SPECIFICATIONS PAGE 55
Millisecond scale 10 to 65530 msec. in 10 msec. steps.
Second scale 1 to 65535 seconds.
Independent on and off delay settings for each input.
Debounce Off
Time: Working in reverse to the Debounce On Time, if the
input is in alarm and goes to the idle state it must remain
there for the Debounce Off time before it is considered
to be idle.
Off = On: Sets the Debounce Off time to be equal to the On time
12.4.2 Hardware analog alarm types
Input
Calibration: To make an analog input usable, it needs to be calibrated
by setting the correspondence between the input
readings and the decimal values they represent, as well
as entering the setpoints that will be used for generating
alarms.
Maximum: The two values entered in the maximum setting controls
are the highest output from the instrument and its
corresponding decimal value. The actual values that can
be entered here depend on which module that the analog
input is in. Details on what is allowed for each module
type are shown in the specification for that module.
Minimum: The two values in the minimum setting controls are the
lowest output from the instrument and its corresponding
decimal value.
Alarm
Setpoints: Set point values for high and low alarms are shown in
bars. Set point values can be modified either by moving
the slider or by entering the value in the Set box below
the sliders. Set point values can have up to 4 digits plus
a decimal point making the range between -9999 and
9999. When setpoints need to be annunciated for values
greater than 9999, the Units settings can be used to
express larger numbers. For the high Set point, there is
an associated High Reset value that is determined by the
Hysteresis setting. When the point has exceeded the
high set point and has become an alarm, it must then
drop below the High Reset level before it is considered
to be in the normal state. Similarly, the value must be
above the Low Reset value to return to normal from a
low alarm state.
Hysteresis: 1% to 25%