BARNSTEAD|THERMOLYNE F30420C, F30420C-33, F30428C,F30420C-33-80, F30420-33-60-80,F30420C-60-80, F30420C-80,F30428C-60-80, F30428C-80,F30430CM, F30430CM-33, F30430CM-33-60, F30430CM-60,F30438CM, F30438CM-60 Operation Manual

Page 1
Type 30400
Thermolyne Furnace
OPERATION MANUAL
AND PARTS LIST
Series 1262
Single Setpoint Models F30420C, F30420C-33, F30428C 8 Segment Programmable F30420C-33-80, F30420-33-60-80
Models with OTP F30420C-60-80, F30420C-80
4 X 16 Segment F30430CM, F30430CM-33, Programmable Models F30430CM-33-60, F30430CM-60 with OTP F30438CM, F30438CM-60
LT1262X1 • 10/8/04
Page 2
IMPORTANT INFORMATION
This manual contains important operating and safety information. You must carefully
read and understand the contents of this manual prior to the use of this equipment.
Safety Information ..............................................................................................................................................4
Alert Signals..................................................................................................................................................4
Warnings ......................................................................................................................................................4
General Specifications ........................................................................................................................................6
Environmental Conditions ............................................................................................................................6
Declaration of Conformity ............................................................................................................................7
Introduction..........................................................................................................................................................8
Intended Use ................................................................................................................................................8
General Usage..............................................................................................................................................8
Principles of Operation ........................................................................................................ ........................9
Unpacking ........................................................................................................................................................10
Installation ........................................................................................................................................................11
Site Selection..............................................................................................................................................11
Electrical Connections ................................................................................................................................11
Operation, All Models........................................................................................................................................12
Power Switch..............................................................................................................................................12
Cycle Light..................................................................................................................................................12
Door Safety Switch ....................................................................................................................................12
Single Setpoint Models with OTP ....................................................................................................................13
Basic Operation..........................................................................................................................................13
Buttons and Indicators................................................................................................................................13
To View or Change the Setpoint ................................................................................................................14
To View the Display Units ..........................................................................................................................14
To View the % Output Power......................................................................................................................14
Controller Parameters ................................................................................................................................14
Alarms ........................................................................................................................................................15
Sensor Break Protection ............................................................................................................................16
Over Temperature Protection (OTP) ..........................................................................................................16
Tuning ........................................................................................................................................................17
Single Ramp and Dwell ....................................................................................................................................18
Functions ....................................................................................................................................................18
Program Overview......................................................................................................................................18
Program Setup............................................................................................................................................19
Running the Program..................................................................................................................................20
Stopping the Program ................................................................................................................................20
Clearing the Flashing End..........................................................................................................................20
Switching from Manual Mode to Automatic Mode......................................................................................20
Verifying a Running Program......................................................................................................................20
8 Segment & 4x16 Segment Programmable Models w/OTP............................................................................21
Basic Operation..........................................................................................................................................21
To Change the Setpoint ......................................................................................................... .....................21
To View the Display Units ..........................................................................................................................22
To View the % Output Power......................................................................................................................22
Buttons and Indicators................................................................................................................................22
Controller Parameters ................................................................................................................................23
Alarms ........................................................................................................................................................26
2
Table of Contents
Page 3
Sensor Break Protection ............................................................................................................................26
Over Temperature Protection......................................................................................................................27
To Operate the Controller as a Single Setpoint Controller ........................................................................27
Programming Controller..............................................................................................................................27
Creating a New Program or Editing an Existing Program..........................................................................28
Setting the Target Setpoint ........................................................................................................................28
Running a Program ....................................................................................................................................34
Holding a Program ......................................................................................................................................35
Cancelling a Program ................................................................................................................................35
Tuning Your Furnace ..................................................................................................................................35
Gain Scheduling ........................................................................................................................................36
Installation and Operation of Air Control ..........................................................................................................38
Installation ..................................................................................................................................................38
Furnace Loading ..............................................................................................................................................39
Preventative Maintenance ................................................................................................................................40
General Cleaning Instructions ....................................................................................................................40
Problem Solving................................................................................................................................................41
Maintenance and Servicing ..............................................................................................................................44
Warning ......................................................................................................................................................44
To Replace a Heating Element ..................................................................................................................44
To Replace a Platinel II Thermocouple ......................................................................................................45
To Replace Solid State Relay ....................................................................................................................46
To Replace Door Switch (Microswitch) ......................................................................................................46
To Realign Door Strike......................................................................................................................................47
To Replace Control Module ..............................................................................................................................48
Replacement Parts List ....................................................................................................................................49
Ordering Procedures ........................................................................................................................................51
Wiring DIagrams................................................................................................................................................52
Two Year Limited Warranty ..............................................................................................................................56
3
TABLE OF CONTENTS
Page 4
Your Barnstead Thermolyne furnace has been designed with function, reliability and safety in mind. It is your re­sponsibility to install it in conformance with local electrical codes. For safe operation, please pay attention to the alert signals throughout the manual.
To avoid electrical shock, this furnace must:
1. Use a properly grounded electrical outlet of cor­rect voltage and current handling capacity.
2. Disconnect from the power supply prior to main­tenance and servicing.
3. Have the door switch operating properly.
To avoid burns, this furnace must:
1. Not be touched on the exterior or interior sur­faces during use or for a period of time after use.
To avoid personal injury:
1. Do not use in the presence of flammable or combustible materials; fire or explosion may result. This device contains components which may ignite such material.
2. Refer servicing to qualified personnel.
Warning
Please note the following WARNINGS: This warning is presented for compliance with California
Proposition 65 and other regulatory agencies and only applies to the insulation in this product. This product contains refractory ceramic, refractory ceramic fiber or fiberglass insulation, which can produce respirable dust or fibers during disassembly. Dust or fibers can cause irritation and can aggravate preexisting respiratory diseases. Refractory ceramic and refractory ceramic fibers (after reaching 1000°C) contain crystalline silica, which can cause lung damage (silicosis). The Internation­al Agency for Research on Cancer (IARC) has classified refractory ceramic fiber and fiberglass as possibly
4
Safety Information
Hot Surface
Hot surfaces alert you to a possibility of personal injury if you come in contact with a surface during use or for a period of time after use.
Caution
Cautions alert you to a possibility of damage to the equipment.
Warning
Warnings alert you to a possibility of personal injury.
Note
Notes alert you to pertinent facts and conditions.
Alert Signals
Page 5
carcinogenic (Group 2B), and crystalline silica as carcino­genic to humans (Group 1).
The insulating materials can be located in the door, the hearth collar, in the chamber of the product or under the hot plate top. Tests performed by the manufacturer indi­cate that there is no risk of exposure to dust or respirable fibers resulting from operation of this product under nor­mal conditions. However, there may be a risk of exposure to respirable dust or fibers when repairing or maintaining the insulating materials, or when otherwise disturbing them in a manner which causes release of dust or fibers. By using proper handling procedures and protective equipment you can work safely with these insulating materials and minimize any exposure. Refer to the appro­priate Material Safety Data Sheets (MSDS) for informa­tion regarding proper handling and recommended protec­tive equipment. For additional MSDS copies, or additional information concerning the handling of refractory ceramic products, please contact the Customer Service Department at Barnstead International (1-800-553-0039).
5
SAFETY INFORMATION
Page 6
Models F30420C, (-33), F30428C, (-60-80)
(-33-60-80), (-33-80), & (-80) (-60-80) & (-80) F30438CM & (-60)
F30430CM, (-33), (-33-60) & (-60)
Overall Dimensions
Width 21 1/2 (55) 21 1/2 (55)
IN. (CM) Height 29 1/2 (75) 29 1/2 (75)
Depth 25 1/2 (65) 25 1/2 (65)
Chamber Dimensions Width 14 (35) 14 (35)
IN. (CM Height 14 (35) 14 (35)
Depth 14 5/8 (37) 14 5/8 (37) Weight Lbs. (KG) 188 (86) 188 (86) Electrical Ratings Volts 240 208
Amps 22.9 26.4
Watts 5500 5500
Freq. 50/60 50/60
Phase 1 1 Temperature Ratings Cont. 400°F-1800°F* 400°F-1800°F*
°F (°C) (204°C)-(982°C) (204°C)-(982°C)
Intermittent 1800°F-2000°F 1800°F-2000°F
(982°C)-(1093°C) (982°C)-(1093°C)
* The maximum continuous temperature for ashing furnaces (-60 models) is 1787°F (975°C).
