THE WALL-MOUNT™ AIR CONDITIONERS - 9.0 EER, (60HZ)
Models W17A2 to W60A2 Right-Side Control Panel
Models W17L2 to W60L2 Left-Side Control Panel
1.5 to 5 Ton (16,400 to 55,000 Btuh)
The Bard Wall-Mount Air Conditioner is a self contained energy efficient
system, which is designed to offer maximum indoor comfort at a minimal
cost without using valuable indoor floor space or outside ground space. This
unit is the ideal product for versatile applications such as: new construction,
modular offices, school modernization, telecommunication structures, portable
structures or correctional facilities. Factory or field installed accessories are
available to meet specific job requirements.
Engineered Features
Aluminum Finned Copper Coils:
Grooved tubing and enhanced louvered
fin for maximum heat transfer and
energy efficiency.
Twin Blowers:
Move air quietly. Most models feature
multispeed blower motors providing
airflow adjustment for high and low
static operation. Motor overload
protection is standard on all models.
Air Conditioner Compressor:
Scroll Compressors eliminate need
for crankcase heater. Standard on all
models.
R-410A Refrigerant:
Designed with R-410A (HFC) non-ozone
depleting refrigerant in compliance with
the Montreal protocol and 2010 EPA
requirements.
Phase Rotation Monitor:
Standard on all 3 phase scroll
compressors. Protects against reverse
rotation if power supply is not properly
connected.
Galvanized 20 Gauge Zinc Coated Steel
Cabinet:
Cleaned, rinsed, sealed and dried before
the polyurethane primer is applied. The
cabinet is handsomely finished with a
baked on textured enamel, which allows
it to withstand 1000 hours of salt spray
tests per ASTM B117-03.
Foil Faced Insulation:
Standard on all units.
Full Length Mounting Brackets:
Built into cabinet for improved
appearance and easy installation.
NOTE: Bottom mounting bracket
included to assist in installation.
Electrical Components:
Are easily accessible for routine
inspection and maintenance through a
right side, service panel opening. Features
a lockable, hinged access cover to the
circuit breaker or toggle disconnect switch.
Electric Heat Strips:
Features an automatic limit and thermal
cut-off safety control. Heater packages
can be factory or field installed.
Filter Service Door:
Separate service door provides easy
access for filter change.
One Inch, Disposable Air Filters:
Are standard equipment. Optional one
inch washable filters available and filter
racks permit the addition of 2" pleated
filter. Factory or field installed.
Condenser Fan and Motor
Shroud Assembly:
Slides out for easy access.
Barometric Fresh Air Damper:
Standard on all units. Allows up to 25%
outside fresh air. Optional ventilation
packages available.
Built-in Circuit Breakers:
Standard on all electric heat versions of
single (230/208 volt) and three phase
(230/208 volt) equipment. Toggle
disconnects are standard on all electric
heat versions of three phase (460 volt)
equipment.
Slope Top:
Standard feature for water run-off.
Top Rain Flashing:
Standard feature on all models.
Liquid Line Filter Drier:
Standard on all units. Protects system
against moisture.
Green refriGerant
r-410a
Compressor Control Module:
Standard on all units. Built-in off-delay
timer adjustable from 30 seconds to 5
minutes. 2-minute on-delay if power
interrupt. 120-second bypass for low
pressure control, and both soft and
manual lockouts for high and low pressure
controls. Alarm output for alarm relay.
High & Low Pressure Switches are
Auto-Reset:
Standard on all units. Built-in lockout
circuit resets from the room thermostat.
Provides commercial quality protection to
the compressor.
• Complies with efficiency requirements of ASHRAE/IESNA 90.1-2010.
• Certified to ANSI/ARI Standard 390-2003 for SPVU (Single Package Vertical Units).
• Intertek ETL Listed to Standard for Safety Heating and Cooling Equipment ANSI/UL
1995/CSA 22.2 No. 236-05, Fourth Edition.
• Commercial Product - Not intended for Residential application.
Form No. S3461-1016
Supersedes S3461-216
Page 1 of 16
Capacity is certified in accordance with ANSI/ARI Standard 390-2003.
EER = Energy Efficiency Ratio and is certified in accordance with ANSI/ARI Standard 390-2003.
W17A2 / W18A2
W17L2 / W18L2
16,40023,60029,40035,00040,00048,50055,000
W24A2
W24L2
W30A2
W30L2
W36A2
W36L2
W42A2
W42L2
W48A2
W48L2
W60A2
W60L2
All ratings based on fresh air intake being 100% closed (no outside air introduction).
Bard Wall-Mounts are designed to provide optional ventilation packages to meet all of your ventilation and indoor air quality requirements. All
units are equipped with a barometric fresh air damper as the standard ventilation package. All ventilation packages can be built-in at the factory
or field-installed at a later date.
BAROMETRIC FRESH AIR DAMPER - BFAD STANDARD
The barometric fresh air damper is a standard feature on all models. It is installed on the inside of the service
door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through
the air inlet openings and to be mixed with the conditioned air. The damper opens during blower operation and
closes when the blower is off. Adjustable blade stops allow different amounts of outside air to be introduced into
the building and can be easily locked closed if required.
BLANK OFF PLATE - BOP OPTIONAL
Barometric Fresh Air Damper
Motorized Fresh Air Damper
Commercial Room Ventilator
A blank off plate is installed on the inside of the service door. It covers the air inlet openings, which restricts any
outside air from entering the unit. The blank off plate should be utilized in applications where outside air is not
required to be mixed with the conditioned air.
