W**AAP Series .....................................17
Table 2 Electrical Specifications –
W**LAP Series .....................................18
......................
..............................
............................
............................
............................
8
9
10
11
12
Manual 2100-678
Page 2 of 24
GENERAL INFORMATION
Free Cooling Unit System
This Bard Free Cooling Unit System is composed of
MULTI-TEC wall-mounted air conditioners matched
with an LC6000 lead/lag controller or Bard th-Tune
single unit controller. If only one wall-mounted air
conditioner is being used, it can be matched with
either the LC6000 lead/lag controller or a th-Tune
single unit controller. If more than one wall mount
is installed, the LC6000 lead/lag controller must be
matched with the air conditioning units. The wall
mounts are specifically engineered for telecom/motor
control center rooms.
NOTE: The LC6000 lead/lag controller (or th-Tune
single unit controller) and MULTI-TEC wallmount units are designed specifically to work
together. These controllers cannot run other
Bard models or other brands of systems, nor
can other controllers run the MULTI-TEC wallmount units. They are a complete system, and
must be used together.
Wall-Mount Air Conditioner Units
The
MULTI-TEC
units will supply 100% of rated cooling airflow in free
cooling mode with ability to exhaust the same amount
through the unit itself without any additional relief
openings in the shelter.
Each of these units are fully charged with refrigerant
and may have optional auxiliary heat.
units operate on VAC power.
The
Controller
A th-Tune single unit controller (Bard P/N 8403-
088) can be used in place of the LC6000 controller
when only one MULTI-TEC wall-mount air conditioner
is being controlled. If using a th-Tune stand-alone
controller instead of the LC6000 controller, the alarm
logging and remote communication capabilities of
the LC6000 controller will not be available. A TEC-
TM
hand-held diagnostic tool is required to program
EYE
the wall-mount unit for th-Tune single unit controller
operation. The th-Tune controller and TEC-EYE
diagnostic tool are available as a kit (Bard P/N 8620-
264).
General
The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.
The refrigerant system is completely assembled and
charged. All internal wiring is complete.
The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.
These instructions explain the recommended method
to install the air cooled self-contained unit and the
electrical wiring connections to the unit.
These instructions and any instructions packaged with
any separate equipment required to make up the entire
air conditioning system should be carefully read before
beginning the installation. Note particularly any tags
and/or labels attached to the equipment.
While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way. Authorities having
jurisdiction should be consulted before the installation
is made. See Additional Publications below for
information on codes and standards.
Sizing of systems for proposed installation should be
based on heat loss and heat gain calculations made
according to methods of Air Conditioning Contractors of
America (ACCA). The supply flange should be installed
in accordance with the Standards of the National
Fire Protection Association for the Installation of Air
Conditioning and Ventilating Systems of Other Than
Residence Type, NFPA No. 90A, and Residence Type
Warm Air Heating and Air Conditioning Systems, NFPA
No. 90B. Where local regulations are at a variance with
instructions, installer should adhere to local codes.
Shipping Damage
Upon receipt of equipment, the cartons should be
checked for external signs of shipping damage. If
damage is found, the receiving party must contact
the last carrier immediately, preferably in writing,
requesting inspection by the carrier’s agent.
These units must remain in upright position at all
times.
Additional Publications
These publications can help when installing the
furnace. They can usually be found at the local library
or purchased directly from the publisher. Be sure to
consult the current edition of each standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation of Air Conditioning
and Ventilating Systems ...................ANSI/NFPA 90A
Standard for Warm Air Heating
and Air Conditioning Systems ............ANSI/NFPA 90B
Load Calculation for Residential Winter
and Summer Air Conditioning ............. ACCA Manual J
For more information, contact these publishers:
Air Conditioning Contractors of America (ACCA)
1712 New Hampshire Ave. N.W.
Washington, DC 20009
Telephone: (202) 483-9370 Fax: (202) 234-4721
Manual 2100-678
Page 3 of 24
American National Standards Institute (ANSI)
11 West Street, 13th Floor
New York, NY 10036
Telephone: (212) 642-4900 Fax: (212) 302-1286
American Society of Heating, Refrigeration and Air
Conditioning Engineers, Inc. (ASHRAE)
National Fire Protection Association (NFPA)
Batterymarch Park
P. O. Box 9101
Quincy, MA 02269-9901
Telephone: (800) 344-3555 Fax: (617) 984-7057
ANSI Z535.5 Definitions:
DANGER: Indicate[s] a hazardous situation which, if
not avoided, will result in death or serious injury. The
signal word “DANGER” is to be limited to the most
extreme situations. DANGER [signs] should not be used
for property damage hazards unless personal injury risk
appropriate to these levels is also involved.
