Bard W30AAPA, W18AAPA, W30AAPB, W30AAPC, W36AAEA Installation Instructions Manual

...
MULTI-TEC® Wall-Mount Air Conditioner/
WR Series Wall-Mount Air Conditioner/
LC6000-100 Controller
Free Cooling Unit System
MULTI-TEC Wall-Mount Units
W18AAPA W24AAPA W24AAPB W24AAPC W30AAPA W30AAPB W30AAPC W36AAEA W36AAEB W36AAEC W36AAMA W36AAMB W36AAMC W36AAPA
W36AAPB W36AAPC W42AAEA W42AAEB W42AAEC W42AAPA W42AAPB W42AAPC W48AAEA W48AAEB W48AAEC W48AAEQ W48AAMA W48AAMB
W48AAMC W48AAPA W48AAPB W48AAPC W48AAPQ W60AAEA W60AAEB W60AAEC W60AAEQ W60AAMA W60AAMB W60AAMC W60AAPA W60AAPB
W60AAPC W60AAPQ W72ABEA W72ABEB W72ABEC W72ABEQ W72ABMA W72ABMB W72ABMC W72ABPA W72ABPB W72ABPC W72ABPQ
W18LAPA W24LAPA W24LAPB W30LAPA W30LAPB W30LAPC W36LAPA W36LAPB W36LAPC W42LAPA W42LAPB W42LAPC W48LAPA W48LAPB
WR Series Wall-Mount Units
WR36APA WR36APB WR58APA WR58APB
W48LAPC W48LAPQ W60LAPA W60LAPB W60LAPC W60LAPQ W72LBPA W72LBPB W72LBPC W72LBPQ
NOTE: LC6000 controller is required for operation when multiple MULTI-TEC
and/or WR Series wall-mount units are used.
Bard Manufacturing Company, Inc. Bryan, Ohio 43506 www.bardhvac.com
Manual: 2100-676B Supersedes: 2100-676A Date: 4-6-18
Page 1 of 88
IMPORTANT
This installation instructions manual is separated into two sections. The first section of the manual explains the installation and set up of MULTI-TEC wall-mount units with an LC6000 controller. The second section explains the installation and set up of WR Series wall-mount units with an LC6000 controller. Check wall-mount unit model number information (found on the model/serial tag) prior to beginning the installation to ensure the proper instructions are being followed.
MULTI-TEC/LC6000 system installation instructions begin on page 3. Proceed to page 47 for WR Series/LC6000 system installation instructions.
SECTION 1:
MULTI-TEC/LC6000
INSTALLATION
INSTRUCTIONS
Page 3 of 88
CONTENTS
MULTI-TEC/LC6000 INSTALLATION/SET UP
General Information ...........................................5
List of Necessary Materials/Tools ....................8
Site Preparation ...................................................9
Model Identification .......................................... 9
New Shelter Installation vs. Retrofit Installation .. 9
Minimum Clearance .......................................... 9
Clearance to Combustibles ................................ 9
Wall-Mount Unit Mounting ..............................11
Mounting the Units ......................................... 11
Supply Air Grill Installation .................................... 12
Wall-Mount Unit Wiring ...................................19
Main Power Wiring .......................................... 19
Low Voltage Wiring ......................................... 19
Preliminary Start Up .........................................23
Running in Stand Alone (Orphan) Mode ............ 23
LC6000 Controller Installation ........................24
LC6000 Controller .......................................... 25
Mounting the LC Controller ....................... 25
Installing Remote Indoor
Temperature/Humidity Sensor(s) ................ 26
FIGURES AND TABLES
Figure 1 MULTI-TEC Model Nomenclature .............8
Figure 2 Dimensions .......................................... 10
Figure 3 Outdoor Sensor Installation
Figure 4A W18/24 Mounting Instructions ..............12
Figure 4B W30/36 Mounting Instructions ..............13
Figure 4C W42/48 Mounting Instructions ..............14
Figure 4D W60/72 Mounting Instructions ..............15
Figure 5 Electric Heat Clearance ......................... 16
Figure 6 Wall Mounting Instructions .................... 16
Figure 7 Wall Mounting Instructions .................... 17
Figure 8 Common Wall Mounting Installations ...... 18
Figure 9 Circuit Routing Label ............................ 19
Figure 10 WIRING: VAC Supply Wiring
Landing Points .....................................19
Figure 11 Cooling and Heating Setpoints ...............23
Figure 12 Typical LC6000 Component Location ..... 24
Figure 13 LC6000 Fused Power Supply Terminal ... 24 Figure 14 Remote Indoor Temperature/Humidity
Sensor Installation ................................26
Figure 15 Additional Remote Sensor Installation ....27
Figure 16 Smoke Detector, Hydrogen Detector
and Generator Run Connections .............28
Figure 17 Communication Wiring (Daisy Chain) ......29
Figure 18 Communication Wiring (Alt. Method) ......29
Figure 19 Placement of Communication Filters ......30
Figure 20 Communication Wiring: Termination
at the Controller ...................................31
Figure 21 Communication Wiring: Termination
at the First Wall-Mount Unit ..................32
Figure 22 Communication Wiring: Termination
at Additional Wall-Mount Units ..............33
Figure 23 LC6000 Controller Circuit Install ...........34
....................
11
Smoke. Hydrogen and Generator Alarms ..... 28
Communication Wiring .............................. 29
Supply Wiring .......................................... 34
System Set Up ....................................................37
TEC-EYE Hand-Held Diagnostic Tool ................ 37
TEC-EYE Status Screen ............................ 38
Setting Up Wall-Mount Units for Operation ....... 38
1. Address Each Wall-Mount Unit .............. 38
2. Execute a Run Test on Each Unit ........... 38
3. Clear Unit Alarm Logs on Each Unit ....... 39
Setting Up LC6000 for Operation .................... 39
4. Set LC Controller Date and Time ............ 39
5. Configure Sensors................................. 40
6. Enter Total Number of Units .................. 42
7. Verify Units are Online .......................... 42
8. Clear Controller Alarm Logs ................... 43
9. Complete Installation ............................ 43
Additional Information ....................................44
Menu Screens and Password Levels.................. 44
Setpoints ....................................................... 44
Calibrating Sensors ......................................... 44
Figure 24 Controller Grounding Posts ....................34
Figure 25 WIRING: LC6000 Wiring Diagram ..........36
Figure 26 TEC-EYE Connection to Unit Control ......37
Figure 27 TEC-EYE Display and Interface ..............37
Figure 28 Unit Configuration ................................38
Figure 29 Executing Run Test ............................... 39
Figure 30 Clearing Unit Alarm Logs .......................39
Figure 31 Setting Controller Date and Time ............ 40
Figure 32 Enable/Disable Zone 1 Indoor
Humidity Sensor ...................................40
Figure 33 Figure 34 Enable/Disable Zone 2 Indoor
Humidity Sensor ...................................41
Figure 35 Enable/Disable Zone 3 Indoor
Humidity Sensor ...................................41
Figure 36 Enable/Disable Zone 1 Indoor
Temperature Sensor .............................. 41
Figure 37 Enable/Disable Zone1 Remote
Temperature Sensor .............................. 41
Figure 38 Enable/Disable Zone 2 Remote
Temperature Sensor .............................. 42
Figure 39 Enable/Disable Zone 3 Remote
Temperature Sensor .............................. 42
Figure 40 Total Units Displayed ............................ 42
Figure 41 Clearing LC6000 Alarm Logs .................43
Figure 42 Adjusting Sensor Offset Value ................44
Table 1 W**A*P Series Electrical Specifications .20 Table 2 W**L*P Series Electrical Specifications ..21 Table 3 W**A*E Series Electrical Specifications .22
Table 4 LC6000-100 Terminal Block Index ........ 35
Table 5 LC6000/TEC-EYE Passwords (Default) ....37
Table 6 MULTI-TEC Unit Status Messages .......... 45
Table 7 LC6000 Status Messages ......................45
LC6000 Controller Display and Interface
...40
Manual 2100-676B Page 4 of 88
GENERAL INFORMATION
Free Cooling Unit System
This Bard Free Cooling Unit System is composed of MULTI-TEC wall-mounted air conditioners matched with an LC6000 supervisory controller or Bard th­TUNE stand-alone controller. If only one wall-mounted air conditioner is being used, it can be matched with either the LC6000 supervisory controller or a th-TUNE stand-alone controller. If more than one wall mount is installed, the LC6000 controller must be matched with the air conditioning units. The wall-mount units are specifically engineered for telecom/motor control center rooms.
