Bard W24HA-B, W30HA-C, W24HA-A, W30HA-B, W24HA-C Installation Instructions Manual

...
INSTALLATION INSTRUCTIONS
WALL MOUNTED PACKAGE
HEAT PUMP
Models:
W18HA-A W24HA-A
W24HA-B W24HA-C
W24HADA W24HADB W24HADC
W30HADA W30HADB W30HADC
W36HADA W36HADB W36HADC
W42HADA W42HADB W42HADC
W48HADA W48HADB W48HADC
W60HADA W60HADB W60HADC
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
www.bardhvac.com
Manual: 2100-654C Supersedes: 2100-654B Date: 7-26-17
Page 1 of 34
CONTENTS
Getting Other Information and Publications .... 3
Wall Mount General Information .........................4
Heat Pump Wall Mount Model Nomenclature .......... 4
Shipping Damage ................................................. 4
General ............................................................... 4
Duct Work ........................................................... 4
Filters ................................................................. 5
Fresh Air Intake ................................................... 5
Condensate Drain ................................................ 5
Installation ............................................................... 6
Wall Mounting Information .................................... 6
Mounting the Unit ................................................ 6
Clearances Required ............................................. 6
Minimum Clearances ............................................ 6
Wiring – Main Power ........................................... 15
Wiring – Low Voltage Wiring ................................. 15
Start Up ................................................................... 19
General ............................................................. 19
Topping Off System Charge ................................. 19
Safety Practices ................................................. 19
Important Installer Note ...................................... 20
High and Low Pressure Switch ............................. 20
Three Phase Scroll Compressor Start Up
Information ........................................................ 20
Phase Monitor .................................................... 20
Condenser Fan Operation .................................... 20
Service Hints ..................................................... 20
Vent Connection Plug .......................................... 20
Sequence of Operation ........................................ 21
Pressure Service Ports ........................................ 21
Defrost Cycle ..................................................... 21
Service ..................................................................... 24
Solid State Heat Pump Control Troubleshooting
Procedure ......................................................... 24
Checking Temperature Sensor Outside
Unit Circuit ........................................................ 25
Troubleshooting Nidec SelecTech Series ECM
Motors ............................................................... 26
Fan Blade Setting Dimensions ............................. 28
Removal of Fan Shroud ....................................... 28
R-410A Refrigerant Charge ................................. 28
Figures
Figure 1 Fresh Air Damper .................................. 5
Figure 2 Unit Dimensions ................................... 7
Figure 3A Mounting Instructions – W18H, W24H .... 8
Figure 3B Mounting Instructions – W30H, W36H .... 9
Figure 3C Mounting Instructions – W42H, W48H .. 10
Figure 3D Mounting Instructions – W60H ............. 11
Figure 4 Electric Heat Clearance ....................... 12
Figure 5 Wall Mounting Instructions .................. 13
Figure 6 Wall Mounting Instructions .................. 13
Figure 7 Common Wall Mounting Installations .... 14
Figure 8 Programmable Thermostat Connections . 17 Figure 9 Non-Programmable Thermostat
Connections ....................................... 18
Figure 10 Defrost Control Board .......................... 23
Figure 11 Motor Connections .............................. 26
Figure 12 Motor Connections .............................. 27
Figure 13 Fan Blade Setting ............................... 28
Tables
Table 1 Wall Thermostats ................................ 16
Table 2 Humidity Controls ............................... 16
Table 3 CO
Table 4 Thermostat Wire Size ........................... 16
Table 5 Troubleshooting .................................. 24
Temperature vs. Resistance .................. 25
Table 6 Fan Blade Dimension .......................... 28
Table 7A Cooling Pressure ................................. 29
Table 7B Heating Pressure ................................. 29
Table 8 Electrical Specifications ...................... 30
Table 9 Recommended Airflow ......................... 31
Table 10 Indoor Blower Performance .................. 31
Table 11 Maximum ESP of Operation
Electric Heat Only Tables ..................... 32
Table 12 Electric Heat ...................................... 32
Table 13 Optional Accessories ........................... 33
Table 14 Vent and Control Options ..................... 34
Controller ..................................... 16
2
Manual 2100-654C Page 2 of 34
GETTING OTHER INFORMATION AND PUBLICATIONS
These publications can help when installing the heat pump. They can usually be found at the local library or purchased directly from the publisher. Be sure to consult the current edition of each standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation ..............ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air .......................ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for ......................... ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for Residential ............... ACCA Manual D
Winter and Summer Air Conditioning and Equipment Selection
For more information, contact these publishers:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute 11 West Street, 13th Floor
New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association
Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manual 2100-654C Page 3 of 34
WALL MOUNT GENERAL INFORMATION
HEAT PUMP WALL MOUNT MODEL NOMENCLATURE
W 42 H A – A 10 X X X X X A
MODEL NUMBER
CAPACITY
18 - 1½ Ton 24 - 2 Ton 30 - 2½ Ton 36 - 3 Ton 42 - 3½ Ton 48 - 4 Ton 60 - 5 Ton
Insert “D” for dehumidification with hot gas reheat. Reference Form 7960-702 for complete details. For 0 KW and circuit breakers (230/208 volt) or toggle disconnect (460V) applications, insert 0Z in the KW field of the model number.