Environmental Conditions
Operating: 17°C - 27°C; 20% to 80% relative humidity, non-condensing. Installation Category II
(over-voltage) in accordance with IEC 664. Pollution Degree 2 in accordance with IEC 664. Altitude limit: 2,000 meters. Storage: -25°C to 65°C; ; 10% to 85% relative humidity.
6
General Specifications
Page 7
Declaration of Conformity
(for 230 volt CE models only)
Barnstead International hereby declares under its sole responsibility that this product conforms with the tech­nical requirements of the following standards:
EMC: EN 61000-3-2 Limits for harmonic current emissions
EN 61000-3-3 Limits for voltage fluctuations and flicker EN 61326-1 Electrical equipment for measurement, control, and laboratory use; Part I:
Generic Requirements
Safety: EN 61010-1 Safety requirements for electrical equipment for measurement, control, and
laboratory use; Part I: General Requirements
EN 61010-2-010 Part II: Particular requirements for laboratory equipment for the heating of
materials
per the provisions of the Electromagnetic Compatibility Directive 89/336/EEC, as amended by 92/31/EEC and 93/68/EEC, and per the provisions of the Low Voltage Directive 73/23/EEC, as amended by 93/68/EEC.
The authorized representative located within the European Community is:
Electrothermal Engineering, Ltd.
419 Sutton Road
Southend On Sea
Essex SS2 5PH United Kingdom
Copies of the Declaration of Conformity are available upon request.
7
GENERAL SPECIFICATIONS
Page 8
Intended Use
1. The Type 30400 Automatic and Programmable furnaces are general laboratory and heat treat­ing furnaces. For optimum element life, Barnstead Thermolyne recommends these fur­naces for applications requiring temperatures from 400°F (204°C) to 1800°F (982°C) for con­tinuous use, or temperatures from 1800°F (982°C) to 2000°F (1093°C) for intermittent use. Continuous use is operating the furnace for more than 3 hours and intermittent use is oper­ating the furnace for less than 3 hours.
2. The unit consists of 1) a heating chamber; 2) an automatic proportioning digital set, digital read control with overtemperature protection and 3) a door interlock relay for user safety.
3. The Type 30400 Programmable furnace is designed to control a programmed temperature profile. The profile is in the format of ramps and dwell segments. The first ramp, RAMP 1, starts at the initial measured furnace temperature. This ramp is positive going at a programmed rate until the programmed level is reached. The set­point will stay at this level for a period deter­mined by the setting of DWELL 1. Additional positive or negative going ramps are now initiat­ed starting at the level at the end of DWELL 1. When the second ramp reaches the second pro­grammed level, the setpoint stays at that level for the duration of the segment. Depending upon the model ordered, additional ramp and dwell segments may be added. See specific model number in proceeding chart for total num­ber of program segments.
4. The Type 30400 Automatic furnace is designed as a single set point controller which reaches and maintains one temperature value.
General Usage
Do not use this product for anything other than its intend­ed usage.
8
Introduction
Note
When in the program RUN mode, the programmable controller serves to pro­vide a programmed temperature pro­file as described earlier. When in the single setpoint automatic mode, the unit serves as an automatic tempera­ture controller.
Page 9
9
INTRODUCTION
Principles of Operation
1. Furnace: The furnace chamber is heated by four electric resistance heaters which are embedded in a refractory material. The chamber is insulated with a ceramic fiber insulation. The temperature is con­trolled by an automatic proportioning controller using a platinel thermocouple to feed back information. The control is located under the furnace chamber and is well insulated from the heat generated in the furnace chamber. The temperature is controlled by one of three types of controllers.
MODEL NUMBER DIGITAL COMMUM. TOTAL NUMBER OF NUMBER OF
PROGRAMMABLE STORED
SEGMENTS PROGRAMS
F30420C-33-80 NO 8 F30420-33-60-80 NO 8 F30420C-60-80 NO 8 F30420C-80 NO 8 F30428C-60-80 NO 8 F30428C-80 NO 8 F30430CM YES 64 16 Segment Programs F30430CM-33 YES 64 16 Segment Programs F30430CM-33-60 YES 64 16 Segment Programs F30430CM-60 YES 64 16 Segment Programs F30438CM YES 64 16 Segment Programs F30438CM-60 YES 64 16 Segment Programs
Page 10
10
1. Visually check for any physical damage to the shipping container.
2. Inspect the equipment surfaces that are adja­cent to any damaged area.
3. Open the furnace door and remove the packing material from inside the furnace chamber.
4. Vacuum the chamber prior to use to remove the insulation dust due to shipment.
5. Retain the original packaging material if reship­ment is foreseen or required.
Unpacking
Page 11
11
Installation
Caution
Be sure ambient temperature does not exceed 40°C (104°F). The recommended ambient temperature is 17°C - 27°C. Ambients above this level may result in damage to the controller.
Warning
To avoid electrical shock, this furnace must always use a properly grounded outlet of correct voltage and current han­dling capacity.
Caution
Allow at least six inches of space between the furnace and any combustible surface. This permits the heat from the furnace case to escape so as not to cre­ate a possible fire hazard.
Site Selection
Install furnace on a sturdy surface and allow adequate space for ventilation.
Electrical Connections
The electrical ratings are located on the specification plate on the back of the furnace. Consult Barnstead/Thermolyne if your electrical service is dif­ferent than those listed on the specification plate. Be sure the front power switch is in the OFF position before connecting the furnace to your electrical supply.
Page 12
12
Operation, All Models
Warning
To avoid personal injury do not use in the presence of flammable or combustible chemicals; fire or explosion may result. This device contains components which may ignite such materials.
Hot Surface
Caution: Avoid Contact. To avoid burns, this furnace must not be touched on the exterior or interior surfaces during use or for a period of time after use.
Warning
To avoid electrical shock, the door safety switch must be operating properly.
Warning
Always wear safety glasses or a safety shield and high temperature gloves when loading or unloading the furnace. Long sleeved, fire retardant clothing and a fire retardant apron is also recommended.
Power Switch
Both the ON/OFF power switch and the digital display will illuminate when power is switched ON. The furnace will begin to heat to its controller's current setpoint. (See the instructions for your type of controller for infor­mation on checking and setting the setpoint.)
Cycle Light
The amber cycle light will illuminate whenever the power is being applied to the heating elements. The cycle light will turn on and off as the furnace reaches the setpoint.
Door Safety Switch
The door safety switch removes power from the heat­ing elements when the door is opened. Open and close the door a few times; note that the amber CYCLE light will switch off when the door is opened. If this condition is not true, consult the Troubleshooting section before proceeding. This check must be done when the furnace is heating and the cycle light is illumi­nated.
Page 13
13
Single Setpoint Models
Output 1
Manual
UP ARROW
Button
Temperature
Display
Display
Window
DOWN ARROW
Button
PAGE
Button
SCROLL
Button
Output 2
MAN
Single Setpoint Models w/OTP
Note
If at any time you want to return to the HOME DISPLAY, simultaneously press the PAGE and SCROLL buttons.
The single setpoint model w/ OTP furnace controller
is a single setpoint controller which provides a single digital display to indicate the current chamber tempera­ture or setpoint temperature. This temperature con­troller features sensor break protection, self-tuning capability and over temperature protection (OTP) with an additional OTP relay device.
Basic Operation
When the controller is turned ON it will perform a short self-test and then display the measured value (process value) in the HOME DISPLAY.
Buttons and Indicators
OP1 (Output 1): Illuminates when the logic output is ON.
OP2 (Output 2): Illuminates when the relay output is ON (will go out during an alarm situation).
PAGE button: Allows you to select a new list of parameters.
