................................................................................................11
Buttons and Indicators................................................................................................................................11
To View or Change the Setpoint ................................................................................................................12
To View the Display Units ..........................................................................................................................12
To View the % Output Power......................................................................................................................12
Controller Parameters ................................................................................................................................12
Alarms ........................................................................................................................................................13
Sensor Break Protection ............................................................................................................................14
Overt Temperature Protection (OTP)..........................................................................................................14
Tuning ........................................................................................................................................................15
Furnace Loading ..............................................................................................................................................16
Preventive Maintenance....................................................................................................................................17
Troubleshooting ................................................................................................................................................18
Maintenance and Servicing ..............................................................................................................................19
To Replace Heating Element......................................................................................................................19
To Replace Thermocouple..........................................................................................................................22
To Replace Insulation ................................................................................................................................24
To Replace Door Switches ........................................................................................................................25
To Replace Solid State Relay ....................................................................................................................26
To Replace PC Board (Controller)..............................................................................................................26
Wiring Diagram..................................................................................................................................................27
Exploded View ................................................................................................................................................28
Page 3
Important Information
This manual contains important operating and safety information. You must carefully read and understand the contents of this manual prior to the use of this equipment.
Your Thermolyne FB1300 Model or FB1400 Model Furnace has been designed with function, reliability, and safety in mind. It is your responsi­bility to install it in conformance with local elec­trical codes. For safe operation, please pay attention to the alert signals throughout the man­ual.
Warnings
To avoid electrical shock, this furnace must:
1. Use a properly grounded electrical outlet of correct voltage and current handling capacity.
2. Be disconnected from the power supply before servicing.
3. Have the door switch operating properly.
To avoid burns:
1. “Caution: Hot Surface. Avoid Contact.” Do not touch the exterior or interior sur­faces of the furnace during use or for a period of time after use.
To avoid personal injury:
1. Do not use in the presence of flammable or combustible materials — fire or explo­sion may result. This device contains components which may ignite such material.
2. Refer servicing to qualified personnel.
Safety Information
Alert Signals
Warning
Warnings alert you to a possibility of personal injury.
Caution
Cautions alert you to a possibility of damage to the equipment.
Note
Notes alert you to pertinent facts and conditions.
Hot Surface
Hot surfaces alert you to a possibility of personal injury if you come in contact with a surface during use or for a period of time after use.
Page 4
Please note the following WARNINGS:
WARNING
This warning is presented for compliance with California Proposition 65 and other regulato­ry agencies and only applies to the insulation in this product. This product contains refracto­ry ceramic, refractory ceramic fiber or fiberglass insulation, which can produce respirable dust or fibers during disassembly. Dust or fibers can cause irritation and can aggravate preexisting respiratory diseases. Refractory ceramic and refractory ceramic fibers (after reaching 1000°C) contain crystalline silica, which can cause lung damage (silicosis). The International Agency for Research on Cancer (IARC) has classified refractory ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to humans (Group 1).
The insulating materials can be located in the door, the hearth collar, in the chamber of the product or under the hot plate top. Tests performed by the manufacturer indicate that there is no risk of exposure to dust or respirable fibers resulting from operation of this product under normal conditions. However, there may be a risk of exposure to respirable dust or fibers when repairing or maintaining the insulating materials, or when otherwise disturbing them in a manner which causes release of dust or fibers. By using proper handling proce­dures and protective equipment you can work safely with these insulating materials and minimize any exposure. Refer to the appropriate Material Safety Data Sheets (MSDS) for information regarding proper handling and recommended protective equipment. For addi­tional MSDS copies, or additional information concerning the handling of refractory ceramic products, please contact the Customer Service Department at Barnstead|Thermolyne Corporation at 1-800-553-0039.
SAFETY INFORMATION
Page 5
Intended Use
The FB1300 Model and FB1400 Model fur­naces are general purpose laboratory and heat treating furnaces. For optimum element life, observe the following temperature ranges: 100°C (212°F) to 982°C (1800°F) for continuous use, or from 982°C (1800°F) to 1100°C (2012°F) for intermittent use. Continuous use is operating the furnace for more than three straight hours, and intermittent use is operating the furnace for less than three hours.
The unit consists of a heating chamber and a digital controller. See Figure 1 for the overall shape and general features of the unit.
General Usage
Do not use this product for anything other than its intended usage.
