These publications can help when installing the
furnace. They can usually be found at the local library
or purchased directly from the publisher. Be sure to
consult the current edition of each standard.
National Fuel Gas Code ..........ANSI Z223.1 / NFPA 54
National Electrical Code .....................ANSI / NFPA 70
Standard for the Installation ............ANSI / NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air .................... ANSI / NFPA 90B
Heating and Air Conditioning Systems
Standard for Chimneys, ............................. NFPA 211
Fireplaces, Vents, and Solid Fuel Burning Appliances
Load Calculation for ........................... ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for Residential .............. ACCA Manual D
Winter and Winter Air Conditioning and Equipment
Selection
Canadian Electrical Code ........................... CSA C22.1
FOR MORE INFORMATION, CONTACT
THESE PUBLISHERS:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Avenue, NW
Washington, DC 20009
Telephone: (202) 483-9370
ANSI American National Standards Institute
11 West Street, 13th Floor
New York, NY 10036
Telephone: (212) 642-4900
Fax: (212) 302-1286
ASHRAE American Society of Heating Refrigerating,
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, NE.
Atlanta, GA 30329-2305
Telephone: (404) 636-8400
Fax: (404) 321-5478
NFPA National Fire Protection Association
Batterymarch Park
P.O. Box 9101
Quincy, MA 02269-9901
Telephone: (800) 344-3555
Fax: (617) 984-7057
Low ambient control is required with economizer for low temperature compressor operation.
Manual 2100-587J
Page 5 of 59
AIR CONDITIONING MODULE OPTIONS
CCM
STDSTDSTDXN/A
STDSTDSTD--HCMA-28
STD = Standard equipment
HPC
LPC
LAC
Factory Installed
Code
Field Installed
Part
CCM Compressor control module has adjustable 30 second to 5 minute delay-on-break timer. On initial
power up, or any time the power is interrupted, the delay-on-make will be 2 minutes plus 10% of
the delay-on-break setting. There is no delay-on-make during routine operation of the unit. The
module also provides the lockout feature (with 1 retry) for high and/or low pressure controls, and a
2 minute timed bypass for low pressure control.
HPC High pressure control is auto reset. Always used with compressor control module (CCM) which is
included. See note
.
LPC Low pressure control is auto reset. Always used with compressor control module (CCM) which is
included. See note
.
LAC Low ambient control permits cooling operation down to 0°F.
CAUTION
During the initial ring of the burners there will probably be some amount of smoke issued to the
circulating air stream as the result of residual oil burning off of the heat exchanger tubes. This oil
is required during the forming process of the stainless steel heat exchanger tubes to facilitate the
bending. OSHA or the National Toxicology Program does not list the oil as a carcinogen. In vapor
form this may be irritating to the eyes or could cause headaches. This is a one-time occurrence, and
ventilation of the space may be required depending upon the space being conditioned.
CFM Cooling and E.S.P.110011001100150015001500170017001700
Filter Sizes (Inches)20 x 30 x 220 x 30 x 220 x 30 x 220 x 30 x 220 x 30 x 220 x 30 x 220 x 30 x 220 x 30 x 220 x 30 x 2
Charge (R-410A)156156156240240240246246246
* 75° C Copper wire size
** Maximum time delay fuse or circuit breaker
Manual 2100-587J
Page 7 of 59
R
41.63
43.38
13.75
34.9
S
S
S
S
S
T
3.75
2.514.883014.12 15.4442.8815.31
4.5
FIGURE 1
Unit Dimensions
0.44
1.257.251.13
3.252.75
12.191040.25
2.253.884217.34 8.44
MIS-3240 A
B
O
B
E
EE
SUPPLY OPENING
BB
RETURNOPENING
BACK
CC
II
Q
GAS
ENTRANCES
X
AA
LOW VOLTAGE
Y
ENTRANCES
ENTRANCES
HIGH VOLTAGE
V
H
FF
GG
HH
A
I
U
Z
M
C
L
KJ
DD
D
CONDENSER
AIRINLETS
RIGHT SIDE
43.81
9.8829.88 15.88 27.25
UNITABCDEFGHIJKLMNOPQR
WG3S231.6387.533.38 28.75
Manual 2100-587J
Page 8 of 59
P
N
VESTIBULE
DOOR
4 DEG. PITCHINTOP
16
UNITSTUVWXYZAABBCCDDEEFFGGHHII
WG3S23.7524.9
W
COMBUSTION
AIRINTAKE
COMBUSTION
AIREXHAUST
FRONTDOOR
FILTER
SERVICE
DOOR
CIRCUITBREAKER/
DISCONNECT ACCESS
PANELDOOR
CONTROL
F
PANEL
VENTOPTION
PANEL(LOCKABLE)
AIROUTLET
CONDENSER
FRONT
G
1. IMPORTANT
The equipment covered in this manual is to be
installed by trained, experienced service and
installation technicians. All duct work or portions
thereof not in the conditioned space should be properly
insulated in order to both conserve energy and prevent
condensation or moisture damage.
