Bard W24H2-A, W24H2-B, W24H2-C, W30H2-A, W30H2-B Installation Instruction

...
Page 1
INSTALLATION INSTRUCTIONS
WALL MOUNTED PACKAGE
HEAT PUMP
Models:
W18H2-A W24H2-A
W24H2-B W24H2-C
W24H2DA W24H2DB W24H2DC
W30H2DA W30H2DB W30H2DC
W36H2DA W36H2DB W36H2DC
W42H2DA W42H2DB W42H2DC
W48H2DA W48H2DB W48H2DC
W60H2DA W60H2DB W60H2DC
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
www.bardhvac.com
Manual: 2100-604B Supersedes: 2100-604A Date: 10-18-16
Page 1 of 28
Page 2
CONTENTS
Getting Other Information and Publications .... 3
Wall Mount General Information .........................4
Wall Mount Model Nomenclature .......................... 4
Shipping Damage ................................................ 4
General .............................................................. 4
Duct Work ........................................................... 5
Filters................................................................. 5
Fresh Air Intake ................................................... 5
Condensate Drain ................................................ 5
Installation ............................................................... 6
Wall Mounting Information ................................... 6
Mounting the Unit ............................................... 6
Clearances Required ............................................ 6
Minimum Clearances ........................................... 6
Wiring – Main Power .......................................... 14
Wiring – Low Voltage Wiring ................................ 14
Figures
Figure 1 Fresh Air Damper Assembly.................... 5
Figure 2 Unit Dimensions ................................... 7
Figure 3A Mounting Instructions W18, W24 ........... 8
Figure 3B Mounting Instructions W30, W36 ........... 9
Figure 3C
Figure 4 Electric Heat Clearance ....................... 11
Figure 5 Wall Mounting Instructions .................. 12
Figure 6 Wall Mounting Instructions .................. 12
Figure 7 Common Wall Mounting Installations .... 13
Figure 8 Defrost Control Board .......................... 18
Figure 9 Fan Blade Setting ............................... 21
Mounting Instructions W42, W48, W60
.. 10
Start Up ................................................................... 15
General ............................................................ 15
Topping Off System Charge ................................. 15
Safety Practices ................................................ 15
Important Installer Note ..................................... 16
High and Low Pressure Switch ............................ 16
Three Phase Scroll Compressor ........................... 16
Phase Monitor ................................................... 16
Condenser Fan Operation ................................... 16
Service Hints .................................................... 16
Sequence of Operation ....................................... 16
Pressure Service Ports ........................................ 17
Defrost Cycle ..................................................... 17
Service ..................................................................... 19
Solid State Heat Pump Control ........................... 19
Checking Temperature Sensor ............................. 20
Fan Blade Setting Dimensions ............................ 21
Removal of Fan Shroud ...................................... 21
Refrigerant Charge ............................................. 21
Tables
Table 1 Troubleshooting .................................. 19
Temperature vs. Resistance ................................ 20
Table 2 Fan Blade Dimension .......................... 21
Table 3A Cooling Pressure ................................. 22
Table 3B Heating Pressure ................................. 22
Table 4A Electrical Specifications ...................... 23
Table 4B Electrical Specifications ...................... 24
Table 5 Recommended Airflow ......................... 25
Table 6 Indoor Blower Performance .................. 25
Tables 7 Maximum ESP Electric Heat Only ......... 26
Table 8 Electric Heat ...................................... 26
Table 9 Optional Accessories ........................... 27
Table 10 Vent and Control Options ..................... 28
Manual 2100-604B Page 2 of 28
Page 3
GETTING OTHER INFORMATION AND PUBLICATIONS
These publications can help when installing the furnace. They can usually be found at the local library or purchased directly from the publisher. Be sure to consult the current edition of each standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation ..............ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air .......................ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for ......................... ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for Residential ............... ACCA Manual D
Winter and Summer Air Conditioning and Equipment Selection
For more information, contact these publishers:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute 11 West Street, 13th Floor
New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association
Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manual 2100-604B Page 3 of 28
Page 4
WALL MOUNT GENERAL INFORMATION
HEAT PUMP WALL MOUNT MODEL NOMENCLATURE
W 42 H 2 – A 10 X X X X X A
MODEL NUMBER
CAPACITY
18 - 1½ Ton 24 - 2 Ton 30 - 2½ Ton 36 - 3 Ton 42 - 3½ Ton 48 - 4 Ton 60 - 5 Ton
For 0 KW and circuit breakers (230/208 volt) or toggle disconnect (460V) applications, insert 0Z in the KW field of the model number. Insert “D” for dehumidification with hot gas reheat. Reference Form 7960-702 for complete details.
NOTE: Vent options X, B and M are without exhaust capability. May require separate field-supplied barometric relief in building.
H - Heat Pump
SPECIALTY PRODUCTS
(Non-Standard)
VENTILATION OPTIONS
X - Barometric Fresh Air Damper (Standard) B - Blank-off Plate M - Motorized Fresh Air Damper V - Commercial Ventilator - Motorized with Exhaust S - Economizer (Std.) - Enthalpy W - Economizer (Full Flow) - Enthalpy T - Economizer (Full Flow) - Temperature R - Energy Recovery Ventilator - Motorized with Exhaust (See Spec. Sheet S3398)
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
REVISIONS
VOLTS & PHASE
A - 230/208/60/1 B - 230/208/60/3 C - 460/60/3
KW
COLOR OPTIONS
X - Beige (Standard) 1 - White 4 - Buckeye Gray 5 - Desert Brown 8 - Dark Bronze
FILTER OPTIONS
X - 1" Throwaway (Standard) W - 2" Washable P - 2" Pleated
OUTLET OPTIONS
X - Front (Standard) T - Top Outlet (W30H, W36H Only)
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
CONTROL MODULES
(See Spec. Sheet S3398)
COIL OPTIONS
X - Standard 1 - Phenolic Coated Evaporator 2 - Phenolic Coated Condenser 3 - Phenolic Coated Evaporator and Condenser
While these instructions are intended as a general
GENERAL
recommended guide, they do not supersede any national and/or local codes in any way. Authorities
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
having jurisdiction should be consulted before the installation is made. See page 3 for information on codes and standards.
Size of unit for a proposed installation should be based on heat loss/gain calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
Manual 2100-604B Page 4 of 28
Page 5
DUCT WORK
FILTERS
All duct work, supply and return, must be properly sized for the design airflow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
Refer to Maximum ESP of operation Electric Heat Tables 7.
Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of 1" of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
Models W18 and W24 are approved for 0" clearance to the supply duct. For model series W30, W36, W42, W48 and W60, a 1/4" clearance to combustible material for the first 3' of duct attached to the outlet air frame is required. See Wall Mounting Instructions and Figures 3 and 4 for further details.
Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.
Some installations may not require any return air duct. A metallic return air grille is required with installations not requiring a return air duct. The spacing between louvers on the grille shall not be larger than 5/8".
Any grille that meets with 5/8" louver criteria may be used. It is recommended that Bard Return Air Grille Kit RG-2W through RG-5W or RFG-2W through RFG­5W be installed when no return duct is used. Contact distributor or factory for ordering information. If using a return air filter grille, filters must be of sufficient size to allow a maximum velocity of 400 fpm.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to installation only in a single story structure.
A 1" throwaway filter is standard with each unit. The filter slides into position making it easy to service. This filter can be serviced from the outside by removing the filter access panel. A 1" washable filter and 2" pleated filter are also available as optional accessories. The internal filter brackets are adjustable to accommodate the 2" filter by bending two tabs down on each side of the filter support bracket.
FRESH AIR INTAKE
All units are built with fresh air inlet slots punched in the service door.
If the unit is equipped with a fresh air damper assembly, the assembly is shipped already attached to the unit. The damper blade is locked in the closed position. To allow the damper to operate, the maximum and minimum blade position stops must be installed (see Figure 1).