WARNING: Indicate[s] a hazardous situation which,
if not avoided, could result in death or serious injury.
WARNING [signs] should not be used for property
damage hazards unless personal injury risk appropriate
to this level is also involved.
CAUTION: Indicate[s] a hazardous situation which, if
not avoided, could result in minor or moderate injury.
CAUTION [signs] without a safety alert symbol may be
used to alert against unsafe practices that can result in
property damage only.
NOTICE: [this header is] preferred to address practices
not related to personal injury. The safety alert symbol
shall not be used with this signal word. As an
alternative to “NOTICE” the word “CAUTION” without
the safety alert symbol may be used to indicate a
message not related to personal injury.
!
WARNING
Electric shock hazard.
Have a properly trained individual perform
these tasks.
Failure to do so could result in electric shock
or death.
!
WARNING
Fire hazard.
Maintain minimum 1/4" clearance between the
supply ange and combustible materials.
Failure to do so could result in re causing
damage, injury or death.
!
WARNING
Heavy item hazard.
Use more than one person to handle unit.
Failure to do so could result in unit damage or
serious injury.
!
CAUTION
Cut hazard.
Wear gloves to avoid contact with sharp
edges.
Failure to do so could result in personal injury.
Manual 2100-678
Page 4 of 24
LIST OF NECESSARY MATERIALS/TOOLS
Additional hardware and miscellaneous supplies are needed for installation. These items are field supplied and must
be sourced before installation. This list also includes tools needed for installation.
LIST OF MATERIALS/TOOLS
• Personal protective equipment/safety devices/anti-
static wrist straps
• Supply and return grilles
• Field-fabricated sleeves (if necessary)
• Fasteners sufficient for mounting the units such as
5/16” diameter anchor/lag bolts
• 7/8” diameter washers
• Fasteners appropriate for the shelter wall
construction to attach the controller to the wall
• Commercial grade outdoor silicone sealant
• Miscellaneous hand and power tools and jobsite or
shop materials
• Lifting equipment with the necessary capacity and
rigging to safely move/install the systems
• Electrical supplies
- Various size circuit breakers for the shelter AC
breaker box (see Tables 1 and 2 on pages 17
and 18)
- High-voltage wire of various gauges
(see Tables 1 and 2)
- Communication wire: 3-wire, 20 gauge
shielded cable
- Miscellaneous electrical supplies including
rigid/flexible conduit and fittings, junction
boxes, wire connectors and supports
MODEL SERIES
18 – 1½ Ton
24 – 2 Ton
30 – 2½ Ton
36 – 3 Ton
FIGURE 1
MULTI-TEC Wall-Mount Unit Model Nomenclature
W 36 A A P A 10 5 X X X X E
CAPACITY
42 – 3½ Ton
48 – 4 Ton
60 – 5 Ton
72 – 6 Ton
A – Right Hand
L – Left Hand
A – 230/208/60/1
B – 230/208/60/3
C – 460/60/3
D – 240/220/50/1
REVISION
P – PLC Logic Board
VOLTS & PHASE
E – 240/220/50/3
or 220/200/50/3
F – 415/380/50/3
Q – 575/60/3
KW
FILTER OPTIONS
X – 1" Throwaway (Standard)
W – 1" Washable
P – 2" Pleated (MERV 8)
VENTILATION OPTIONS
B – Blank-off Plate
5 – Economizer: Default Enthalpy Convert to DB Only
COLOR OPTIONS
X – Beige (Standard)
1 – White
4 – Buckeye Gray
COIL OPTIONS
X – Standard
1 – Phenolic Coated Evaporator
2 – Phenolic Coated Condenser
3 – Phenolic Coated Evaporator
and Condenser
SUPPLY AIR OUTLET
X – Front (Standard)
CONTROL MODULES
E – LAC
C – LAC & CCH
Manual 2100-678
Page 5 of 24
WALL-MOUNT UNIT SITE PREPARATION
Model Identification
Identify the specific model using the model
nomenclature information found in Figure 1 and the
model/serial tag found on the unit on the opposite side
of the control and access panels. See Figure 2 on page
8 for dimensions and critical installation requirements.