2. APPLICATION
This is a fan-assisted forced air gas furnace with electric
air conditioning for outdoor installation. A fan-assisted
furnace is equipped with an integral mechanical means
to draw products of combustion through the combustion
chamber and heat exchanger. The furnace installation
must conform with local building codes and ordinances
or, in their absence, with the National Fuel Gas Code
ANSI Z223.1 or CAN/CGA-B149.1, latest edition,
and the National Electrical Code ANSI/NFPA-7 or CSA
C22.1, latest edition. It is the personal responsibility
and obligation of the purchaser to contact a qualified
installer to assure that installation is adequate and is in
conformance with governing codes and ordinances.
3. DUCT WORK
The unit is designed for use with or without duct work
(see Warning on this page). Flanges are provided
for attaching the supply and return ducts. These
instructions explain the recommended method to
install the air cooled self-contained electric air
conditioning and gas heating unit and the electrical
wiring connections and gas piping to the unit. The
refrigerant system is completely assembled and
charged. All internal wiring is complete.
These instructions and any instructions packaged with
any separate equipment required to make up the entire
heating/cooling system should be carefully read before
beginning the installation. Note particularly “Starting
Procedure” and any tags and/or labels attached to the
equipment.
All duct work, supply and return, must be properly
sized for the design airflow requirement of the
equipment. Air Conditioning Contractors of America
(ACCA) is an excellent guide to proper sizing.
Refer to Table 9 in this Manual for maximum static
pressure available for duct design.
See Figure 3 and clearance information in Section 9
and Table 2 for additional information.
Design the duct work according to methods given by
the Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should
be insulated with a minimum of 1" of insulation. Use
INSTALLATION
WARNING
In all cases, there must be a metal duct
connection made to the supply air ange,
and a 1" clearance to combustibles must be
maintained to this duct connection.
For free blow applications, a metal sleeve
must be used in the wall opening itself, again
maintaining a 1" clearance to combustibles.
Failure to use the sheet metal can cause re
resulting in property damage, injury, or death.
insulation with a vapor barrier on the outside of the
insulation. Flexible joints should be used to connect
the duct work to the equipment in order to keep the
noise transmission to a minimum.
A 1” clearance to combustible material for the
first 3’ of duct attached to the outlet air frame
is required. See Wall Mounting Instructions and
Figures 2, 2A, 3 and 3A for further details.
Ducts through the walls must be insulated and all
joints taped or sealed to prevent air or moisture
entering the wall cavity.
Some installations may not require any return air
duct. A metallic return air grille is required with
installations not requiring a return air duct. The
spacing between louvers on the grille shall not be
larger than 5/8”.
Any grille that meets with the 5/8” louver criteria
may be used. It is recommended that Bard Return
Air Grille or Return Filter Grille be installed when
no return duct is used. Contact distributor or
factory for ordering information. If using a return
air filter grille, filters must be of sufficient size to
allow a maximum velocity of 400 fpm.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to
installation only in a single story structure.
4. HIGH ALTITUDE APPLICATIONS
Ratings of gas utilization equipment are based on
sea level operation and need not be changed for
’
operation at elevations up to 6,000
’
elevations above 6,000
recommendations from the local authority having
jurisdiction, equipment ratings shall be reduced as
specified in Section 21.
and in the absence of specific
. For operation at
Manual 2100-587J
Page 9 of 59
5. TRANSPORTATION DAMAGE
8. MOUNTING THE UNIT
All units are packed securely in shipping container.
All units should be carefully inspected upon arrival
for damage. In the event of damage, the consignee
should:
1. Note on delivery receipt of any damage to
container.
2. Notify carrier promptly, and request an inspection.
3. In case of concealed damage, the carrier must be
notified as soon as possible within 15 days after
delivery.
4. Claims for any damage, apparent or concealed,
should be filed with the carrier, using the following
supporting documents:
A. Original Bill of Lading, certified copy or
indemnity bond.
B. Original paid freight bill of indemnity in lieu
thereof.
C. Original invoice or certified copy thereof
showing trade and other discounts or
deductions.