All capacity, efficiency and cost of operation information is based upon the fresh air blank-off plate in place and is recommended for maximum energy efficiency.
The blank-off plate is available upon request from the factory and is installed in place of the fresh air damper shipped with each unit.
CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.
FIGURE 1
Fresh Air Damper
Manual 2100-604B Page 5 of 28
Page 6
INSTALLATION
WALL MOUNTING INFORMATION
1. Two holes for the supply and return air openings must be cut through the wall as shown in Figure 3.
2. On wood frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration.
3. Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installed unit.
MOUNTING THE UNIT
WARNING
Failure to provide the 1/4" clearance between the supply duct and a combustible surface
for the rst 3ʹ of duct can result in re causing damage, injury or death.
1. These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides. A bottom mounting bracket, attached to skid for shipping, is provided for ease of installation, but is not required.
2. The unit itself is suitable for 0" clearance, but the supply air duct flange and the first 3' of supply air duct require a minimum of 1/4" clearance to combustible material for model series W30, W36, W42, W48 and W60. However, it is generally recommended that a 1" clearance is used for ease of installation and maintaining the required clearance to combustible material. See Figure 3 for details on opening sizes.
3. Locate and mark lag bolt locations and bottom mounting bracket location (see Figure 3).
4. Mount bottom mounting bracket.
5. Hook top rain flashing, attached to front-right of supply flange for shipping, under back bend of top.
Clearances Required for Service Access and Adequate Condenser Airflow
MODELS LEFT SIDE RIGHT SIDE
W18H, W24H, W30H, W36H 15" 20"
W42H, W48H, W60H 20" 20"
6. Position unit in opening and secure with 5/16" lag bolts; use 7/8" diameter flat washers on the lag bolts.
7. Secure rain flashing to wall and caulk across entire length of top (see Figure 3).
8. For additional mounting rigidity, the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance if combustible wall.
9. On side-by-side installations, maintain a minimum of 20" clearance on right side to allow access to control panel and heat strips, and to allow proper airflow to the outdoor coil. Additional clearance may be required to meet local or national codes.
NOTE: Refer to Figures 2 – 7 for dimensions and various mounting configurations.
Minimum Clearances Required to Combustible Materials
MODELS
W18H, W24H 0" 0"
W30H, W36H 1/4" 0"
W42H, W48H, W60H 1/4" 0"
SUPPLY AIR DUCT
FIRST 3'
CABINET
Manual 2100-604B Page 6 of 28
Page 7
3"
11"
7.88
1.00
31.88
Heat
models.
Electric
Hood for ECONWMT
MIS-2487 G
1
1
1
Condenser
Filter Access Panel
Front View
Air Outlet
Standard flush vent door for non-ERV/ Econ. models
Ventilation Air
5.88
F
W
G
Low Voltage
Electrical
Entrance
High Voltage
Side View
Drain
Electrical
Cond.
Air
Inlet
Heater
Access
Panel
4° Pitch
Built In
Rain Hood
Disconnect
Access Panel
(Lockable)
Entrance
C. Breaker/
Hood for ERV and ECONWMS models only
C
I
D
J
H
A
2.13
K
Mounting
Supply Air Opening
Side Wall
Brackets
Location
Shipping
Return Air Opening
(Built In)
Optional
Electrical
Entrances
Top Rain
Flashing
Bottom Installation Bracket
Back View
P
M
O
E
R
S
S
S
S
S
T
.44
N
Q
B
L
FIGURE 2
Dimensions of Basic Unit for Architectural and Installation Requirements (Nominal)
Width
Depth
Model
(W)
W18H2
33.300 17.125 70.563 7.88 19.88 11.88 19.88 35.00 18.50 25.75 20.56 26.75 28.06 29.25 27.00 2.63 34.13 22.06 10.55 5.00 12.00 5.00
W24H2
W30H2
38.200 17.125 70.563 7.88 27.88 13.88 27.88 40.00 18.50 25.75 17.93 26.75 28.75 29.25 27.00 2.63 39.13 22.75 9.14 5.00 12.00 5.00
W36H2
W42H2
42.075 22.432 84.875 9.88 29.88 15.88 29.88 43.88 19.10 31.66 30.00 32.68 26.94 34.69 32.43 3.37 43.00 23.88 10.00 1.44 16.00 1.88
W48H2
W60H2 42.075 22.432 94.875 9.88 29.88 15.88 29.88 43.88 13.56 41.66 30.00 42.68 36.94 44.69 42.43 3.37 43.00 33.88 10.00 1.44 16.00 1.88
Height
(D)
All dimensions are in inches. Dimensional drawings are not to scale.
Supply Return
(H)
A B C B E F G I J K L M N O P Q R S T
W**H RIGHT UNIT
Optional top outlet (factory installed only) for W30H and W36H models only.
Manual 2100-604B Page 7 of 28
Page 8
12"
12"
12"
1"
12"
20"
20"
"
3"
4"
Typ.
8"
20
1
2
"
12"
1"
3
1
8
"
4"
Typ.
5"
7
8
"
3
13
16
"
2" 2"
7
1
16
" 7
1
16
12"
Right Side View
RETURN AIR
DUCT
IS ON OPPOSITE (LEFT) SIDE.
OPENING
ENTIRE LENGTH OF TOP.
TOP
WALL
OF CAULKING ALONG
PANEL
FOAM AIR SEAL
WALL STRUCTURE
NOTES:
RAIN FLASHING
HEATER ACCESS
TOP FLASHING AT TIME OF INSTALLATION.
THE SIDE MOUNTING FLANGES AND UNDER
SILICONE CAULKING BE PLACED BEHIND
CONTROLS AND HEATER ACCESS
MIS-353 D
Wall Opening and Hole Location View
SEAL WITH BEAD
IT IS RECOMMENDED THAT A BEAD OF
W**A UNIT SHOWN, W**L UNIT
SUPPLY AIR
SUPPLIED
Return Opening
Supply Opening
FIGURE 3A
W18H2, W24H2
Mounting Instructions
Manual 2100-604B Page 8 of 28
Page 9
D
12"
12"
12"
12"
12"
C CA
28"
1"
3"
4"
Typ.
4
1
2
"
B
E
14"
1"
3
1
8
"
4"
Typ.
5"
4
1
2
"
7
8
"
RETURN AIR
SUPPLIED
Return Opening
16 7/84 9/164 1/21030
17 5/83 13/165 1/48 1/228 1/2
EDCBA
COMBUSTIBLE MATERIALS
RECOMMENDED 1" CLEARANCE FROM
REQUIRED DIMENSIONS TO MAINTAIN
THE SIDE MOUNTING FLANGES AND UNDER
1/4" CLEARANCE ON ALL
RAIN FLASHING
COMBUSTIBLE MATERIALS
DUCT
TOP FLASHING AT TIME OF INSTALLATION.
1/4" MIN. CLEARANCE FROM
REQUIRED DIMENSIONS TO MAINTAIN
OPENING
ENTIRE LENGTH OF TOP.
MATERIALS
NOTES:
OF CAULKING ALONG
PANEL
FOAM AIR SEAL
FOUR SIDES OF SUPPLY
AIR DUCT IS REQUIRED
FROM COMBUSTABLE
WALL STRUCTURE
TOP
MIS-311 C
Wall Opening and Hole Location View Right Side View
WALL
HEATER ACCESS
SEAL WITH BEAD
IT IS RECOMMENDED THAT A BEAD OF
SILICONE CAULKING BE PLACED BEHIND
SUPPLY AIR
Supply Opening
W*R UNIT SHOWN, W*L UNIT
CONTROLS AND HEATER ACCESS
IS ON OPPOSITE (LEFT) SIDE.
FIGURE 3B
W30H2, W36H2
Mounting Instructions
Manual 2100-604B Page 9 of 28
Page 10
D
16"
16"
16"
16"
16"
1
7
8
"
6
1
2
" 6
1
2
"
2
1
8
"
7
8
"
1"
3"
4"
Typ.