Principles of Operation
The furnace chamber is heated by a single three section resistant heater which is embed­ded in a refractory material. The chamber is insulated with a ceramic fiber insulation. The temperature is controlled by an electronic con­trol. The temperature is measured by a thermo­couple and is registered on a digital display. For safety, door switches are incorporated to remove power from the heating elements when the door is opened. The furnace is supported by the control section which also houses the elec­trical connections.
Introduction
Page 6
General Specifications
FB1300 Models
Dimensions: (handle not included)
Chamber: 4” W x 3.75” H x 4.5” D (10.2 x 9.5 x 11.4 cm)
Overall : 7.9” W x 13.8” H x 8.5” D (20.0 x 34.9 x 21.6 cm)
Weight: 15.7 lb. (7.1 kg) Electrical Ratings:
Model # Volts Amps Watts Phase Frequency FB1310M 220-240 4.4 1060 1 50/60 FB1310M-26 220-240 4.4 1060 1 50/60 FB1310M-33 220-240 4.4 1060 1 50/60 FB1314M 100 10.6 1060 1 50/60 FB1315M 120 8.9 1060 1 50/60 FB1318M 208 5.1 1060 1 50/60
Temperature: Operating Range (continuous): 982°C; (intermittent): 1100°C. Environmental Conditions:
Operating: 17°C - 27°C; 20% - 80% relative humidity, non-condensing. Installation Category II (over-voltage) in accordance with IEC 664. Pollution Degree 2 in accordance with IEC 664. Altitude limit: 2,000 meters. Storage: -25°C - 65°C; 20% - 80% relative humidity.
FB1400 Models
Dimensions: (handle not included) Chamber: 5.00” W x 4.25” H x 6.00” D (12.7 x 10.8 x 15.2 cm) Overall: 9.7” W x 15.8” H x 11.1” D (24.6 x 39.0 x 28.3 cm)
Weight: 23 lb. (10.4 kg) Electrical Ratings:
Model # Volts Amps Watts Phase Frequency
FB1410M 220-240 6.3 1520 1 50/60 FB1410M-26 220-240 6.3 1520 1 50/60 FB1410M-33 220-240 6.3 1520 1 50/60 FB1414M 100 14.5 1520 1 50/60 FB1415M 120 12 1450 1 50/60
FB1418M 208 7.3 1520 1 50/60
Temperature: Operating Range (continuous): 982°C; (intermittent): 1100°C.
Environmental Conditions:
Operating: 17°C - 27°C; 20% - 80% relative humidity, non-condensing. Installation Category II (over-voltage) in accordance with IEC 664. Pollution Degree 2 in accordance with IEC 664. Altitude limit: 2,000 meters. Storage: -25°C - 65°C; 20% - 80% relative humidity.
Page 7
Declaration of Conformity
Barnstead|Thermolyne hereby declares under its sole responsibility that this product conforms with the techni­cal requirements of the following standards (-33 models only):
EMC: EN 50081-1 Generic Emission Standard;
EN 50082-1 Generic Immunity Standard.
Safety: EN 1010-1-92 Safety requirements for
electrical equipment for measurement,control and laboratory use; Part I: General Requirements
EN 1010-2-010 Part II: Particular requirements
for laboratory equipment for the heating of materials
per the provisions of the Electromagnetic Compatibility Directive 89/336/EEC, as amended by 92/31/EEC and 93/68/EEC, and per the provisions of the Low Voltage Directive 73/23/EEC, as amended by 93/68/EEC.
The authorized representative located within the European Community is:
Electrothermal Engineering, Ltd.
419 Sutton Road
Southend On Sea
Essex SS2 5PH United Kingdom
Copies of the Declaration of Conformity are available upon request.
GENERAL SPECIFICATIONS
Page 8
Unpacking
1. Visually check for any physical damage to the shipping container.
2. Inspect the equipment surfaces that are adjacent to any damaged area.
3. Open the furnace door and remove the packing material from inside the furnace chamber.
4. Vacuum the chamber prior to use to remove the insulation dust due to shipment.
5. Retain the original packaging mate­rial if reshipment is foreseen or required.
Page 9
Installation
Caution
Be sure ambient temperature does not exceed 40°C (104°F). The rec­ommended ambient temperature is 17°C - 27°C. Ambients above this level may result in damage to the controller.