SCROLL button: Allows you to select a parameter within a list of parameters.
DOWN button: Allows you to decrease a value. UP button: Allows you to increase a value.
Page 14
14
SINGLE SETPOINT MODELS W/OTP
To View or Change the Setpoint
To view the setpoint, press and release the UP or DOWN buttons. If you want to change the setpoint, continue press­ing until the desired setpoint value is displayed and then release the button. Afew seconds after the button is released, the controller will accept the new value and revert to the HOME DISPLAY.
To View the Display Units
From the HOME DISPLAY press the SCROLL button. The display will show the temperature units in °C/F/K and then return to the HOME DISPLAY. (Call Customer Service if you require a different temperature unit.)
To View the % Output Power
From the HOME DISPLAY press the SCROLL button twice. Press and release the UP or DOWN button to view the % output power. This value is a read-only value and cannot be changed.
Controller Parameters
Home display
°C: Temperature units in Celsius. Temperature units can not be changed without entering the configuration. Contact Customer Service if a different temperature unit is required.
OP: % output power demand.
IdHi: Deviation high alarm.
Al List
IdHi: Deviation high alarm.
Atun List
tunE: One-shot autotune enable.
Page 15
15
SINGLE SETPOINT MODELS W/OTP
Note
The following alarm messages are factory default settings and may vary if you have changed the configuration of your controller:
IDHi: = 50°C 2FSH = 1118°C
Pid List
Pb: Proportional band (in display units). ti: Integral time in seconds. td: Derivative time in seconds. ACCS List Code: Access code (Code needed to enter or
change the other configuration parameters which are not normally accessible.) Not accessable.
Alarms
The controller will flash an alarm message in the home display if an alarm condition is detected.
2FSH: Measured value full scale high alarm.
IdHi: Measured value deviation high alarm. S.br: Sensor break: check that sensor is connected cor-
rectly. L.br: Loop break: check that the heating circuits are work-
ing properly. Ld.F: Heater Circuit fault: indication of either an open or
short solid sate relay, a blown fuse, missing supply or open circuit heater.
Page 16
16
Sensor Break Protection
This controller provides sensor break protection in the event the thermocouple opens. If an open thermocou­ple condition occurs, the digital display will blink “S.br” and the power to the heating element will be shut OFF (Cycle light will extinguish).
Over-Temperature Protection (OTP)
The OTP will be in effect during any alarm condition when the temperature of the furnace has deviated beyond the limit. The “Deviation High” alarm is the only alarm value which can be changed. To change it, press the SCROLL button until “IdHi” appears on the display. Press the UP or DOWN button to select the OTP value you desire. We recommend a value of 20° above your working temperature to provide protection for your workload.
In addition to over-temperature protection, units con­taining a single setpoint controller w/OTP feature a mechanical OTP relay device which disconnects power from the elements in an alarm condition (only in fur­naces with OTP relay). See models listed on front page.
SINGLE SETPOINT MODELS W/OTP
Page 17
17
Note
Furnace must be at ambient temperature before starting a tune.
Note
Tune has completed when “tunE” stops flashing on display.
SINGLE SETPOINT MODELS W/OTP
Tuning
This controller incorporates a self-tuning feature which determines the optimum control parameters for the best temperature accuracy with your load and setpoint. Use this feature the first time you use your furnace and each time you change either your setpoint or the type of load you are heating. Barnstead|Thermolyne recom­mends you use this feature to provide the best temper­ature accuracy the controller can attain. To use the tun­ing feature:
1. Adjust the setpoint to your desired value.
2. Press the PAGE button until display reads,
“Atun.”
3. Press the SCROLL button. Display will read,
“tunE.”
4. Press the UP or DOWN button to select, “on.”
5. Simultaneously press the PAGE and
SCROLL buttons to return to the HOME DIS­PLAY. The display will alternately flash between “tunE” and the HOME DISPLAY while tuning is in progress.
6. The controller will then turn the heating on
and off to induce an oscillation. When the measured value reaches the required setpoint the first cycle will end.
7. Tuning will be complete after two oscillation
cycles and then the tuner will turn itself off.
8. Normal control function will resume after the
controller calculates tuning parameters.
Note
“Stat” and “Sp.rr” in Sp list must be set to OFF or “tunE” will not initiate.
Page 18
18
Single Ramp & Dwell
Note
These instructions are used with the Single Setpoint models with OTP only (See models listed on front page).
Functions
This type of controller has single ramp and dwell program­ming capabilities. The Ramp and Dwell can be configured to five different modes.
1. Mode 1 (Opt. 1) is a Ramp (if needed) to the Setpoint temperature, a Dwell, and then a cool down.
2. Mode 2 (Opt. 2) is the same as mode 1, except the controller continues to heat at the Setpoint after the Dwell has completed. (This mode does not cool down.)
3. Mode 3 (Opt. 3) is the same as mode 1, except the Dwell time includes the Ramp (if needed).
4. Mode 4 (Opt. 4) is the same as mode 2, except the Dwell time includes the Ramp (if needed).
5. Mode 5 (Opt. 5) is a Dwell (delay time) before the controller Ramps (if needed) to the Setpoint tem­perature.
Program Overview
•Aprogram mode can be set by changing the “tm.OP” variable to “Opt. 1, Opt. 2, Opt. 3, Opt. 4, or Opt. 5.
•ARamp rate may be set by changing the “SPrr” variable to a value. The Ramp rate units are in degrees per minute.
The Dwell time can be set by changing the “dwEll” variable to the desired value. Dwell time units are in minutes.
The program Status can be set by changing the “StAt” variable to “run” or “oFF.” This variable will start or stop the program.
Mode 1 (Opt. 1)
Mode 2 (Opt. 2)
Mode 3 (Opt. 3)
Mode 4 (Opt. 4)
Mode 5 (Opt. 5)
Page 19
19
SINGLE RAMP & DWELL CONTROLLER
Note
The program must be stopped and the controller must be displaying the actual temperature before beginning the Setup.
Program Setup
1. Press the PAGE button until the “SP” is displayed.
2. Press the SCROLL button once, “SPrr” (Ramp Rate) will be displayed, set the desired Ramp rate with the UP or DOWN buttons, if the ramp to setpoint feature is needed. If the Ramp rate is not needed, then set to “OFF” with the UP or DOWN buttons.
3. Press the SCROLL button once, “tm.OP” (Ramp & Dwell mode) will be displayed, select the desired mode with the UP or DOWN buttons. (Opt. 1, Opt. 2, Opt. 3, Opt. 4, Opt. 5)
4. Press the SCROLL button once, “dwEll” will be dis­played, set the desired Dwell time with the UP or DOWN buttons. (Dwell in minutes.)
5. Press the PAGE button until the Actual temperature is displayed.
Running the Program
1. Press the SCROLL button until “StAt” is displayed, set to “run” with the UP or DOWN buttons.
2. Press the PAGE button to display Actual temperature.
Stopping the Program
Press the SCROLL button until “StAt” is displayed, set to “oFF” with the UP or DOWN buttons.
Clearing the Flashing End
Press the PAGE and SCROLL buttons at the same time.
Page 20
20
Verifying a Running Program
Press the SCROLL button until “StAt” is displayed. The display will show “run” if the program is running, or “oFF” if it is not running. Press the PAGE button to dis­play Actual temperature.
SINGLE RAMP & DWELL CONTROLLER
Page 21
21
8 Segment & 4x16 Segment
Programmable Models w/OTP
Output 1
PAGE
Button
AUTO/MAN
Button
Display
Window
Upper
Display
Lower
Display
RUN/HOLD
Button
UP ARROW
Button
DOWN ARROW
Button
SCROLL
Button
Note
The controller will return to the HOME DISPLAY if left idle for more than a few seconds.
Note
Once the desired parameter has been selected, depressing either the UP or DOWN button will change the parameter value. In all cases, the value shown on the display is the current working value of that parameter.