4"
Typ.
6
1
2
"
30"
E
16"
A CC
3
1
8
"
B
Wall Opening and Hole Location View
RETURN AIR
1
REQUIRED DIMENSIONS TO MAINTAIN
1/4" MIN. CLEARANCE FROM
COMBUSTIBLE MATERIALS
REQUIRED DIMENSIONS TO MAINTAIN
29
DUCT
COMBUSTIBLE MATERIALS
A B C DE
30 1/2
10 1/2
6 1/4 1 1/4 29 3/4
32 12 5 1/2
2
NOTES:
WALL STRUCTURE
1
SUPPLY AIR
IT IS RECOMMENDED THAT A BEAD OF
OPENING
Right Side View
RAIN FLASHING
SILICONE CAULKING BE PLACED BEHIND
RECOMMENDED 1" CLEARANCE FROM
THE SIDE MOUNTING FLANGES AND UNDER
TOP FLASHING AT TIME OF INSTALLATION.
TOP.
PANEL
HEATER ACCESS
FOUR SIDES OF SUPPLY
AIR DUCT IS REQUIRED
FROM COMBUSTABLE
WALL
1/4" CLEARANCE ON ALL
MATERIALS
Supply Opening
FOAM AIR SEAL
SUPPLIED
SEAL WITH BEAD
OF CAULKING ALONG
ENTIRE LENGTH OF
TOP
1
Return Opening
MIS-416 E
Dimension is 21" on 95" tall units.
2
Dimension is 10" on T48H1 & T60H1.
2
Dimension is 6" on T48H1 & T60H1.
3
3
FIGURE 3C
W42H2, W48H2, W60H2
Manual 2100-604B Page 10 of 28
Mounting Instructions
Page 11
FIGURE 4
Electric Heat Clearance
W30H2, W36H2, W42H2, W48H2, W60H2
SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1/4" CLEARANCE TO COMBUSTIBLE SURFACES.
WARNING
A minimum of 1/4" clearance must be maintained between the supply air duct and combustible materials. This is required for the
rst 3ʹ of ducting.
It is important to insure that the 1/4" minimum spacing is
maintained at all points.
Failure to do this could result in overheating the combustible material and may result in a re causing damage, injury or death.
Manual 2100-604B Page 11 of 28
Page 12
Wall Mounting Instructions
DUCT
OPENING
RETURN AIR
SUPPLY AIR
WOOD FRAME WALL INSTALLATION
OPENING
WALL BEFORE
MOUNT ON UNIT
OPENING
BEFORE INSTALLATION
BOTTOM MOUNTING
CONCRETE BLOCK WALL INSTALLATION
BRACKET. MOUNT ON
OPENING
WOOD OR STEEL SIDING
OPENING
INSTALLING UNIT.
RETURN AIR
WALL STRUCTURE
RETURN AIR
SUPPLY AIR
FACTORY SUPPLIED
RAIN FLASHING.
SUPPLY AIR
MIS-548 A
SIDE VIEW
I
A
C
K
E + 1.000
B
1.000
SUPPLY DUCT
OVER FRAME
INTERIOR FINISHED WALL
ALL AROUND DUCT
FRAMING MATERIAL
EXTERIOR FINISH WALL
OPENING
FOR ACTUAL DIMENSIONS.
2 x 4'S, 2 x 6'S &/OR
STRUCTURAL STEEL
ATTACH TO TOP
1.000" CLEARANCE
1.000" CLEARANCE
PLATE OF WALL
C
SEE UNIT DIMENSIONS, FIGURE 2,
OPENING
RETURN DUCT
2 x 6
ATTACH TO BOTTOM
OVER FRAME
PLATE OF WALL
L
THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR REST OF WALL. A SECOND MEMBER MAY BE REQUIRED FOR SOME WALLS.
MIS-549 B
ALL AROUND DUCT
SEE FIGURE 3 – MOUNTING INSTRUCTIONS
FIGURE 5
FIGURE 6
Wall Mounting Instructions
IF REQUIRED
IF REQUIRED
Manual 2100-604B Page 12 of 28
Page 13
FIGURE 7
LOWERED
RAISED FLOOR
RAFTERS
SUPPLY AIR
CEILING SURFACE
WALL SLEEVE
RETURN AIR
CLOSET WALL
GRILLE
FLASHING
RETURN AIR
FLASHING
SUPPLY DUCT MAYBE LOCATED IN AN ATTIC
OR BELOW CEILING RAFTERS AS SHOWN
SUPPLY DUCT MAY BE LOCATED IN AN ATTIC
SURFACE
RAFTERS
FINISHED CEILING
SUPPLY AIR DUCT
WALL
OPENING W/ GRILLE
SUPPLY DUCT MAYBE LOCATED IN AN ATTIC
OR BELOW CEILING RAFTERS AS SHOWN
CEILING
RAIN
RETURN AIR
SLEEVE
WALL
SUPPLY AIR DUCT
RAFTERS
RAFTERS
RETURN AIR OPENING W/ GRILLE
RAIN
FALSE WALL INSTALLATION
DUCTED SUPPLY
GRILLE
OUTSIDE
SPACE
FALSE WALL
RETURN AIR GRILLE
OUTSIDE
OR BELOW CEILING RAFTERS AS SHOWN
FINISHED CEILING SURFACE
RAIN
FLASHING
RAIN
FLASHING
RETURN AT UNITNO DUCT
WALL
SUPPLY AIR DUCT
CLOSET INSTALLATION
RETURN AIR
FINISHED
FINISHED CEILING SURFACE
MIS-550 B
FREE AIR FLOW
OUTSIDE
WALL
OUTSIDE
WALL
SUPPLY AIR DUCT W/ GRILLE
Common Wall Mounting Installations
Manual 2100-604B Page 13 of 28
Page 14
WIRING – MAIN POWER
WIRING – LOW VOLTAGE WIRING
Refer to the unit rating plate for wire sizing information and maximum fuse or circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75° C copper) for all models including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.
The unit rating plate lists a maximum time delay relay fuse or circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.
All 230/208V 1 phase and 3 phase equipment have dual primary voltage transformers.
All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:
TAP RANGE 240 253 – 216 208 220 – 187
NOTE: The voltage should be measured at the field
power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).
For wiring size and connections, refer to Wiring Manual 2100-516.
The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect. To convert for the locking capability, bend the tab located in the bottom left-hand corner of the disconnect opening under the disconnect access panel straight out. This tab will now line up with the slot in the door. When shut, a padlock may be placed through the hole in the tab preventing entry.
See “Start Up” section for important information on three phase scroll compressor start ups.
See Table 4 for Electrical Specifications.
Manual 2100-604B Page 14 of 28
Page 15
START UP
THESE UNITS REQUIRE R-410A REFRIGERANT AND POLYOL ESTER OIL.
GENERAL
1. Use separate service equipment to avoid cross contamination of oil and refrigerants.
2. Use recovery equipment rated for R-410A refrigerant.
3. Use manifold gauges rated for R-410A (800 psi/250 psi low).
4. R-410A is a binary blend of HFC-32 and HFC-125.
5. R-410A is nearly azeotropic—similar to R-22 and R-12. Although nearly azeotropic, charge with liquid refrigerant.
6. R-410A operates at 40-70% higher pressure than R-22 and systems designed for R-22 cannot withstand this higher pressure.
7. R-410A has an ozone depletion potential of zero, but must be reclaimed due to its global warming potential.
8. R-410A compressors use Polyol Ester oil.
9. Polyol Ester oil is hygroscopic; it will rapidly absorb moisture and strongly hold this moisture in the oil.
10. A liquid line dryer must be used—even a deep vacuum will not separate moisture from the oil.
11. Limit atmospheric exposure to 15 minutes.
12. If compressor removal is necessary, always plug compressor immediately after removal. Purge with small amount of nitrogen when inserting plugs.
