Bard W42L User Manual

INSTALLATION INSTRUCTIONS
WALL MOUNTED
PACKAGE AIR CONDITIONERS
MODELS W18A1 W18L1 W24A1 W24L1 W30A1 W30L1 W36A1 W36L1 W42A1 W42L1 W48A1 W48L1 W60A1 W60L1 W70A1 W70L1
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
Since 1914...Moving ahead just as planned.
Manual : 2100-508A Supersedes: 2100-508 File: Volume III Tab 16 Date: 02-10-09
© Copyright 2008
Manual 2100-508A Page 1 of 25
Contents
Getting Other Information and Publications 3
Wall Mount General Information
Wall Mount Model Nomenclature ............................ 4
Shipping Damage .................................................... 4
General ................................................................ 4
Duct Work ................................................................ 5
Filters ................................................................ 5
Fresh Air Intake ....................................................... 5
Condensate Drain .................................................... 5
Installation Instructions
Wall Mounting Information ....................................... 6
Mounting the Unit .................................................... 6
Clearances Required ............................................... 6
Minimum Clearances ............................................... 6
Wiring – Main Power ............................................. 14
Wiring – Low Voltage Wiring ................................. 14
Figures
Figure 1 Fresh Air Damper Assembly ................... 5
Figure 2 Unit Dimensions ...................................... 7
Figure 3A Mounting Instructions .............................. 8
Figure 3B Figure 3C
Figure 4 Electric Heat Clearance .........................11
Figure 5 Wall Mounting Instructions .................... 12
Figure 6 Wall Mounting Instructions .................... 12
Figure 7 Common Wall Mounting Installations .... 13
Figure 8 Fan Blade Setting ................................. 18
Mounting Instructions - W18, 24, 30, 36 .... 9
Mounting Instructions - W42, 48, 60, 70 ... 10
Start Up
General .............................................................. 15
Topping Off System Charge ................................... 15
Safety Practices ..................................................... 15
Important Installer Note ......................................... 16
High Pressure Switch ............................................ 16
Three Phase Scroll Compressor............................ 16
Phase Monitor ....................................................... 16
Condenser Fan Operation ..................................... 16
Service Hints ......................................................... 16
Sequence of Operation .......................................... 17
Compressor Control Module .................................. 17
Adjustments ........................................................... 17
Pressure Service Ports .......................................... 17
Troubleshooting
Fan Blade Setting Dimensions .............................. 18
Removal of Fan Shroud ......................................... 18
Refrigerant Charge ................................................ 18
Tables
Table 1 Fan Blade Dimensions .......................... 18
Table 2A Refrigerant Charge ............................... 18
Table 2B Refrigerant Charge ............................... 18
Table 3 Cooling Pressure .................................. 19
Table 4 Electrical Specifications W**A .............. 20
Table 5 Electrical Specifications W**L ............... 21
Table 6 Recommended Airflow .......................... 22
Table 7 Indoor Blower Performance .................. 22
Table 8 Maximum ESP Electric Heat Only........ 22
Table 9 Electric Heat ......................................... 23
Table 10 Optional Accessories ............................ 24
Table 11 Vent & Control Options ......................... 25
Manual 2100-508A Page 2 of 25
GETTING OTHER INFORMATION AND PUBLICATIONS
These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation .............. ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ...................... ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for ............................ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for Residential .............. ACCA Manual D
Winter and Summer Air Conditioning and Equipment Selection
FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute
11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigeration
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association
Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manufactured under the following
U.S. Patent numbers:
5,485,878; 5,301,777; 5,002,116; 4,924,934;
4,875,520; 4,825,936
Manual 2100-508A Page 3 of 25
WALL MOUNT GENERAL INFORMATION
AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE
W 42 A 1– A 10 X X X X X A
MODEL NUMBER
CAPACITY
½
Ton
18 - 1 24 - 2 Ton
½ Ton
30 - 2 36 - 3 Ton 42 - 3½ Ton 48 - 4 Ton 60 - 5 Ton 70 - 6 Ton
NOTE: Vent options X, B and M are without exhaust capability. May require separate field supplied barometric relief in building.
A - Right Hand Air Conditioner L - Left Hand Air Conditioner
VENTILATION OPTIONS
X - Barometric Fresh Air Damper (Standard) B - Blank-off Plate M - Motorized Fresh Air Damper V - Commercial Ventilator - Motorized with Exhaust E - Economizer (Internal) - Fully Modulating with Exhaust R - Energy Recovery Ventilator - Motorized with Exhaust
(See Spec. Sheet S3397)
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
REVISIONS
VOLTS & PHASE
A - 230/208/60/1 B - 230/208/60/3 C - 460/60/3
KW
COLOR OPTIONS
X - Beige (Standard) 1 - White 2 - Mesa Tan 4 - Buckeye Gray 5 - Desert Brown 6 - Dark Bronze A - Aluminum S - Stainless Steel
FILTER OPTIONS
X - One Inch Throwaway (Standard) W - One Inch Washable P - Two Inch Pleated
OUTLET OPTIONS
X - Front (Standard) T - Top Outlet (W30A, W36A Only)
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
CONTROL MODULES
(See Spec. Sheet S3397)
COIL OPTIONS
X - Standard 1 - Phenolic Coated Evaporator 2 - Phenolic Coated Condenser 3 - Phenolic Coated Evaporator
and Condenser
While these instructions are intended as a general
GENERAL
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 3 for information on codes and standards.
Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
Manual 2100-508A Page 4 of 25
DUCT WORK
All duct work, supply and return, must be properly sized for the design airflow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
Refer to Maximum ESP of operation Electric Heat Table 6.
FILTERS
A 1-inch throwaway filter is standard with each unit. The filter slides into position making it easy to service. This filter can be serviced from the outside by removing the filter access panel. A 1-inch washable filter and 2­inch pleated filter are also available as optional accessories. The internal filter brackets are adjustable to accommodate the 2-inch filter by bending two (2) tabs down on each side of the filter support bracket.
Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
Models W18 & W24 as approved for zero inch clearance to the supply duct. For model series W30, W36, W42, W48, W60 and W70 a 1/4 inch clearance to combustible material for the first three feet of duct attached to the outlet air frame is required. See Wall Mounting Instructions and Figures 3 and 4 for further details.
Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.
Some installations may not require any return air duct. A metallic return air grille is required with installations not requiring a return air duct. The spacing between louvers on the grille shall not be larger than 5/8 inch.
Any grille that meets with 5/8 inch louver criteria may be used. It is recommended that Bard Return Air Grille Kit RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used. Contact distributor or factory for ordering information. If using a return air filter grille, filters must be of sufficient size to allow a maximum velocity of 400 fpm.
FRESH AIR INTAKE
All units are built with fresh air inlet slots punched in the service door.
If the unit is equipped with a fresh air damper assembly, the assembly is shipped already attached to the unit. The damper blade is locked in the closed position. To allow the damper to operate, the maximum and minimum blade position stops must be installed. See Figure 1.
All capacity, efficiency and cost of operation information is based upon the fresh air blank-off plate in place and is recommended for maximum energy efficiency.
The blank-off plate is available upon request from the factory and is installed in place of the fresh air damper shipped with each unit.
CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.
NOTE: If no return air duct is used, applicable installation
codes may limit this cabinet to installation only in a single story structure.
FIGURE 1
FRESH AIR DAMPER
Manual 2100-508A Page 5 of 25
INSTALLATION INSTRUCTIONS
WALL MOUNTING INFORMATION
1. Two holes for the supply and return air openings must be cut through the wall as shown in Figure 3.
2. On wood frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration.
3. Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installed unit.
MOUNTING THE UNIT
1. These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides. A bottom mounting bracket, attached to skid for shipping, is provided for ease of installation, but is not required.
2. The unit itself is suitable for 0 inch clearance, but the supply air duct flange and the first 3 feet of supply air duct require a minimum of 1/4 inch clearance to combustible material for model series W30, W36, W42, W48, W60 and W70. However, it is generally recommended that a 1-inch clearance is used for ease of installation and maintaining the required clearance to combustible material. See Figure 3 for details on opening sizes.
3. Locate and mark lag bolt locations and bottom mounting bracket location. See Figure 3.
WARNING
Failure to provide the 1/4 inch clearance between the supply duct and a combustible surface for the first 3 feet of duct can result in fire causing damage, injury or death.
6. Position unit in opening and secure with 5/16 lag bolts; use 7/8 inch diameter flat washers on the lag bolts.
7. Secure rain flashing to wall and caulk across entire length of top. See Figure 3.
8. For additional mounting rigidity, the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance if combustible wall.
9. On side-by-side installations, maintain a minimum of 20 inches clearance on right side to allow access to control panel and heat strips, and to allow proper airflow to the outdoor coil. Additional clearance may be required to meet local or national codes.
4. Mount bottom mounting bracket.
5. Hook top rain flashing, attached to front - right of supply flange for shipping, under back bend of top.
sseccAecivreSrofderiuqeRsecnaraelC
wolfriAresnednoCetauqedAdna
SLEDOM EDISTFEL EDISTHGIR
A63W,A03W,A42W,A81W "51 "02
L63W,L03W,L42W,L81W "02 "51
A07W,A06W,A84W,A24W "02 "02
L07W,L06W,L84W,L24W "02 "02
NOTE: For side by side installation of two (2) W**A models there must be 20" between units. This can be reduced to 15" by using a W**L model (left side compressor and controls) for the left unit and WA (right side compressor and controls) for right unit.
See W**A Specification S3397 & W**L Specification S3400.