NOTE: The LC6000 supervisory controller and
MULTI-TEC wall-mount units are designed specifically to work together. The controller cannot run other brands of systems, nor can other controllers run the MULTI-TEC wall-mount units. They are a complete system, and must be used together.
LC6000 Series
Wall-Mount Air Conditioner Units
The
MULTI-TEC cooling airflow in freecooling mode with ability to exhaust the same amount through the unit itself without any additional relief openings in the shelter.
MULTI-TEC units are available with optional electric heat and/or dehumidification.
units
will supply 100% of rated
Controller
LC6000 controller and accessories included shown below.
General
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
TEC-EYETM Hand-Held Diagnostic Tool Bard P/N 8301-059
LC6000 Series Programmable Logic Controller
* One remote temperature/humidity sensor and 35' of 5-wire shielded cable are included with the LC6000
controller. If the site in which the LC6000 controller will be used has more than one zone (maximum three zones per LC6000), additional remote temperature/humidity sensors (one sensor per zone) will need to be purchased and installed in the additional zones. One additional temperature-only sensor (Bard P/N 8301-
058) may also be used in Zone 1 but will also need to be purchased separately. Temperature-only sensors require field-supplied 2-wire shielded cable with drain.
Remote Temperature/
Humidity Sensor*
(with 35' shielded cable)
Bard P/N 8403-079
Communication
EMI Filters
Bard P/N 8301-055
Single Unit Operation
A th-TUNE stand-alone controller (Bard P/N 8403-088) can be used in place of the LC6000 controller when only one MULTI-TEC wall-mount air conditioner is being installed. If using a th-TUNE stand-alone controller instead of the LC6000 controller, the alarm logging and remote communication capabilities of the LC6000 controller will not be available. See th-TUNE manual 2100-678 for information on installing and setting up a th-TUNE stand-alone controller for single unit operation. A TEC-EYE hand-held diagnostic tool is required to program the wall-mount unit for th-TUNE stand-alone controller operation. The th-TUNE stand-alone controller and TEC-EYE diagnostic tool are available as a kit (Bard P/N 8620-264).
Manual 2100-676B Page 5 of 88
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly any tags and/or labels attached to the equipment.
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Additional Publications for information on codes and standards.
Sizing of systems for proposed installation should be based on heat loss and heat gain calculations made according to methods of Air Conditioning Contractors of America (ACCA). The supply flange should be installed in accordance with the Standards of the National
Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with
instructions, installer should adhere to local codes.
Shipping Damage
Upon receipt of equipment, the cartons should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
These units must remain in upright position at all times.
Additional Publications
These publications can help when installing the furnace. They can usually be found at the local library or purchased directly from the publisher. Be sure to consult the current edition of each standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation of Air Conditioning
and Ventilating Systems ...................ANSI/NFPA 90A
Standard for Warm Air Heating
and Air Conditioning Systems ............ANSI/NFPA 90B
Load Calculation for Residential Winter
and Summer Air Conditioning ............. ACCA Manual J
For more information, contact these publishers:
Air Conditioning Contractors of America (ACCA) 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
American National Standards Institute (ANSI) 11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc. (ASHRAE)
1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
National Fire Protection Association (NFPA) Batterymarch Park P. O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manual 2100-676B Page 6 of 88
ANSI Z535.5 Definitions:
DANGER: Indicate[s] a hazardous situation which, if
not avoided, will result in death or serious injury. The signal word “DANGER” is to be limited to the most extreme situations. DANGER [signs] should not be used for property damage hazards unless personal injury risk appropriate to these levels is also involved.
WARNING: Indicate[s] a hazardous situation which, if not avoided, could result in death or serious injury. WARNING [signs] should not be used for property damage hazards unless personal injury risk appropriate to this level is also involved.
CAUTION: Indicate[s] a hazardous situation which, if not avoided, could result in minor or moderate injury. CAUTION [signs] without a safety alert symbol may be used to alert against unsafe practices that can result in property damage only.
NOTICE: [this header is] preferred to address practices not related to personal injury. The safety alert symbol shall not be used with this signal word. As an alternative to “NOTICE” the word “CAUTION” without the safety alert symbol may be used to indicate a message not related to personal injury.
!
WARNING
Electrical shock hazard.
Have a properly trained individual perform these tasks.
Failure to do so could result in electric shock or death.
!
WARNING
Fire hazard.
Maintain minimum 1/4" clearance between the
supply ange and combustible materials.
Failure to do so could result in re causing damage, injury or death.
!
WARNING
Heavy item hazard.
Use more than one person to handle unit.
Failure to do so could result in unit damage or serious injury.
!
CAUTION
Cut hazard.
Wear gloves to avoid contact with sharp edges.
Failure to do so could result in personal injury.
Manual 2100-676B Page 7 of 88
LIST OF NECESSARY MATERIALS/TOOLS
Additional hardware and miscellaneous supplies are needed for installation. These items are field supplied and must be sourced before installation. This list also includes tools needed for installation.
List of Materials/Tools
Personal protective equipment/safety devices/anti­static wrist straps
Supply and return grilles
Field-fabricated sleeves (if necessary)
Fasteners sufficient for mounting the units such as 5/16" diameter anchor/lag bolts
7/8" diameter washers
Fasteners appropriate for the shelter wall construction to attach the controller to the wall
Commercial grade outdoor silicone sealant
Miscellaneous hand and power tools and jobsite or shop materials
Lifting equipment with the necessary capacity and rigging to safely move/install the systems
Electrical supplies
- Various size circuit breakers for the shelter AC breaker box (see Tables 1, 2 and 3 on pages 20, 21 and 22)
- High-voltage wire of various gauges (see Tables 1, 2 and 3)
-
16 gauge minimum, 14 gauge maximum power wire to connect controller to shelter power source
-
5-wire, 18 gauge shielded cable for remote temperature and humidity sensors (2-wire, 18 gauge shielded cable for temperature-only sensors)
- Communication wire: 2-wire, 18 gauge, shielded with drain
- 18 gauge non-shielded wire for connecting smoke detector, hydrogen detector and/or generator, if applicable, to controller
-
CAT 6 Ethernet cable of field-determined length (for remote communication, if applicable)
-
2 hole grounding lug (to be used with supplied 1/4" bolts and nuts for grounding controller box)
- Miscellaneous electrical supplies including rigid/ flexible conduit and fittings, 2" x 4" junction boxes (one per temperature/humidity sensor), wire connectors and supports
MULTI-TEC Wall-Mount Unit Model Nomenclature
W 36 A A P A 10 5 X X X X E
MODEL SERIES
CAPACITY
18 – 1½ Ton
24 – 2 Ton
30 – 2½ Ton
36 – 3 Ton
M – PLC Logic Board w/Mechanical Dehumidification 
Reference Supplemental Instructions
7960-801 for complete details.