D. Copy of the inspection report issued by
carrier’s representative at the time damage is
reported to carrier.
6. GENERAL INFORMATION
Size of unit for proposed installation should be based
on heat loss/heat gain calculations made according to
methods of Air Conditioning Contractors of America
(ACCA). The air duct should be installed in accordance
with the Standards of the National Fire Protection
Association for the Installation of Air Conditioning and
Ventilating Systems of Other Than Residence Type,
NFPA No. 90A, and Residence Type Warm Air Heating
and Air Conditioning Systems, NFPA No. 90B. Where
local regulations are at a variance with instructions,
installer should adhere to local codes.
1. These units are secured by wall mounting brackets
which secure the unit to the outside wall surface at
both sides. A bottom mounting bracket is provided
for ease of installation but is not required.
CAUTION
If the bottom bracket is used, be certain the
bracket is secured to the outside wall surface
in a way sufcient to support the entire
weight of the unit during installation until side
mounting brackets are secured.
2. The WG3S2, WG4S2 and WG5S2 models are
suitable for 0" clearance on the installation
mounting wall and to the top. For all models the
supply air duct flange and the first 3' of supply
air duct require a minimum of 1" clearance to
combustible material.
WARNING
Failure to provide the 1" clearance between the
supply duct and a combustible surface for the
rst 3' of duct can result in re causing damage,
injury or death.
3. Locate and mark lag bolt locations and bottom
mounting bracket location.
4. Mount bottom mounting bracket.
5. Hook top rain flashing under back bend of top. Top
rain flashing is shipped secured to the right side of
the back.
7. WALL MOUNTING INFORMATION
1. Two holes for the supply and return air openings
must be cut through the wall as detailed in Figure
4.
2. On wood-frame walls, the wall construction must
be strong and rigid enough to carry the weight of
the unit without transmitting any unit vibration.
3. Concrete block walls must be thoroughly inspected
to insure that they are capable of carrying the
weight of the installed unit.
Manual 2100-587J
Page 10 of 59
6. Position unit in opening and secure with 5/16
lag bolts; use 7/8" diameter flat washers on the
lag bolts. Use lag bolts long enough to support
the unit’s weight when mounted to the structure.
This length may be dependant on the type of
construction.
7. Secure rain flashing to wall and caulk across entire
length of top (see Figure 3).
8. On side-by-side installations, maintain a minimum
of 20" clearance on right side to allow access to
control panel and burner compartment, and to
allow proper airflow to the outdoor coil. Additional
clearance may be required to meet local or national
codes.
FIGURE 2A
Mounting Instructions for WG3S2
Manual 2100-587J
Page 11 of 59
FIGURE 2B
Mounting Instructions for WG4S2 and WG5S2
Manual 2100-587J
Page 12 of 59
FIGURE 3
Combustible Clearance
WARNING
A minimum of 1" clearance must be maintained between the supply air duct and combustible materials. This is
required for the rst 3' of ducting.
It is important to insure that the 1" minimum spacing is maintained at all points.
Failure to do this could result in overheating the combustible material and may result in a re causing damage, injury
or death.
Manual 2100-587J
Page 13 of 59
FIGURE 4
Wall Mounting Instructions
FIGURE 5
Wall Mounting Instructions
Manual 2100-587J
Page 14 of 59
FIGURE 6
Common Wall Mounting Installations
Manual 2100-587J
Page 15 of 59
9. CLEARANCES
Minimum clearances, as specified in Table 2, must
be maintained from adjacent structures to provide
adequate fire protection, adequate combustion air and
room for service personnel.
While minimum clearances are acceptable for safety
reasons, they may not allow adequate air circulation
around the unit for proper operation in the cooling
mode. Whenever possible, it is desirable to allow
additional clearance, especially around the condenser
inlet and discharge openings. DO NOT install the unit
in a location that will permit discharged air from the
condenser to recirculate to the condenser inlet.
WARNING
Clearances from combustible materials
must be maintained as specied. Failure to
maintain clearances could cause re resulting
in property damage, injury, or death.
TABLE 2
Minimum Installation Clearances
Outlet Duct
(from combustible materials)
Vent Terminal
(from combustible materials)
Condenser Inlet20"
TopSee Figure 3
Burner Service20"
Combustible Base (Wood or Class A,
B or C roof covering material)
* See Figure 3
1" first 3'
* 17"
0"
FIGURE 7
Location of Vent Terminal in Shipping
Manual 2100-587J
Page 16 of 59
10.