NOTE: Vent options X, B and M are without exhaust capability. May require separate field-supplied barometric relief in building.
H - Heat Pump
SPECIALTY PRODUCTS
(Non-Standard)
VENTILATION OPTIONS
X - Barometric Fresh Air Damper (Standard) B - Blank-Off Plate M - Motorized Fresh Air Damper V - Commercial Ventilator - Motorized with Exhaust S - Economizer (Std.) - Enthalpy W - Economizer (Full Flow) - Enthalpy T - Economizer (Full Flow) - Temperature R - Energy Recovery Ventilator - Motorized with Exhaust (See Spec. Sheet S3523)
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
REVISIONS
VOLTS & PHASE
A - 230/208/60/1 B - 230/208/60/3 C - 460/60/3
KW
COLOR OPTIONS
X - Beige (Standard) 1 - White 4 - Buckeye Gray 5 - Desert Brown 8 - Dark Bronze
FILTER OPTIONS
X - 1" Throwaway (Standard) W - 1" Washable P - 2" Pleated
OUTLET OPTIONS
X - Front
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See page 3 for information on codes and standards.
CONTROL MODULES
(See Spec. Sheet S3523)
COIL OPTIONS
X - Standard 1 - Phenolic Coated Evaporator 2 - Phenolic Coated Condenser 3 - Phenolic Coated Evaporator and Condenser
Size of unit for a proposed installation should be
GENERAL
based on heat loss/gain calculation made according to methods of Air Conditioning Contractors of America
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and
(ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
return ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the
DUCT WORK
All duct work, supply and return, must be properly sized for the design airflow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
equipment.
Manual 2100-654C Page 4 of 34
Refer to Maximum ESP of Operation Electric Heat Table 11 on page 32.
Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of 1" of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
Models W18 and W24 are approved for 0" clearance to the supply duct. For models W30, W36, W42, W48 and W60, a 1/4" clearance to combustible material for the first 3' of duct attached to the outlet air frame is required. See MOUNTING THE UNIT on page 6 and Figures 3A – D (pages 8 – 11) and Figure 4 (page 12) for further details.
Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.
Some installations may not require any return air duct. A metallic return air grille is required with installations not requiring a return air duct. The spacing between louvers on the grille shall not be larger than 5/8".
Any grille that meets with 5/8" louver criteria may be used. It is recommended that Bard Return Air Grille Kit RG-2W through RG-5W or RFG-2W through RFG­5W be installed when no return duct is used. Contact distributor or factory for ordering information. If using a return air filter grille, filters must be of sufficient size to allow a maximum velocity of 400 fpm.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to installation only in a single story structure.
FILTERS
A 1" throwaway filter is standard with each unit. The filter slides into position making it easy to service. This filter can be serviced from the outside by removing the filter access panel. A 1" washable filter and 2" pleated filter are also available as optional accessories. The internal filter brackets are adjustable to accommodate the 2" filter by bending two tabs down on each side of the filter support bracket.