42 – 3½ Ton
48 – 4 Ton 60 – 5 Ton 72 – 6 Ton
A – Right Hand
L – Left Hand
REVISION
E – PLC Logic Board w/Electric Reheat
P – PLC Logic Board
A – 230/208/60/1 B – 230/208/60/3 C – 460/60/3 D – 240/220/50/1
VOLTS & PHASE
E – 240/220/50/3 or 220/200/50/3 F – 415/380/50/3 Q – 575/60/3
FIGURE 1
KW
VENTILATION OPTIONS
B – Blank-off Plate 5 – Economizer
CONTROL MODULES
E – Low Ambient Control C – Low Ambient Control & Crank Case Heater
COIL OPTIONS
X – Standard 1 – Phenolic Coated Evaporator 2 – Phenolic Coated Condenser 3 – Phenolic Coated Evaporator and Condenser
SUPPLY AIR OUTLET
X – Front (Standard)
COLOR OPTIONS
X – Beige (Standard) 1 – White 4 – Buckeye Gray
FILTER OPTIONS
X – 1" Throwaway (Standard) W – 1" Washable P – 2" Pleated (MERV 8)
Manual 2100-676B Page 8 of 88
SITE PREPARATION
Model Identification
Identify the specific model using the model nomenclature information found in Figure 1 and the model/serial tag found on the unit. See Figure 2 on page 11 for dimensions and critical installation
requirements.
New Shelter Installation vs. Retrofit Installation
These installation instructions cover both new shelter installations and retrofit installations. Each installation is unique and may require special accommodations and modifications. Although Bard Manufacturing follows a long-established tradition of manufacturing equipment using industry standard dimensions for building penetration, it is occasionally necessary to move or enlarge supply and return openings when replacing non-standardized equipment in a retrofit application.
Minimum Clearance
Wall-mount air conditioners are available in both right­hand access models and left-hand access models. Right-hand access models have the heat strip access panel, external circuit breakers access panel and internal controls access panel on the right side of the unit. Left-hand access models are a mirror image of the right-hand access models, and allow two wall-mount units to be placed in relatively close proximity and yet still allow complete access for maintenance and repair.
On side-by-side installations, maintain a minimum of 20" clearance on control side to allow access to control panel and heat strips, and to allow proper airflow to the outdoor coil. For installations where units are installed with both control panels facing each other (inward), maintain a minimum of 36" clearance to allow access. Additional clearance may be required to meet local or national codes.
Care should be taken to ensure that the recirculation and obstruction of condenser discharge air does not occur. Recirculation of condenser discharge air can be from either a single unit or multiple units. Any object such as shrubbery, a building or a large object can cause obstructions to the condenser discharge air. Recirculation or reduced airflow caused by obstructions will result in reduced capacity, possible unit pressure safety lockouts and reduced unit service life.
For units with blow through condensers, such as these wall-mount units, it is recommended there be a minimum distance of 10' between the front of the unit and any barrier or 20' between the fronts of two opposing (facing) units.
Clearances Required for Service Access and Adequate Condenser Airflow
LEFT
MODELS
W18A, W24A, W30A, W36A 15" 20" 10'
W18L, W24L, W30L, W36L 20" 15" 10'
W42A, W48A, W60A, W72A 20" 20" 10'
W42L, W48L, W60L, W72L 20" 20" 10'
NOTE: For side-by-side installation of two units there must be 20" between units. This can be reduced to 15" by using a W**L model (left side compressor and controls) for the left unit and W**A (right side compressor and controls) for right unit.
See Specifications Sheet S3532.
SIDE
RIGHT
SIDE
DISCHARGE
SIDE
Clearance to Combustibles
!
WARNING
Fire hazard.
Maintain minimum 1/4" clearance between the supply air duct and combustible materials in
the rst 3' of ducting.
Failure to do so could result in re causing damage, injury or death.
The unit itself is suitable for 0" clearance, but the supply air duct flange and the first 3' of supply air duct require a minimum of 1/4" clearance to combustible material. However, it is generally recommended that a 1" clearance is used for ease of installation and maintaining the required clearance to combustible material. See Figures 4A-D on pages 12-15 for details on opening sizes.
Minimum Clearances Required to Combustible Materials
MODELS
W18A, L W24A, L
W30A, L W36A, L
W42A, L W48A, L W60A, L W72A, L
SUPPLY AIR DUCT
FIRST 3'
0" 0"
1/4" 0"
1/4" 0"
CABINET
Manual 2100-676B Page 9 of 88
FIGURE 2
Dimensions of Basic Unit for Architectural and Installation Requirements (Nominal)
WIDTH
DEPTH
MODEL
W18** W24**
W30** W36**
W42** W48**
W60** W72**
(W)
33.300 17.125 74.563 7.88 19.88 11.88 19.88 35.00 10.88 29.75 20.56 30.75 32.06 33.25 31.00 2.63 34.13 26.06 10.55 4.19 12.00 9.00
38.200 17.125 74.563 7.88 27.88 13.88 27.88 40.00 10.88 29.75 17.93 30.75 32.75 33.25 31.00 2.75 39.13 26.75 9.14 4.19 12.00 9.00
42.075 22.432 84.875 9.88 29.88 15.88 29.88 43.88 13.56 31.66 30.00 32.68 26.94 34.69 32.43 3.37 43.00 23.88 10.00 1.44 16.00 1.88
42.075 22.432 93.000 9.88 29.88 15.88 29.88 43.88 13.56 37.00 30.00 40.81 35.06 42.81 40.56 3.37 43.00 31.00 10.00 1.44 16.00 10.00
HEIGHT
(D)
All dimensions are in inches. Dimensional drawings are not to scale.
SUPPLY RETURN
(H)
A B C B E F G I J K L M N O P Q R S T
W**A RIGHT UNIT
W**L LEFT UNIT
5.88
E O
Supply Air Opening
B
Return Air Opening
Back View
MIS-3889
W
Filter Access Panel
Ventilation Air
Condenser
Air Outlet
Front View
.44
Bottom Installation Bracket
MIS-3889
1
5.88
F
G
MIS-3890
MIS-3890
R
S
S
S
S
S
T
Built In Rain Hood 4° Pitch
2.13
A
I
C
K
D
1.250
Cond.
Air
Inlet
Side View
J
D
1.250
Cond.