MOTORIZED FRESH AIR DAMPER - MFAD OPTIONAL
The motorized fresh air damper is internally mounted behind the service door and allows outside ventilation air,
up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed
with the conditioned air. The two position damper can be fully open or closed. The damper blade is powered
open by a 24VAC motor with spring return on power loss. The damper can be controlled by indoor blower
operation or can be field connected to be managed based on building occupancy.
NOTE: The above vent systems are intake only without built-in exhaust capability. Building will likely require
separate field installed barometric relief or mechanical exhaust elsewhere within the conditioned space.
Balancing dampers in the return air grille may be required to achieve specified amount of outdoor air intake.
COMMERCIAL ROOM VENTILATOR - CRV OPTIONAL
The built-in commercial room ventilator is internally mounted behind the service door and allows outside
ventilation air, up to 50% of the total airflow rating of the unit, to be introduced through the air inlet openings.
It includes a built-in exhaust air damper.
The commercial room ventilator (CRV) is a simple and innovative approach to improving the indoor air quality
by providing fresh air intake and exhaust capability through the CRV. The damper can be easily adjusted
to control the amount of fresh air supplied into the building. The CRV can be controlled by indoor blower
operation or field controlled based on room occupancy. Two versions available (except on 1.5 and 2-Ton
models). The CRV and CRVS are power open - spring return on power loss, and CRVP is power open and
power close. Complies with ANSI/ASHRAE Standard 62.1 “Ventilation for Acceptable Indoor Air Quality”.
Economizer
Energy Recovery Ventilator
ECONOMIZER – ECONWM-Series OPTIONAL
The built-in economizer system is internally mounted behind the service door and allows outdoor air to be
introduced through the air inlet openings. The amount of outdoor air varies in response to the system controls and
settings defined by the end user. It includes a built-in exhaust air damper. The economizer is designed to provide
“free cooling” when outside air conditions are cool and dry enough to satisfy cooling requirements without running
the compressor. This in turn provides lower operating costs, while extending the life of the compressor.
• ECONWMT Equipment Building versions have extended 11" air intake hood to deliver up to 100% of cooling rated airflow.
• ECONWMS Standard versions have 3" air intake hood to deliver up to 75% of cooling rated airflow.
Standard Features:
• Fully modulating
• Honeywell Direct Drive Hi-Torque Actuator
• No linkage required
• Simple single blade design
• Positive shut-off with non-stick gaskets
• Electronic DB and/or Enthalpy sensors depending upon version
• Honeywell JADE electronic economizer module with precision settings and diagnostics
• DB or Enthalpy economizer versions available
WALL-MOUNT ENERGY RECOVERY VENTILATOR - ERVF OPTIONAL
The wall-mount energy recovery ventilator (ERV) is a highly innovative approach to meeting indoor air quality
ventilation requirements as established by ANSI/ASHRAE Standard 62.1. The ERV allows from 200 to 450 CFM
(depending upon model) of fresh air and exhaust through the unit while maintaining superior indoor comfort and
humidity levels. In most cases this can be accomplished without increasing equipment sizing or operating costs.
Heat transfer efficiency is up to 67% during summer and 75% during winter conditions.
The ERV consists of a unique “rotary energy recovery cassette” that provides effective sensible and latent heat
transfer capabilities during summer and winter conditions. Various control schemes are addressed including
limiting ventilation during building occupancy only.
The ERV is designed to be internally mounted behind the service door in the W**A or W**L model wall-mount
units. It can be built-in at the factory (W**A only) or field installed as an option. ERVF-*3 and ERVF-*5 can be
independently adjusted for intake and exhaust rates.
Form No. S3461-1016
Supersedes S3461-216
Page 3 of 16
Page 4
0
100
200
300
400
500
600
700
800
900
1000
1100
ABCDEF
Airflow (cfm)
Vent Position
Total Air 0 ESP
Total Air .15 ESP
Total Air .3 ESP
Vent Air 0 ESP
Vent Air .15 ESP
Vent Air .3 ESP
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
ABCDEF
Airflow (cfm)
Vent Position
Total Air 0 ESP
Total Air .15 ESP
Total Air .3 ESP
Vent Air 0 ESP
Vent Air .15 ESP
Vent Air .3 ESP
0
100
200
300
400
500
600
700
800
900
1000
ABCDEF
Airflow (cfm)
Vent Position
Total Air 0 ESP
Total Air .15 ESP
Total Air .3 ESP
Vent Air 0 ESP
Vent Air .15 ESP
Vent Air .3 ESP
W30 & W36 LOW SPEED TOTAL AND VENTILATION AIRFLOW
Airflow amounts less than 100 CFM may not be achievable.Airflow amounts less than 100 CFM may not be achievable.
W17/W18 & W24 TOTAL AND VENTILATION AIRFLOW
W30 & W36 HIGH SPEED TOTAL AND VENTILATION AIRFLOW
Commercial Room Ventilator Performance Data - CRV-2
Form No. S3461-1016
Supersedes S3461-216
Page 4 of 16
Commercial Room Ventilator Performance Data - CRVS-3 and CRVP-3
Airflow amounts less than 100 CFM may not be achievable.