Caution
Allow at least six inches of space between the furnace and any com­bustible surface. This permits the heat from the furnace case to
escape so as not to create a pos-
sible fire hazard.
Site Selection
Install furnace on a sturdy surface and allow adequate space for ventilation.
Electrical Connections
The electrical ratings are located on the spec­ification plate on the back of the furnace. Consult Barnstead/Thermolyne if your electri­cal service is different than those listed on the specification plate. Be sure the front power switch is in the OFF position before connect­ing the furnace to your electrical supply.
Warning
To avoid electrical shock, this fur­nace must always use a properly grounded outlet of correct voltage and current handling capacity.
Page 10
Operation, All Modes
Warning
To avoid personal injury do not use in the presence of flammable or combustible chemicals; fire or explosion may result. This device contains components which may ignite such materials.
Power Switch
Both the ON/OFF power switch and the digital display will illuminate when power is switched
Hot Surface
Caution: Avoid Contact. To avoid burns, this furnace must not be touched on the exterior or interior surfaces during use or for a period of time after use.
ON. The furnace will begin to heat to the con­troller's current setpoint. (See the instructions for your type of controller for information on checking and setting the setpoint.)
Cycle Light
The amber cycle light will illuminate whenever the power is being applied to the heating ele­ments. The cycle light will turn on and off as the furnace reaches the setpoint.
Warning
Always wear safety glasses or a safety shield and high temperature gloves when loading or unloading the furnace. Long sleeved, fire retardant clothing and a fire retar­dant apron is also recommended.
Warning
To avoid electrical shock, the door safety switch must be operating properly.
Door Safety Switch
The door safety switch removes power from the heating elements when the door is opened. Open and close the door a few times; note that the amber CYCLE light will switch off when the door is opened. If this condition is not true, consult the Troubleshooting section before proceeding. This check must be done when the furnace is heating and the cycle light is illuminated.
Page 11
Single Setpoint Controller
Output 1
PAGE
Button
Single Setpoint Models
Output 2
SCROLL
Button
DOWN ARROW
Button
Temperature
Display
Display
Window
UP ARROW
Button
The single setpoint model furnace controller is a single setpoint controller which provides a single digital display to indicate the current chamber temperature or setpoint temperature. This temperature controller features sensor break protection and self-tuning capability.
Basic Operation
When the controller is turned ON it will per­form a short self-test and then display the measured value (process value) in the HOME DISPLAY.
Buttons and Indicators
OP1 (Output 1): Illuminates when the logic output is ON.
OP2 (Output 2): Illuminates when the relay output is ON (will go out during an alarm situ­ation).
PAGE button: Allows you to select a new list of parameters.
Note
If at any time you want to return to the HOME DISPLAY, simultane­ously press the PAGE and SCROLL buttons.
SCROLL button: Allows you to select a para­meter within a list of parameters.
DOWN button: Allows you to decrease a value.
UP button: Allows you to increase a value.
To View or Change the Setpoint
To view the setpoint, press and release the UP or DOWN buttons. If you want to change the setpoint, continue pressing until the
Page 12
SINGLE SETPOINT CONTROLLER
desired setpoint value is displayed and then release the button. A few seconds after the button is released, the controller will accept the new value and revert to the HOME DISPLAY.
To View the Display Units
From the HOME DISPLAY press the SCROLL button. The display will show the temperature units in °C/F/K and then return to the HOME DIS­PLAY. (Call Customer Service if you require a dif­ferent temperature unit.)
To View the % Output Power
From the HOME DISPLAY press the SCROLL button twice. Press and release the UP or DOWN button to view the % output power. This value is a read-only value and cannot be changed.
Controller Parameters
Home display
°C: Temperature units in Celsius. Temperature units can not be changed without entering the configuration. Contact Customer Service if a dif­ferent temperature unit is required.
OP: % output power demand. IdHi: Deviation high alarm.
Al List
IdHi: Deviation high alarm.
Page 13
SINGLE SETPOINT CONTROLLER
Atun List
tunE: One-shot autotune enable.
Pid List
Pb: Proportional band (in display units). ti: Integral time in seconds. td: Derivative time in seconds. ACCS List Code: Access code (Code need-
ed to enter or change the other configuration parameters which are not normally accessi­ble.) Not accessable.
Alarms
The controller will flash an alarm message in the home display if an alarm condition is detected.