Air
Inlet
Side View
2.13
A
C
K
J
Drain
Electric Heat
I
Side Wall
Mounting
Brackets
(Built In)
Top Rain
Flashing Shipping Location
Optional
Electrical
H
Entrances
L
Heater Access Panel
C. Breaker/ Disconnect Access Panel (Lockable)
Standard flush
vent door for
non-ERV/CRV
Econ. models
Hood for ECON models only
7.000
Low Voltage Electrical Entrance
High Voltage Electrical Entrance
M
P
N
Q
Built In
Rain Hood
W
Hood for ECON models only
Filter Access Panel
1
Standard
F
G
Ventilation Air
Condenser
flush vent door for non­ERV/CRV Econ. models
Air Outlet
4° Pitch
Heater
Access
Panel
Electric
Heat
C. Breaker/ Disconnect
Access Panel
(Lockable)
7.00
Low Voltage
Electrical Entrance
High Voltage
Electrical Entrance
Front View
E O
Supply Air Opening
B
Return Air Opening
Back View
Side Wall Mounting Brackets (Built In)
Top Rain
Flashing Shipping Location
Optional Electrical Entrances
H
L
M
P
N
Q
R
S
S
S
S
S
T
Drain
.44
Bottom
Installation
Bracket
Manual 2100-676B Page 10 of 88
WALL-MOUNT UNIT MOUNTING
Mounting the Units
!
WARNING
Heavy item hazard.
Use more than one person to handle unit.
Failure to do so could result in unit damage or serious injury.
NOTE: It may be best to spot some electrical
knockouts (such as those located on the back of the wall-mount unit) before units are mounted and access is unavailable or limited (see Figure 2 to locate pre-punched knockouts).
Two holes for the supply and return air openings must be cut through the wall as shown in Figures 4A-D on pages 12-15. On wood frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration. All walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installed unit.
In retrofit (unit replacement) installations, the openings cut for the original equipment may not line up exactly with needs of this installation. Modifications may need to be made, such as increasing or decreasing the size of the wall cutouts. The existing bolt placement may not line up in which case the original bolts would need to be removed or cut away.
1. These units are secured by full-length mounting flanges built into the cabinet on each side which secure the unit to the outside wall surface. A bottom mounting bracket, attached to skid for shipping, is provided for ease of installation, but is not required.
2. The unit itself is suitable for 0" clearance, but the supply air duct flange and the first 3' of supply air duct require a minimum of 1/4" clearance to combustible material. However, it is generally recommended that a 1" clearance is used for ease of installation and maintaining the required clearance to combustible material. See Figures 4A-D for details on opening sizes.
3. Locate and mark lag bolt locations and location for optional bottom mounting bracket, if desired (see Figures 4A-D).
4. Mount bottom mounting bracket (if used).
5. If desired, hook top rain flashing (attached to front­right of supply flange for shipping) under back bend of top.
6. Position unit in opening and secure with fasteners sufficient for the application such as 5/16" lag/ anchor/carriage bolts; use 7/8" diameter flat washers on the lag bolts. It is recommended that a bead of silicone caulking be placed behind the side mounting flanges.
7. Secure optional rain flashing to wall and caulk across entire length of top (see Figures 4A-D).
8. For additional mounting rigidity, the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance if combustible wall.
9. A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.
10. Install outdoor temperature/humidity sensor (see Figure 3). Remove grommet from base and sensor. Discard shipping bracket. Place sensor extension through hole in base under condenser fan and secure to base with screw.
FIGURE 3
Outdoor Sensor Installation
Manual 2100-676B Page 11 of 88
MIS-3157 A
FOAM AIR SEAL
SUPPLIED
RAIN FLASHING
FIGURE 4A
SEAL WITH BEAD
OF CAULKING ALONG
ENTIRE LENGTH OF TOP.
TOP
Mounting Instructions
W18A, W18L, W24A, W24L
WALL STRUCTURE
NOTES:
RETURN AIR
SUPPLY AIR
DUCT
PANEL
HEATER ACCESS
WALL
"
1
8"
2
20
OPENING
12"
IT IS RECOMMENDED THAT A BEAD OF
SILICONE CAULKING BE PLACED BEHIND
THE SIDE MOUNTING FLANGES AND UNDER
TOP FLASHING AT TIME OF INSTALLATION.
IS ON OPPOSITE (LEFT) SIDE.
CONTROLS AND HEATER ACCESS
J**A UNIT SHOWN, J**L UNIT
5"
"
1
16
"
1
8
3
4"
Typ.
2"
Manual 2100-676B Page 12 of 88
20"
Supply Opening
" 7
1
16
7
"
13
16
3
12"
12"
20"
Return Opening
12"
12"
1"
3"
12"
4"
Typ.
"
2"
7
8
Wall Opening and Hole Location View Right Side View
9"
FOUR SIDES OF SUPPLY
Wall Opening and Hole Location View
1/4" MIN. CLEARANCE FROM
COMBUSTIBLE MATERIALSCRECOMMENDED 1" CLEARANCE FROM
REQUIRED DIMENSIONS TO MAINTAIN
COMBUSTIBLE MATERIALS
REQUIRED DIMENSIONS TO MAINTAIN
AIR DUCT IS REQUIRED
1/4" CLEARANCE ON ALL
FROM COMBUSTABLE
MIS-3820
MATERIALS
FOAM AIR SEAL
SUPPLIED
RAIN FLASHING
FIGURE 4B
SEAL WITH BEAD
OF CAULKING ALONG
Mounting Instructions
W30A, W30L, W36A, W36L
ENTIRE LENGTH OF TOP.
ED
TOP
17 5/8
3 11/16
4 7/16
WALL STRUCTURE
WALL
SUPPLY AIR
DUCT
PANEL
HEATER ACCESS
B
TOP FLASHING AT TIME OF INSTALLATION.
IT IS RECOMMENDED THAT A BEAD OF
THE SIDE MOUNTING FLANGES AND UNDER
RETURN AIR
OPENING
NOTES:
SILICONE CAULKING BE PLACED BEHIND
W**A UNIT SHOWN, W**L UNIT
CONTROLS AND HEATER ACCESS
IS ON OPPOSITE (LEFT) SIDE.
Right Side View
"
7
8
4
E
14"
"
16
11
4
5 3/8
B
8 3/8A9 7/829 7/8
4 5/8 16 7/8
28 3/8
C
A
Supply Opening
Return Opening
28"
C
D
12"
12"
12"
12"
4"
"
Typ.
1
8
3
"
7
8
"
7
8
2
"
7
8
12"
4"
Typ.
"
1
16
9
"
16
11
4
Manual 2100-676B Page 13 of 88
D
16"
16"
16"
16"
16"
1
7
8
"
6
1
2
" 6
1
2
"
2
1
8
"
7
8
"
1"
3"
4"
Typ.
4"
Typ.
6
1
2
"
30"
E
16"
A CC
3
1
8
"
B
Wall Opening and Hole Location View
RETURN AIR
1
REQUIRED DIMENSIONS TO MAINTAIN
1/4" MIN. CLEARANCE FROM
COMBUSTIBLE MATERIALS
REQUIRED DIMENSIONS TO MAINTAIN
29
DUCT
COMBUSTIBLE MATERIALS
A B C DE
30 1/2
10 1/2
6 1/4 1 1/4 29 3/4
32 12 5 1/2
2
NOTES:
WALL STRUCTURE
1
SUPPLY AIR
IT IS RECOMMENDED THAT A BEAD OF
OPENING
Right Side View
RAIN FLASHING
SILICONE CAULKING BE PLACED BEHIND
RECOMMENDED 1" CLEARANCE FROM
THE SIDE MOUNTING FLANGES AND UNDER
TOP FLASHING AT TIME OF INSTALLATION.