TOPPING OFF SYSTEM CHARGE
If a leak has occurred in the system, Bard Manufacturing recommends reclaiming, evacuating (see criteria above) and charging to the nameplate charge. If done correctly, topping off the system charge can be done without problems.
With R-410A, there are no significant changes in the refrigerant composition during multiple leaks and recharges. R-410A refrigerant is close to being an azeotropic blend (it behaves like a pure compound or single component refrigerant). The remaining refrigerant charge, in the system, may be used after leaks have occurred and then “top-off” the charge by utilizing the pressure charts on the inner control panel cover as a guideline.
REMEMBER: When adding R-410A refrigerant, it must come out of the charging cylinder/tank as a liquid to avoid any fractionation, and to insure optimal system performance. Refer to instructions for the cylinder that is being utilized for proper method of liquid extraction.
WARNING
Failure to conform to these practices could lead to damage, injury or death.
SAFETY PRACTICES
1. Never mix R-410A with other refrigerants.
2. Use gloves and safety glasses. Polyol Ester oils can be irritating to the skin, and liquid refrigerant will freeze the skin.
3. Never use air and R-410A to leak check; the mixture may become flammable.
4. Do not inhale R-410A—the vapor attacks the nervous system, creating dizziness, loss of coordination and slurred speech. Cardiac irregularities, unconsciousness and ultimate death can result from breathing this concentration.
5. Do not burn R-410A. This decomposition produces hazardous vapors. Evacuate the area if exposed.
6. Use only cylinders rated DOT4BA/4BW 400.
7. Never fill cylinders over 80% of total capacity.
8. Store cylinders in a cool area, out of direct sunlight.
9. Never heat cylinders above 125°F.
10. Never trap liquid R-410A in manifold sets, gauge lines or cylinders. R-410A expands significantly at warmer temperatures. Once a cylinder or line is full of liquid, any further rise in temperature will cause it to burst.
Manual 2100-604B Page 15 of 28
Page 16
IMPORTANT INSTALLER NOTE
PHASE MONITOR
For improved start up performance, wash the indoor coil with a dishwashing detergent.
HIGH AND LOW PRESSURE SWITCH
All W**H wall mounted air conditioner series models are supplied with a remote reset for the high and low pressure switch. If tripped, this pressure switch may be reset by turning the thermostat off then back on again.
THREE PHASE SCROLL COMPRESSOR START UP INFORMATION
Scroll compressors, like several other types of compressors, will only compress in one rotational direction. Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction.
However, three phase compressors will rotate in either direction depending upon phasing of the power. Since there is a 50-50 chance of connecting power in such a way as to cause rotation in the reverse direction, verification of proper rotation must be made. Verification of proper rotation direction is made by observing that suction pressure drops and discharge pressure rises when the compressor is energized. Reverse rotation also results in an elevated sound level over that with correct rotation, as well as substantially reduced current draw compared to tabulated values.
Verification of proper rotation must be made at the time the equipment is put into service. If improper rotation is corrected at this time, there will be no negative impact on the durability of the compressor. However, reverse operation for over 1 hour may have a negative impact on the bearing due to oil pump out.
NOTE: If compressor is allowed to run in reverse
rotation for several minutes, the compressor’s internal protector will trip.
All three phase ZP compressors are wired identically internally. As a result, once the correct phasing is determined for a specific system or installation, connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction.
The direction of rotation of the compressor may be changed by reversing any two line connections to the unit.
All units with three phase scroll compressors are equipped with a three phase line monitor to prevent compressor damage due to phase reversal.
The phase monitor in this unit is equipped with two LEDs. If the Y signal is present at the phase monitor and phases are correct the green LED will light.
If phases are reversed, the red fault LED will be lit and compressor operation is inhibited.
If a fault condition occurs, reverse two of the supply leads to the unit. Do not reverse any of the unit factory
wires as damage may occur.
CONDENSER FAN OPERATION
Applies to W42, W48 and W60 models only. The condenser fan motor on 230/208 volt, one and three phase, 60 HZ units is a two-speed motor that comes factory wired on high speed for peak performance. If ambient conditions permit, it can be reconnected to low speed (red wire) for lower sound level. See wiring diagram.
50 HZ models must have fan wired on low speed. These models are factory wired on low speed.
SERVICE HINTS
1. Caution owner/operator to maintain clean air filters at all times and to not needlessly close off supply and return air registers. This reduces airflow through the system, which shortens equipment service life as well as increasing operating costs.
2. Check all power fuses or circuit breakers to be sure they are the correct rating.
3. Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential.
SEQUENCE OF OPERATION
COOLING – Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation.
HEATING – A 24V solenoid coil on reversing valve controls heating cycle operation. Two thermostat options, one allowing “Auto” changeover from cycle to cycle and the other constantly energizing solenoid coil during heating season, and thus eliminating pressure equalization noise except during defrost, are to be used. On “Auto” option a circuit is completed from R-W1 and R-Y on each heating “on” cycle, energizing reversing valve solenoid and pulling in compressor contactor starting compressor and outdoor motor. R-G also make
Manual 2100-604B Page 16 of 28
Page 17
starting indoor blower motor. Heat pump heating cycle now in operation. The second option has no “Auto” changeover position, but instead energizes the reversing valve solenoid constantly whenever the system switch on subbase is placed in “Heat” position, the “B” terminal being constantly energized from R. A Thermostat demand for heat completes R-Y circuit, pulling in compressor contactor starting compressor and outdoor motor. R-G also make starting indoor blower motor.
PRESSURE SERVICE PORTS
High and low pressure service ports are installed on all units so that the system operating pressures can be observed. Pressure tables covering all models can be found on page 22. It is imperative to match the correct pressure table to the unit by model number.
This unit employs high-flow Coremax valves instead of the typical Shrader type valves.
WARNING! Do NOT use a Schrader valve core removal tool with these valves. Use of such a tool could result in eye injuries or refrigerant burns!
To change a Coremax valve without first removing the refrigerant, a special tool is required which can be obtained at www.fastestinc.com/en/SCCA07H. See the replacement parts manual for replacement core part numbers.
DEFROST CYCLE
The defrost cycle is controlled by temperature and time on the solid state heat pump control.
When the outdoor temperature is in the lower 40°F temperature range or colder, the outdoor coil temperature is 32°F or below. This coil temperature is sensed by the coil temperature sensor mounted near the bottom of the outdoor coil. Once coil temperature reaches 30°F or below, the coil temperature sensor sends a signal to the control logic of the heat pump control and the defrost timer will start accumulating run time.
After 30, 60 or 90 minutes of heat pump operation at 30°F or below, the heat pump control will place the system in the defrost mode.
During the defrost mode, the refrigerant cycle switches back to the cooling cycle, the outdoor motor stops, electric heaters are energized, and hot gas passing through the outdoor coil melts any accumulated frost. When the temperature rises to approximately 57°F, the coil temperature sensor will send a signal to the heat pump control which will return the system to heating operations automatically.
If some abnormal or temporary condition such as a high wind causes the heat pump to have a prolonged defrost cycle, the heat pump control will restore the system to heating operation automatically after 8 minutes.
The heat pump defrost control board has an option of 30, 60 or 90-minute setting. By default, this unit is shipped from the factory with the defrost time on the 60 minute pin. If circumstances require a change to another time, remove the wire from the 60-minute terminal and reconnect to the desired terminal. Refer to Figure 8.
There is a cycle speed up jumper on the control. This can be used for testing purposes to reduce the time between defrost cycle operation without waiting for time to elapse.
Use a small screwdriver or other metallic object, or another ¼" QC, to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost.
Be careful not to touch any other terminals with the instrument used to short the SPEEDUP terminals. It may take up to 10 seconds with the SPEEDUP terminals shorted for the speedup to be completed and the defrost cycle to start.
