Bard W48A23, W48L23, W60L23, W60A23 Installation Instructions Manual

INSTALLATION INSTRUCTIONS
WALL MOUNTED
P ACKAGE AIR CONDITIONERS
MODELS
W48A23 W48L23 W60A23 W60L23
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
Since 1914...Moving ahead just as planned.
Manual : 2100-594 Supersedes: NEW File: Volume III Tab 16 Date: 04-23-13
Manual 2100-594 Page 1 of 19
Contents
Getting Other Information and Publications 3 Wall Mount General Information
Wall Mount Model Nomenclature Shipping Damage
General .................................................................4
Duct Work Condensate Drain
Filters .................................................................5
Installation Instructions
Wall Mounting Information Mounting the Unit Clearances Required Wiring – Main Power
Wiring – Low Voltage Wiring
Start Up — R-410A
Figures
Figure 1 Unit Dimensions .......................................7
Figure 2 Unit Dimensions .......................................8
Figure 3 Unit Dimensions .......................................9
Figure 4 Unit Dimensions .....................................10
Figure 5 Wall Mounting Instructions .....................11
Figure 6 Wall Mounting Instructions .....................11
Figure 7 Common Wall Mounting Installations .....12
Figure 13 Fan Blade Setting ...................................17
.................................................................5
.....................................................4
....................................................5
......................................................6
................................................6
...............................................13
..............................4
........................................6
...................................13
General ...............................................................14
Topping Off System Charge Safety Practices Important Installer Note
High & Low Pressure Switch
Three Phase Scroll Compressor Phase Monitor Condenser Fan Operation Service Hints Sequence of Operation Compressor Control Module
Adjustments
Pressure Service Ports
Troubleshooting
Fan Blade Setting Dimensions Removal of Fan Shroud Refrigerant Charge
Tables
Table 1 Maximum ESP Electric Heat Only ...........6
Table 2 Fan Blade Dimensions ...........................17
Table 3 Rated CFM & ESP .................................17
Table 4 Indoor Blower Performance ...................17
Table 5 Cooling Pressure ....................................18
Table 6 Electrical Specications W**A/L .............18
Table 7 Optional Accessories ..............................19
Table 8 Electric Heat ...........................................19
......................................................14
.........................................................15
...........................................................15
............................................................16
.................................................17
....................................14
...........................................15
...................................15
.............................15
......................................15
...........................................16
...................................16
...........................................16
................................17
..........................................17
Manual 2100-594 Page 2 of 19
GETTING OTHER INFORMATION AND PUBLICATIONS
These publications can help you install the air
conditioner or heat pump. You can usually nd these
at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code .......................ANSI/NFPA 70
Standard for the Installation ............... ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for W arm Air .......................ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for ......................... ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for Residential ...............ACCA Manual D
Winter and Summer Air Conditioning and Equipment Selection
FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:
ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute 11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc. 1791 Tullie Circle, N.E.
Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manual 2100-594 Page 3 of 19
WALL MOUNT GENERAL INFORMATION
AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE
W 48 A 2 3 A 10 B X X X X A
MODEL NUMBER
CAPACITY
48 - 4 Ton 60 - 5 Ton
A - Air Conditioner L - Left Hand Air Conditioner
3 - 3 Ton Air Openings on 5 Ton Cabinet
NOTE: Vent option B is without exhaust capability. May require separate eld supplied barometric relief in building.
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
REVISIONS
KW
VOLTS & PHASE
A - 230/208/60/1
VENTILATION OPTIONS
B - Blank-off Plate
FILTER OPTIONS
X - No Filters Required
COLOR OPTIONS
X - Beige (Standard) 1 - White 4 - Buckeye Gray 5 - Desert Brown 8 - Dark Bronze
OUTLET OPTIONS
X - Front (Standard)
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
CONTROL MODULES
(See Spec. Sheet S3402)
COIL OPTIONS
X - Standard 1 - Phenolic Coated Evaporator 2 - Phenolic Coated Condenser 3 - Phenolic Coated Evaporator and Condenser
While these instructions are intended as a general
GENERAL
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 3 for information on codes and standards.
Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
Manual 2100-594 Page 4 of 19
DUCT WORK
CONDENSATE DRAIN
All duct work, supply and return, must be properly
sized for the design airow requirement of the
equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
Refer to Maximum ESP of operation Electric Heat Table.
Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
For model series W48 and W60, a 1/4 inch clearance
to combustible material for the rst three feet of duct
attached to the outlet air frame is required. See Wall Mounting Instructions and Figures for further details.
Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.
A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.
FILTERS
NOTE: W48A23, W48L23, W60A23 and W60L23 models
require the use of a return air lter grille.
Some installations may not require any return air duct. A metallic return air grille is required with installations not requiring a return air duct. The spacing between louvers on the grille shall not be larger than 5/8 inch.
Any grille that meets with 5/8 inch louver criteria may be used. It is recommended that Bard Return Air Grille Kit RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used. Contact distributor or factory for ordering information. If using a return air
lter grille, lters must be of sufcient size to allow a
maximum velocity of 400 fpm.
NOTE: If no return air duct is used, applicable installation codes may limit this cabinet to installation only in a single story structure.
Manual 2100-594 Page 5 of 19
INSTALLATION INSTRUCTIONS
WALL MOUNTING INFORMATION
1.
T wo holes for the supply and return air openings must be cut through the wall as shown in Figure 1 or 2. Figure 1 is for models W48A23 and W60A23.
2. On wood frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration.
WARNING
Fire hazard can result if 1/4 inch clearance to
combustible materials for supply air duct is not
maintained.
3. Concrete block walls must be thoroughly inspected
to insure that they are capable of carrying the weight of the installed unit.
WARNING
Failure to provide the 1/4 inch clearance between the supply duct and a combustible
surface for the rst 3 feet of duct can result in re causing damage, injury or death.
8. For additional mounting rigidity, the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance if combustible wall.
9. On side by side installations, maintain a minimum of 20 inches clearance on right side to allow access to control panel and heat strips, and to allow proper
airow to the outdoor coil. Additional clearance
may be required to meet local or national codes.
MOUNTING THE UNIT
1. These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides. A bottom mounting bracket is provided for ease of installation, but is not required.
2.
The unit itself is suitable for 0 inch clearance, but the
supply air duct ange and the rst 3 feet of supply air duct
require a minimum of 1/4 inch clearance to combustible material. If a combustible wall, use a minimum of 30½" x 10½" dimensions for sizing. However, it is generally recommended that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material. The supply air opening would then be 32" x 12".
3. Locate and mark lag bolt locations and bottom mounting bracket location.
4. Mount bottom mounting bracket.
5.
Hook top rain ashing under back bend of top. Top rain ashing is shipped secured to the right side of the back.
6.
Position unit in opening and secure with 5/16 lag bolts;
use 7/8 inch diameter at washers on the lag bolts.
7. Secure rain ashing to wall and caulk across entire
length of top.
Clearances Required for Service Access
and Adequate Condenser Airow
MODELS LEFT SIDE RIGHT SIDE
W48A, W60A 20" 20" W48L, W60L 20" 20"
NOTE: For side by side installation of two (2) W**A models there must be 20" between units. This can be reduced to 15" by using a W**L model (left side compressor and controls) for the left unit and WA (right side compressor and controls) for right unit.
See W**A / W**L Specication S3402.
TABLE 1
MAXIMUM ESP OF OPERATION
ELECTRIC HEAT ONLY
MODELS ESP
W60A23 - ONLY W60L23 - ONLY
VALUES SHOWN ARE FOR UNITS EQUIPPED WITH STANDARD 1" THROWAWAY FILTERS OR 1" WASHABLE FILTERS. DERATE ESP BY .15 FOR 2" PLEATED FILTERS.
A05 A10
.4 .3
Manual 2100-594 Page 6 of 19
Loading...
+ 13 hidden pages