Page 5
W60 HIGH SPEED TOTAL AND VENTILATION AIRFLOW
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
ABCDEF
Airflow (cfm)
Vent Position
Total Air 0 ESP
Total Air .2 ESP
Total Air .4 ESP
Vent Air 0 ESP
Vent Air .2 ESP
Vent Air .4 ESP
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
ABCDEF
Airflow (cfm)
Vent Position
Total Air 0 ESP
Total Air .2 ESP
Total Air .4 ESP
Vent Air 0 ESP
Vent Air .2 ESP
Vent Air .4 ESP
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
ABCDEF
Airflow (cfm)
Vent Position
Total Air 0 ESP
Total Air .2 ESP
Total Air .4 ESP
Vent Air 0 ESP
Vent Air .2 ESP
Vent Air .4 ESP
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
ABCDEF
Airflow (cfm)
Vent Position
Total Air 0 ESP
Total Air .2 ESP
Total Air .4 ESP
Vent Air 0 ESP
Vent Air .2 ESP
Vent Air .4 ESP
W60 LOW SPEED TOTAL AND VENTILATION AIRFLOW
Commercial Room Ventilator Performance Data - CRVS-5 and CRVP-5
Airflow amounts less than 100 CFM may not be achievable.
Airflow amounts less than 100 CFM may not be achievable.Airflow amounts less than 100 CFM may not be achievable.
W42 & W48 HIGH SPEED TOTAL AND VENTILATION AIRFLOW
Commercial Room Ventilator Performance Data - CRVS-5 and CRVP-5
W42 & W48 LOW SPEED TOTAL AND VENTILATION AIRFLOW
Airflow amounts less than 100 CFM may not be achievable.
Form No. S3461-1016
Supersedes S3461-216
Page 5 of 16
F V LT VLS VLL HRT HRS HRL V LT VLS VLL HRT HRS HRL V LT VLS VLL HRT HRS HRL
757065
O.D.
DB/
WB
0
6331
10854
4341
3256
3256
4341
9587
14110
0
9450
16200
6480
4860
4860
6480
21060
14310
0
7796
13365
5345
4009
4009
5345
17374
11805
0
20250
11812
8100
6075
6075
8100
26325
17887
0
9213
15794
6318
4738
4738
6318
20533
13952
0
24300
14175
9720
7290
7290
9720
31590
21465
8075706560
2261
3256
5517
3375
4860
8235
2784
4009
6793
4218
6075
10293
3290
4738
8029
5062
7290
12352
90
0
3256
3256
0
4860
4860
0
4009
4009
0
6075
6075
0
4738
4738
0
7290
7290
0
3256
3256
0
4860
4860
0
4009
4009
0
6075
6075
0
4738
4738
0
7290
7290
0
7416
3346
11939
2170
2170
2170
2170
9587
5517
2170
14110
0
4995
17820
11070
3240
3240
3240
3240
8235
3240
21060
14310
0
9132
4120
14701
2672
2672
2672
2672
6793
2672
17374
11805
0
6243
22275
13837
4050
4050
4050
4050
4050
26325
17887
10293
0
4870
17374
10793
3159
3159
3159
3159
8029
3159
20533
13952
0
7492
26730
16605
4860
4860
4860
4860
4860
31590
21465
12352
8075706560
85
0
2170
2170
0
3240
3240
0
2672
2672
0
4050
4050
0
3159
3159
0
4860
4860
8502
4432
1085
1085
9587
5517
6615
12690
1620
1620
8235
14310
5457
10469
1336
1336
6793
11805
8268
15862
2025
2025
17887
10293
6449
12372
1580
1580
8029
13952
9922
19035
2430
2430
21465
12352
757065
80
814
1085
1899
1215
1620
2835
1002
1336
2338
1518
2025
3543
1184
1580
2764
1822
2430
4252
0
1085
1085
0
1620
1620
0
1336
1336
0
2025
2025
0
1580
1579
0
2430
2430
60
5517
1899
000
5517
1899
8235
2835
000
8235
2835
6793
2338
000
6793
2338
3543
10293
000
3543
10293
8029
2764
000
8029
2764
4252
12352
000
4252
12352
706560
75
0
0
0
0
0
0
0
0
ERVF-*5 WINTER HEATING PERFORMANCE
0
0
0
0
300 CFM
82% EFFICIENCY
375 CFM
81% EFFICIENCY
VENTILATION RATE
(INDOOR DESIGN CONDITIONS 70°F DB)
450 CFM
80% EFFICIENCY
65243019442025164016201328
60486038884050328032402656
55729058326075492048603985
50972077768100656164805313
4512150972010125820181006642
40145801166412150984197207970
O.D.
Ambient
DB/°FWVLWHRWVLWHRWVLWHR
3517010136081417511481113409298
30194401555216200131221296010627
25218701749618225147621458011955
20243001944020250164021620013284
15267302138422275180421782014612
NOTE: Sensible performance only is shown for winter application.