New Shelter Installation vs. Retrofit
Installation
These installation instructions cover both new shelter
installations and retrofit installations. Each installation
is unique and may require special accomodations and
modifications. Although Bard Manufacturing follows a
long-established tradition of manufacturing equipment
using industry standard dimensions for building
penetration, it is occasionally necessary to move or
enlarge supply and return openings when replacing
non-standardized equipment in a retrofit application.
Minimum Clearance
Wall-mount air conditioners are available in both righthand access models and left-hand access models.
Right-hand access models have the heat strip access
panel, external circuit breakers access panel and
internal controls access panel on the right side of the
unit. Left-hand access models are a mirror image of the
right-hand access models, and allow two wall-mount
units to be placed in relatively close proximity and yet
still allow complete access for maintenance and repair.
On side-by-side installations, maintain a minimum of
20" clearance on control side to allow access to control
panel and heat strips, and to allow proper airflow to the
outdoor coil. For installations where units are installed
with both control panels facing each other (inward),
maintain a minimum of 36" clearance to allow access.
Additional clearance may be required to meet local or
national codes.
Care should be taken to ensure that the recirculation
and obstruction of condenser discharge air does not
occur. Recirculation of condenser discharge air can
be from either a single unit or multiple units. Any
object such as shrubbery, a building or a large object
can cause obstructions to the condenser discharge air.
Recirculation or reduced airflow caused by obstructions
will result in reduced capacity, possible unit pressure
safety lockouts and reduced unit service life.
For units with blow through condensers, such as
these wall-mount units, it is recommended there be
a minimum distance of 10' between the front of the
unit and any barrier or 20' between the fronts of two
opposing (facing) units.
Clearances Required for Service Access and
Adequate Condenser Airflow
LEFT
MODELS
W18A, W24A, W30A, W36A15"20"10'
W18L, W24L, W30L, W36L20"15"10'
W42A, W48A, W60A, W72A20"20"10'
W42L, W48L, W60L, W72L20"20"10'
NOTE: For side-by-side installation of two units there must be
20" between units. This can be reduced to 15" by using a W**L
model (left side compressor and controls) for the left unit and
W**A (right side compressor and controls) for right unit.
See Specifications Sheet S3532.
SIDE
RIGHT
SIDE
DISCHARGE
SIDE
Clearance to Combustibles
!
WARNING
Fire hazard.
Maintain minimum 1/4" clearance between the
supply air duct and combustible materials in
the rst 3' of ducting.
Failure to do so could result in re causing
damage, injury or death.
The unit itself is suitable for 0" clearance, but the
supply air duct flange and the first 3' of supply air duct
require a minimum of 1/4" clearance to combustible
material. However, it is generally recommended that
a 1" clearance is used for ease of installation and
maintaining the required clearance to combustible
material. See Figures 4A-D on pages 9-12 for details
on opening sizes.
Minimum Clearances Required to
Combustible Materials
MODELS
W18A, L
W24A, L
W30A, L
W36A, L
W42A, L
W48A, L
W60A, L
W72A, L
SUPPLY AIR DUCT
FIRST 3'
0"0"
1/4"0"
1/4"0"
CABINET
Manual 2100-678
Page 6 of 24
FIGURE 2
Dimensions of Basic Unit for Architectural and Installation Requirements (Nominal)
All dimensions are in inches. Dimensional drawings are not to scale.
SUPPLYRETURN
(H)
ABCBEFGIJKLMNOPQRST
W**A
RIGHT
UNIT
W**L
LEFT
UNIT
5.88
E
O
Supply Air Opening
B
Return Air Opening
Back View
MIS-3889
W
Filter Access Panel
Ventilation Air
Condenser
Air Outlet
Front View
.44
Bottom Installation
Bracket
MIS-3889
1
5.88
F
G
MIS-3890
MIS-3890
R
S
S
S
S
S
T
Built In
Rain Hood
4° Pitch
2.13
A
I
C
K
D
1.250
Cond.
Air
Inlet
Side View
J
D
1.250
Cond.