FRESH AIR INTAKE
All units are built with fresh air inlet slots punched in the service door.
If the unit is equipped with a fresh air damper assembly, the assembly is shipped already attached to the unit. The damper blade is locked in the closed position. To allow the damper to operate, the maximum and minimum blade position stops must be installed (see Figure 1).
All capacity, efficiency and cost of operation information is based upon the fresh air blank-off plate in place and is recommended for maximum energy efficiency.
The blank-off plate is available upon request from the factory and is installed in place of the fresh air damper shipped with each unit.
CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.
FIGURE 1
Fresh Air Damper
BLADE IS LOCKED CLOSED FOR SHIPPING
MIS-938
Manual 2100-654C Page 5 of 34
INSTALLATION
WALL MOUNTING INFORMATION
1. Two holes for the supply and return air openings must be cut through the wall as shown in Figures 3A – D.
2. On wood frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration.
3. Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installed unit.
NOTE: Before mounting the heat pump unit,
consideration should be given to the condensate removal from the outdoor coil when in heating mode. The unit must be mounted high enough above grade to ensure that ice will not build up under the unit and come into contact with the base of the unit. If allowed, this could cause damage to the coil and other base components. Also, be sure there are no air obstructions to the sides or front of the unit, such as bushes or fences, that would inhibit condenser airflow.
MOUNTING THE UNIT
1. These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides. A bottom mounting bracket, attached to skid for shipping, is provided for ease of installation, but is not required.
2. The unit itself is suitable for 0" clearance, but the supply air duct flange and the first 3' of supply air duct require a minimum of 1/4" clearance to combustible material for model series W30, W36, W42, W48 and W60. However, it is generally recommended that a 1" clearance is used for ease of installation and maintaining the required clearance to combustible material. See Figures 3A – D for details on opening sizes.
Minimum Clearances Required to Combustible Materials
MODELS
W18H/W24H 0" 0"
W30H/W36H 1/4" 0"
W42H/W48H/W60H 1/4" 0"
SUPPLY AIR DUCT
FIRST 3'
CABINET
Clearances Required for Service Access and Adequate Condenser Airflow
MODELS LEFT SIDE RIGHT SIDE
W18H, W24H, W30H, W36H 15" 20"
W42H, W48H, W60H 20" 20"
3. Locate and mark lag bolt locations and bottom mounting bracket location (see Figures 3A – D).
4. Mount bottom mounting bracket.
5. Hook top rain flashing, attached to front - right of supply flange for shipping, under back bend of top.
6. Position unit in opening and secure with fasteners sufficient for the application such as 5/16" lag/ anchor/carriage bolts; use 7/8" diameter flat washers on the bolts.
7. Secure rain flashing to wall and caulk across entire length of top (see Figures 3A – D).
8. For additional mounting rigidity, the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance if combustible wall.
9. On side-by-side installations, maintain a minimum of 20" clearance on right side to allow access to control panel and heat strips, and to allow proper airflow to the outdoor coil. Additional clearance may be required to meet local or national codes.
WARNING
Failure to provide the 1/4" clearance between the supply duct and a combustible surface
for the rst 3' of duct can result in re causing damage, injury or death.
Manual 2100-654C Page 6 of 34
NOTE: Refer to Figures 2 – 7 for dimensions and various mounting configurations.
FIGURE 2
Dimensions of Basic Unit for Architectural and Installation Requirements (Nominal)
WIDTH
DEPTH
MODEL
W18HA W24HA
W30HA W36HA
W42HA W48HA
W60HA 42.075 22.432 93.000 9.88 29.88 15.88 29.88 43.88 13.56 37.00 30.00 40.81 35.06 42.81 40.56 3.37 43.00 31.00 10.00 1.44 16.00 10.00
(W)
33.300 17.125 74.563 7.88 19.88 11.88 19.88 35.00 10.88 29.75 20.56 30.75 32.06 33.25 31.00 2.63 34.13 26.06 10.55 4.19 12.00 9.00
38.200 17.125 74.563 7.88 27.88 13.88 27.88 40.00 10.88 29.75 17.93 30.75 32.75 33.25 31.00 2.75 39.13 26.75 9.14 4.19 12.00 9.00
42.075 22.432 84.875 9.88 29.88 15.88 29.88 43.88 13.56 31.66 30.00 32.68 26.94 34.69 32.43 3.37 43.00 23.88 10.00 1.44 16.00 1.88
HEIGHT
(D)
All dimensions are in inches. Dimensional drawings are not to scale.