0
0
0
5265
5265
0
8100
8100
0
6739
6739
0
10530
10530
0
8164
8164
0
12960
12960
105
5265
5265
0
8100
8100
0
6739
6739
0
10530
10530
0
8164
8164
0
12960
12960
73
7019
3363
4387
4387
4387
4387
7751
4460
4387
11407
0
112
5175
10800
6750
6750
6750
6750
6862
6750
17550
11925
0
93
8985
4305
5616
5616
5616
5616
9921
5709
5616
14601
0
146
6727
14040
8775
8775
8775
8775
8921
8775
22815
15502
0
113
5216
10886
6804
6804
6804
6804
6717
6804
17690
12020
0
180
8280
17280
10800
10800
10800
10800
28080
19080
10980
10800
8075706560
100
2486
5265
7751
3825
65% EFFICIENCY
8100
VENTILATION RATE -- 250 CFM
VENTILATION RATE -- 325 CFM
SUMMER COOLING PERFORMANCE
(INDOOR DESIGN CONDITIONS 75°DB/62°WB)
VENTILATION RATE -- 400CFM
Performance and Application Data- ERVF-*3 Performance and Application Data- ERVF-*5
Ambient
11925
3182
6739
9921
4972
64% EFFICIENCY
10530
15502
3855
8164
12020
6120
63% EFFICIENCY
12960
19080
F V LT VLS VLL HRT HRS HRL V LT VLS VLL HRT HRS HRL V LT VLS VLL HRT HRS HRL
757065
O.D.
DB/
WB
0
7897
4241
4387
3510
3510
4387
7751
11407
0
6525
12150
6750
5400
5400
6750
17550
11925
0
5428
10108
5616
4492
4492
5616
9921
14601
0
8482
15795
8775
7020
7020
8775
22815
15502
0
6577
12247
6804
5443
5443
6804
17690
12020
0
19440
10440
8640
8640
10800
10800
28080
19080
8075706560
950
3510
4460
1462
5400
6862
1216
4492
5709
1901
7020
8921
1474
5443
6917
2340
8640
10980
95
0
3510
3510
0
5400
5400
0
4492
4492
0
7020
7020
0
5443
5443
0
8640
8640
0
8774
5118
3510
2632
2632
3510
7751
11407
0
7875
13500
5400
4050
4050
5400
17550
11925
0
6552
11232
4492
3369
3369
4492
9921
14601
0
17550
10237
7020
5265
5265
7020
22815
15502
0
7938
13608
5443
4082
4082
5443
17690
12020
0
21600
12600
8640
6480
6480
8640
28080
19080
8075706560
1828
2632
4460
2812
4050
6862
2340
3369
5709
3656
5265
8921
2835
4082
6917
4500
6480
10980
90
0
2632
2632
0
4050
4050
0
3369
3369
0
5265
5265
0
4082
4082
0
6480
6480
0
2632
2632
0
4050
4050
0
3369
3369
0
5265
5265
0
4082
4082
0
6480
6480
0
9652
5996
2705
1755
1755
1755
1755
7751
4460
1755
11407
0
9225
4162
14850
2700
2700
2700
2700
6862
2700
17550
11925
0
7675
3463
12355
2246
2246
2246
2246
9921
5709
2246
14601
0
5411
19305
11992
3510
3510
3510
3510
8921
3510
22815
15502
0
9298
4195
14968
2721
2721
2721
2721
6917
2721
17690
12020
0
6660
23760
14760
4320
4320
4320
4320
4320
28080
19080
10980
8075706560
85
0
1755
1755
0
2700
2700
0
2246
2246
0
3510
3510
0
2721
2721
0
4320
4320
6873
3583
877
877
7751
4460
5512
10575
1350
1350
6862
11925
8798
4586
1123
1123
9921
5709
7166
13747
1755
1755
8921
15502
5556
10659
1360
1360
6917
12020
8820
16920
2160
2160
19080
10980
757065
80
658
877
1535
1012
1350
2362
842
1123
1965
1316
1755
3071
1020
1360
2381
1620
2160
3780
0
877
877
0
1350
1350
0
1123
1123
0
1755
1755
0
1360
1360
0
2160
2160
60
4460
1535
000
4460
1535
6862
2362
000
6862
2362
5709
1965
000
5709
1965
8921
3071
000
8921
3071
6917
2380
000
6917
2381
3780
10980
000
3780
10980
706560
75
0
0
0
0
0
0
0
0
0
0
ERVF-*3 WINTER HEATING PERFORMANCE
0
0
LEGEND:
VLT = Ventilation Load - Total
VLS = Ventilation Load - Sensible
VLL = Ventilation Load - Latent
HRT = Heat Recovery - Total
HRS = Heat Recovery - Sensible
HRL = Heat Recovery - Latent
WVL = Winter Ventilation Load
WHR = Winter Heat Recovery
250 CFM
77% EFFICIENCY
325 CFM
76% EFFICIENCY
VENTILATION RATE
(INDOOR DESIGN CONDITIONS 70°F DB)
400 CFM
75% EFFICIENCY
65216016201755133313501039
60432032403510266727002079
55648048605265400140503118
50864064807020533554004158
451080081008775666967505197
4012960972010530800281006237
O.D.
Ambient
DB/°FWVLWHRWVLWHRWVLWHR
35151201134012285933694507276
3017280129601404010670108008316
2519440145801579512004121509355
20216001620017550133381350010395
15237601782019305146711485011434
NOTE: Sensible performance only is shown for winter application.
Form No. S3461-1016
Supersedes S3461-216
Page 7 of 16
Page 8
Electrical Specifications — W**A2 Series
MODEL
Volts &
Phase
Rated
W17, 18A2-A00,A0Z
W24A2-A00, A0Z
W24A2-B00, B0Z
W24A2-C00, C0Z
W30A2-A00*, A0Z*
W30A2-B00*, B0Z*
W30A2-C00*, C0Z*
W36A2-A00*, A0Z*
W36A2-B00*, B0Z*
W36A2-C00*, C0Z*
W42A2-A00, A0Z
W42A2-B00, B0Z
W42A2-C00, C0Z
W48A2-A00, A0Z
W48A2-B00, B0Z
W48A2-C00, C0Z
W60A2-A00, A0Z
W60A2-B00, B0Z
W60A2-C00, C0Z
Maximum size of the time delay fuse or HACR type circuit breaker for protection of eld wiring conductors.
Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes.
A05
A08
A10
A04
A05
A08
A10
B06
C06
A05*
A08
A10*
A15
B06
B09*
B15
C06
C09*
C12
C15
A05*
A08
A10*
A15
B06*
B09*
B15
C06*
C09*
C12
C15
A05
A10
A15
A20
B09
B15
B18
C09
C15
A05
A10
A15
A20
B09
B15
B18
C09
C15
A05
A10
A15
A20
B09
B15
B18
C09
C15
230/208-1
230/208-1
230/208-3
460-3
230/208-1
230/208-3
460-3
230/208-1
230/208-3
460-3
230/208-1
230/208-3
460-3
230/208-1
230/208-3
460-3
230/208-1
230/208-3
460-3
No.
Field
Power
Circuits
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1 or 2
1
1
1
1
1
1
1
1
1
1
1
1
1
1 or 2
1
1
1
1
1
1
1
1
1
1
1
1
1 or 2
1 or 2
1
1
1
1
1
1
1
1
1
1
1 or 2
1 or 2
1
1
1
1
1
1
1
1
1
1
1 or 2
1 or 2
1
1
1
2
1
1
1
Minimum
Circuit
Ampacity
16
30
46
56
21
25
30
46
56
15
22
9
11
24
32
47
58
84
18
24
33
51
11
12
17
21
26
29
32
47
58
84
23
24
33
51
11
12
16
21
26
32
32
58
84
110
24
33
51
60
12
17
26
39
39
58
84
110
27
33
51
60
13
17
26
42
42
60
86
112
28
35
53
N/A
15
18
27
These “Minimum Circuit Ampacity” values are to be used for sizing the eld power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor sizing.
Caution: When more than one eld power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity
Adjustment Factors when more than three (3) current carrying conductors are in a raceway.
* Top outlet supply option is available only factory installed and only on the selected models.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized over-current protection and conductor wires in accordance with the National
Electrical Code and all local codes.
Single CircuitDual Circuit
Maximum
External
Fuse or
Ckt. Brkr.
20
30
50
60
30
30
30
50
60
20
25
15
15
35
35
50
60
90
20
25
35
60
15
15
20
25
30
35
35
50
60
90
30
30
35
60
15
15
20
25
30
50
50
60
90
125
35
35
60
60
15
20
30
50
50
60
90
125
40
40
60
60
20
20
30
60
60
60
90
125
40
40
60
N/A
20
20
30
Field
Power
Wire Size
12
10
8
6
10
10
10
8
6
12
10
14
14
8
8
8
6
4
12
10
8
6
14
14
12
10
10
8
8
8
6
4
10
10
8
6
14
14
12
10
10
8
8
6
4
2
8
8
6
6
14
12
10
8
8
6
4
2
8
8
6
6
12
12
10
8
8
6
3
2
8
8
6
N/A
12
12
10
Minimum
Ground
Wire
12
10
10
10
10
10
10
10
10
12
10
14
14
10
10
10
10
8582660306101010
12
10
10
10
14
14
12
10
10
10
10
10
10
8582660306101010
10
10
10
10
14
14
12
10
10
10
10
10
8
6
10
10
10
10
14
12
10
10
10
10
8
6
10
10
10
10
12
12
10
10
10
10
8
6
10
10
10
N/A352840308101010
12
12
10
Circuit
Ampacity
Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B
58
58
58
58
60
60
26
52
26
52
26
52
Maximum
External Fuse or
Ckt. Breaker
60
30
60
60
60
30
60
60
60
30
60
60
Field Power
Wire Size
6
6
6
6
6
6
Ground
Wire Size
10
10
6
10
6
10
6
10
10
10
10
10
10
10
10
10
10
10
Form No. S3461-1016
Supersedes S3461-216
Page 8 of 16
Page 9
Electrical Specifications — W**L2 Series
MODEL
Volts &
Phase
Rated
W17, 18L2-A00,A0Z
W24L2-A00, A0Z
W24L2-B00, B0Z
W30L2-A00, A0Z
W30L2-B00, B0Z
W30L2-C00, C0Z
W36L2-A00, A0Z
W36L2-B00, B0Z
W36L2-C00, C0Z
W42L2-A00, A0Z
W42L2-B00, B0Z
W42L2-C00, C0Z
W48L2-A00, A0Z
W48L2-B00, B0Z
W48L2-C00, C0Z
W60L2-A00, A0Z
W60L2-B00, B0Z
W60L2-C00, C0Z
Maximum size of the time delay fuse or HACR type circuit breaker for protection of eld wiring conductors.
Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes.
A05
A08
A10
A05
A08
A10
B06
A05
A08
A10
A15
B09
B15
C09
C15
A05
A10
A15
B09
B15
C09
C15
A05
A10
A15
B09
B15
C09
C15
A05
A10
A15
B09
B15
C09
C15
A05
A10
A15
B09
B15
C09
C15
230/208-1
230/208-1
230/208-3
230/208-1
230/208-3
460-3
230/208-1
230/208-3
460-3
230/208-1
230/208-3
460-3
230/208-1
230/208-3
460-3
230/208-1
230/208-3
460-3
No.