2FSH: Measured value full scale high alarm.
IdHi: Measured value deviation high alarm. S.br: Sensor break: check that sensor is con-
nected correctly. L.br: Loop break: check that the heating cir-
cuits are working properly. Ld.F: Heater Circuit fault: indication of either
an open or short solid sate relay, a blown fuse, missing supply or open circuit heater.
Note
The following alarm messages are factory default settings and may vary if you have changed the configuration of your controller:
IDHi: = 50°C 2FSH = 1125°C
Page 14
SINGLE SETPOINT CONTROLLER
Sensor Break Protection
This controller provides sensor break protection in the event the thermocouple opens. If an open ther­mocouple condition occurs, the digital display will blink “S.br” and the power to the heating element will be shut OFF (Cycle light will extinguish).
Over-Temperature Protection (OTP)
The OTP will be in effect during any alarm condi­tion when the temperature of the furnace has devi­ated beyond the limit. The “Deviation High” alarm is the only alarm value which can be changed. To change it, press the SCROLL button until “IdHi” appears on the display. Press the UP or DOWN button to select the OTP value you desire. We rec­ommend a value of 20° above your working tem­perature to provide protection for your workload.
Tuning
This controller incorporates a self-tuning feature which determines the optimum control parameters for the best temperature accuracy with your load and setpoint. Use this feature the first time you use your furnace and each time you change either your setpoint or the type of load you are heating. Barnstead|Thermolyne recommends you use this feature to provide the best temperature accuracy the controller can attain. To use the tuning feature:
1. Adjust the setpoint to your desired value.
2. Press the PAGE button until display reads, “Atun.”
Note
Furnace must be at ambient temperature before starting a tune.
Page 15
SINGLE SETPOINT CONTROLLER
3. Press the SCROLL button. Display will read, “tunE.”
4. Press the UP or DOWN button to select, “on.”
5. Simultaneously press the PAGE and SCROLL buttons to return to the HOME DISPLAY. The display will alternately flash between “tunE” and the HOME DISPLAY while tuning is in progress.
6. The controller will then turn the heat­ing on and off to induce an oscillation. When the measured value reaches the required setpoint the first cycle will end.
7. Tuning will be complete after two oscillation cycles and then the tuner will turn itself off.
Note
Tune has completed when “tunE” stops flashing on display.
8. Normal control function will resume after the controller calculates tuning parameters.
Page 16
For best results of furnace loading, use less than two-thirds of any dimension of the chamber. Maintain a 3/4" clearance between the load and the sides of the chamber.
If you are heating a number of small parts, spread them throughout the mid­dle two thirds of the chamber.
Keep objects away from thermocouple.
Raise your load up off the furnace floor with small pieces of ceramic or a hearth plate to promote even heating.
Use insulated tongs and mittens when loading and unloading furnace.
Always wear safety glasses.
Furnace Loading
Caution
Do not overload your furnace chamber or allow the load to touch the thermocouple. If the load is to be heated uniformly, it should not occupy more than two-thirds of any dimension of the chamber. Failure to observe these cautions could result in damage to furnace components and/or load.
Page 17
Preventive Maintenance
Warning
Before using any cleaning or decontamination method except those recommended by Barnstead|Thermolyne, users should check with Barnstead|Thermolyne that the proposed method will not damage the equipment.
Contamination is a major cause of element failure, therefore, when possible, remove the fume forming material before heating (e.g., cleaning cutting oil from tool steel).
The resistance wire is high-grade nickel-chromium. Some chemicals, notably sulphur, halogens, and cyanides, attack this wire at high temperatures, so avoid spilling these chemicals in the furnace or heating them any hotter than necessary. The refractory cement helps to protect the wire, but will not completely immunize it from damage.
Warning
Disconnect the furnace from power supply before clean­ing.
Warning
Opening the door for an extended period of time will cause the painted surfaces above the door to be discol­ored or burnt.
All heating elements must be considered expend­able, and replacement is expected; however, rea­sonable care in their use will greatly extend the ser­vice they will give. As the manufacturer has no con­trol over the use or care of the elements, no specif­ic service guarantee can be made.
Housekeeping is vital to your electric furnace— KEEP IT CLEAN! Run your furnace up to 871°C (1600°F) empty occasionally to burn off the conta­mination that may exist on the insulation and ele­ments. Run for approximately two hours with the door slightly open. See warning.