4x16 & 8 Segment Programmable Models with OTP
The 8 segment programmable controller consists of a microprocessor based three-mode PID (Proportional, Integral, Derivative), programmable temperature controller with over-temperature protec­tion and appropriate output switching devices to con­trol the furnace. The digital readout continuously dis­plays chamber (upper display) and setpoint (lower display) temperatures unless the SCROLL or PAGE button is depressed. The programmable controller can be used as a single setpoint controller or as a pro­grammable controller. The 8 segment digital model enables eight segments of programming.
The 4x16 segment programmable controller con- sists of a microprocessor based three-mode PID (Proportional, Integral, Derivative), programmable temperature controller with over-temperature protec­tion and appropriate output switching devices to con­trol the furnace. The digital readout continuously dis­plays chamber (upper display) and setpoint (lower display) temperatures unless the SCROLL or PAGE button is depressed. The programmable controller can be used as a single setpoint controller or as a pro­grammable controller. The 4 program controller has four 16 segment programs.
Basic Operation
When the controller is turned ON, it will perform a short self-test and then change to the HOME DIS­PLAY. The HOME DISPLAY shows the measured temperature (process value) in the upper display and the desired value (setpoint) in the lower display.
To Change the Setpoint
If you want to change the setpoint, press the UP or DOWN button until the desired setpoint value is dis­played in the lower display and then release the but­ton.
Page 22
22
8 SEGMENT & 4X16 SEGMENT PROGRAMMABLE MODELS W/OTP
To View Display Units
From the HOME DISPLAY press the SCROLL button. The display will briefly show the temperature units in °C/F/K and then return to the HOME DISPLAY. (If you require a different temperature unit call Barnstead|Thermolyne Customer Service.)
To View the % Output Power
From the HOME DISPLAY press the SCROLL button twice. This value is a read-only value and cannot be changed.
Buttons and Indicators
OP1 (Output 1): illuminates when the heating output of the temperature controller is on.
AUTO/MAN: (Auto/Manual Mode): when the controller is in the automatic mode the output automatically adjusts to keep the temperature or process value at the setpoint. The “AUTO” light will illuminate. The manual mode has been disabled through factory configuration. Call Customer Service for further information.
RUN/HOLD (Run/Hold button):
Starts a program when pressed once—RUN light illuminates.
Holds a program when pressed again—HOLD light illuminates.
Cancels hold and continues running when pressed again—HOLD light is off and RUN light illuminates.
Exits a program when the button is held down for two seconds—RUN and HOLD lights are off.
At the end of a program the RUN light will flash.
During holdback the HOLD light will flash.
Page 23
8 SEGMENT & 4X16 SEGMENT PROGRAMMABLE MODELS W/OTP
PAGE button: allows you to choose a parameter from a
list of parameters. SCROLL button: allows you to choose a parameter within
a list of parameters. UP button: allows you to increase the value in the lower
display. DOWN button: allows you to decrease the value in the
lower display.
Controller Parameters
Home Display °C: measured temperature in Celsius. Temperature units
can not be changed without entering the configuration. Contact Customer Service if a different temperature unit is required.
OP: % output power demand; displayed in lower display (cannot be changed).
C.id: Controller identification number. PrG: Program number (displayed when a program is run-
ning; 4x16 programmable models only.)
IdHi: Deviation High Alarm tunE: One-shot autotune enable.
run LiSt (Program Run List) PrG: Currently running program (only used on 4x16 pro-
grammable models) StAt: Displays the program status [OFF, run (running
active program), hoLd (program on hold), HbAc (waiting for process to catch up), End (program completed)] in the lower display. The controller will default to “OFF.”
FASt: Fast run through program (no/YES). The controller will default to “no.”
SEG.d: Flash active segment type in the lower display of the home display (no/YES). The controller will default to “no.”
23
Page 24
24
ProG LiSt (Program Edit List) PrG.n: Press the UP or DOWN ARROW to select the
program number (program number will be displayed in lower display on 4x16 programmable models only.)
Hb: Press the UP or DOWN ARROW to select the holdback type [OFF (disables holdback), Lo (deviation low holdback), Hi (deviation high holdback) or bAnd (deviation band holdback)] for the entire program. The controller will default to “OFF.”
Hb.U: Press the UP or DOWN ARROW to select the holdback value (in display units).
rmP.U: Press the UP or DOWN ARROW to toggle between ramp units (SEc, min or Hour). Controller will default to “SEc.”
dwL.U: Press the UP or DOWN ARROW to toggle between dwell units (SEc, min or Hour). Controller will default to “SEc.”
Cyc.n: Press the UP or DOWN ARROW to set the number of program cycles (1 to 999 or cont). The con­troller will default to “cont.”
SEG.n: Press the UP or DOWN ARROW to select the segment number (1-8 in 8 segment models, 1-16 in 4x16 models).
tYPE: Press the UP or DOWN ARROW to select the segment type [End (end of program), rmP.r = ramp rate (ramp to a specified setpoint at a set rate), rmp.t = ramp time (ramp to a specified temperature in a set time), dwEll (to maintain a constant temperature for a set time), StEP (climb instantaneously from current to specified temperature), cALL (to call a program as a subroutine, available only on 4x16 programmable mod­els)]. The controller will default to “End.” Other parame­ters used with tYPE include; tGt target setpoint), Rate (rate of temperature increase) and dur (time to target setpoint or time to dwell).
End.t: End segment type: dwELL (dwell continuous), rSEt (reset) and S OP (End Segment Output power level.
8 SEGMENT & 4X16 SEGMENT PROGRAMMABLE MODELS W/OTP
Page 25
25
8 SEGMENT & 4X16 SEGMENT PROGRAMMABLE MODELS W/OTP
AL LiSt (Alarm List) IdHi: Deviation High Alarm.
Atun LiSt: (Autotune List) tunE: One-shot autotune enable. drA: Adaptive tune enable.
drA.t: Adaptive tune trigger level in display units.
Range = 1 9999.
Pid LiSt G.SP (Gain Setpoint): Is the temperature at which the
controller switches from the (SEt1) PID values to the (SEt 2) PID values.
Pb: Proportional band in display units. (SEt 1) ti: Integral time in seconds. (SEt 1) td: Derivative time in seconds. (SEt 1) Pb2: Proportional band. (SEt 2) ti2: Integral time in seconds. (SEt 2) td2: Derivative time in seconds. (SEt 2)
ACCS LiSt (Access List)
Access Code (Code needed to enter or change the other configuration parameters which are not normally accessible.) Not accessable.
Page 26
26
Note
The following alarm messages are factory default settings and may vary if you have changed the configuration of your controller:
IDHi: = 50°C 2FSH = 1118°C (all models
except -60)
2FSH = 1000°C (-60 models only)
Alarms
The controller will flash an alarm message in the home display if an alarm condition is detected.
IdHi: PV deviation high alarm. 2FSH: PV full scale high alarm.
LCr: load current low alarm. HCr: load current high alarm. S.br: Sensor break: check that sensor is connected
correctly. L.br: Loop Break: Check that the heating circuits are
working properly. Ld.F: Heater Circuit Fault: indication of either an open
or short solid sate relay, a blown fuse, missing supply or open circuit heater.
SSr.F: Solid state relay failure indications in a solid state relay: indicates either an open or short circuit in the SSR.
Htr.F: Heater failure: Indication that there is a fault in the heating circuit: indicates either a blown fuse, miss­ing supply or open circuit heater.
Sensor Break Protection
This controller provides sensor break protection in the event the thermocouple opens. If an open thermocou­ple condition occurs, the digital display will Blink “S.br” and the power to the heating element will be shut OFF (Cycle light will extinguish).
8 SEGMENT & 4X16 SEGMENT PROGRAMMABLE MODELS W/OTP
Page 27
27
8 SEGMENT & 4X16 SEGMENT PROGRAMMABLE MODELS W/OTP
Over-Temperature Protection (OTP)
The OTP will be in effect during any alarm condition when the temperature of the furnace has deviated beyond the limit. The “Deviation High” alarm is the only alarm value which can be changed. To change it, press the SCROLL button until “idHi” appears on the display. Press the UP or DOWN button to select the OTP value you desire. We recommend a value of 20° above your working temperature to provide protection for your workload.