Field
Power
Circuits
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1 or 2
1
1
1
1
1
1
1
1
1
1 or 2
1
1
1
1
1
1
1
1
1
1 or 2
1
1
1
1
1
1
1
1
1
1 or 2
1
1
1
1
1
1
1
1
1
1 or 2
1
1
1
1
1
1
Minimum
Circuit
Ampacity
16
30
46
56
21
30
46
56
15
22
24
32
47
58
84
18
33
51
11
17
26
29
32
58
84
23
33
51
11
16
26
32
32
58
84
24
33
51
12
17
26
39
39
58
84
27
33
51
13
17
26
42
42
60
86
28
35
53
15
18
27
These “Minimum Circuit Ampacity” values are to be used for sizing the eld power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor sizing.
Caution: When more than one eld power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity
Adjustment Factors when more than three (3) current carrying conductors are in a raceway.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized over-current protection and conductor wires in accordance with the National
Electrical Code and all local codes.
Single CircuitDual Circuit
Maximum
External
Fuse or
Ckt. Brkr.
20
30
50
60
30
30
50
60
20
25
35
35
50
60
90
20
35
60
15
20
30
35
35
60
90
30
35
60
15
20
30
50
50
60
90
35
35
60
15
20
30
50
50
60
90
40
40
60
20
20
30
60
60
60
90
40
40
60
20
20
30
Field
Power
Wire Size
12
10
8
6
10
10
8
6
12
10
8
8
8
6
4
12
8
6
14
12
10
8
8
6
4
10
8
6
14
12
10
8
8
6
4
8
8
6
14
12
10
8
8
6
4
8
8
6
12
12
10
8
8
6
3
8
8
6
12
12
10
Minimum
Ground
Wire
12
10
10
10
10
10
10
10
12
10
10
10
10
10
8582660306101010
12
10
10
14
12
10
10
10
10
8582660306101010
10
10
10
14
12
10
10
10
10
8582660306101010
10
10
10
14
12
10
10
10
10
8582660306101010
10
10
10
12
12
10
10
10
10
8602660306101010
10
10
10
12
12
10
Circuit
Ampacity
Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B
Maximum
External Fuse or
Ckt. Breaker
Field Power
Wire Size
Ground
Wire Size
Form No. S3461-1016
Supersedes S3461-216
Page 9 of 16
Page 10
Indoor Blower Performance (60 Hz) - CFM at Rated Volts
Above data is with 1" standard throwaway filter and 1" washable filter.
For optional 2" pleated filter - reduce ESP by .15 in.
See installation instructions for maximum ESP information on various KW application.
W17/W18W24W30W36W42/W48W60
Dry
Coil
High
Low Single High
Wet
Dry
Wet
Coil
Coil
Coil
Dry
Coil
Wet
Coil
Dry
Coil
Wet
Coil
Dry
Coil
Low
Wet
Coil
Dry
Coil
High
Wet
Coil
Dry
Coil
Low
Wet
Coil
Dry
Coil
High
Wet
Coil
Dry
Coil
Low
Wet
Coil
Factory Connected Speed.
High
Dry
Coil
Wet
Coil
Dry
Coil
Low
Electric Heat Table - Refer to Electrical Specifications for Availability by Unit Model
(1) These electric heaters are available in 230/208V units only.
(2) These electric heaters are available in 480V units only.
At 240V (1)At 208V (1)At 480V (2)At 460V (2)
1-Ph
Amps
3-Ph
Amps
BtuhKw
1-Ph
Amps
3-Ph
Amps
BtuhKw
3-Ph
Amps
BtuhKw
3-Ph
Amps
Btuh
Wet
Coil
Form No. S3461-1016
Supersedes S3461-216
Page 10 of 16
Page 11
Heater Packages - Field Installed "A" Series Right-Hand Units
• Designed for adding Electric Heat to 0 KW Units• ETL US & Canada Listed
• Circuit Breaker Standard on 230/208V Models• Toggle Disconnect Standard on 460V Models
Air
Conditioner
Models
W17A2
W18A2
W24A2
W30A2
W36A2
W42A2
W48A2
W60A2
-A00 Models
230/208-1
Heater Model #KWHeater Model #KWHeater Model #KW
EHWA02-A05B
EHW02A-A08B
EHWA02A-A10B
EHWA24A-A04B
EHWA02-A05B
EHW02A-A08B
EHWA02A-A10B
EHWA03-A05B
EHWA03-A08B
EHWA03-A10B
EHWA03-A15B
EHWA03-A05B
EHWA03-A08B
EHWA03-A10B
EHWA03-A15B
EHWA05-A05B
EHWA05-A10B
EHWA05-A15B
EHWA05-A20B
EHWA60-A05B
EHWA05-A10B
EHWA05-A15B
EHWA05-A20B
5
8
10
4
5
8
10
5
8
10
15
5
8
10
15
5
10
15
20
5
10
15
20
-B00 Models
230/208-3
N/AN/A
EHWA24-B06B6EHWH24B-C066
EHWA03-B06B
EHWA03-B09B
EHWA37-B15B
EHW36A-B06B
EHWA03-B09B
EHWA37-B15B
EHWA05-B09B
EHWA05-B15B
EHWA05-B18B
EHW60A-B09B
EHWA05-B15B
EHW05A-B18B
6
9
15
6
9
15
9
15
18
9
15
18
-C00 Models
460-3
EHWC03A-C06
EHWC03A-C09
EHWA03A-C12
EHWA03A-C15
EHWC03A-C06
EHWC03A-C09
EHWA03A-C12
EHWA03A-C15
EHWA05A-C09
EHWA05A-C15
EHWA05A-C09
EHWA05A-C15
6
9
12
15
6
9
12
15
9
15
9
15
NOTE: Field installed Heater Packages are not approved for use with top supply opening models.
