Bard W49A1, W61A1, W38A1 User Manual

THE WALL-MOUNT™ “Quiet Climate” A/C – 10.0 EER
Models W38A1, W49A1, W61A1 3 to 5 Ton (35,600 to 57,500 Btuh) Right Side Control Panel 60Hz
GREEN REFRIGERANT
R-410A
The Bard Wall-Mount Air Conditioner is a self contained energy efficient system, which is designed to offer maximum indoor comfort at a minimal cost without using valuable indoor floor space or outside ground space. This unit is the ideal product for versatile applications such as: new construction, modular offices, school modernization, telecommunication structures, portable structures or correctional facilities. Factory or field installed accessories are available to meet specific job requirements.
Engineered Features
Aluminum Finned Copper Coils:
Grooved tubing and enhanced louvered fin for maximum heat transfer and energy efficiency.
Twin Blowers:
ECM Indoor Blower Motor:
Features a variable speed motor providing super-high efficiency, low sound levels and soft-start capabilities. The motor is self-adjusting to provide the proper airflow rate for the staged capacity, and for higher static pressure in ducted installations without user adjustment or wiring changes.
Air Conditioner Compressor:
Copeland scroll compressors are designed for increased efficiency, quieter operation and improved reliability for longer life. Eliminates need for crankcase heater.
R-410A Refrigerant:
Designed with R-410A (HFC) non-ozone depleting refrigerant in compliance with the Montreal protocol and 2010 EPA requirements.
Phase Rotation Monitor:
Standard on all 3 phase scroll compressors. Protects against reverse rotation if power supply is not properly connected.
Galvanized 20 Gauge Zinc Coated Steel Cabinet:
Cleaned, rinsed, sealed and dried before the polyurethane primer is applied. The cabinet is handsomely finished with a baked on textured enamel, which allows it to withstand 1000 hours of salt spray tests per ASTM B117-03.
Foil Faced Insulation:
Standard on all units.
Full Length Mounting Brackets:
Built into cabinet for improved appearance and easy installation. NOTE: Bottom mounting bracket included to assist in installation.
Electrical Components:
Are easily accessible for routine inspection and maintenance through a right side, service panel opening. Features a lockable, hinged access cover to the circuit breaker or toggle disconnect switch.
Electric Heat Strips:
Features an automatic limit and thermal cut-off safety control. Heater packages can be factory or field installed for all 1½ through 5 ton models.
Filter Service Door:
Separate service door provides easy access for filter change.
One Inch, Disposable Air Filters:
Are standard equipment. Optional one inch washable filters available and filter racks permit the addition of 2" pleated filter. Factory or field installed.
Condenser Fan and Motor Shroud Assembly:
Slides out for easy access.
Barometric Fresh Air Damper:
Standard on all units. Allows up to 25% outside fresh air. Optional ventilation packages available.
Built-in Circuit Breakers:
Standard on all electric heat versions of single (230/208 volt) and three phase (230/208 volt) equipment. Rotary disconnects are standard on all electric heat versions of three phase (460 volt) equipment.
PTCR Start Assist:
Standard on 1-phase models.
Slope Top:
Standard feature for water run-off.
Top Rain Flashing:
Standard feature on all models.
Liquid Line Filter Drier:
Standard on all units. Protects system against moisture.
Compressor Control Module:
Standard on all units. Built-in off-delay timer adjustable from 30 seconds to 5 minutes. 2-minute on-delay if power interrupt. 120-second bypass for low pressure control, and both soft and manual lockouts for high and low pressure controls. Alarm output for alarm relay.
High & Low Pressure Switches are Auto-Reset:
Standard on all units. Built-in lockout circuit resets from the room thermostat. Provides commercial quality protection to the compressor.
Complies with efficiency requirements of ANSI/ASHRAE/IESNA 90.1-2010.
Certified to ANSI/ARI Standard 390-2003 for SPVU (Single Package Vertical Units).
Intertek ETL Listed to Standard for Safety Heating and Cooling Equipment ANSI/UL
1995/CSA 22.2 No. 236-05, Fourth Edition.
Commercial Product - Not intended for Residential application.
Form No. S3412-1112 Supersedes S3412-712 Page 1 of 12
M E
C
F
B
S
Capacity and Efficiency Ratings
SLEDOM 1A83W 1A94W 1A16W
1
HUTByticapaCgnilooC
2
REE
1 Capacity is certified in accordance with ANSI/ARI Standard 390-2003. 2 EER = Energy Efficiency Ratio and is certified in accordance with ANSI/ARI Standard 390-2003.
006,53005,64005,75
00.0100.0100.01
All ratings based on fresh air intake being 100% closed (no outside air introduction).
