The Energy Recovery Ventilator was designed to
provide energy efficient, cost effective ventilation to
meet I.A.Q. (Indoor Air Quality) requirements while still
maintaining good indoor comfort and humidity control
for a variety of applications such as schools, classrooms,
lounges, conference rooms, beauty salons and others. It
provides a constant supply of fresh air for control of
airborne pollutants including CO2, smoke, radon,
formaldehyde, excess moisture, virus and bacteria.
The ventilator incorporates patented rotary heat
exchanger technology to remove both heat and moisture.
It is designed as a single package, which can be easily
factory or field installed for new installations or retrofit to
Bard WF wall mounted units. The package consists of a
unique rotary Energy Recovery Cassette that can be easily
removed for cleaning or maintenance. The cassette has a
21-inch diameter heat transfer wheel for efficient heat
transfer. The heat transfer wheel uses a permanently
bonded dry desiccant coating for total heat recovery.
Ventilation is accomplished with two (2) blower/motor
assemblies each consisting of a drive motor and dual
blowers for maximum ventilation at low sound levels.
On non-independent motor control models, the air is
exhausted at the same rate that fresh air is brought into
the structure, thus not impacting building pressure. On
independent motor control models, the air can be
exhausted at a different rate than the intake or fresh air.
Never operate the fresh air at a lower speed than the
exhaust air. Operating the fresh air at a higher speed
than the exhaust air will help maintain a slight positive
pressure in the building. The rotating energy wheel
provides the heat transfer effectively during both
summer and winter conditions. Provides required
ventilation to meet the requirements of ASHRAE 62.12007 standard.
Color
-X = Beige
-4 = Buckeye Gray
NOTE: Never set intake blower at a lower speed than
the exhaust blower, as it will create a
negative pressure in the room.
During operation below 5 degrees F outdoor
temperature, freezing of moisture in the heat
transfer wheel can occur. Consult the factory
if this possibility exists.
GENERAL INFORMATION
The ventilator should only be installed by a trained
heating and air conditioning technician. These
instructions serve as a guide to the technician installing
the ventilator package. They are not intended as a stepby-step procedure with which the mechanically-inclined
owner can install the package.
The ventilator housing is shipped in one carton, which
contains the following:
1.Energy Recovery Ventilator
2.Service Door
3.Rain Hood and Mist Eliminator
4.Installation Instructions
UNPACKING
Upon receipt of the equipment, be sure to compare the
model number found on the shipping label with the
accessory identification information on the ordering and
shipping document to verify that the correct accessory
has been shipped.
Inspect the carton housing of each ventilator as it is
received, and before signing the freight bill, verify that
all items have been received and that there is no visible
damage. Note any shortages or damage on all copies of
the freight bill. The receiving party must contact the last
carrier immediately, preferably in writing, requesting
inspection by the carrier’s agent. Concealed damage not
discovered until after loading must be reported to the
carrier within 15 days of its receipt.
1. Unpack the ventilator assembly, which includes the
integral ventilator with attached electrical harness
and miscellaneous hardware.
WARNING
Open breaker switch before installing this
accessory to prevent injury or death due to
electrical shock or contact with moving parts.
Turn thermostat to OFF.
htiWesUroF
ledoM
VREFW521-050FW
2. Remove intake hood assembly from back of
ventilator. (See Figure 1.)
3. Remove the existing exterior vent option door on
the unit. (See Figure 2.)
4. Remove and save existing unit air filter. Remove
and discard the rear exhaust cover plate. (See
Figure 3.)
5. Install exhaust blower assembly in rear exhaust
opening and secure with four (4) screws. Position 4
pin connector so it is accessible. (See Figure 4.)
Assemble exhaust blower enclosure as shown in
Figure 2A. Fasten exhaust blower enclosure to
bottom of unit as shown in Figure 4.
6. Install ventilator into the unit. (See Figure 5.)
IMPORTANT NOTE: Position front lip of ventilator
over front grille and on top of condenser partition.
(See Figure 5.) This is important to insure proper
stinUgniwolloFlacirtcelE
1-802/032
esahp3ro
drainage of any water entering damper assembly.
7. Remove cassette and plug in exhaust blower.
Replace cassette. (See Figure 6.)
8. Open control panel to gain access to unit low
voltage terminal block. (Insure all power is OFF
prior to opening the control panel.)
9. Remove female plug of low voltage wiring harness
from the heat recovery assembly and snap into filter
rack. Route electrical harness leads through the
bushing into the low voltage box. (See Figure 5.)
10. Connect leads C (black), W (blue), and G (orange)
with fork terminal to corresponding points on
terminal strip. (See Figure 7 for 230V units.)
NOTE: These 24 volt control wires control the
starting and stopping of the Energy Recovery
Ventilator and can be independently controlled
by an energy management control or timer.
See separate section on Control Wiring for
suggested control schemes.
11. Remove female plug of high voltage wiring harness
from the heat recover assembly and snap into filter
rack. Wire to terminal block. (See Figure 7 for
230V units.)
12. Plug male plug from female at filter rack.
(See Figure 5.)
13. Close control panel cover.
14. Replace filter and one (1) screw in condenser grille.
(See Figure 3)
15. Ventilator checkout
A. Resupply power to unit.
B. Energize the evaporator blower by
switching thermostat to the manual fan
position with Heat/Cool in OFF position.
C. Ventilator heat transfer wheels should
rotate slowly (49 RPM). Intake and
exhaust blowers should run.
(See Figure 9.)
D. De-energize the evaporator blower.
Energy Recovery wheels, and fresh air
and exhaust air blowers should stop.
E. This completes ventilator checkout.
7/8"
Manual 2100-495A
Page5 of 21
16. Disconnect the wires connected in Step 10 if other
control options are to be used.
17. Replace the lower service access panel with the
new panel provided. Attach air intake hood with
screws provided. (See Figure 9.) Be sure to insert
the top flange of the air intake hood into and
through the slot in the service door and between the
door and insulation to prevent bowing of the door.
INTAKE HOOD ASSEMBLY
18. Close front door.
19. Apply Certification label, included with Installation
Instructions, next to unit Serial Plate.
20. Assemble exhaust blower enclosure as shown in
Figure 2A and install on unit as shown in Figure 4
(with screws provided).
21. Ventilator is now ready for operation.
FIGURE 1
Manual 2100-495A
Page6 of 21
FRONT DOOR
VENT
OPTION
DOOR
FIGURE 2
REMOVE VENT OPTION DOOR
EXHAUST
COVER PLATES
FIGURE 2A
ASSEMBLY OF EXHAUST BLOWER ENCLOSURE
PART NUMBERS
COLORABC
BEIGE134-248-X134-244-X134-243-X
GRAY134-248-4134-244-4134-243-4
A
B
MIS-2350
B
C
A
MIS-2461
Manual 2100-495A
Page7 of 21
Loading...
+ 14 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.