TOP.
PANEL
HEATER ACCESS
FOUR SIDES OF SUPPLY
AIR DUCT IS REQUIRED
FROM COMBUSTABLE
WALL
1/4" CLEARANCE ON ALL
MATERIALS
Supply Opening
FOAM AIR SEAL
SUPPLIED
SEAL WITH BEAD
OF CAULKING ALONG
ENTIRE LENGTH OF
TOP
1
Return Opening
MIS-416 E
Dimension is 21" on 95" tall units.
2
Dimension is 10" on T48H1 & T60H1.
2
Dimension is 6" on T48H1 & T60H1.
3
3
FIGURE 4C
W42A, W42L, W48A, W48L
Manual 2100-676B Page 14 of 88
Mounting Instructions
D
16"
16"
16"
16"
16"
2
"6
8
" 5
8 97
"
1"
3"
Typ.
1
4"
4"
Typ.
6
1
2
"
30"
E
16"
A CC
"
7
8
3
B
"
8
7
1
1
2
"6
1 1/430 1/2
1/4" CLEARANCE ON ALL
SUPPLIED
FOAM AIR SEAL
A
Supply Opening
SILICONE CAULKING BE PLACED BEHIND
DUCT
FOUR SIDES OF SUPPLY
FROM COMBUSTABLE
1/4" MIN. CLEARANCE FROM
COMBUSTIBLE MATERIALS
REQUIRED DIMENSIONS TO MAINTAIN
OPENING
COMBUSTIBLE MATERIALS
B D E
PANEL
AIR DUCT IS REQUIRED
32
10 1/2
Right Side View
SUPPLY AIR
RECOMMENDED 1" CLEARANCE FROM
MIS-3789
RAIN FLASHING
REQUIRED DIMENSIONS TO MAINTAIN
12
TOP.
MATERIALS
5 1/2
WALL STRUCTURE
2
6 1/4
29
29 3/4
IT IS RECOMMENDED THAT A BEAD OF
THE SIDE MOUNTING FLANGES AND UNDER
WALL
C
Wall Opening and Hole Location View
NOTES:
TOP FLASHING AT TIME OF INSTALLATION.
HEATER ACCESS
RETURN AIR
SEAL WITH BEAD
OF CAULKING ALONG
ENTIRE LENGTH OF
TOP
Return Opening
FIGURE 4D
Mounting Instructions
W60A, W60L, W72A, W72L
Manual 2100-676B Page 15 of 88
FIGURE 5
DUCT
OPENING
RETURN AIR
SUPPLY AIR
WOOD FRAME WALL INSTALLATION
OPENING
WALL BEFORE
MOUNT ON UNIT
OPENING
BEFORE INSTALLATION
BOTTOM MOUNTING
CONCRETE BLOCK WALL INSTALLATION
BRACKET. MOUNT ON
OPENING
WOOD OR STEEL SIDING
OPENING
INSTALLING UNIT.
RETURN AIR
WALL STRUCTURE
RETURN AIR
SUPPLY AIR
FACTORY SUPPLIED
RAIN FLASHING.
SUPPLY AIR
MIS-548 A
SIDE VIEW
Electric Heat Clearance
Wall Mounting Instructions
See FIGURE 2 – Mounting Instructions
FIGURE 6
Manual 2100-676B Page 16 of 88
FIGURE 7
I
A
C
K
E + 1.000
B
1.000
SUPPLY DUCT
OVER FRAME
INTERIOR FINISHED WALL
ALL AROUND DUCT
FRAMING MATERIAL
EXTERIOR FINISH WALL
OPENING
FOR ACTUAL DIMENSIONS.
2 x 4'S, 2 x 6'S &/OR
STRUCTURAL STEEL
ATTACH TO TOP
1.000" CLEARANCE
1.000" CLEARANCE
PLATE OF WALL
C
SEE UNIT DIMENSIONS, FIGURE 1.2,
OPENING
RETURN DUCT
2 x 6
ATTACH TO BOTTOM
OVER FRAME
PLATE OF WALL
L
THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR REST OF WALL. A SECOND MEMBER MAY BE REQUIRED FOR SOME WALLS.
MIS-549 B
ALL AROUND DUCT
Wall Mounting Instructions
SEE UNIT DIMENSIONS, FIGURE 2, FOR ACTUAL DIMENSIONS
Manual 2100-676B Page 17 of 88
FIGURE 8
Common Wall Mounting Installations
SUPPLY DUCT MAY BE LOCATED IN AN ATTIC
OR BELOW CEILING RAFTERS AS SHOWN
RAIN
FLASHING
OUTSI DE
WALL
RAFTERS
FINISHED CEILING SURFACE
SUPPLY AIR DUCT W/GRILLE
WALL SLEEVE
RETURN AIR OPENING W/GRILLE
WALL SLEEVE
FREE AIR FLOW
NO DUCT
SUPPLY DUCT MAY BE LOCATED IN AN ATTIC
OR BELOW CEILING RAFTERS AS SHOWN
RAIN
FLASHING
RAFTERS
RAIN
FLASHING
SUPPLY AIR DUCT
OUTSI DE
WALL
RAFTERS
FINISHED CEILING SURFACE
RETURN AI R OPENI NG W/ GRILLE
WALL SLEEVE
DUCTED SUPPLY
RETURN AT UNIT
SUPPLY DUCT MAY BE LOCATED IN AN ATTIC OR
BELOW CEILING RAFTERS AS SHOWN
RAIN
FLASHING
RAFTERS
OUTSI DE
WALL
FALSE WALL INSTALLATION
Manual 2100-676B Page 18 of 88
SUPPLY AIR DUCT
FINISHED CEILING SURFACE
WALL SLEEVE
FALSE WALL
RETURN AI R GRILLE
RETURN AI R
SPACE
OUTSI DE
WALL
SUPPLY AIR DUCT
LOWERED CEILING
CLOSET WALL
WALL SLEEVE
RAISED FLOOR
RETURN AI R
SUPPLY AIR
GRILLE
FINISHED CEILING
SURFACE
RETURN AI R GRILLE
CLOSET INSTALLATION
MIS-550 C
NOTICE / AVIS
WHITE 3/16" LETTERING
!
WARNING
Electrical shock hazard.
Have a properly trained individual perform these tasks.
Failure to do so could result in electric shock or death.
MAIN POWER WIRING
Refer to the unit rating plate or Table 1 (page 20), Table 2 (page 21) or Table 3 (page 22) for wire sizing information and maximum fuse or circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. The field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit rating plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.
The unit rating plate and Tables 1, 2 and 3 list fuse and wire sizes (75°C copper) for all models including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.
The unit rating plate lists a maximum circuit breaker or fuse that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.
Route all field wires to the right of the wire shield as shown in the circuit routing label found in Figure 9 (and also on the wall-mount units).
See Figure 10 to reference VAC landing points.
The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect. To convert for the locking capability, bend the tab located in the bottom left-hand corner of the disconnect opening under the disconnect access panel straight out. This tab will now line up with the slot in the door. When shut, a padlock may be placed through the hole in the tab preventing entry.