Specifications 3 Ton through 5 Ton
SLEDO
zH06--gnitaRlacirtcel
egnaRegatloVgnitarepO352-791352-791605-414352-791352-791605-414352-791352-791605-414
AtiucriC--rosserpmo
egatloV 802/032 802/032 064 802/032 802/032 064 802/032 802/032 064
spmAdaoLdetaR 6.51/3.41 6.11/6.01 3.5 4.02/9.81 2.41/1.31 3.6 9.62/2.42 4.81/5.61 6.8
tiucriChcnarB
tnerruCnoitceleS
spmArotoRkcoL211/21188/8844431/43119/1964851/851551/55157 epyTrosserpmoCllorcSllorcSllorcSllorcSllorcSllorcSllorcSllorcSllorcS
resnednoC&rotoMna
DPS-MPR-PH--rotoMnaF2-058-3/12-058-3/12-058-3/12-058-3/12-058-3/12-058-3/12-058-3/12-058-3/12-058-3/1
spmA--rotoMnaF5.25.23.15.25.23.15.25.23.1
MFC/AID--naF0062-"420062-"420062-"420062-"420062-"420062-"420062-"420062-"420062-"42
.pavE&rotoMrewol
DPS-MPR-PH--rotoMrewolBelbairaV2/1elbairaV2/1elbairaV2/1elbairaV2/1elbairaV2/1elbairaV2/1elbairaV4/3elbairaV4/3elbairaV4/3
spmA--rotoMrewolB5.45.45.40.50.50.50.50.50.5
.P.S.E&gnilooCMFC
)lioCteW-detaR(retliF/w
.DTS)sehcni(seziSretliF1x03x021x03x021x03x021x03x021x03x021x03x021x03x021x03x021x03x02
.SBL--thgieWgnippih
A-1A83W B-1A83W C-1A83W A-1A94W B-1A94W C-1A94W A-1A16W B-1A16W C-1A16W
1-802/032 3-802/032 3-064 1-802/032 3-802/032 3-064 1-802/032 3-802/032 3-064
0.81 3.31 0.6 1.32 1.61 1.7 2.03 6.02 7.9
51.-001151.-001151.-001102.-003102.-003102.-003102.-054102.-054102.-0541
525 525 525 525 525 525 575 575 575
Form No. S3412-1112 Supersedes S3412-712 Page 2 of 12
Ventilation System Packages
Bard Wall-Mounts are designed to provide optional ventilation packages to meet all of your ventilation and indoor air quality requirements. All units are equipped with a barometric fresh air damper as the standard ventilation package. All ventilation packages can be built-in at the factory or field-installed at a later date.
BAROMETRIC FRESH AIR DAMPER - BFAD STANDARD
The barometric fresh air damper is a standard feature on all models. It is installed on the inside of the service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed with the conditioned air. The damper opens during blower operation and closes when the blower is off. Adjustable blade stops allow different amounts of outside air to be introduced into the building and can be easily locked closed if required.
Barometric Fresh Air Damper
Motorized Fresh Air Damper
Commercial Room Ventilator
Economizer
BLANK OFF PLATE - BOP OPTIONAL
A blank off plate is installed on the inside of the service door. It covers the air inlet openings, which restricts any outside air from entering the unit. The blank off plate should be utilized in applications where outside air is not
required to be mixed with the conditioned air.
MOTORIZED FRESH AIR DAMPER - MFAD OPTIONAL
The motorized fresh air damper is internally mounted behind the service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed with the conditioned air. The two position damper can be fully open or closed. The damper blade is powered open by a 24VAC motor with spring return on power loss. The damper can be controlled by indoor blower operation or can be field connected to be managed based on building occupancy.
NOTE: The above vent systems are intake only without built-in exhaust capability. Building will likely require separate field installed barometric relief or mechanical exhaust elsewhere within the conditioned space. Balancing dampers in the return air grille may be required to achieve specified amount of outdoor air intake.
COMMERCIAL ROOM VENTILATOR - CRV OPTIONAL
The built-in commercial room ventilator is internally mounted behind the service door and allows outside ventilation air, up to 50% of the total airflow rating of the unit, to be introduced through the air inlet openings. It includes a built-in exhaust air damper.
The commercial room ventilator (CRV) is a simple and innovative approach to improving the indoor air quality by providing fresh air intake and exhaust capability through the CRV. The damper can be easily adjusted to control the amount of fresh air supplied into the building. The CRV can be controlled by indoor blower operation or field controlled based on room occupancy. Two versions available (except on 1.5 and 2-Ton models). The CRV and CRVS are power open - spring return on power loss, and CRVP is power open and power close. Complies with ANSI/ASHRAE Standard 62.1 “Ventilation for Acceptable Indoor Air Quality”.