Manual 2100-508A Page 6 of 25
otderiuqeRsecnaraelCmuminiM
slairetaMelbitsubmoC
SLEDOM
L,A42W/L,A81W"0"0 L,A63W/L,A03W"4/1"0 L,A84W/L,A24W
L,A07W/L,A06W
TCUDRIAYLPPUS
TEEFEERHTTSRIF
"4/1"0
TENIBAC
FIGURE 2
HTDIW
HTPED
LEDOM
)W(
)D(
L,A81W
003.33521.71365.0788.788.9188.1188.9100.5300.1157.5265.0257.6260.8252.9200.7236.231.4360.2255.0191.400.2100.5
L,A42W L,A03W
002.83521.71365.0788.788.7288.3188.7200.0400.1157.5239.7157.6257.8252.9200.7257.291.9357.2241.991.400.2100.5
L,A63W
THGIEH
)H(
L,A24W L,A84W
570.24234.22578.4888.988.9288.5188.9288.3436.3166.1300.0386.2349.6296.4334.2373.388.2488.3200.0100.200.6188.1
L,A06W L,A07W570.24234.22578.4988.988.9288.5188.9288.3436.3166.1400.0386.2449.6396.4434.2473.388.2488.3300.0100.200.6188.1
All dimensions are in inches. Dimensional drawings are not to scale.
W**A RIGHT
W
UNIT
5.75
F
G
Condenser
Air Outlet
YLPPUSNRUTER
AB C B E F G I J K L MNO P QRST
E
Built In
Rain Hood
4° Pitch
Heater
Access
Panel
Electric
C. Breaker/ Disconnect
Access Panel
(Lockable)
Filter Access Panel
Vent Option Door
Ventilation Air
Low Voltage
Electrical Entrance
High Voltage
Electrical Entrance
Heat
D
Cond.
Air
Inlet
7.88
2
2
1.00
2.13 Side Wall
A
Mounting
Brackets
(Built In)
I
Top Rain
Flashing Shipping Location
Optional
C H
Electrical
Entrances
K
J
L
M
P
O
2
31.88
Supply Air Openi ng
B
Return Air Openi ng
.44
)lanimoN(stnemeriuqeRnoitallatsnIdnalarutcetihcrAroftinUcisaBfosnoisnemiD
R
S
S
S
1
S
1
S
Front View
Side View
Drain
1 Dimension is 21.00 inches on W70A & W70L models. 2 Optional top outlet (factory installed only) for W30A and W36A models only.
W**L LEFT UNIT
R
S
S
S
S
S
T
1
1
Drain
.44
Supply Air Openi ng
Return Air Openi ng
Bottom
Installation
Bracket
E O
Back View
9.06
Side Wall Mounting Brackets (Built In)
Top Rain
Flashing Shipping Location
Optional Electrical Entrances
M
P
2.63
D
2.13 A
I
C
H
K
L
Cond.
J
Air
Inlet
Built In Rain Hood 4° Pitch
Electric Heat
Heater Access Panel
C. Breaker/ Disconnect Access Panel (Lockable)
Filter Access
Low Voltage Electrical Entrance
High Voltage Electrical Entrance
N
Panel
Ventilation
Vent Option
Door
T
W
Bottom Installation Bracket
MIS-2487 B
5.75
F
G
Back View
Q
Air
Condenser
Air Outlet
Front ViewSide View
MIS-2488 B
Manual 2100-508A Page 7 of 25
1/4" CLEARANCE ON ALL
FOUR SIDES OF SUPPLY
MIS-353 C
MATERIALS
AIR DUCT IS REQUIRED
FROM COMBUSTABLE
WALL STRUCTURE
FOAM AIR SEAL
RAIN FLASHING
SUPPLIED
FIGURE 3A
SEAL WITH BEAD
OF CAULKING ALONG
TOP
ENTIRE LENGTH OF TOP.
MOUNTING INSTRUCTIONS
W18A1, W18L1, W24A1, W24L1
WALL
DUCT
SUPPLY AIR
PANEL
HEATER ACCESS
8"
NOTES:
THE SIDE MOUNTING FLANGES AND UNDER
SILICONE CAULKING BE PLACED BEHIND
IT IS RECOMMENDED THAT A BEAD OF
RETURN AIR
OPENING
CONTROLS AND HEATER ACCESS
W**A UNIT SHOWN, W**L UNIT
TOP FLASHING AT TIME OF INSTALLATION.
IS ON OPPOSITE (LEFT) SIDE.
Right Side View
"
1
2
20
12"
1"
Manual 2100-508A Page 8 of 25
"
1
16
20"
Supply Opening
" 7
1
16
7
12"
"
13
16
3
12"
Return Opening
12"
20"
12"
"
1
8
3
4"
Typ.
1"
4"
3"
"
7
8
12"
Typ.
2" 2"
Wall Opening and Hole Location View
5"
Loading...
+ 17 hidden pages