Element life is reduced somewhat by repeated heating and cooling. If the furnace is to be used again within a few hours, it is best to keep it at the operating temperature or at a reduced level such as 260°C (500°F).
During normal use, the thermocouple in your fur­nace can become oxidized and cause inaccurate readings; therefore, we suggest that if you regularly use your furnace you should change your thermo­couple once every six months to assure the accura­cy of your controller readings.
Clean by wiping the outside case of the unit with a damp cloth and mild soap solution.
Page 18
Troubleshooting
Problem Possible Causes Corrective Action
The furnace does not heat No power. Check power source and fuses or (CYCLE light does not illuminate). breakers.
Power is not cut to heating elements Door switches are not functioning Re-align or replace door switches. when the door is open.
Defective electrical hookup. Repair electrical hookup. Thermocouple has oxidized and Replace thermocouple.
opened the circuit. (Open thermocouple is indicated on the display as a temperature of 0-5 degrees).
Fuse(s) blown Replace fuse(s). Controller malfunction. Replace controller. Door switches malfunction. Re-align or replace door safety switches. Defective solid state relay. Replace output relay.
Slow heatup. Low line voltage. Install line of sufficient size and proper
Heavy load in chamber. Lighten load in chamber. Wrong heating element. Install proper element.
Repeated element burnout. Overheating furnace. Keep furnace under maximum
Heating harmful materials. Enclose material in container. Clean up
Contamination present from Replace insulation material. pervious burnout.
Inaccurate temperature Oxidized or contaminated Replace thermocouple. readout. thermocouple.
Poor thermocouple connection. Tighten connections. Improper loading procedures. Use proper loading procedures. Poor ventilation of base. Clear area around furnace base. Thermocouple connections Reconnect thermocouple correctly.
reversed. (Indicated by downscaling of temperature on display.)
voltage. (Isolate furnace from other electrical loads.)
temperature.
spills in and on chamber. Ventilate chamber by opening door slightly when heating known harmful reagents.
Controller malfunction. Replace controller.
Page 19
Figure 3: Replacement of a Heating Element
Maintenance and Servicing
Warning
Disconnect the furnace from the power supply before servicing. Refer servicing to qualified personnel.
To Replace Heating Element
1. Set the furnace on its top. (See Figure 3). Remove thermocouple cover. (If equipped.)
Note
Perform only maintenance described in this manual. Contact an authorized dealer or our factory for parts and assistance.
Note
It is seldom necessary to dis­connect the thermocouple from the controller if the thermocou­ple is in good condition.
Thermocouple cover
Porcelin insulation
2. Remove screw and clamp holding ther­mocouple, then grasp the thermocouple at the bend where it enters the furnace chamber and pull straight back. Retain porcelain insulator.
3. When the thermocouple tip is clear of the furnace back, bend it out of the way.
4. Remove the screws holding the steel back plate to the case.
5. Remove the steel back plate.
Step 1(if equipped)
Heating element with rough side up
Straight edge (or board)
Step 4
Step 2
Bend up
Step 5 Step 6
Step 3
Page 20
MAINTENANCE AND SERVICING
Note
The hearth plate contains no heating coil, and may be saved for re-installation if it is in good condition. The hearth plate is replaceable independent of the heating element.
6. Remove the back insulation block by open­ing the door and gently pushing it out. Support this insulation block while removing it, as it is quite soft and easily crumbled at the edges.
7. Remove bottom cover to obtain access to terminals.
These steps will expose the heating element leads and insulating bushings in the bottom plate of the furnace.
8. Cut the element leads between the element and the terminal block. (There are two leads.) The element and hearth plate unit may now be removed by pushing it straight back out of the furnace. Use care not to damage the chamber insulation when removing the hearth plate and element as it can be reused if it has not been contaminat­ed.
9. Remove the old element lead wire and power wires from the terminal block, and save the sleeving for re-installation on the new element leads. Sleeving must be replaced if cracked or brittle!
10. New elements are shipped flat to protect them from damage in shipment, and to save space in storage. They must be formed before installation.
11. Place the element on a flat surface with the rough side up. Place a board or other straight edge along one row of notches.
12. Gently bend the element along the straight edge. The refractory cement will break along the row of notches.
Page 21
MAINTENANCE AND SERVICING
Note
Nicking or damaging the ele­ment leads will cause prema­ture element failure.