WALL-MOUNT UNIT WIRING
FIGURE 9
Circuit Routing Label
ROUTE ALL HIGH VOLTAGE FIELD
WIRES TO THE RIGHT OF THE WIRE
SHIELD AS SHOWN
ACHEMINER LES FILS HAUTE
TENSION SUR LA DROITE VERS LA
PROTECTION, COMME INDIQUÉ
CIRCUIT BREAKER
/DISJONCTEUR
WIRE SHIELD /
PROTECTION
CONTACTOR /
COMPRESSOR
COMPRESSEUR
CONTACTEUR DU
7961-393
FIGURE 10
VAC Supply Wiring Landing Points
Factory
Wiring
NOTE: Right-hand access model wiring landing points
are shown here; left-hand access models will mirror this image.
LOW VOLTAGE WIRING
230/208V 1 phase and 3 phase equipment use dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. It is very important that the correct voltage tap is used. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are: 240V Tap (253 – 216) and 208 Tap (220 – 197).
NOTE: The voltage should be measured at the field
power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition.
For low voltage wiring, an 18 gauge copper, color-coded cable is recommended.
Field Wiring
Manual 2100-676B Page 19 of 88
Electrical Specifications – W**A*P Series
Rated
A05 A08 A10
A04 A05 A08 A10
B06
C06
A05 A08 A10 A15
B06 B09 B15
C06 C09 C12 C15
A05 A08 A10 A15
B06 B09 B15
C06 C09 C12 C15
A05 A10 A15 A20
B06 B09 B15 B18
C09 C15
A05 A10 A15 A20
B06 B09 B15 B18
C09 C15
Q15
A05 A10 A15 A20
B06 B09 B15 B18
C09 C15
Q15
A05 A10 A15 A20
B06 B09 B15 B18
C09 C15
Q15
Volts
&
Phase
230/208-1
230/208-1
230/208-3
460-3
230/208-1
230/208-3
460-3
230/208-1
230/208-3
460-3
230/208-1
230/208-3
460-311
230/208-1
230/208-3
460-311
575-3
230/208-1
230/208-3
460-311
575-3
230/208-1
230/208-3
460-311
575-3
MODEL
W18AAPA00, A0Z
W24AAPA00, A0Z
W24AAPB00, B0Z
W24AAPC00, C0Z
W30AAPA00, A0Z
W30AAPB00, B0Z
W30AAPC00, C0Z
W36AAPA00, A0Z
W36AAPB00, B0Z
W36AAPC00, C0Z
W42AAPA00, A0Z
W42AAPB00, B0Z
W42AAPC00, C0Z
W48AAPA00, A0Z
W48AAPB00, B0Z
W48AAPC00, C0Z
W48AAPQ00, Q0Z
W60AAPA00, A0Z
W60AAPB00, B0Z
W60AAPC00, C0Z
W60AAPQ00, Q0Z
W72ABPA00, A0Z
W72ABPB00, B0Z
W72ABPC00, C0Z
W72ABPQ00, Q0Z
See footnotes under TABLE 2
Manual 2100-676B Page 20 of 88
No. Field
Power
Circuits
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 or 2
1 1 1 1 1 1 1 1 1 1 1 1 1
1 or 2
1 1 1 1 1 1 1 1 1 1 1
1 1 or 2 1 or 2
1 1 1 1 1
1
1
1
1 1 or 2 1 or 2
1
1
1
1
1
1
1
1
1
1
1 1 or 2 1 or 2
1
1
1
1
2
1
1
1
1
1 1 or 2 1 or 2 1 or 3
1
1
1
1
2
1
1
1
Minimum
Circuit
Ampacity
Single Circuit Multiple Circuit
110
110
112
N/A
114
N/A
16 30 46 56 21 25 30 46 56 15 22
9 11 26 32 47 58 84 19 24 33 51
9 12 17 21 26 29 32 47 58 84 23 24 33 51 11 12 17 21 26 32 32 58 84
25 25 33 51 60 12 17 26 34 34 58 84
26 26 33 51 60 12 17 26 12 24 38 38 60 86
27 27 35 53
14 18 27 13 24 58 58 62 88
40 40 40 55
18 18 27 14 24
Maximum
External
Fuse or
Ckt. Brkr.
20 30 50 60 30 30 30 50 60 20 25 15 15 35 35 50 60 90 20 25 35 60 15 15 20 25 30 35 35 50 60 90 30 30 35 60 15 15 20 25 30 50 50 60 90
125
35 35 35 60 60 15 20 30 50 50 60 90
125
35 35 35 60 60 15 20 30 15 25 60 60 60 90
125
40 40 40 60
N/A
20 20 30 20 25 60 60 70 90
125
60 60 60 60
N/A
25 25 30 20 25
Field
Power
Wire
Size
12 10
8
6 10 10 10
8
6 12 10 14 14
8
8
8
6
4 12 10
8
6 14 14 12 10 10
8
8
8
6
4 10 10
8
6 14 14 12 10 10
8
8
6
4
2
8
8
8
6
6 14 12 10
8
8
6
4
2
8
8
8
6
6 14 12 10 14 10
8
8
6
3
2
8
8
8
6
N/A
12 12 10 12 12
6
6
6
3
2
8
8
8
6
N/A
10 10 10 12 10
Ground
Wire
12 10 10 10 10 10 10 10 10 12 10 14 14 10 10 10 10
8 58 26 60 30 6 10 10 10 12 10 10 10 14 14 12 10 10 10 10 10 10
8 58 26 60 30 6 10 10 10 10 10 10 10 14 14 12 10 10 10 10 10
86585826
10 10 10 10 10 14 12 10 10 10 10
86585826
10 10 10 10 10 14 12 10 14 10 10 10 10
86606026
10 10 10 10
N/A 35 28 40 30 8 10 10 10
12 12 10 12 12 10 10
8
8
6 10 10 10 10
N/A 40 28 60 30 8 10 10 10
10 10 10 12 10
TABLE 1
Minimum
Circuit
Ampacity
Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C
52
52
52
58
26
58
52
58
52 52
Maximum
External Fuse or
Ckt. Breaker
606030
60
606030
60
606030
60
60
30
60
60
60
60 60
Field Power
Wire Size
6610
6610
6610
6 6 6
6
6
6
10
6 6 6
Ground
Wire Size
101010
101010
101010
10 10 10
10
10
10
10 10 10 10
TABLE 2
Electrical Specifications – W**L*P Series
MODEL
W18LAPA00,A0Z
W24LAPA00, A0Z
W24LAPB00, B0Z
W24LAPC00, C0Z
W30LAPA00, A0Z
W30LAPB00, B0Z
W30LAPC00, C0Z
W36LAPA00, A0Z
W36LAPB00, B0Z
W36LAPC00, C0Z
W42LAPA00, A0Z
W42LAPB00, B0Z
W42LAPC00, C0Z
W48LAPA00, A0Z
W48LAPB00, B0Z
W48LAPC00, C0Z
W48LAPQ00, Q0Z
W60LAPA00, A0Z
W60LAPB00, B0Z
W60LAPC00, C0Z
W60LAPQ00, Q0Z
W72LBPA00, A0Z
W72LBPB00, B0Z
W72LBPC00, C0Z
W72LBPQ00, Q0Z
Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors. Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes. These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor
sizing.