As soon as the defrost cycle kicks in remove the shorting instrument from the SPEEDUP terminals.
Otherwise the timing will remain accelerated and run through the 1-minute minimum defrost length sequence in a matter of seconds and will automatically terminate the defrost sequence.
There is an initiate defrost jumper (sen jump) on the control that can be used at any outdoor ambient during the heating cycle to simulate a 0° coil temperature.
This can be used to check defrost operation of the unit without waiting for the outdoor ambient to fall into the defrost region.
By placing a jumper across the SEN JMP terminals (a ¼" QC terminal works best) the defrost sensor mounted on the outdoor coil is shunted out and will activate the timing circuit. This permits the defrost cycle to be checked out in warmer weather conditions without the outdoor temperature having to fall into the defrost region.
In order to terminate the defrost test the SEN JMP jumper must be removed. If left in place too long, the compressor could stop due to the high pressure control opening because of high pressure condition created by operating in the cooling mode with outdoor fan off. Pressure will rise fairly fast as there is likely no actual frost on the outdoor coil in this artificial test condition.
There is also a 5-minute compressor time delay function built into the HPC. This is to protect the compressor from short cycling conditions. The board’s LED will have a fast blink rate when in the compressor time delay. In some instances, it is helpful to the service technician to override or speed up this timing period, and shorting out the SPEEDUP terminals for a few seconds can do this.
Manual 2100-604B Page 17 of 28
Page 18
Low Pressure Switch Bypass Operation - The control
120*
SW1SW
2 TIME (SEC)
OFF OFF
ON ON
OFF
ON
OFF
ON
30 60
180
OFF
LOW PRESSURE BYPASS TIMER SWITCH *(FACTORY SETTING 120 SECONDS)
ACCUMULATED DEFROST TIME TIMER (FACTORY SETTING 60 MIN.)
ON
has a selectable (SW1) low pressure switch bypass set up to ignore the low pressure switch input during the first (30, 60, 120 or 180 seconds) of “Y” operation.
After this period expires, the control will then monitor the low pressure switch input normally to make sure that the switch is closed during “Y” operation.
Defrost Control Board
High Pressure Switch Operation - The control has a built-in lockout system that allows the unit to have the high pressure switch trip up to two times in 1 hour and only encounter a “soft” lockout. A “soft” lockout shuts the compressor off and waits for the pressure switch to reset, which at that point then allows the compressor to be restarted as long as the 5-minute short cycle timer has run out. If the high pressure switch trips a third time within one hour, the unit is in “hard” lockout indicating something is certainly wrong and it will not restart itself.
FIGURE 8
Manual 2100-604B Page 18 of 28
MIS-2668A
Page 19
SERVICE
SOLID STATE HEAT PUMP CONTROL TROUBLESHOOTING PROCEDURE
1. NOTE: A thorough understanding of the defrost cycle sequence is essential. Review that section earlier in this manual prior to troubleshooting the control. Turn on AC power supply to unit.
2. Turn thermostat blower switch to “fan on”— the indoor blower should start. (If it doesn’t, troubleshoot indoor unit and correct problem.)
3. Turn thermostat blower to “auto” position. Indoor blower should stop. NOTE: Many models have a
1-minute blower time delay on “off” command; wait for this to time-out.
4. Set system switch to “heat” or “cool”. Adjust thermostat to call for heat or cool. The indoor blower, compressor and outdoor fan should start.
NOTE: If there was no power to 24 volt transformer, the compressor and outdoor fan motor will not start for 5 minutes. This is because of the compressor short cycle protection.
LED BLINK CODES
BLINK FUNCTION
Slow Normal function (1.0 sec on/1.0 sec off) Fast Compressor Delay timer active (0.1 sec on/0.1 sec off) 1 Low pressure switch failure 2 High pressure switch failure/“Soft” Lockout 3 Defrost mode active 4 High pressure switch failure/“Hard” Lockout
TABLE 1 – TROUBLESHOOTING
Sympton Description, Check & Possible Causes What & How to Check / Repair
Compressor will not start
(heating or cooling)
Fan outdoor motor does not run
(cooling or heating except during defrost)
Reversing
valve does not
energize (heating only)
Unit will not go
into defrost
(heating only)
Unit will not come out of defrost
(heating only)
1. Check for LED illumination.
Is there an LED illuminated on the board (ashing)?
2. Check for error codes.
Is the LED ashing a Code?
3. Check for power at board.
Is there 24 volts AC between R and C?
4. Check codes.
What code is blinking?
5. Compressor delay active.
Wait for 5 minute delay or jump board's "speed up pins".
6. Low pressure fault. Check wiring circuit and unit pressures.
7. High pressure fault. Check wiring circuit and unit pressures.
8. Check for Compressor input signal.
Is there 24 volts AC between Y and C?
9. No power to board. The unit either does not have unit voltage, the transformer is bad or the unit wiring is incorrect.
10. Check for Compressor output signal.
Is there 24 volts AC between CC & C?
11. No "Y" compressor input signal.
12. No "CC" compressor output signal. Check compressor contactor for proper operation and nally check compressor.
13. Faulty board. Replace defrost board.
Heat pump control defective
Motor defective Check for open or shorted motor winding. Replace motor.
Motor capacitor defective Check capacitor rating. Check for open or shorted capacitor. Replace capacitor.
Heat pump control defective
Reversing valve solenoid coil defective
Temperature sensor or heat pump control defective
Temperature sensor or heat pump control defective
Yes = go to Step #2; No = go to Step #3
Yes = go to Step #4; No = go to Step #8
Yes = go to Step #13; No = go to Step #9
Code "1", go to Step #6; Code "2", go to Step#7; Fast Blink, go to Step #5
Check for proper operation; if still needed, go back to Step #1.
Yes = go to Step #10; No = go to Step #11
Yes = go to Step #12; No = go to Step #13
Check thermostat wiring, incorrect phase of unit (see section on Phase Monitor), and nally unit wiring.
Check across fan relay on heat pump control. (Com-NC) Replace heat pump control.
Check for 24V between RV-C and B-C.
1. Check control circuit wiring.
2. Replace heat pump control.
Check for open or shorted coil.
Replace solenoid coil.
Disconnect temperature sensor from board and jumper across "SPEEDUP" terminals and "SEN JMP" terminals. This should cause the unit to go through a defrost cycle within one minute.
1. If unit goes through defrost cycle, replace temperature sensor.
2. If unit does not go through defrost cycle, replace heat pump control.
Jumper across "SPEEDUP" terminal.
This should cause the unit to come out of defrost within one minute.