Make the bend 90°, avoiding excessive bend­ing. (The element wires will be exposed at the corner thus formed. This will not affect its life or performance.)
13. Bend the other side of the element.
14. Place the hearth plate across the open end of the ‘’U” shaped element.
15. Slide the element and hearth plate unit into the chamber, pushing it firmly against the hearth collar. Use care not to damage the soft insulation. Remove any crumbs of insulation that may get between the unit and the hearth collar.
16. Thread the element leads through the ceram­ic bushings. Bend the leads so they lie close to the refractory plate and the bottom insula­tion block. (The easiest and safest way to do this is to press the wire flat with a stick or blunt pusher. Do not use a sharp object or nick the wire.)
17. Replace the sleeving and bend the lead 3/4 turn around the terminal screw. Cut off the excess wire. Replace power wires on top of element lead wires and tighten screw. Do not cross the wire over itself around the terminal; this makes it difficult to keep the connection tight and prevents good electrical contact. If you have excess wire, cut it off. Make sure element lead wires are not touching any other wires.
18. Replace the back insulation block and back plate.
19. Examine the thermocouple, and, if it is good, reinsert it into the chamber. It should extend
Page 22
MAINTENANCE AND SERVICING
about 1-1/2" into the chamber. Make sure porcelain insulator is in place for the ther­mocouple to pass through on the steel back plate. Replace clamp and screw. (Excessive scaling, pitting, or cracks are some indications that the thermocouple may need to be replaced.)
20. Replace bottom cover of control unit.
21. Replace thermocouple cover.
22. If replacement of back insulation is neces­sary, carefully redrill hole for thermocou­ple, using back cover as guide.
23. Reconnect furnace to power supply.
24. Test operation of furnace.
Warning
Disconnect the furnace from the power supply before servicing.
Note
If the thermocouple touches metal, this could short out the signal, causing the control to display room temperature. This could cause the furnace temperature to run away, possibly damaging furnace compo­nents.
To Replace Thermocouple
1. Set furnace on its top.
2. Remove thermocouple cover. (If equipped.)
3. Remove screw and clamp holding the ther­mocouple, then grasp the thermocouple at the bend where it enters the chamber and pull it straight back from the furnace. Retain porcelain insulator.
4. Remove bottom cover.
5. Disconnect the thermocouple from the ter­minal block by removing the screws on the terminals. Pull the thermocouple through the hole in the furnace base and discard.
6. Insert the new thermocouple into the back of the furnace chamber. Make sure the porcelain insulator extends through the steel back plate to prevent the lead wires from touching metal.
Page 23
MAINTENANCE AND SERVICING
Note
If the control temperature display moves downward, the thermo­couple leads are reversed.
7. Thread the thermocouple through the hole in the base which has a nylon insulator, replace clamp and screw.
8. Bend the thermocouple sharply toward ter­minal block.
9. Secure the two yellow wires marked “+” together on the terminal block. Secure the two red wires “-” together on the adjacent terminal. Make sure connections are secure to terminal block.
A polarity test of the thermocouple and lead wire is easily made with the use of a magnet. On chromel alumel thermocouples and lead wire, the non-mag­netic wire is positive ( + ) and the magnetic wire is negative ( - ).
Warning
Disconnect furnace from power supply before servicing.
10. Replace bottom plate.
11. Replace thermocouple cover. (If equipped.)
12. Reconnect furnace to power supply.
13. Test operation of furnace.
To Replace Insulation
1. Remove thermocouple cover. (If equipped.)
2. Set furnace on its top and remove screw and clamp securing thermocouple, then grasp thermocouple and remove by pulling it straight back. Retain porcelain insulator.
3. Remove back plate.
4. Remove bottom cover.
5. Disconnect the element leads from terminal block.
Page 24
MAINTENANCE AND SERVICING
Note
Identify or mark wires discon­nected to ensure proper place­ment and connection when rein­stalling.
6. Disconnect thermocouple leads from terminal block.
7. Remove four nuts holding control section to furnace chamber.
8. Remove the ground nut.
9. Remove the control section from the furnace
chamber. Remove plates, screws, spacers
and nuts. Be sure to note how plates are assembled together for reassembly.