SUPPLY RETURN
(H)
A B C B E F G I J K L M N O P Q R S T
5.88
Built In
Rain Hood
W
Hood for CRV and ECON models only
Filter Access Panel
1
Standard
F
G
Ventilation Air
Condenser
flush vent door for non­ERV/CRV Econ. models
Air Outlet
4° Pitch
Heater
Access
Panel
Electric
Heat
C. Breaker/ Disconnect
Access Panel
(Lockable)
3"
7.00
Low Voltage
Electrical Entrance
High Voltage
Electrical Entrance
Front View
D
1.250
Cond.
Air
Inlet
Side View
2.13
J
Drain
Side Wall
A
Mounting
Brackets
(Built In)
I
Top Rain
Flashing Shipping Location
Optional
C
Electrical
H
Entrances
K
L
M
P
N
Supply Air Opening
Return Air Opening
Q
E O
B
Back View
.44
Bottom Installation Bracket
MIS-3796
R
S
S
S
S
S
T
Manual 2100-654C Page 7 of 34
12"
12"
12"
12"
12"
20"
20"
8"
20
1
2
"
12"
3
13
16
"
2"
2"
7
1
16
" 7
1
16
"
5"
1"
3"
4"
Typ.
3
1
8
"
4"
Typ.
7
8
"
9"
NOTES:
WALL STRUCTURE
ENTIRE LENGTH OF TOP.
TOP
WALL
OF CAULKING ALONG
PANEL
FOAM AIR SEAL
DUCT
RAIN FLASHING
HEATER ACCESS
MIS-3157 A
Wall Opening and Hole Location View Right Side View
RETURN AIR
TOP FLASHING AT TIME OF INSTALLATION.
OPENING
THE SIDE MOUNTING FLANGES AND UNDER
SEAL WITH BEAD
IT IS RECOMMENDED THAT A BEAD OF
SILICONE CAULKING BE PLACED BEHIND
SUPPLY AIR
SUPPLIED
Return Opening
Supply Opening
J**A UNIT SHOWN, J**L UNIT
CONTROLS AND HEATER ACCESS
IS ON OPPOSITE (LEFT) SIDE.
FIGURE 3A
W18H, W24H
Mounting Instructions
Manual 2100-654C Page 8 of 34
28"
AC
D
C
12"
12"
12"
12"
12"
B
E
14"
4
11
16
"
4
11
16
"
4"
Typ.
2
7
8
"
7
8
"
7
8
"
4"
Typ.
3
1
8
"
9
1
16
"
4
7
8
"
NOTES:
DUCT
HEATER ACCESS
1/4" CLEARANCE ON ALL
ENTIRE LENGTH OF TOP.
TOP
OF CAULKING ALONG
PANEL
FOAM AIR SEAL
WALL STRUCTURE
TOP FLASHING AT TIME OF INSTALLATION.
FOUR SIDES OF SUPPLY
RAIN FLASHING
FROM COMBUSTABLE
MATERIALS
SUPPLY AIR
SUPPLIED
SILICONE CAULKING BE PLACED BEHIND
RETURN AIR
Right Side View
MIS-3158 A
AIR DUCT IS REQUIRED
OPENING
THE SIDE MOUNTING FLANGES AND UNDER
SEAL WITH BEAD
IT IS RECOMMENDED THAT A BEAD OF
WALL
Wall Opening and Hole Location View
Return Opening
16 7/84 7/164 5/89 7/829 7/8
17 5/83 11/165 3/88 3/828 3/8
EDCBA
COMBUSTIBLE MATERIALS
RECOMMENDED 1" CLEARANCE FROM
REQUIRED DIMENSIONS TO MAINTAIN
COMBUSTIBLE MATERIALS
1/4" MIN. CLEARANCE FROM
REQUIRED DIMENSIONS TO MAINTAIN
Supply Opening
J*R UNIT SHOWN, J*L UNIT
CONTROLS AND HEATER ACCESS
IS ON OPPOSITE (LEFT) SIDE.