1. If unit comes out of defrost cycle, replace temperature sensor.
2. If unit does not come out of defrost cycle, replace heat pump control.
Manual 2100-604B Page 19 of 28
Page 20
CHECKING TEMPERATURE SENSOR OUTSIDE UNIT CIRCUIT
1. Disconnect temperature sensor from board and from outdoor coil.
2. Use an ohmmeter and measure the resistance of the sensor. Also use ohmmeter to check for short or open.
Temperature (F) vs. Resistance (R) of Temperature Sensor
F R F R F R F R
-25.0 196871 13.0 56985 53.0 19374 89.0 7507
-24.0 190099 14.0 55284 52.0 18867 90.0 7334
-23.0 183585 15.0 53640 53.0 18375 91.0 7165
-22.0 177318 16.0 52051 54.0 17989 92.0 7000
-21.0 171289 17.0 50514 55.0 17434 93.0 6840
-20.0 165487 18.0 49028 56.0 16984 94.0 6683
-19.0 159904 19.0 47590 57.0 16547 95.0 6531
-18.0 154529 20.0 46200 58.0 16122 96.0 6383
-17.0 149355 21.0 44855 59.0 15710 97.0 6239
-16.0 144374 22.0 43554 60.0 15310 98.0 6098
-15.0 139576 23.0 42295 61.0 14921 99.0 5961
-14.0 134956 24.0 41077 62.0 14544 100.0 5827
-13.0 130506 25.0 39898 63.0 14177 101.0 5697
-12.0 126219 26.0 38757 64.0 13820 102.0 5570
-11.0 122089 27.0 37652 65.0 13474 103.0 5446
-10.0 118108 28.0 36583 66.0 13137 104.0 5326
-9.0 114272 29.0 35548 67.0 12810 105.0 5208
-8.0 110575 30.0 34545 68.0 12492 106.0 5094
-7.0 107010 31.0 33574 69.0 12183 107.0 4982
-6.0 103574 32.0 32634 70.0 11883 108.0 4873
-5.0 100260 33.0 31723 71.0 11591 109.0 4767
-4.0 97064 34.0 30840 72.0 11307 110.0 4663
-3.0 93981 35.0 29986 73.0 11031 111.0 4562
-2.0 91008 36.0 29157 74.0 10762 112.0 4464
-1.0 88139 37.0 28355 75.0 10501 113.0 4367
0.0 85371 38.0 27577 76.0 10247 114.0 4274
1.0 82699 39.0 26823 77.0 10000 115.0 4182
2.0 80121 40.0 26092 78.0 9760 116.0 4093
3.0 77632 41.0 25383 79.0 9526 117.0 4006
4.0 75230 42.0 24696 80.0 9299 118.0 3921
5.0 72910 43.0 24030 81.0 9077 119.0 3838
6.0 70670 44.0 23384 82.0 8862 120.0 3757
7.0 68507 45.0 22758 83.0 8653 121.0 3678
8.0 66418 46.0 22150 84.0 8449 122.0 3601
9.0 64399 47.0 21561 85.0 8250 123.0 3526
10.0 62449 48.0 20989 86.0 8057 124.0 3452
11.0 60565 49.0 20435 87.0 7869
12.0 58745 50.0 19896 88.0 7686
3. Check resistance reading to chart of resistance. Use sensor ambient temperature. (Tolerance of part is ± 10%.)
4. If sensor resistance reads very low, then sensor is shorted and will not allow proper operation of the heat pump control.
5. If sensor is out of tolerance, shorted, open or reads very low ohms then it should be replaced.
Manual 2100-604B Page 20 of 28
Page 21
FAN BLADE SETTING DIMENSIONS
REMOVAL OF FAN SHROUD
The correct fan blade setting for proper air delivery across the outdoor coil is shown in Figure 9. Refer to Table 2 for unit specific dimension.
Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly.
FIGURE 9
Fan Blade Setting
TABLE 2
MIS-1724
Fan Blade Dimension
MODEL
W18H2 W24H2
W30H2 W36H2
W42H2 W48H2 W60H2
DIMENSION A
(INCHES)
1.00"
1.25"
1.75"
1. Disconnect all power to the unit.
2. Remove the screws holding both grilles, one on each side of unit, and remove grilles.
3. Remove nine screws holding fan shroud to condenser and bottom.
4. Unwire condenser fan motor.
5. Slide complete motor, fan blade and shroud assembly out the left side of the unit.
6. Service motor/fan as needed.
7. Reverse steps to re-install.
R-410A REFRIGERANT CHARGE
This unit was charged at the factory with the quantity of refrigerant listed on the serial plate. AHRI capacity and efficiency ratings were determined by testing with this refrigerant charge quantity.
The following pressure tables show nominal pressures for the units. Since many installation specific situations can affect the pressure readings, this information should only be used by certified technicians as a guide for evaluating proper system performance. They shall not be used to adjust charge. If charge is in doubt, reclaim, evacuate and recharge the unit to the serial plate charge.
Manual 2100-604B Page 21 of 28
Page 22
TABLE 3A – Cooling Pressure Table
RETURN
MODEL
W18H2
W24H2
W30H2
W36H2
W42H2
W48H2
W60H2
Low side pressure ± 4 PSIG High side pressure ± 10 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate charge weight.
NOTE: Pressure table based on high speed condenser fan operation. If condensing pressures appear elevated check condenser fan wiring. See “Condenser Fan Operation”.
AIR
TEMP.
75 DB
62 WB
80 DB
67 WB
85 DB
72 WB
75 DB
62 WB
80 DB
67 WB
85 DB
72 WB
75 DB
62 WB
80 DB
67 WB
85 DB
72 WB
75 DB
62 WB
80 DB
67 WB
85 DB
72 WB
75 DB
62 WB
80 DB
67 WB
85 DB
72 WB
75 DB
62 WB
80 DB
67 WB
85 DB
72 WB
75 DB
62 WB
80 DB
67 WB
85 DB
72 WB
PRESSURE
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
75° 80° 85° 90° 95° 100° 105° 110° 115° 120°
132 292 141 299 146 309 124 329 133 337 138 349 125 326 134 334 139 346 122 329 131 337 136 349 127 354 136 363 141 376 129 352 138 361 143 374 126 332 135 341 140 353
134 311 143 319 148 330 126 351 135 360 140 373 128 350 137 359 142 372 124 351 133 360 138 373 130 372 139 382 144 395 132 374 141 384 146 397 128 352 137 361 142 374
AIR TEMPERATURE ENTERING OUTDOOR COIL
137 332 146 340 151 352 128 373 137 383 142 396 131 373 140 383 145 396 126 375 135 385 140 398 132 392 141 402 146 416 134 398 143 408 148 422 131 373 140 383 145 396
138 353 148 362 153 375 131 398 140 408 145 422 133 398 142 408 147 422 128 399 137 409 142 423 134 413 143 424 148 439 136 422 145 433 150 448 133 397 142 407 147 421
140 376 150 386 155 400 133 423 142 434 147 449 136 423 144 438 150 449 130 424 137 444 144 450 135 437 143 452 149 464 137 449 147 460 152 476 135 421 143 434 149 447
142 400 152 410 157 424 135 449 144 460 149 476 137 448 147 459 152 475 132 449 141 461 146 477 136 461 145 473 150 490 139 476 149 488 154 505 137 448 147 459 152 475
144 424 154 435 159 450 137 475 146 487 151 504 139 472 149 484 154 501 135 476 144 488 149 505 137 488 146 500 151 518 141 505 151 518 156 536 139 476 149 488 154 505
146 450 156 462 161 478 138 503 148 516 153 534 141 496 151 509 156 527 137 503 146 516 151 534 137 516 146 529 151 548 143 535 153 549 158 568 141 505 151 518 156 536
148 477 158 489 164 506 140 531 150 545 155 564 143 522 153 535 158 554 138 530 148 544 153 563 137 546 146 560 151 580 145 566 155 581 160 601 143 536 153 550 158 569
150 505 160 518 166 536 142 561 152 575 157 595 145 547 155 561 160 581 141 559 151 573 156 593 136 578 145 593 150 614 146 600 156 615 161 637 145 568 155 583 160 603
RETURN
MODEL
AIR
TEMP.
W18H2 70
W24H2 70
W30H2 70
W36H2 70
W42H2 70
W48H2 70
W60H2 70
Manual 2100-604B Page 22 of 28
TABLE 3B – Heating Pressures (All Temperatures °F)
AIR TEMPERATURE ENTERING OUTDOOR COIL
PRESSURE
Low Side
High Side482905228556282612826628572290792978730795319
Low Side
High Side57292552965530157307593146432370332773428635496367
Low Side
High Side53254532665527858290613016631272322803328834297351
Low Side
High Side47281492825128355287592926430070308773198533193345
Low Side
High Side50299503005230354308583146232268331753428435593370
Low Side
High Side42268452704927454278592846429170298773078431792327
Low Side
High Side39294432964730052305583116331970328763388434992362
0 5 10 15 20 25 30 35 40 45 50 55 60
104 334
114 352
108 380
108 360
103 361
104 386
100 339
100 376
124 372
121 395
119 369
113 379
115 404
109 352
109 391
135 394
135 411
132 377
124 398
128 423
118 366
118 408
Page 23
TABLE 4A
Electrical Specifications
No.