ECONOMIZER - ECONWM-Series OPTIONAL
The built-in economizer system is internally mounted behind the service door and allows outdoor air to be introduced through the air inlet openings. The amount of outdoor air varies in response to the system controls and settings defined by the end user. It includes a built-in exhaust air damper. The economizer is designed to provide “free cooling” when outside air conditions are cool and dry enough to satisfy cooling requirements without running the compressor. This in turn provides lower operating costs, while extending the life of the compressor.
ECONWMT Equipment Building versions have extended air intake hood to deliver up to 100% of cooling rated airflow.
16" for ECONWMT-E2 or T2, and E3 or T318" for ECONWMT-E5 or T5
ECONWMS Classroom versions have 3" air intake hood to deliver up to 75% of cooling rated airflow.
Standard Features:
Fully modulating
Honeywell Direct Drive Hi-Torque Actuator
No linkage required
Simple single blade design
Positive shut-off with non-stick gaskets
Electronic DB and/or Enthalpy sensors depending upon version
Honeywell JADE electronic economizer module with precision settings and diagnostics
DB or Enthalpy economizer versions available
Energy Recovery Ventilator
WALL-MOUNT ENERGY RECOVERY VENTILATOR - ERVF OPTIONAL
The wall-mount energy recovery ventilator (ERVF) is a highly innovative approach to meeting indoor air quality ventilation requirements as established by ANSI/ASHRAE Standard 62.1. The ERVF allows from 300 to 450 CFM (depending upon model) of fresh air and exhaust through the unit while maintaining superior indoor comfort and humidity levels. In most cases this can be accomplished without increasing equipment sizing or operating costs. Heat transfer efficiency is up to 67% during summer and 75% during winter conditions.
The ERVF consists of a unique “rotary energy recovery cassette” that provides effective sensible and latent heat transfer capabilities during summer and winter conditions. Various control schemes are addressed including limiting ventilation during building occupancy only.
The ERVF is designed to be internally mounted behind the service door in the W**A, W**H or W**L model wall­mount units. It can be built-in at the factory or field installed as an option. ERVF-*3 and ERVF-*5 can be independently adjusted for intake and exhaust rates.
Manufactured under U.S. Patent Nos. 5,485,878; 5,301,744
Form No. S3412-1112 Supersedes S3412-712 Page 3 of 12
W
W
W
W
W
W
W
W
W
Electrical Specifications
tiucriCelgniS tiucriClauD
ledoM
stloV
esahPdna
Z0A-1A83 50A
detaR
80A
1-802/032 01A 51A Z0B-1A83 60B 90B
3-802/032
51B Z0C-1A83 60C 90C
3-064
51C Z0A-1A94 50A 80A
1-802/032 01A 51A Z0B-1A94 60B 90B
3-802/032 51B
Z0C-1A94 60C 90C
3-064
51C Z0A-1A16 50A 80A
1-802/032 01A 51A
Z0B-1A16
90B
3-802/032 51B Z0C-1A16 90C
3-064
51C
1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes. 3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor sizing.
Caution: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment
Factors when more than three (3) current carrying conductors are in a raceway.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses & conductor wires in accordance with the National Electrical Code & all local codes.
3 muminiM
dleiF.oN rewoP stiucriC
1 1 1
2ro1
2ro1 1 1 1 1 1 1 1 1 1 1 1
2ro1
2ro1 1 1 1 1 1 1 1 1 1 1 1
2ro1
2ro1 1 1 1 1 1 1
1 mumixaM
tiucriC
yticapmA
23 53 05 16 78 62 72 63 45 41 51 91 82 93 93 15 16 78 03 03 73 55 51 51 91 82 84 84 15 16 78 63 73 55 81 91 82
2 dleiF esuFlanretxE .rkrB.tkCro
54 54 05 07 09 53 53 04 06 51 51 02 03 05 05 06 07 09 54 54 54 06 02 02 02 03 06 06 06 07 09 05 05 06 52 52 03
2 dnuorG
rewoP
eziSeriW
8 8 8 6 3 8 8 8 6
41 41 21
01 8 8 6 6 3 8 8 8 6
21
21
21
01 8 8 6 6 3 8 8 6
01
01
01
3 muminiM
eriW
1 mumixaM
tiucriC
yticapmA
2 dleiF esuFlanretxE .rkrB.tkCro
2 dnuorG
rewoP
eziSeriW
eziSeriW
A.tkC B.tkC A.tkC B.tkC A.tkC B.tkC A.tkC B.tkC 01 01 01
8 8
53
62
54
03
8
01
01
53
25
54
06
8
6
01
01
01 01 01 01 01 41 41 21 01 01 01 01
93
62
05
03
8
01
01
8
93
25
05
06
8
8
6
01
01
01 01 01 01 01 21 21 21 01 01 01
8 8 8
84
62
06
03
6
01
01
84
25
06
06
6
6
01
01
01 01 01 01 01 01 01
Form No. S3412-1112 Supersedes S3412-712 Page 4 of 12
Loading...
+ 8 hidden pages