CAUTION: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to Note 8 of Table 310 regarding Ampacity
Adjustment Factors when more than three current carrying conductors are in a raceway.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with the National
Rated
Volts &
Phase
A05
230/208-1
A08 A10
A05
230/208-1
A08 A10
230/208-3
B06
460-3
C06
A05 A08
230/208-1 A10 A15
B09
230/208-311 B15
C09
460-3
C15
A05
230/208-1 A10
A15
B09
230/208-311 B15
C09
460-3
C15
A05
230/208-1 A10
A15
B06
230/208-3 B09
B15
C09
460-3
C15
A05
230/208-1 A10
A15
B06
230/208-3 B09
B15
C09
460-3
C15
575-3
Q15
A05
230/208-1 A10
A15
B06
230/208-3 B09
B15
C09
460-3
C15
575-3
Q15
A05
230/208-1 A10
A15
B06
230/208-3 B09
B15
C09
460-3
C15
575-3
Q15
Electrical Code and all local codes.
No.
Field
Power
Circuits
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 or 2
1 1 1 1 1 1 1
1 or 2
1 1 1 1 1 1 1
1 or 2
1 1 1 1 1 1 1 1 1 1
1 or 2
1 1 1 1 1 1 1 1 1 1 1 1
1 or 2
1 1 1 1 1 1 1 1 1 1
1 1 or 2 1 or 2
1
1
1
1
1
1
1
1
1
Minimum
Circuit
Ampacity
16 30 46 56 21 30 46 56 15 22
9 11 26 32 47 58 84 19 33 51
9 17 26 29 32 58 84 23 33 51 11 17 26 32 32 58 84 25 25 33 51 12 17 26 34 34 58 84 26 26 33 51 12 17 26 12 24 38 38 60 86 27 27 35 53 14 18 27 13 24 58 58 62 88 40 40 40 55 18 18 27 14 24
Single Circuit Dual Circuit
Maximum
External
Fuse or Ckt.
Brkr.
20 30 50 60 30 30 50 60 20 25 15 15 35 35 50 60 90 20 35 60 15 20 30 35 35 60 90 30 35 60 15 20 30 50 50 60 90 35 35 35 60 15 20 30 50 50 60 90 35 35 35 60 15 20 30 15 25 60 60 60 90 40 40 40 60 20 20 30 20 25 60 60 70 90 60 60 60 60 25 25 30 20 25
Field
Power
Wire Size
12 10
8
6 10 10
8
6 12 10 14 14
8
8
8
6
4 12
8
6 14 12 10
8
8
6
4 10
8
6 14 12 10
8
8
6
4
8
8
8
6 14 12 10
8
8
6
4
8
8
8
6 14 12 10 14 10
8
8
6
3
8
8
8
6 12 12 10 12 12
6
6
6
3
8
8
8
6 10 10 10 12 10
Minimum
Ground
Wire
12 10 10 10 10 10 10 10 12 10 14 14 10 10 10 10
8 58 26 60 30 6 10 10 10 12 10 10 14 12 10 10 10 10
8 58 26 60 30 6 10 10 10 10 10 10 14 12 10 10 10 10
8 58 26 60 30 6 10 10 10 10 10 10 10 14 12 10 10 10 10
8 58 26 60 30 6 10 10 10 10 10 10 10 14 12 10 14 10 10 10 10
8 60 26 60 30 6 10 10 10 10 10 10 10 12 12 10 12 12 10 10
8
8 10 10 10 10 10 10 10 12 10
Circuit
Ampacity
Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B
58 58
26 52
Maximum
External Fuse or
Ckt. Breaker
60
30
60
60
Field Power
Wire Size
6
10
6
Ground
Wire Size
10
6
10
10 10
Manual 2100-676B Page 21 of 88
TABLE 3
Electrical Specifications – W**A*E Series
Single Circuit Dual Circuit
Model
W36AAEA15 230/208-1 1 or 2 104 110 2 6 52 52 60 60 6 6 10 10
W36AAEB15 230/208-3 1 or 2 66 70 4 8 21 48 30 50 10 8 10 10
W36AAEC15 460-3 1 34 35 8 10
W48AAEA15 230/208-1 1 or 2 110 110 2 6 58 52 60 60 6 6 10 10
W48AAEB15 230/208-3 1 or 2 69 70 4 8 24 49 30 50 10 8 10 10
W48AAEC15 460-3 1 34 35 8 10
W60AAEA15 230/208-1 1 or 3 114 120 2 6 36 52 52 40 60 60 8 6 6 10 10 10
W60AAEB15 230/208-3 1 or 2 72 80 4 8 26 50 30 50 10 8 10 10
W60AAEC15 460-3 1 36 40 8 10
W72ABEA15 230/208-1 1 or 3 134 140 1/0 6 58 52 26 60 60 30 6 6 10 10 10 10
Rated
Volts &
Phase
No.
Field
Power
Circuits
Minimum
Circuit
Ampacity
Maximum
External
Fuse or
Ckt. Brkr.
Field
Power
Wire Size
Ground
Wire
Minimum
Circuit
Ampacity
Ckt. ACkt. BCkt. CCkt. ACkt. BCkt. CCkt. ACkt. BCkt. CCkt. ACkt. BCkt.
Maximum
External Fuse or
Ckt. Breaker
Field Power Wire
Size
Ground
Wire Size
C
W72ABEB15 230/208-3 1 or 2 83 90 4 8 38 52 40 60 8 6 10 10
W72ABEC15 460-3 1 40 45 8 10
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code
(latest version), Article 310 for power conductor sizing.
Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
CAUTION: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to
note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) current carrying conductors are in a raceway.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor
wires in accordance with the National Electrical Code and all local codes.
Manual 2100-676B Page 22 of 88
PRELIMINARY START UP
Running in Stand Alone (Orphan) Mode
With the AC breakers turned on, each MULTI-TEC wall-mount unit has the capability to run without the LC6000 controller or th-TUNE connected—this feature is called stand alone or orphan mode. This keeps the shelter between 60°F and 77°F (factory default settings) by the use of the factory-installed return air sensor in each wall-mount unit. In stand­alone mode, the wall unit uses a continuous blower setting to circulate room air into the return air inlet and uses the return air temperature sensor to control room temperature.
The wall-mount unit can be turned on and off with the TEC-EYE hand-held diagnostic tool. When ON is chosen, the wall-mount unit will heat or cool. When set to OFF using the TEC-EYE, the wall-mount unit will not heat, cool or ventilate.
To turn the unit on or off with TEC-EYE:
1. Connect the TEC-EYE diagnostic tool to the control board located in the unit.
2. Press MENU key to go to the Main Menu screen.
3. Press UP or DOWN keys and ENTER key to enter USER password 2000.
4. Press UP or DOWN keys to scroll to On/Off; press ENTER key.
5. Press UP or DOWN keys to change value from On to Off or from Off to On.
6. Press ESCAPE key several times to return to Main Menu screen.
To verify or change the wall-mount unit cooling and heating setpoints in stand alone mode:
1. Connect the TEC-EYE diagnostic tool to the control board located in the unit.
2. From the Status screen, press UP or DOWN key until Quick Menu displays Setpoints (SET) icon. Press ENTER key.
3. Press ENTER key to scroll to the selected choice (see Figure 11).
4. Press UP or DOWN key on desired value until value displays correctly.
5. Press ENTER key to save and scroll to next parameter.
6. Press ESCAPE key until Main Menu screen is displayed.
FIGURE 11
Cooling and Heating Setpoints
During installation, the ability to run in stand alone mode allows deactivation of one of the existing, older wall-mount units, while keeping the shelter cool with the other unit still operating. Once the first of the Bard MULTI-TEC wall-mount units is installed, orphan mode can be enabled early in the installation—keeping the climate inside the shelter stable and the installers comfortable while the remainder of the older equipment is removed and the remaining Bard MULTI-TEC wall­mount units and LC6000 controller are installed.