To Operate the Controller as a Single Setpoint Controller
1. Switch the circuit breaker to the “ON” posi-
tion. The setpoint temperature presently set in the controller will appear in the lower display. (The upper display indicates the actual cham­ber temperature.)
2. To change the setpoint, press the UP or
DOWN button until the desired setpoint value is displayed; then release the button.
3. The furnace will begin to heat if the new set-
point temperature is higher than the present chamber temperature.
Programming the Controller
The controller is capable of varying temperature or process value with time through programming. Apro­gram is stored as a series of segments and can be run once, repeated a set number of times or run continu­ously. To create a customized program using the con­troller parameters listed under “Controller Parameters” at the beginning of this section, follow the procedures outlined in the proceeding sections of this manual.
Page 28
28
8 SEGMENT & 4X16 SEGMENT PROGRAMMABLE MODELS W/OTP
Creating a New Program or Editing an Existing Program (4x16 Segment Programmable Models Only)
The same steps are used when creating a new pro­gram and editing an existing program with the excep­tion being that a new program starts with all its seg­ments set to End in the tYPE parameter. Temporary changes can be made to these parameters when the program is in the hold state but permanent changes must be made in the reset state. Follow the steps below to create or edit a program.
1. Press the PAGE button until you reach the program list (ProG LiSt).
2. Press the SCROLL button until display reads, “PrG.n.”
3. Press the UP or DOWN button to select a number for a new program or to edit an exist­ing program.
Hb: Holdback
Holdback consists of a value and a type. If the meas­ured value lags behind the setpoint by an undesirable amount during a ramp or dwell, the holdback feature can be used to freeze the program at its current state (the HOLD light will flash). The program will resume when the error comes within the holdback value.
OFF: holdback is disabled. Lo (Deviation Low Holdback): holds the program
back when process variable deviates below the set­point by more than the holdback value.
Hi (Deviation High Holdback): holds the program back when process variable deviates above the set­point by more than the holdback value.
Page 29
29
8 SEGMENT & 4X16 SEGMENT PROGRAMMABLE MODELS W/OTP
bAnd (Deviation Band Holdback): combines the fea-
tures of the high and low deviation holdback in that it holds the program back when the process variable deviates above or below the setpoint by more than the holdback value.
To set the holdback type:
1. Press the PAGE button until you reach the program list (ProG LiSt).
2. Press the SCROLL button until display reads, “Hb.”
3. Press the UP or DOWN button to toggle between “bAnd, Hi, Lo and OFF.”
Hb U: Holdback Value
To set the holdback value:
1. Press the PAGE button until you reach the program list (ProG LiSt).
2. Press the SCROLL button until display reads, “Hb.U.”
3. Press the UP or DOWN button to enter a holdback value.
rmP.U: Setting Ramp Units
Ramp units are time units which are used in “rmP.r” segments (ramp to a setpoint at degrees per second, minute or hour) and “rmP.t” segments (ramp to setpoint in a specific amount of time). See “Setting the Segment Type” for an explanation on how to set a ramp segment.
1. Press the PAGE button until you reach the program list (ProG LiSt).
2. Press the SCROLL button until display reads, “rmP.U.”
3. Press the UP or DOWN button to toggle between seconds, minutes and hours.
Note
The value set in this parameter is always for the entire program.
Page 30
30
8 SEGMENT & 4X16 SEGMENT PROGRAMMABLE MODELS W/OTP
dwL.U: Setting Dwell Units
Dwell units are time units which are used in “dwELL” seg­ments (amount of time to remain at a specific temperature ). See “Setting the Segment Type” for an explanation on how to set a dwell segment.
1. Press the PAGE button until you reach the pro­gram list (ProG LiSt).
2. Press the SCROLL button until display reads, “dwL.U.”
3. Press the UP or DOWN button to toggle between seconds, minutes and hours.
CYC.n: Setting the Number of Cycles
Set the number of times a group of segments or programs are to be repeated by following the steps listed below.
1. Press the PAGE button until you reach the pro­gram list (ProG LiSt).
2. Press the SCROLL button until display reads,”CYC.n.”
3. Press the UP or DOWN button to select the num­ber of cycles you want to run or, press the DOWN button to select “cont.” so the program will run continuously.
Setting the Segment Type
There are five segment types. Proceed with the following steps according to the type of segment you have selected.
rmP.r (Ramp)
To ramp linearly at a set rate to a specified temperature:
1. Press the PAGE button until you reach the pro­gram list (ProG LiSt).
2. Press the SCROLL button until display reads,”tYPE.”
3. Press the UP or DOWN button until display reads, “rmP.r.”
Note
The program ramp rate is designed to reduce the heatup rate or cooling rate that the furnace normally exhibits. When not using this feature, the fur­nace will operate at its maximum heating and cooling capability.
Note
When the program ramp has ended or has been reset, the furnace will continue to maintain setpoint temper­ature. It will not cool to ambient tem­perature unless the setpoint is set to ambient temperature by the program or by the operator.
Page 31
31
8 SEGMENT & 4X16 SEGMENT PROGRAMMABLE MODELS W/OTP
Steps 4 and 5 are used in the 4 program model only. If you are using an 8 segment program, skip to step 6.
4. Press the SCROLL button until display reads “Hb.”
5. Press the UP or DOWN button to toggle between “bAnd, Hi, Lo and OFF.”
6. Press the SCROLL button until display reads, “tGt.”
7. Press the UP or DOWN button to set a target setpoint.
8. Press the SCROLL button until display reads,”rAtE.”
9. Press the UP or DOWN button to select a value in ramp units (seconds, minutes or hours; set in the “rmP.U” parameter).
rmP.t
To ramp to a specified temperature at a set time:
1. Press the PAGE button until you reach the program list (ProG LiSt).
2. Press the SCROLL button until display reads, “tYPE.”
3. Press the UP or DOWN button until display reads, “rmP.t.”
4. Press the SCROLL button until display reads, “tGt.”
5. Press the UP or DOWN button to set a target setpoint.
6. Press the SCROLL button until display reads, “dur.”
7. Press the UP or DOWN button to select a time in ramp units (seconds, minutes or hours; set in the “rmP.U” parameter.
Page 32
32
8 SEGMENT & 4X16 SEGMENT PROGRAMMABLE MODELS W/OTP
dwEll
To maintain a constant temperature for a specified time:
1. Press the PAGE button until you reach the pro­gram list (ProG LiSt).
2. Press the SCROLL button until display reads, “tYPE.”
3. Press the UP or DOWN button until display reads, “dwEll.”
4. Press the SCROLL button until display reads, “dur.”
5. Press the UP or DOWN button to select a time in dwell units (seconds, minutes or hours; set in the “dwL.U” parameter).
StEP
To climb instantaneously from the current temperature to a specified temperature.
1. Press the PAGE button until you reach the pro­gram list (ProG LiSt).
2. Press the SCROLL button until display reads, tYPE.”
3. Press the UP or DOWN button until the display reads, “StEP.”
4. Press the SCROLL button until display reads, “tGt.”
5. Press the UP or DOWN button to set a target set­point.
cALL (Running Multiple Programs; 4x16 Segment Programmable Models Only)
To call a program as a subroutine: If you want to run multiple programs, you can program the controller to “call” or link one program to another. This makes it possible to run one program at any time during another program and also return to the original program if desired.
1. Press the PAGE button until you reach the pro­gram list (ProG LiSt).
Page 33
33
8 SEGMENT & 4X16 SEGMENT PROGRAMMABLE MODELS W/OTP
2. Press the SCROLL button until display reads, “tYPE.”
3. Press the UP or DOWN button until display reads, “cALL.”
4. Press the SCROLL button until display reads, “PrG.n.”
5. Press the UP or DOWN button to select a pro­gram number to be linked.
6. Press the SCROLL button until display reads, “CYC.n.”
7. Press the UP or DOWN button to select the number of cycles the linked program is to be run.
End
To end or repeat a program:
1. Press the PAGE button until you reach the pro­gram list (ProG LiSt).
2. Press the SCROLL button until display reads, “tYPE.”
3. Press the UP or DOWN button until display reads, “End.”
4. Press the SCROLL button until display reads, “End.t.”
5. Press the UP or DOWN button to toggle between “dwEll” (an indefinite dwell), “S OP” (End Segment Output Power) and “rSET” (reset).