Field
Power
Circuits
1
1 or 2
1 1 1 1
1 or 2
1 1 1 1 1 1
1 1 or 2 1 or 2
1
1
1
1
1
1
1
1
1
1 1 or 2 1 or 2 1 or 2
1
1
1
1
1
1
1
1
1
1 1 or 2 1 or 2 1 or 2 1 or 2
1
1
1
1 1 or 2
1
1
1
1 1 or 2 1 or 2 1 or 2 1 or 2
1
1
1 1 or 2
1
1
1
A04 A08
A04 A08
B06
C06
A05* A10*
B06
B09*
C06
C09*
C15
A05
A10*
A15
B06
B09*
B15
C06
C09*
C15
A04 A05 A10
m A15
B06 B09
B15
C06 C09
C15
A04 A05 A10
m A15 m A20
B06 B09
B15 B18
C09
C15
A05 A10
m A15 m A20
B09
B15 B18
C09
C15
Rated Volts
& Phase
230/208-111
230/208-111
230/208-3
460-3
230/208-111
230/208-311
460-3
230/208-1
230/208-3
460-3
230/208-1
230/208-3
460-3
230/208-1
230/208-3
460-3
230/208-1
230/208-3
460-3
MODEL
W18H2-A00, A0Z
W24H2-A00, A0Z
W24H2-B00, B0Z
W24H2-C00, C0Z
W30H2-A00, A0Z*
W30H2-B00, B0Z*
W30H2-C00, C0Z*
W36H2-A00, A0Z*
W36H2-B00, B0Z*
W36H2-C00, C0Z*
W42H2-A00, A0Z
W42H2-B00, B0Z
W42H2-C00, C0Z
W48H2-A00, A0Z
W48H2-B00, B0Z
W48H2-C00, C0Z
W60H2-A00, A0Z
W60H2-B00, B0Z
W60H2-C00, C0Z
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor sizing. CAUTION: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) current carrying conductors are in a raceway.
Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.Maximum KW that can operate with the heat pump on is 9KW. Full heat available during emergency heat mode. m Maximum KW that can operate with the heat pump on is 10KW. Full heat available during emergency heat mode. n Based on 75°copper wire. All wiring must conform to the National Electrical Code and all local codes.
* Available factory-built only with top outlet supply as an option.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with the National Electrical Code and all local codes.
Minimum
Circuit
Ampacity
16 37 58 24 44 65 17 35 11 21 24 50 76 18 36 45 11 20 25 26 29 55 81 84 23 41 50 51 12 21 25 26 36 57 62 88 88 26 44 53 53 13 22 26 26 37 58 63 89 89
111
29 47 56 56 62 14 27 27 41 67 93 93
111
28 55 55 62 16 28 28
Single Circuit Dual Circuit
Maximum
External
Fuse or
Ckt. Brkr.
20 40 60 25 50 70 20 40 15 25 35 50 80 25 40 45 15 20 25 30 40 60 90 90 30 45 50 60 15 25 25 30 50 60 70 90 90 35 50 60 60 15 25 30 30 50 60 70 90 90
125
35 50 60 60 70 20 30 30 60
80 100 100 125
40
60
60
70
20
30
30
n
Field
Power
Wire Size
12
8 6
10
8 6
12
8 14 10
8
8
4 10
8
8 14 12 10 10
8
6
4
4 10
8
8
8 14 10 10 10
8
6
6
3
3
8
8
6
6 14 10 10 10
8
6
6
3
3
2
8
8
6
6
6 12 10 10
8
4
3
3
2
8
6
6
6 12 10 10
Minimum
n
Ground
Wire
12 10 10 10 10
8 44 21 45 25 8 10 10 10 12 10 14 10 10 10
8 50 26 50 30 8 10 10 10 10 10 10 14 12 10 10 10 10
8
8 10 10 10 10 14 10 10 10 10 10
8
8
8 10 10 10 10 14 10 10 10 10 10
8
8
8
6 10 10 10 10
8 34 28 40 30 8 10 10 10 12 10 10 10
8
8
8
6 10 10 10 10 34 28 40 30 8 10 10 10 12 10 10
Circuit
Ampacity
Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B
555526526060306066106101010
36 36 36
37 37 37 59
41 41 41 59
26 52 52
26 52 52 52
26 52 52 52
Maximum
External Fuse or
Ckt. Breaker
50
30
50
60
50
60
50
30
50
60
50
60
60
60
60
30
60
60
60
60
60
60
n
Field Power
Wire Size
8
10 8 8
8
10 8 8 6
8
10 8 8 6
Ground
Wire Size
10
6
10
6
10
10
6
10
6
10
6
10
10
6
10
6
10
6
10
Manual 2100-604B Page 23 of 28
n
10
10 10 10
10 10 10 10
10 10 10 10
Page 24
TABLE 4B
Electrical Specifications — Dehumidification Models
MODEL
W24H2DA00, A0Z
W24H2DB00, B0Z
W24H2DC00, C0Z
W30H2DA00, A0Z
W30H2DB00, B0Z
W30H2DC00, C0Z
W36H2DA00, A0Z
W36H2DB00, B0Z
W36H2DC00, C0Z
W42H2DA00, A0Z
W42H2DB00, B0Z
W42H2DC00, C0Z
W48H2DA00, A0Z
W48H2DB00, B0Z
W48H2DC00, C0Z
W60H2DA00, A0Z
W60H2DB00, B0Z
W60H2DC00, C0Z
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor sizing.
CAUTION: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) current carrying conductors are in a raceway.
Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
Based on 75°copper wire. All wiring must conform to the National Electrical Code and all local codes.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with the National Electrical Code and all local codes.
Rated Volts
& Phase
A04
230/208-111
A08
230/208-3
B06
460-3
C06
A05
230/208-111
A10
B06
230/208-311
B09
C06
460-311
C09
A05
230/208-111
A10
B06
230/208-311
B09
C06
460-311
C09
A05
230/208-111 or 2
A10
B06
230/208-311
B09
C06
460-311
C09
A05
230/208-111 or 2
A10
B06
230/208-311
B09
460-3
C09
A05
230/208-111 or 2
A10
230/208-3
B09
460-3
C09
No.
Field
Power
Circuits
1 or 2
1 1
1 1
1 or 2
1
1
1 or 2
1
1
1 or 2
1
1
1 or 2
1
1 1
1 or 2
1 1
1 1
Minimum
Circuit
Ampacity
24 44 65
17 35
12 21
27 52 79
19 37 47
12 21 26
30 56 82
24 42 51
12 21 25
40 66 92
28 46 55
14 23 27
38 64 90
29 47 56
14 27
41 67 93
28 55
15 28
Single Circuit Dual Circuit
Maximum
External
Fuse or
Ckt. Brkr.
25 50 70
20 40
15 25
35 60 80
25 40 50
15 25 30
40 60 90
30 50 60
15 25 25
60 70
100
40 50 60
20 25 30
50 80 90
35 50 60
20 30
60 80
100
40 60
20 30
Field
Power
Wire Size
10
8 6
12
8
14 10
8 6 4
10
8 8
14 10 10
10
6 4
10
8 6
14 10 10
8 6 3
8 8 6
12 10 10
8 6 3
8 8 6
12 10
8 4 3
8 6
12 10
Minimum
Ground
Wire
10 10
8 44 21 45 25 8 10 10 10
12 10
14 10
10 10
8 52 26 60 30 6 10 10 10
10 10 10
14 10 10
10 10
8 55 26 60 30 6 10 10 10
10 10 10
14 10 10
10
8 8
10 10 10
12 10 10
10
8 8
10 10 10
12 10
10
8 8
10 10
12 10
Circuit
Ampacity
Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B
40402652505030
38382652505030
41412652606060
Maximum
External Fuse or
Ckt. Breaker
60
60
60
Field Power
Wire Size
88106101010
88106101010
106101010
8 8
Ground
Wire Size
10
10
10
Manual 2100-604B Page 24 of 28
Page 25
TABLE 5
Recommended Airflow
Model Rated CFM * Rated ESP *
W18H
W24H 800 .20 700 - 950 High
W30H 1000 .40 930 - 1300 High
W36H 1100 .30 930 - 1350 High
W42H 1400 .30 1600 - 1150 High
W48H 1550 .20 1750 - 1285 High
W60H 1650 .30 1950 - 1375 High
* Rated CFM and ESP on high speed tap. Rated CFM and ESP on low speed tap.