Field installed Heater Package not available for W70L models.
These heater packages approved for use in dehumidification versions with hot gas reheat.
Heater Packages - Field Installed "L" Series Left-Hand Units
Form No. S3461-1016
Supersedes S3461-216
Page 11 of 16
Page 12
Clearances Required for Service Access
and Adequate Condenser Inlet Airflow
MODELS LEFT SIDE RIGHT SIDE
W17A, W18A, W24A, W30A, W36A15"20"
W42A, W48A, W60A20"20"
NOTE: For side-by-side installation of two (2) WA models, there
must be 20" between units. This can be reduced to 15" by
using a WL model (left side compressor and controls) for the left
unit and WA (right side compressor and controls) for right unit.
Minimum Clearances Required to
Combustible Materials
MODELS
SUPPLY AIR DUCT
FIRST THREE FEET
W17A, W18A, W24A0"0"
W30A, W36A1/4"0"
W42A, W48A, W60A1/4"0"
Refer to the Installation Manual for more detailed information.
CABINET
Dimensions of W17-60A Basic Unit for Architectural & Installation Requirements (Nominal)
Standard
flush vent
door for
non-ERV/
Econ.
models
Hood for
ECONWMT
models.
3"
11"
Low Voltage
Electrical
Entrance
High Voltage
Electrical
Entrance
D
7.88
1.250
Cond.
Air
Inlet
Side View
2
2
1.00
2.13
Side Wall
A
Mounting
Brackets
(Built In)
I
Top Rain
Flashing
Shipping
Location
Optional
C
H
Electrical
Entrances
K
J
L
M
Supply Air Opening
Return Air Opening
P
Drain
N
Q
E
O
31.88
B
Back View
2
.44
Bottom Installation
Bracket
R
S
S
S
S
S
T
MIS-2487 H
Not used when ECONWMT Economizers installed. Filter access is through the ECONWMT hood.
Optional top outlet (factory installed only) in place of standard front supply air opening for W30A and W36A models only.
Form No. S3461-1016
Supersedes S3461-216
Page 12 of 16
Page 13
Clearances Required for Service Access
and Adequate Condenser Inlet Airflow
MODELS LEFT SIDE RIGHT SIDE
W17L, W18L, W24L, W30L, W36L20"15"
W42L, W48L, W60L20"20"
NOTE: For side-by-side installation of two (2) WL models, there
must be 20" between units. This can be reduced to 15" by
using a WL model (left side compressor and controls) for the left
unit and WA (right side compressor and controls) for right unit.
Minimum Clearances Required to
Combustible Materials
MODELS
W17L, W18L, W24L0"0"
W30L, W36L1/4"0"
W42L, W48L, W60L1/4"0"
Refer to the Installation Manual for more detailed information.
SUPPLY AIR DUCT
FIRST THREE FEET
CABINET
Dimensions of W17-60L Basic Unit for Architectural & Installation Requirements (Nominal)
Below 65°F, unit requires a factory or field installed low ambient control.
Outdoor temperatures shown are measured at the condenser section air inlet.
Return air temperature °F.
Form No. S3461-1016
Supersedes S3461-216
Page 14 of 16
Page 15
Air Conditioning Wall-Mount Model Nomenclature
W36A2A10XXXXX X
SERIES |
NOMINAL
CAPACITY |
17 - 1½ Ton
18 - 1½ Ton
24 - 2 Ton
30 - 2½ Ton
36 - 3 Ton
42 - 3½ Ton
48 - 4 Ton
60 - 5 Ton
REVISION
A = Compressor &
Controls - Right Side
L = Compressor &
Controls - Left Side
D = DEHUMIDIFICATION OPTION
Models W30A2, W36A2, W42A2,
W48A2 & W60A2 only.
Insert D in place of dash (-).
VOLTS & PHASE
A - 230/208/60/1
B - 230/208/60/3
C - 460/60/3
KW
VENTILATION OPTIONS
(See Table Below)
FILTER OPTIONS
X - 1-inch Throwaway (Standard)
W - 1-inch Washable
P - 2-inch Pleated (MERV 8)
COLOR OPTIONS
X - Beige (Standard)
1 - White
4 - Buckeye Gray
5 - Desert Brown
8 - Dark Bronze
A - Aluminum
S - Stainless Steel
| COIL OPTIONS
X - Standard
1 - Phenolic Coated Evaporator
2 - Phenolic Coated Condenser
3 - Phenolic Coated Evaporator
and Condenser
| SUPPLY AIR OUTLET
X - Front (Standard)
T - Top (on W30A and
W36A Models)
For 0KW and circuit breakers (230/208 Volt) or toggle disconnects (460 Volt) applications, insert 0Z in the KW field of the model number.