Page 34
34
8 SEGMENT & 4X16 SEGMENT PROGRAMMABLE MODELS W/OTP
Setting the Target Setpoint (4x16 Segment Programmable Models Only)
1. Press the PAGE button until you reach the program list (ProG LiSt).
2. Press the SCROLL button until display reads, “tGt.”
3. Press the UP or DOWN button to set the tar­get setpoint temperature.
Running a Program (8 Segment Programmable Models)
To run a program, press the RUN/HOLD button. (The RUN light will illuminate.)
Running a Program (4x16 Segment Programmable Models)
To run a program, press the RUN/HOLD button. (The RUN light will illuminate) or:
1. Press the PAGE button until you reach the run list (run LiSt).
2. Press the SCROLL button until display reads, “PrG.”
3. Press the UP or DOWN button to select the program number you want to run.
4. Press the RUN/HOLD button once to start the program. (The RUN light will illuminate.)
Page 35
35
Holding a Program
To put a running program on hold, press the RUN/HOLD button. (The HOLD light will illuminate.)
Cancelling a Program
To cancel a program, hold the RUN/HOLD button down until the RUN and HOLD lights go off.
Tuning your Furnace
The purpose of tuning your furnace is to match the char­acteristics of your controller to the characteristics of the process being controlled. Good control is evidenced by: stable, straight-line control of the setpoint temperature with no fluctuations; No overshoot or undershoot of the setpoint temperature; rapid restoration of the setpoint temperature when external disturbances cause deviations from the setpoint.
This controller has automatic tuning features which install optimum tuning parameters to give the best temperature accuracy. No manual loading of tuning parameters is needed. We recommend that you tune the furnace to your specific application to obtain the best results. To provide the best temperature accuracy possible, use these fea­tures when you install your furnace and whenever you change your application or procedure.
Tuning Error
The display will flash “tu.ER” if an error occurs during tun­ing. To clear the error and restart tuning, simultaneously press the PAGE and SCROLL buttons and follow the steps outlined in “Autotuning.”
Note
Display will flash “tu.ER” if an error occurs during tuning. To clear the error and restart tuning, simultane­ously press the PAGE and SCROLL buttons and follow the steps outlined in “Autotuning.”
Note
To stop the tuning function, simulta­neously press the PAGE and SCROLL buttons.
Page 36
36
Gain Scheduling
G.SP: Gain Scheduling
Gain scheduling is the automatic transfer of control between two sets of PID values. The 2416 controller does this at a presettable process value. Gain schedul­ing is used for difficult control processes which show large changes in their response time or sensitivity at high or low temperatures, or when heating or cooling.
The G.SP gain schedule setpoint is factory set at 700° C. The G.SP must be adjusted to 200°C from the desired setpoint temperature when tuning.
Setting the Transfer Point If gain scheduling has been enabled, “G.SP will appear at the top of the PID list. This sets the value at which the transfer will occur. When the process value is below this level, PID1 will be active and when it is above, Pid2 will be active. Set a value between the control regions that show the greatest change to achieve the best point of transfer.
Tuning The two sets of PID values can be manually set or automatically tuned. To tune automatically you must tune above and below the transfer point G.SP. If the process value is below the transfer point G.SP, the cal­culated values will automatically be inserted into the (SEt 1) set and if the process value is above G.SP, the calculated values will automatically be inserted into the (SEt 2).
Autotuning
The Autotune feature automatically sets up the PID val­ues in the control parameters to suit new process con­ditions.
To tune your furnace using autotuning:
1. Load your furnace with a load similar to your normal load and close the door.
8 SEGMENT & 4X16 SEGMENT PROGRAMMABLE MODELS W/OTP
Page 37
37
8 SEGMENT & 4X16 SEGMENT PROGRAMMABLE MODELS W/OTP
2. Set the setpoint temperature.
3. Press the PAGE button until the display reads,
“Atun LiSt.”
4. Press the SCROLL button until “tunE OFF” is
displayed.
5. Press the UP or DOWN button to select “on.”
6. Simultaneously press the PAGE and SCROLL
buttons to return to the HOME DISPLAY. The display will flash “tunE” while tuning is in progress.
Adaptive Tuning
Adaptive tuning continuously evaluates tuning parame­ters. Adaptive tuning automatically installs new values if better accuracy is possible. Adaptive tuning should be used when the characteristics of a process change due to load or setpoint changes or, in a process that can not handle the oscillation caused by a one-shot tune.
To tune your furnace using adaptive tuning:
1. Load your furnace with a load characteristic of
those you intend to heat in it.
2. Press the PAGE button until display reads, “Atun
LiSt.”
3. Press the SCROLL button until “drA OFF” is dis-
played.
4. Press the UP or DOWN button to select “on.”
5. Press the SCROLL button until “drA.t” is dis-
played.
6. Press the UP or DOWN button until the desired
trigger value is achieved.
Page 38
38
Installation and Operation of Air Control
Note
Ashing furnaces -60 models contain a feature to provide air (or inert gas) flow within the furnace chamber.
Note
A pressurized air line with a minimum working pressure range of 0 to 40 psi is required.
Note
If furnace is to be used regularly, the airline regulator may be left open to 30 psi.
Note
Appropriate exhaust must be provided to remove smoke and gases produced in an ashing procedure.
Models F30420-33-60-80, F30420C-60-80, F30428C-60-80, F30430CM-33-60, F30430CM­60, F30438CM-60
Installation
Compressed air hook-up
1. A 0.250 inch tube fitting is located at the rear of
the furnace.
2. Using 0.250 inch I.D. rubber tubing, connect a
length of tubing from this input fitting to a corre­sponding 0.250 inch fitting located on the regulat­ed side of a pressurized air service line.
3. Prior to making connections at the regulator,
insure that the regulator is turned fully closed (0 psi).
4. Turn flow control valve located at the bottom of
the flow meter (front control panel) fully clockwise to closed position.
5. Turn regulator to maximum output pressure of 30
psi. Check for any leaks at connection points of connecting tubing.
6. Open flow control valve slowly until ball in flow
meter reads between 40 to 45 liters per minute flow rate.
7. Open furnace door and check that air is exhaust-
ing from the manifold located at the bottom rear of the chamber.
8. Turn flow control valve to off (fully clockwise).
Exhaust tubing hook-up
Using accessory tubing available from Barnstead International (part number AY408X1A for furnace temper­atures less than 975°C, part number AY718X1 for furnace temperatures of 975°C or greater) or equal quality 2.5" I.D. tubing appropriate for the temperatures at which you will operate your furnace, connect flexible tubing from vent port at top of furnace case to an appropriate negative pressure exhaust system. This exhaust system must be capable of handling smoke and gases produced in an ashing proce­dure.
Page 39
39
Furnace Loading
Note
Failure to connect the exhaust port to an appropriate exhaust system will re­sult in smoke and gases filling the work area. Without the connection, gases and smoke will escape around the door seal and at the rear of the furnace.
Caution
Do not overload your furnace cham­ber. If the load is to be heated uniform­ly it should not occupy more than two­thirds of the furnace chamber. Failure to observe this caution could result in damage to furnace components.
For best results, use only the center two-thirds of the furnace chamber.
Use Hearth plate to elevate load when placing on bottom heating element. This prevents bot­tom heating element from overheating and burn­ing out. (Part Numbers PHX1 & PHX2)
If you are heating a number of small parts, spread them throughout the center of the fur­nace chamber.
Keep objects away from thermocouple.
Use insulated tongs and mittens when loading and unloading furnace.
Always wear safety glasses.
Page 40
40
Preventative Maintenance
This unit is equipped with a venting system on the top of the furnace. This is for the removal of fumes from the chamber of the unit. Contamination is a major cause of el­ement failure, therefore, remove all fume forming material before heating. (e.g. clean cutting oil from tool steel).