FIGURE 3B
W30H, W36H
Mounting Instructions
Manual 2100-654C Page 9 of 34
D
16"
16"
16"
16"
16"
1
7
8
"
6
1
2
" 6
1
2
"
2
1
8
"
7
8
"
1"
3"
4"
Typ.
4"
Typ.
6
1
2
"
30"
E
16"
A CC
3
1
8
"
B
Wall Opening and Hole Location View
RETURN AIR
1
REQUIRED DIMENSIONS TO MAINTAIN
1/4" MIN. CLEARANCE FROM
COMBUSTIBLE MATERIALS
REQUIRED DIMENSIONS TO MAINTAIN
29
DUCT
COMBUSTIBLE MATERIALS
A B C DE
30 1/2
10 1/2
6 1/4 1 1/4 29 3/4
32 12 5 1/2
2
NOTES:
WALL STRUCTURE
1
SUPPLY AIR
IT IS RECOMMENDED THAT A BEAD OF
OPENING
Right Side View
RAIN FLASHING
SILICONE CAULKING BE PLACED BEHIND
RECOMMENDED 1" CLEARANCE FROM
THE SIDE MOUNTING FLANGES AND UNDER
TOP FLASHING AT TIME OF INSTALLATION.
TOP.
PANEL
HEATER ACCESS
FOUR SIDES OF SUPPLY
AIR DUCT IS REQUIRED
FROM COMBUSTABLE
WALL
1/4" CLEARANCE ON ALL
MATERIALS
Supply Opening
FOAM AIR SEAL
SUPPLIED
SEAL WITH BEAD
OF CAULKING ALONG
ENTIRE LENGTH OF
TOP
1
Return Opening
MIS-416 E
Dimension is 21" on 95" tall units.
2
Dimension is 10" on T48H1 & T60H1.
2
Dimension is 6" on T48H1 & T60H1.
3
3
FIGURE 3C
W42H, W48H
Manual 2100-654C Page 10 of 34
Mounting Instructions
D
16"
16"
16"
16"
16"
2
"6
8
" 5
8 97
"
1"
3"
Typ.
1
4"
4"
Typ.
6
1
2
"
30"
E
16"
A CC
"
7
8
3
B
"
8
7
1
1
2
"6
1 1/430 1/2
1/4" CLEARANCE ON ALL
SUPPLIED
FOAM AIR SEAL
A
Supply Opening
SILICONE CAULKING BE PLACED BEHIND
DUCT
FOUR SIDES OF SUPPLY
FROM COMBUSTABLE
1/4" MIN. CLEARANCE FROM
COMBUSTIBLE MATERIALS
REQUIRED DIMENSIONS TO MAINTAIN
OPENING
COMBUSTIBLE MATERIALS
B D E
PANEL
AIR DUCT IS REQUIRED
32
10 1/2
Right Side View
SUPPLY AIR
RECOMMENDED 1" CLEARANCE FROM
MIS-3789
RAIN FLASHING
REQUIRED DIMENSIONS TO MAINTAIN
12
TOP.
MATERIALS
5 1/2
WALL STRUCTURE
2
6 1/4
29
29 3/4
IT IS RECOMMENDED THAT A BEAD OF
THE SIDE MOUNTING FLANGES AND UNDER
WALL
C
Wall Opening and Hole Location View
NOTES:
TOP FLASHING AT TIME OF INSTALLATION.
HEATER ACCESS
RETURN AIR
SEAL WITH BEAD
OF CAULKING ALONG
ENTIRE LENGTH OF
TOP
Return Opening
W60H
FIGURE 3D
Mounting Instructions
Manual 2100-654C Page 11 of 34
Loading...
+ 23 hidden pages