See Pages 8 & 9 for available Factory Installed KW options and Page 11 for Field Installed Heater Packages.
| CONTROL MODULES
(See Chart Below)
Ventilation Options
Models
Description
Barometric Fresh Air Damper - Standard XBFAD-2XBFAD-3XBFAD-5
Blank-Off PlateBBOP-2BBOP-3BBOP-5
Motorized Fresh Air DamperMMFAD-2MMFAD-3MMFAD-5
Commercial Ventilator - Spring Return w/ExhaustVCRV-2VCRVS-3VCRVS-5
Commercial Ventilator - Power Return w/Exhaust------PCRVP-3PCRVP-5
Economizer - Standard Versions, Enthalpy
Economizer - Equipment Bldg., Enthalpy
Economizer - Equipment Bldg., DB Temp
Energy Recovery Ventilator - 230 Volt R
Energy Recovery Ventilator - 460 Volt
Door Kit for ERVF (Required) N/A
Intake and exhaust can be independently adjusted.
Insert color to match unit ("X" = Beige; "4" = Buckeye Gray; etc.)
WMDK Door Kit must be ordered in addition to ERVF Assembly & color matched to unit ("X" = Beige; "4" = Buckeye Gray; etc.)
Partial Full Flow (75% of Rated Cooling CFM). All ECONWMS versions have 3" deep intake hood.
Full Flow (100% of Rated Cooling CFM). All ECONWMT versions have 11" deep intake hood.
Model W24A2-C & W24L2-C only.
Energy Recovery Ventilator must be field-installed on W**L models. Also see Note .
W17A2, W18A2, W24A2
W17L2, W18L2, W24L2
Factory Installed
Code No.
S
W
T
N/A
Field Installed
Part No.
ECONWMS-E2B
ECONWMT-E2B
ECONWMT-T2B
ERVF-A2
ERVF-C2 R ERVF-C3 R ERVF-C5
WMDK2-
Factory Installed
Air Conditioning Control Modules
HPC LPC CCM LAC ALR SK SK ODT DDC
STDSTDSTDXN/AN/A
STDSTDSTD
STDSTDSTD
STDSTDSTD
STDSTDSTD
STDSTDSTD
STDSTDSTD
STDSTDSTD
STDSTDSTD
STDSTDSTD
STDSTDSTD
STD = Standard equipment for these specified models.
HPC. High pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note .
LPC. Low pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note .
CCM. Compressor control module has adjustable 30-second to 5-minute delay-on-break timer. On initial power-up, or any time the power is interrupted, the delay-on-make
will be 2-minutes plus 10% of the delay-on-break setting. There is no delay-on-make during routine operation of the unit. The module also provides the lockout
feature (with 1 retry) for high and/or low pressure controls, and a 2-minute timed bypass for low-pressure control.
LAC. Low ambient control permits cooling operation down to 0°F. LAC is fan-cycling control for outdoor fan motor on all models except W42, W48, W60 Dehum. units, which have modulating control.
ALR.
The alarm relay has a set of normally open and normally closed dry contacts to provide the ability to signal a condition of shutdown on either high or low pressure controls.
SK.
PTCR start kit can be used with all -A single phase models. Increases starting torque 2-3x. Not used for -B or -C three phase models. Do not use if SK111 or SK121 is used.
SK. Start capacitor & potential relay start kit can be used with all -A single phase models. Increases starting torque 9x. Not used for -B or -C three phase models. Do
not use if CMC-15 is used.
ODT. Outdoor thermostat is adjustable from 0 to 50°F. It is suitable for use as a compressor cut-off thermostat.
DDC. Incorporates 4 additional sensors: discharge air temperature, indoor blower airflow, compressor current, and dirty filter. These sensing devices function to input analog
data such as temperature, as well as digital data such as airflow, compressor status or filter status. Special economizer required; consult factory.
s “V” control module should be ordered in conjunction with direct digital controller (DDC). Refer to “V” Module document F1605 for more information.
⑪
Option not available for Model W18A.
⑫
Use option N for Alarm Relay on Model W18A only.
⑬
LAC consists of special heat transfer device suitable for operation down to 0°F. Fan-cycling control is not used.
l
ll
ll
lll
l
l
l
lllV s
l
l
W30A2, W36A2
W30L2, W36L2
Code No.
S
W
T
R ERVF-A3 R ERVF-A5
N/A
Field Installed
Part No.
ECONWMS-E3B
ECONWMT-E3B
ECONWMT-T3B
WMDK3-
All Models Except As Noted
Factory Installed CodeField Installed Part
⑪
E
⑪
J
⑪
K
⑪
M
N, W18A Only
Field Installed OnlyCMC-15CMC-15
Field Installed OnlyCMA-14N/A
Field Installed Only
Field Installed Only
⑫
⑪
CMC-15 and CMA-28N/A
CMA-23 for W17-36
CMA-24 for W42-70
W42A2, W48A2, W60A2
W42L2, W48L2, W60L2
Factory Installed
Code No.
S
W
T
N/A
CMA-28N/A
Factory OnlyJ ⑬
Factory OnlyM ⑬
N/AN/A
Factory OnlyN/A
SK111 Except W70
SK121 W70 Only
Field Installed
ECONWMS-E5B
ECONWMT-E5B
ECONWMT-T5B
Form No. S3461-1016
Supersedes S3461-216
Page 15 of 16
Part No.
WMDK5-
W17A2
W17L2
Factory Only
N/A
SK111
Page 16
NOTES
Form No. S3461-1016Supersedes S3461-216
Page 16 of 16
Bard Manufacturing Company, Inc.
Bryan, Ohio 43506
www.bardhvac.com
Due to our continuous product improvement policy,
all specifications subject to change without notice.
Before purchasing this appliance, read important energy
cost and efficiency information available from your retailer.
Form No.
S3461
October, 2016
Supersedes S3461-216