Housekeeping is vital to your electric furnace - KEEP IT CLEAN. Run your furnace up to 1600°F empty occasion­ally to burn off the contamination that may exist on the in­sulation and elements. Maintain 1600°F for at least 4 hours to insure complete ashing of foreign materials. Element life is reduced somewhat by repeated heating and cooling. If the furnace is to be used again within a few hours, it is best to keep it at the operating tempera­ture or at a reduced level such as 500°F (260°C).
General Cleaning Instructions
Wipe exterior surfaces with lightly dampened cloth con­taining mild soap solution.
Page 41
41
Problem Solving
The Problem Solving section is intended to aid in defining and correcting possible service problems. When using the chart, select the problem category that resembles the malfunction. Then proceed to the possible causes category and take necessary corrective action.
Problem Probable Causes Corrective Action
The cycle light does The furnace is not connected to Check furnace connection not illuminate. power supply. to power source.
ON and OFF power switch is Replace power switch. defective.
Door switch defective. Realign door strike or
replace door safety switch.
Incorrect power source. Check power source. Defective circuit breaker. Replace circuit breaker.
The furnace does not heat. No power. Check power source and fuses or
breakers. Defective electrical hookup. Repair electrical hookup. Thermocouple has oxidized Replace thermocouple.
and opened the circuit. Controller malfunction. Contact customer service.
Two or more heating elements Replace defective elements. burned out.
Door switch malfunction. Realign door strike or replace door
safety switch.
Defective safety relay. Replace safety repay. Defective solid state relay (SSR) Replace SS relay.
Page 42
42
PROBLEM SOLVING
Problem Probable Causes Corrective Action
Slow heatup. Low line voltage. Install line of sufficient size
and proper voltage (Isolate
furnace from other electrical loads).
Heavy load in chamber. Lighten load in chamber
to allow heat to circulate.
Wrong heating element Install proper element.
One or more heating Replace burned out elements. elements are burned out.
Wired improperly. Check wiring diagram for
correct wiring of your furnace.
Door switch does not cut Door switch is not functioning. Realign door strike or power to the furnace chamber. replace door safety switch.
Safety relay malfunction. Replace safety relay.
Repeated element burnout. Overheating furnace. Do not exceed the maximum
operating temperature of furnace or recommended continuous intermittent use values.
Heating harmful materials. Enclose material in container.
Clean up spills on chamber. Ventilate chamber by leaving door cracked slightly open when heating known harmful reagents.
Page 43
43
PROBLEM SOLVING
Problem Probable Causes Corrective Action
Contamination present from Clean and/or replace insulation previous burnout. material.
Wired improperly. Check wiring diagram for
correct wiring of your furnace.
Inaccurate. Oxidized or contaminated Replace thermocouple.
thermocouple. Poor thermocouple connections. Tighten connections. Improper loading. Use proper loading procedures. Poor ventilation of base. Clear area around furnace base. Control out of calibration. Contact customer service.
Page 44
44
Maintenance and Servicing
Warning
Refer servicing to qualified personnel.
Warning
Replace fuses with same type and rating.
Warning
This product contains refractory ceramic, refractory ceramic fiber or fiberglass insulation, which can pro­duce respirable dust or fibers during disassembly. Dust or fibers can cause irritation and can aggravate preexisting respiratory diseases. Refractory ceramic and refractory ceramic fibers (after reaching 1000°C) contain crys­talline silica, which can cause lung damage (silicosis). The International Agency for Research on Cancer (IARC) has classified refractory ceram­ic fiber and fiberglass as possibly carcinogenic (Group 2B), and crys­talline silica as carcinogenic to humans (Group 1).
Warning
To avoid electrical shock, this furnace must always be disconnected from the power supply prior to maintenance and service.
Perform only maintenance described in this manual. Contact an authorized dealer or our factory for parts and as­sistance.
Warning
Please note the following WARNINGS: This warning is presented for compliance with California
Proposition 65 and other regulatory agencies and only applies to the insulation in this product. This product contains refractory ceramic, refractory ceramic fiber or fiberglass insulation, which can produce respirable dust or fibers during disassembly. Dust or fibers can cause irritation and can aggravate preexisting respiratory diseases. Refractory ceramic and refractory ceramic fibers (after reaching 1000°C) contain crystalline silica, which can cause lung damage (silicosis). The Internation­al Agency for Research on Cancer (IARC) has classified refractory ceramic fiber and fiberglass as possibly carcinogenic (Group 2B), and crystalline silica as carcinogenic to humans (Group 1).
The insulating materials can be located in the door, the hearth collar, in the chamber of the product or under the hot plate top. Tests performed by the manufacturer indicate that there is no risk of exposure to dust or respirable fibers resulting from operation of this product under normal conditions. However, there may be a risk of exposure to respirable dust or fibers when repairing or maintaining the insulating materials, or when otherwise disturbing them in a manner which causes release of dust or fibers. By using proper handling procedures and protective equipment you can work safely with these insulating materials and minimize any exposure. Refer to the appropriate Material Safety Data Sheets (MSDS) for information regarding proper handling and recommended protective equipment. For additional MSDS copies, or additional information concerning the handling of refracto­ry ceramic products, please contact the Customer Service Department at Barnstead International at 1-800-553-0039.
To Replace a Heating Element
a. Disconnect furnace from power supply. b. Remove the back terminal cover of the furnace
(Note placement and connections of wires).
c. Loosen the screws and nuts on the terminals of
Page 45
MAINTENANCE AND SERVICING
c. Loosen the screws and nuts on the terminals of
the element to be replaced.
d. Open the door and pull the defective element
out.
e. Slide the new element into place, threading the
leads through the insulating porcelain bushing on the back of the furnace.
f. Cut off any excess lead wire. Be careful not to
nick element lead wires. Reinstall terminal con-
nections and tighten screws and nuts securely. g. Replace the back terminal cover. h. Reconnect furnace to power supply. i. Test operation of furnace.
To Replace a Platinel II Thermocouple
a. Disconnect furnace from power supply. b. Remove the back terminal cover of the furnace.
(Note placement and connection of T/C lead
wires). c. Remove the screws on the thermocouple termi-
nals and pull the thermocouple straight out. d. Insert the new thermocouple into the furnace
with colored beaded lead connected to the posi-
tive (+) marked terminal and other lead to nega-
tive (-) terminal. e. Secure connections with screws removed earlier. f. Replace the back terminal cover. g. Reconnect the furnace to power supply. h. Test operation of furnace.
45
Page 46
46
MAINTENANCE AND SERVICING
To Replace Solid State Relay:
a. Disconnect furnace from power supply. b. Remove the screws on the front dial and the
screws on the lower back cover. c. Remove the upper back cover. d. Disconnect the element lead wires and one
ground wire from back of furnace. Also, discon-
nect T/C lead wire from terminal block. (Note
placement and connection of wires). e. Slide control section forward and disconnect two
wires from door switch. (Note placement and
connection of wires). f. Control section can now be removed from fur-
nace housing. g. Disconnect the wires from the relay and remove
relay. (Note placement and connection of wires). h. Install new relay. i. Reverse steps a - e to reassemble furnace. j. Test operation of furnace.
To Replace Door Switch (Microswitch)
a. Disconnect furnace from power supply. b. Remove the screws on the front dial and the
screws on the lower back cover. c. Remove the upper back cover. d. Disconnect the element lead wires and one
ground wire from back of furnace. Also, discon-
nect the lead wire from terminal block (note
placement and location of wires).
Page 47
47
MAINTENANCE AND SERVICING
e. Slide the control section forward. f. Disconnect the wires from the door switch.
(Note connection and placement of wires to Microswitch).
g. Control section can now be removed from fur-
nace housing.
h. Remove the two screws and nuts from the
Microswitch.
i. Insert new Microswitch and secure with screws
and nuts removed in Step h.
j. Slide control section back and replace the wires
on the door switch.
k. Reverse steps b, c, d and e to reassemble fur-
nace. l. Reconnect to power supply. m. Test operation of door switch. (To realign door
strike, see To Realign Door Strike).