10. Remove back piece of insulation by opening door and pushing it out gently.
11. Remove bottom piece of insulation by lifting it out.
12. Remove element and hearth plate by pulling it straight back out of the furnace chamber.
(Be careful not to damage elements.)
13. Remove side insulating pieces.
14. To remove top insulating piece and hearth collar, position the furnace on its side. Remove both objects from furnace.
15. Reposition furnace on its top. Reinsert new hearth collar and the new top piece of insu­lation. Insert the new side pieces of insula­tion last.
16. Reinsert element and hearth plate unit into the chamber, pushing it firmly against the
hearth collar. (Be careful not to damage insulation.)
17. Reinsert new bottom piece of insulation over hearth plate. (Element leads and ceramic bushings should be exposed above insula-
tion bottom piece.)
Page 25
MAINTENANCE AND SERVICING
18. Thread the element leads and ceramic bushings through the bottom plate. Bend the leads so they lie close to the refractory
plate and the bottom insulation block. (The
easiest and safest way to do this is to press
the wire flat with a stick or blunt pusher. Do
not use a sharp object or nick the wire.) Secure plate to furnace chamber.
19. Reverse steps 1-9 to reassemble furnace.
To Replace Door Switches
1. Place furnace upside down and remove bot-
tom cover.
2. Disconnect wires from door switches. Identify
or mark wires disconnected from door switch-
es to ensure proper placement and connec­tion when reinstalling.
3. Remove two screws and nuts from door
switches and slide door switches out.
4. Install new door switches to bracket. Place furnace in an upright position. Adjust door
switches until a click is heard from the
switches, when furnace door is approximate­ly 2" from being completely closed. Secure
door switches to bracket.
5. Place furnace upside down. Reconnect the wires to new door switches.
6. Replace bottom cover and place furnace
upright.
7. Reconnect furnace to power supply.
8. Test operation of door switches as described in step 4.
Warning
Disconnect furnace from power supply before servicing.
Page 26
MAINTENANCE AND SERVICING
Warning
Disconnect furnace from power supply before servicing.
Warning
Disconnect furnace from power supply before servicing.
To Replace Solid State Relay
1. Place furnace upside down and remove the bottom cover.
2. Disconnect the wires from the solid state relay. Identify or mark the wires disconnect­ed to ensure proper placement and connec­tion when re-installing.
3. Remove solid state relay from bottom cover. Note placement of solid state relay.
4. Install new solid state relay and reconnect wires.
5. Replace bottom cover and place furnace upright.
6. Reconnect furnace to power supply.
To Replace Controller
1. Place furnace upside down and remove bottom cover.
2. Disconnect wires from the controller. Identify or mark wires disconnected to ensure proper placement and connection when re-installing.
3. Remove the controller from bottom cover.
4. Install new controller and secure.
5. Reconnect wires identified in step 3 to new controller.
6. Replace bottom cover and place furnace upright.
7. Reconnect furnace to power supply.
Page 27
Wiring Diagrams
FB 1400 models
FB1300 models
Page 28
EXPLODED VIEW
Page 29
EXPLODED VIEW
29
Page 30
Quantity
Key# Description Required Part Number
1 Heating element (100V - FB1314M) 1 EL140X2 1 Heating element (120V - FB1315M) 1 EL44X1 1 Heating element (208V - FB1318M) 1 EL44X3 1 Heating element (240V - FB1310M, -33) 1 EL44X2 1 Heating element (100V - FB1414M) 1 EL186X2 1 Heating element (120V - FB1415M) 1 EL48X1 1 Heating element (208V - FB1418M) 1 EL48X3 1 Heating element (208V - FB1410M, -33) 1 EL48X2 2 Thermocouple (FB1300 models) 1 TC1256X1 2 Thermocouple (FB1400 models) 1 TC746X1A 3 Solid State Relay (all models) 1 RYX34 4 Door Switches (all models) 2 SWX163 5 Control (FB1300M & FB1400M models except FB1410M-33) 1 CN71X81 5 Control (FB1400M-33 model only) 1 CN71X101 6 Insulation Btm (all FB1300 models) 1 JC44X1 6 Insulation Btm (all FB1400 models) 1 JC48X2 7 Insulation Back (all FB1300 models) 1 JC44X4 7 Insulation Back (all FB1400 models) 1 JC48X1 8 Insulation Top (all FB1300) 1 JC44X3 8 Insulation Top (all FB1400) 1 JC48X3 9 Insulation Hearth Collar (FB1300) 1 HC44X1