Air
Inlet
Side View
2.13
A
C
K
J
Drain
Electric
Heat
I
Side Wall
Mounting
Brackets
(Built In)
Top Rain
Flashing
Shipping
Location
Optional
Electrical
H
Entrances
L
Heater
Access
Panel
C. Breaker/
Disconnect
Access Panel
(Lockable)
Standard flush
vent door for
non-ERV/CRV
Econ. models
Hood for
ECON models
only
7.000
Low Voltage
Electrical
Entrance
High Voltage
Electrical
Entrance
M
P
N
Q
Built In
Rain Hood
W
Hood for ECON
models only
Filter Access Panel
1
Standard
F
G
Ventilation Air
Condenser
flush vent
door for nonERV/CRV
Econ.
models
Air Outlet
4° Pitch
Heater
Access
Panel
Electric
Heat
C. Breaker/
Disconnect
Access Panel
(Lockable)
7.00
Low Voltage
Electrical
Entrance
High Voltage
Electrical
Entrance
Front View
E
O
Supply Air Opening
B
Return Air Opening
Back View
Side Wall
Mounting
Brackets
(Built In)
Top Rain
Flashing
Shipping
Location
Optional
Electrical
Entrances
H
L
M
P
N
Q
R
S
S
S
S
S
T
Drain
.44
Bottom
Installation
Bracket
Manual 2100-678
Page 7 of 24
WALL-MOUNT UNIT INSTALLATION
Mounting the Units
!
WARNING
Heavy item hazard.
Use more than one person to handle unit.
Failure to do so could result in unit damage or
serious injury.
NOTE: It may be best to spot some electrical knockouts
(such as those located on the back of the wallmount unit) before units are mounted and access is
unavailable or limited (see Figure 2 to locate prepunched knockouts).
Two holes for the supply and return air openings must
be cut through the wall as shown in Figures 4A-D on
pages 9-12. On wood frame walls, the wall construction
must be strong and rigid enough to carry the weight
of the unit without transmitting any unit vibration. All
walls must be thoroughly inspected to insure that they
are capable of carrying the weight of the installed unit.
In retrofit (unit replacement) installations, the openings
cut for the original equipment may not line up exactly
with needs of this installation. Modifications may need
to be made, such as increasing or decreasing the size
of the wall cutouts. The existing bolt placement may
not line up in which case the original bolts would need
to be removed or cut away.
1. These units are secured by wall mounting flanges
which secure the unit to the outside wall surface at
both sides. A bottom mounting bracket, attached
to skid for shipping, is provided for ease of
installation, but is not required.
2. The unit itself is suitable for 0" clearance, but the
supply air duct flange and the first 3' of supply
air duct require a minimum of 1/4" clearance to
combustible material. However, it is generally
recommended that a 1" clearance is used for
ease of installation and maintaining the required
clearance to combustible material. See Figures
4A-D for details on opening sizes.
3. Locate and mark lag bolt locations and location for
optional bottom mounting bracket, if desired (see
Figures 4A-D).
4. Mount bottom mounting bracket (if used).
5. If desired, hook top rain flashing (attached to frontright of supply flange for shipping) under back
bend of top.
6. Position unit in opening and secure with fasteners
sufficient for the application such as 5/16" lag/
anchor/carriage bolts; use 7/8" diameter flat washers
on the lag bolts. It is recommended that a bead
of silicone caulking be placed behind the side
mounting flanges.
7. Secure optional rain flashing to wall and caulk
across entire length of top (see Figures 4A-D).
8. For additional mounting rigidity, the return air
and supply air frames or collars can be drilled
and screwed or welded to the structural wall itself
(depending upon wall construction). Be sure to
observe required clearance if combustible wall.
9. A plastic drain hose extends from the drain pan at
the top of the unit down to the unit base. There are
openings in the unit base for the drain hose to pass
through. In the event the drain hose is connected
to a drain system of some type, it must be an open
or vented type system to assure proper drainage.
10. Install outdoor temperature/humidity sensor (see
Figure 3). Remove grommet from base and sensor.
Discard shipping bracket. Place sensor extension
through hole in base under condenser fan and
secure to base with screw.
FIGURE 3
Outdoor Sensor Installation
Manual 2100-678
Page 8 of 24
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.