To Realign Door Strike
a. Disconnect furnace from power supply. b. Loosen the screws which retain the door strike
on the bottom left side of the door. c. Move the bracket closer to the furnace to make
strike engage sooner. Move bracket further
away to make strike engage later. (Lightly tight-
en screws between each adjustment to hold
bracket while you test the strike.) d. The door switch should click when the door is
approximately 1” from being completely closed. e. Tighten screws when bracket is positioned cor-
rectly.
Page 48
48
MAINTENANCE AND SERVICING
f. Reconnect to power supply. g. To test the operation of the door strike: turn the
power switch on, set the control to a setting high enough to keep the control from cycling, open and close the door; the cycle light should switch on when the door is approximately 1” from being closed.
To Replace Control Module
a. Gently pry the retaining tabs on both sides out,
then pull the control straight out of the sleeves. Install the new controller to the sleeve.
Page 49
49
Replacement Parts
Single Setpoint Models
F30420C, F30420C-33, F30428C
Part Number Description Quantity Notes
CAX99 Line filter 1 “-33” model only CA1249X1 Capacitor 1 “-33” model only CN71X88 Controller 1 All models EL412X1 Element 1 208V model EL412X2 Element 1 208V model EL412X3 Element 2 208V model EL412X4 Element 1 240 V model EL412X5 Element 1 240 V model EL412X6 Element 2 240 V model FA1262X1 Fan 1 All models PLX82 Pilot light 1 All models RYX37 S.S. relay 1 All models RYX62 Mechanical relay 1 All models SWX103 Circuit breaker 1 All models SWX144 Power switch 1 All models SWX163 Door switch 1 All models TC412X119 Thermocouple 1 All models TRX96 Terminal block 1 All models TRX178 Terminal block 1 All models
F30420C-33-80, F30420-33-60-80, F30420C-60-80, F30420C-80, F30428C-60-80, F30428C-80
Part Number Description Quantity Notes
CAX98 Line Filter 1 “-33” model only CA1249X1 Capacitor 1 “-33” model only CN71X89 Controller 1 F30420C-38-80, F30420C-80, F30428C-80
CN71X91 Controller 1 F30420-33-60-80, F30420C-60-80,
F30428C-60-80
EL412X1 Element 1 208V model
EL412X2 Element 1 208V model
EL412X3 Element 2 208V model
EL412X4 Element 1 240 V model
EL412X5 Element 1 240 V model EL412X6 Element 2 240 V model FA1262X1 Fan 1 All models SWX103 Circuit breaker 1 All models PLX82 Pilot light 1 All models RYX37 S.S. relay 1 All models
8 Segment Programmable Models with OTP
Page 50
50
REPLACEMENT PARTS
4X16 Segment Programmable Models with OTP
F30430CM, F30430CM-33, F30430CM-33-60, F30430CM-60, F30438CM, F30438CM-60
Part Number Description
Quantity Notes
CAX99 Line Filter 1 “-33” model only CA1249X1 Capacitor 1 “-33” model only CN71X90 Controller 1 F30430CM, F30430CM-33, F30438CM
CN71X92 Controller 1 F30430CM-33-60, F30430CM-60,
F30438CM-60
EL412X1 Element 1 208V model
EL412X2 Element 1 208V model
EL412X3 Element 2 208V model
EL412X4 Element 1 240 V model
EL412X5 Element 1 240 V model EL412X6 Element 2 240 V model FA1262X1 Fan 1 All models SWX103 Circuit breaker 1 All models PLX82 Pilot light 1 All models RYX37 S.S. relay 1 All models RYX62 Mechanical relay 1 All models SWX144 Power switch 1 All models
SWX163 Door switch 1 All models TRX96 Terminal block 1 All models TRX178 Terminal Block 1 All models
TC412X1A Thermocouple 1 All models
RYX62 Mechanical relay 1 All models SWX144 Power switch 1 All models
SWX163 Door switch 1 All models TRX96 Terminal block 1 All models TRX178 Terminal Block 1 All models
TC412X1A Thermocouple 1 All models
Page 51
51
Please refer to the Specification Plate for the complete model number, serial number, and series number when requesting service, replacement parts or in any correspondence concern­ing this unit.
All parts listed herein may be ordered from the Barnstead
International dealer from whom you purchased this unit or can be obtained promptly from the factory. When service or replacement parts are needed we ask that you check first with your dealer. If the dealer cannot handle your request, then con­tact our Customer Service Department at 563-556-2241 or 800-553-0039. Prior to returning any materials to Barnstead International, please contact our Customer Service Department for a “Return Goods Authorization” number (RGA). Material returned without a RGA number will be refused.
Ordering Procedures
Page 52
52
Wiring Diagrams
SINGLE SETPOINT CONTROL
WIRING DIAGRAM
Page 53
53
WIRING DIAGRAMS
SEGMENT PROGRAMMABLE CONTROL
WIRING DIAGRAM
Page 54
54
WIRING DIAGRAMS
4X16 SEGMENT PROGRAMMABLE CONTROL
WIRING DIAGRAM
Page 55
55
Page 56
56
Two Year Limited Warranty
BARNSTEAD INTERNATIONAL (“BARNSTEAD”) warrants that a product manufactured by Barnstead shall be free of defects in materials and workmanship for two (2) year from the first to occur of (i) the date the product is sold by BARNSTEAD or (ii) the date the product is purchased by the original retail customer (the “Commencement Date”). Except as expressly stated above, BARNSTEAD MAKES NO OTHER WARRANTY, EXPRESSED OR IMPLIED, WITH RESPECT TO THE PRODUCTS AND EXPRESSLY DISCLAIMS ANY AND ALL WARRANTIES, INCLUDING BUT NOT LIMITED TO, WARRANTIES OF DESIGN, MERCHANTABILITY AND FITNESS FOR APARTICULAR PURPOSE.
An authorized representative of BARNSTEAD must perform all warranty inspections. In the event of a defect covered by BARNSTEAD’s warranty, BARNSTEAD shall, as its sole obligation and exclusive remedy, provide free replacement parts to remedy the defective product. In addition, for products sold by BARNSTEAD within the continental United States or Canada, BARNSTEAD shall provide provide free labor to repair the products with the replacement parts, but only for a period of ninety (90) days from the Commencement Date.
BARNSTEAD’s warranty provided hereunder shall be null and void and without further force or effect if there is any (i) repair made to the product by a party other than BARNSTEAD or its duly authorized service repre­sentative, (ii) misuse (including use inconsistent with written operating instructions for the product), mishan­dling, contamination, overheating, modification or alteration of the product by any customer or third party or (iii) use of replacement parts that are obtained from a party who is not an authorized dealer of BARNSTEAD.
Heating elements, because of their susceptibility to overheating and contamination, must be returned to the BARNSTEAD factory and if, upon inspection, it is concluded that failure is due to factors other than excessive high temperature or contamination, BARNSTEAD will provide warranty replacement. As a condition to the return of any product, or any constituent part thereof, to BARNSTEAD’s factory, it shall be sent prepaid and a prior written authorization from BARNSTEAD assigning a Return Goods Number to the product or part shall be obtained.
IN NO EVENT SHALL BARNSTEAD BE LIABLE TO ANY PARTY FOR ANY DIRECT, INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, OR FOR ANY DAMAGES RESULTING FROM LOSS OF USE OR PROFITS, ANTICIPATED OR OTHERWISE, ARISING OUT OF OR IN CONNECTION WITH THE SALE, USE OR PERFORMANCE OF ANY PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CON­TRACT, TORT (INCLUDING NEGLIGENCE), ANY THEORY OF STRICT LIABILITY OR REGULATORY ACTION.
The name of the authorized Barnstead International dealer nearest you may be obtained by calling 1-800-446­6060 (563-556-2241) or writing to:
2555 Kerper Boulevard P.O. Box 797 Dubuque, Iowa 52001-0797 Phone: 563-556-2241 or 800-553-0039 Fax: 563-589-0516 E-mail: mkt@barnstead.com www.barnstead.com
Loading...