9 Insulation Hearth Collar (FB1400) 1 HC48X1 10 Insulation Sides (FB1300) 2 JC460X2 10 Insulation Sides (FB1400) 2 JC48X4 11 Cycle Light (amber) (all 100V & 120V) 1 PLX76 11 Cycle Light (amber) (all 208V & 240V) 1 PLX82 12 Terminal Block 1 TRX136 13 Terminal Block 1 TRX96 14 Power Switch (100 & 120V models) 1 SWX143 14 Power Switch (208 & 240V models) 1 SWX144 15 Door Assembly (FB1300 all models) 1 DR347X1A 15 Door Assembly (FB1400 all models) 1 DR348X1A 16 Element Sleeving (all models) 1 SL745X1 17 Element Sleeving (all FB1300 models) 1 SL59X2 18 Hearth Plate (all FB1300 models) 1 PH44X1 18 Hearth Plate (all FB1400 models) 1 PH48X1 19 Filter (all -33 models) 1 CAX98 20 Fuse Holder (all models) 1 FZX26 21 Fuse 10 amp .25 x 1.25 - (Buss™ Type ABC, 2 FZX30
240V & 208V models)
21 Fuse 15 amp .25 x 1.25 (Buss™ Type ABC, 2 2-58147
120V models)
21 Fuse 20 amp .25 x 1.25 (Buss™ Type ABC, 2 FZX29
100V models) 22 Dial Plate Label (FB1300) 1 DLX248 22 Dial Plate Label (FB1400) 1 DLX249
Replacement Parts List
Page 31
Page 32
One Year Limited Warranty
BARNSTEAD|THERMOLYNE CORPORATION (“BARNSTEAD”) warrants that if a product manufactured by Barnstead shall be free of defects in materials and workmanship for one (1) year from the first to occur of (i) the date the product is sold by BARNSTEAD or (ii) the date the product is purchased by the original retail cus­tomer (the “Commencement Date”). Except as expressly stated above, BARNSTEAD MAKES NO OTHER WARRANTY, EXPRESSED OR IMPLIED, WITH RESPECT TO THE PRODUCTS AND EXPRESSLY DIS­CLAIMS ANYAND ALL WARRANTIES, INCLUDING BUT NOT LIMITED TO, WARRANTIES OF DESIGN, MERCHANT ABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
An authorized representative of BARNSTEAD must perform all warranty inspections. In the event of a defect covered by BARNSTEAD’s warranty, BARNSTEAD shall, as its sole obligation and exclusive remedy, provide free replacement parts to remedy the defective product. In addition, for products sold by BARNSTEAD within the continental United States or Canada, BARNSTEAD shall provide provide free labor to repair the products with the replacement parts, but only for a period of ninety (90) days from the Commencement Date.
BARNSTEAD’s warranty provided hereunder shall be null and void and without further force or effect if there is any (i) repair made to the product by a party other than BARNSTEAD or its duly authorized service repre­sentative, (ii) misuse (including use inconsistent with written operating instructions for the product), mishan­dling, contamination, overheating, modification or alteration of the product by any customer or third party or (iii) use of replacement parts that are obtained from a party who is not an authorized dealer of BARNSTEAD.
Heating elements, because of their susceptibility to overheating and contamination, must be returned to the BARNSTEAD factory and if, upon inspection, it is concluded that failure is due to factors other than excessive high temperature or contamination, BARNSTEAD will provide warranty replacement. As a condition to the return of any product, or any constituent part thereof, to BARNSTEAD’s factory, it shall be sent prepaid and a prior written authorization from BARNSTEAD assigning a Return Goods Number to the product or part shall be obtained.
IN NO EVENT SHALL BARNSTEAD BE LIABLE TO ANY PARTY FOR ANY DIRECT, INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, OR FOR ANY DAMAGES RESULTING FROM LOSS OF USE OR PROFITS, ANTICIPATED OR OTHERWISE, ARISING OUT OF OR IN CONNECTION WITH THE SALE, USE OR PERFORMANCE OF ANY PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CON­TRACT, TORT (INCLUDING NEGLIGENCE), ANY THEORY OF STRICT LIABILITY OR REGULATORY ACTION.
Loading...