To ensure units will go into stand alone mode, disconnect the plug marked R-T-/R+T+/GND on the control board located in the wall-mount unit. Be sure to reconnect the plug before operating the wall-mount unit as part of the Bard Free Cooling Unit System.
Additionally, should any or all of the MULTI-TEC wall­mount units lose communication with the LC6000 controller (such as during maintenance), they will continue to serve the shelter’s needs until a repair can be made.
NOTE: Screenshots shown in this manual reflect
default settings (when applicable).
Manual 2100-676B Page 23 of 88
LC6000 CONTROLLER INSTALLATION
FIGURE 12
Typical LC6000 Component Location
RJ11 Cable
to Display
Transformer
Ethernet Cable
Connection
Four Fused
Power Supply
Terminals
Smoke Alarm
Jumper
Hydrogen Alarm
Jumper
Generator Run
Alarm Jumper
Control Board
USB Cable
Terminal Block
Manual 2100-676B Page 24 of 88
!
WARNING
Electrical shock hazard.
Disconnect VAC power supplies before
servicing.
Failure to do so could result in electric shock or death.
IMPORTANT: When working with circuit board
components, an anti-static wrist strap to prevent static
electricity shorts to electronic controls.
Bard recommends the use of
LC6000 Controller
The LC6000 controller is part of the Free Cooling Unit system by Bard. It is used to control up to 14 wall-mount air conditioners from one controller. The microprocessor control provides an easy-to-read interface with large LCD graphical display. It provides control for redundancy for the structure and equal wear on all units.
Conduit is recommended for all wiring. Route communication wiring and power supply wiring in their own separate conduits.
The LC6000 controller is not weatherproof and is intended for use in weathertight structure.
Mounting the LC6000 Controller
The dimensions of the LC controller are 16" x 12" x 6".
Because the LC6000 controller utilizes a remote temperature sensor as opposed to one located in the controller box, the controller itself can be installed in any indoor location that is suitable, preferably at eye level. Four (4) mounting holes are provided for mounting to the wall and holes for conduit connections are provided in both the base, sides and top of the controller.
The LC6000 controller includes four fused power supply terminals in the terminal block. Before connecting wires to the terminal block, confirm that the fuse in each of the four fuse holders is in the proper position (active) as shown in see Figure 13.
FIGURE 13
LC6000 Fused Power Supply Terminal
Fuse in Active Position
Shipping Position
Manual 2100-676B Page 25 of 88
Installing Remote Indoor Temperature/Humidity Sensor(s)
47 51
49 53
55
59
57
60
48
50 52
54
56
58
One remote indoor temperature/humidity sensor and 35' of 18 gauge 5-conductor shielded cable is included with the controller. This sensor must be installed for proper operation. Mount the temperature/humidity sensor in a location least likely to be affected by open doors, rack-mounted fans, radiant heat sources, etc. Locating the sensor between both return grilles is often the best location, but every installation is unique. Location height should be approximately 60" above the floor. The sensor should be installed on a 2" x 4" junction box to allow for control wire conduit (see Figure 14). Use shielded cable to connect to controller.
FIGURE 14
Remote Indoor Temperature/Humidity Sensor Installation
1. Connect wires from the 18 gauge shielded cable to terminals #12, #13, #18, #19 and #22.
TB#
Wire
Mark
Sensor Description
18 B6 NTC OUT Indoor Remote Sensor (Zone 1)
19 GND NTC OUT Ground
12 B2 OUT H Remote Indoor Humidity Sensor: 0-1 VDC (Zone 1)
13 GND M (GO) Ground
22 +VDC + (G) Power for B2
212523
11 13
9
8 10 12
14
16 18
15
17
19
20
22 24
26
27
28
29
30 32 34 36
313533
37
40
39 4341 45
38
42 44
46
2. Connect the other end of the shielded cable to the sensor terminals. Be sure wires are connected to proper terminals as shown in table above. Sensor jumpers need to be positioned for 0-1 V. With sensor oriented as shown in image to right, move both jumpers to left position (DP1 and DP2 set to OFF).
This applies to all temperature/humidity sensors connected
to the LC controller.
Sensor is best mounted on a junction box, and it is
recommended that the cable be in conduit.
Manual 2100-676B Page 26 of 88
DP1
DP2
Jumper
For proper operation, the remote indoor temperature/humidity sensor must be configured properly with the controller. An additional remote indoor temperature-only sensor can be purchased and installed in Zone 1. Also, temperature and humidity sensors can also be purchased and installed in Zones 2 and 3 (one per zone). For information on remote indoor sensor configuration, see page 26. For each additional sensor installed, be sure to enable the sensor in the controller menus (see Configure Sensors beginning on page 40).
FIGURE 15
Additional Remote Temperature and Temperature/Humidity Sensor Installation
One additional temperature sensor can be added to Zone 1 and additional temperature/humidity sensors may be added to Zones 2 and 3 (one per zone). Be sure the sensors are connected to the proper terminals on the terminal
block and sensor as listed below.
212523
3
2
1
4
5
6
9
8 10 12
7
11 13
15
14
16 18
17
20
19
22 24
27
262830 32 34 36
29
313533
37
40
39 4341 45
38
42 44
47 51
46 48
49 53
50 52
60
58
59
55
54
57
56
Zone 1:
Optional Remote
Temperature Sensor
Terminals 20 & 21*
Zone 2:
Optional Remote
Temperature/Humidity Sensor
Terminals 26, 27, 14, 15 & 23
Zone 3:
Optional Remote
Temperature/Humidity Sensor
Terminals 28, 29, 16, 17 & 24
TB#
Wire
Mark
Description
20 B7 Indoor Remote Sensor (Zone 1 – optional)
21 GND Ground
* The two wire connections for the optional remote temperature sensor
are not polarity sensitive.
TB#
Wire
Mark
Sensor Description
26 B8 NTC OUT Indoor Remote Sensor (Zone 2)
27 GND NTC OUT Ground
14 B3 OUT H Remote Indoor Humidity Sensor: 0-1 VDC (Zone 2)
15 GND M (GO) Ground
23 +VDC + (G) Power for B3
TB#
Wire
Mark
Sensor Description
28 B9 NTC OUT Indoor Remote Sensor (Zone 3)
29 GND NTC OUT Ground
16 B4 OUT H Remote Indoor Humidity Sensor: 0-1 VDC (Zone 3)
17 GND M (GO) Ground
24 +VDC + (G) Power for B4
Zones 2 and 3 can also use temperature-only sensors in place of the temperature/humidity sensors. Zone 2 will connect to TB# 26 and 27. Zone 3 will connect to TB# 28 and 29. The wire connections for the temperature-only sensors are not polarity sensitive.
Manual 2100-676B Page 27 of 88
Loading...
+ 61 hidden pages