VENT TERMINAL AND COMBUSTION
AIR INLET HOOD
The vent terminal is shipped in the burner
compartment (see Figure 7). Remove the two shipping
screws and separate the two-piece assembly. Install
the vent terminal by using the four screws provided.
Make sure gasket is in place (see Figure 8). The
combustion air intake hood is factory installed.
11. OPTIONAL VERTICAL VENTING
With the optional vertical venting kit (VVK-5), this unit
may be vented vertically through a roof or overhang.
The kit includes a stainless steel transition drain tee,
silicone sealant and drain tubing.
If unit is installed with vertical vent kit, annually
inspect the vent system and drain. Replace any portion
of the vent system that shows signs of deterioration.
Make sure drain is open and free of obstruction.
CAUTION
Vent terminal must be installed as shown in Figure 8 for proper operation of the heating system.
NOTE: The inner vent hood gasket is designed to stretch over and seal around the combustion
air blower outlet. This is a very critical seal to prevent water and ue products from entering the
unit. Care must be taken to insure this gasket is in place and sealing properly.
FIGURE 8
Vent Terminal and Combustion Air Intake
Manual 2100-587J
Page 17 of 59
12. VENT RESIZING INSTRUCTIONS
When an existing furnace is removed from a venting
system servicing other appliances, the venting system
is likely to be too large to properly vent the remaining
attached appliances.
The following steps shall be followed with each of
the appliances remaining connected to the common
venting system, placed in operation one at a time
while the other appliances remaining connected to the
common venting system are not in operation.
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National
Fuel Gas code, ANSI Z223.1 or the CAN/CGA
B149 Installation Codes and these instructions.
Determine that there is no blockage or restriction,
leakage, corrosion and other deficiencies which
could cause an unsafe condition.
3. In so far as is practical, close all building doors
and windows and all doors between the space
in which the appliance(s) connected to the
venting system are located and other spaces of
the building. Turn on clothes dryers and any
appliances not connected to the venting system.
Turn on any exhaust fans, such as range hoods
and bathroom exhausts, so they will operate
at maximum speed. Do not operate a summer
exhaust fan. Close fireplace dampers.
4. Follow the lighting instructions. Place the
appliance being inspected in operation. Adjust
thermostat so appliance shall operate continuously.
5. Test for draft hood equipped appliance spillage at
the draft hood relief opening after 5 minutes of
main burner operation. Use the flame of a match
or candle.
6. After it has been determined that each appliance
connected to the venting system properly vents
when tested as outlined above, return doors,
windows, exhaust fans, fireplace dampers and
any other gas-burning appliances to their previous
conditions of use.
7. If improper venting is observed during any of the
above tests, the venting system must be corrected.
13. FRESH AIR INTAKE
All units are built with fresh air inlet slots punched in
the service panel.
The default unit is built with blank-off plates
installed. All capacity, efficiency and cost of operation
information as required for Department of Energy
“Energyguide” Fact Sheets is based upon the fresh
air blank-off plate in place and is recommended for
maximum energy efficiency.
One of several other ventilation options may be
installed. Refer to model number and/or supplemental
installation instructions.
14. CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at
the top of the unit down to the unit base. There are
openings in the unit base for the drain hose to pass
through. In the event the drain hose is connected to
a drain system of some type, it must be an open or
vented type system to assure proper drainage.
15. WIRING – MAIN POWER
WARNING
For your personal safety, turn off electric
power at service entrance panel before
making any electrical connections. Failure to
do so could result in electric shock or re.
Refer to unit rating plate for wire sizing information and
maximum fuse or circuit breaker size. Each outdoor
unit is marked with a “Minimum Circuit Ampacity”.
This means that the field wiring used must be sized to
carry that amount of current. All models are suitable
only for connection with copper wire. Each unit and/or
wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer
to the National Electrical Code (NEC) for complete
current carrying capacity data on the various insulation
grades of wiring material. All wiring must conform to
NEC and all local codes.
The electrical data lists fuse and wire sizes (75° C
copper) for all models.
The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or circuit breaker that is to be used with
the equipment. The correct size must be used for
proper circuit protection and also to assure that there
will be no nuisance tripping due to the momentary high
starting current of the compressor motor.
The disconnect access door on this unit may be locked
to prevent unauthorized access to the disconnect. To
convert for the locking capability, bend the tab located
in the bottom left hand corner of the disconnect
opening under the disconnect access panel straight
out. This tab will now line up with the slot in the door.
When shut, a padlock may be placed through the hole
in the tab preventing entry.
See “Start Up” section for important information on
three phase scroll compressor start ups.
Manual 2100-587J
Page 18 of 59
Loading...
+ 41 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.