600
.30 575 - 725 High
Recommended
Airflow Range
Factory Speed
Connection
TABLE 6
Indoor Blower Performance
W18H, W24H W18H W30H, W36H W42H, W48H W60H
E.S.P.
High Speed Low Speed High Speed Low Speed High Speed Low Speed High Speed Low Speed
In
Dry
Wet
Dry
Wet
Dry
H
O
2
Coil
Coil
Coil
Coil
.0
1020 .1 .2 .3 .4 .5
960 865 820 735 615
975 905 800 735 650 535
750 735 710 660 605 540
700 675 650 600 550 490
1395 1340 1285 1205 1110 1005
Coil
Wet Coil
1315 1270 1190 1100 1000
870
Dry
Coil
950 930 910 855 800
—
Wet
Coil
935 915 885 830 755
—
Dry
Coil
1885 1770 1635 1500 1370 1250
Wet Coil
1800 1665 1540 1400 1285 1150
Dry
Coil
1650 1550 1450 1350 1300
—
Wet Coil
1600 1500 1400 1300 1175
—
2200 2100 2000 1875 1775 1650
Dry Coil
Wet Coil
2000 1900 1800 1700 1600 1475
Dry
Coil
1600 1525
— — — —
Wet Coil
1450 1375
— — — —
Manual 2100-604B Page 25 of 28
Page 26
TABLES 7
Maximum ESP of Operation
Electric Heat Only
Model ESP
W18H W24H
W24H
W24H
A00 A04 A08
B00 B06
C00 C06
Model
Speed KW
-A00
-A04
-A05
-A10
-A15
-A20
-B00
-B09
-B15
-B18
-C00
-C09
-C15
High Speed Low Speed High Speed Low Speed High Speed Low Speed
W30H W36H
W30H W36H
W30H W36H
Model
A00 A05 A10 A15
B00 B06 B09 B15
C00 C06 C09 C15
.50 .50 .40
.50 .50
.50 .50
W42H W48H W60H
.50
----­.50 .50 .50
-----
.50 .50 .50
-----
.50 .50 .50
.50
----­.50 .45 .45
-----
.50 .45 .45
-----
.50 .40 .40
.50 .50 .50 .50 .50 .50
.50 .50 .50 .50
.50 .50 .50
.50 .50 .50 .45 .45 .45
.50 .45 .45 .45
.50 .40 .40
Front Outlet Top Outlet
Low
Speed
.50 .40 .35 .35
.50 .40 .35 .35
.50 .50 .30 .30
.50
----­.50 .50 .50 .50
.50 .50 .50 .50
.50 .50 .50
High
Speed
.50 .50 .40 .40
.50 .50 .45 .45
.50 .50 .40 .40
Low
Speed
.50 .40 .25
NA
.50
NA
.30
NA
.50
NA
.35
NA
.40
----­.25 .25 .25 .25
.40 .30 .30 .30
.40 .35 .35
High
Speed
.50 .50 .40
NA
.50
NA
.40
NA
.50
NA
.45
NA
Models 240V-1 208V-1 240V-3 208V-3 460V-3
KW Amps BTUH Amps BTUH Amps BTUH Amps BTUH Amps BTUH
4 16.7 13650 14.4 10240
5 20.8 17065 18.1 12800
6 14.4 20500 12.5 15360 7.2 20500
8 33.3 27300 28.8 20475
9 21.7 30600 18.7 23030 10.8 30700
10 41.6 34130 36.2 25600
15 62.5 51250 54.0 38400 36.2 51200 31.2 38400 18.0 51200
18 43.3 61430 37.5 46100
20 83.2 68260 72.1 51200
Manual 2100-604B Page 26 of 28
TABLE 8
Electric Heat
Page 27
TABLE 9
Optional Accessories
Part Number
EHWH02A-A04 X
EHWH02A-A08 X
EHW24H-A04 X
EHW24H-A08 X
EHW24H-B06 X
EHWH30-A05 X
EHWH30-A10 X
EHWH36-A05 X
EHWH36-A10 X
EHWH36-A15 X
EHWH03-B06 X
EHW36H-B06 X
EHWH03-B09 X X
EHW30H-B15 X
EHWC03A-C06 X X
Heater Kits
Circuit Breaker (WMCB) &
EHWH42-A05 X X
EHWH42-A10 X X
EHWH42-A15 X X
EHWH-04-A20 X X
EHWH05-B06 X X
EHWH05-B09 X X X
EHWH05-B15 X X X
EHWH42-C06 X
EHWH05A-C09 X X X
EHWH05A-C15 X X X
EHWH04-A15 X
EHWH04-A10 X
EHW05H-B18 X X
WMCB-02A X
WMCB-02B X
WMCB-03A X
WMCB-03B X X
WMCB-06A X X
WMCB-05B X X
WMCB-07B X
WMCB-08A X X
Pull Disconnect (WMPD)
WMCB-09A X
WMPD-01C X X X X X X
W18H2-A
W24H2-A
W24H2-B
W24H2-C
W30H2-A
W30H2-B
W30H2-C
W36H2-A
W36H2-B
W36H2-C
W42H2-A
W42H2-B
W42H2-C
W48H2-A
W48H2-B
W48H2-C
W60H2-A
W60H2-B
W60H2-C
Manual 2100-604B Page 27 of 28
Page 28
TABLE 10
Vent and Control Options
Part Number Description
CMH-14A ODT X X X
CMC-15
SK111
CMC-28 LAC X X X
BFAD-2 Barometric Fresh Air Damper - Standard X
BOP-2 Blank Off Plate X
MFAD-2 Motorized Fresh Air Damper X
CRV-2 Commercial Ventilator - Spring Return X
ECONWMS-E2B Economizer X
ERVF-A2 Energy Recovery Ventilator - 230 Volt X
BFAD-3 Barometric Fresh Air Damper - Standard X
BOP-3 Blank Off Plate X
MFAD-3 Motorized Fresh Air Damper X
CRVS-3 Commercial Ventilator - Spring Return X
CRVP-3 Commercial Ventilator - Power Return X
ECONWMS-E3B Economizer X
ERVF-A3 Energy Recovery Ventilator - 230 Volt X
ERVF-C3 Energy Recovery Ventilator - 460 Volt X
BFAD-5 Barometric Fresh Air Damper - Standard X
BOP-5 Blank Off Plate X
MFAD-5 Motorized Fresh Air Damper X
CRVS-5 Commercial Ventilator - Spring Return X
CRVP-5 Commercial Ventilator - Power Return X
ECONWMS-E5B Economizer X
ERVF-A5 Energy Recovery Ventilator - 230 Volt X
ERVF-C5 Energy Recovery Ventilator - 460 Volt X
Start Kit (230V 1-Phase only)
Start Kit (230V 1-Phase only)
W18, W24
W30, W36
X X X
X X X
W42, W48, W60
PTCR Start Kit can be used with all -A single phase models. Increases starting torque 2-3x. Not used for -B or -C three phase models. Do not use if SK111 is used.
Start Capacitor and potential relay start kit can be used with all -A single phase models. Increases starting torque 9x. Not used for -B or -C three phase models. Do not use if CMC-15 is used.
Manual 2100-604B Page 28 of 28
Loading...