Bard W60H1D, W24H1, W60H1, W30H1D, W42H1 User Manual

...
INSTALLATION INSTRUCTIONS
WALL MOUNTED
PACKAGE HEAT PUMPS
MODELS
W18H1 W24H1 W24H1D W30H1 W30H1D W36H1 W36H1D W42H1 W42H1D W48H1 W48H1D W60H1 W60H1D
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
Since 1914...Moving ahead just as planned.
Manual 2100-511F Page 1 of 27
Contents
Getting Other Information and Publications 3 Wall Mount General Information
Wall Mount Model Nomenclature ............................ 4
Shipping Damage .................................................... 4
General ................................................................ 4
Duct Work ................................................................ 5
Filters ................................................................ 5
Fresh Air Intake ....................................................... 5
Condensate Drain.................................................... 5
Installation Instructions
Wall Mounting Information....................................... 6
Mounting the Unit .................................................... 6
Clearances Required............................................... 6
Minimum Clearances ............................................... 6
Wiring – Main Power ............................................. 14
Wiring – Low Voltage Wiring ................................. 14
Figures
Figure 1 Fresh Air Damper Assembly ................... 5
Figure 2 Unit Dimensions...................................... 7
Figure 3A Mounting Instructions .............................. 8
Figure 3B Figure 3C
Figure 4 Electric Heat Clearance .........................11
Figure 5 Wall Mounting Instructions .................... 12
Figure 6 Wall Mounting Instructions .................... 12
Figure 7 Common Wall Mounting Installations .... 13
Figure 8 Defrost Control Board ........................... 18
Figure 9 Fan Blade Setting ................................. 21
Mounting Instructions - W18, W24, W30, W36 .... 9
Mounting Instructions - W42, W48, W60.....10
Start Up
General .............................................................. 15
Topping Off System Charge................................... 15
Safety Practices..................................................... 15
Important Installer Note ......................................... 16
Wall Mounted Air Conditioner ................................ 16
Three Phase Scroll Compressor............................ 16
Phase Monitor ....................................................... 16
Condenser Fan Operation ..................................... 16
Service Hints ......................................................... 16
Sequence of Operation.......................................... 17
Pressure Service Ports.......................................... 17
Defrost Cycle ......................................................... 17
Troubleshooting
Solid State Heat Pump Control.............................. 19
Checking Temperature Sensor .............................. 20
Fan Blade Setting Dimensions .............................. 21
Removal of Fan Shroud......................................... 21
Refrigerant Charge ................................................ 21
Tables
Table 1 Troubleshooting .................................... 19
Table 2 Fan Blade Dimension............................ 21
Table 3A Cooling Pressure .................................. 22
Table 3B Heating Pressure .................................. 22
Table 4 Electrical Specifications W**H .............. 23
Table 5 Recommended Airflow .......................... 24
Table 6 Indoor Blower Performance .................. 24
Tables 7 Maximum ESP Electric Heat Only........ 25
Table 8 Electric Heat ......................................... 25
Table 9 Optional Accessories ........................... 26
Table 10 Vent & Control Options ......................... 27
Manual 2100-511F Page 2 of 27
GETTING OTHER INFORMATION AND PUBLICATIONS
These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation .............. ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ...................... ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for............................ ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for Residential .............. ACCA Manual D
Winter and Summer Air Conditioning and Equipment Selection
FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute
11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigeration
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association
Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manual 2100-511F Page 3 of 27
WALL MOUNT GENERAL INFORMATION
HEAT PUMP WALL MOUNT MODEL NOMENCLATURE
W 42 H 1– A 10 X X X X X A
MODEL NUMBER
CAPACITY
18 - 1
½
Ton
24 - 2 Ton
½ Ton
30 - 2 36 - 3 Ton 42 - 3½ Ton 48 - 4 Ton 60 - 5 Ton
1 For 0 KW and circuit breakers (230/208 volt) or toggle disconnect (460V) applications, insert 0Z in the KW field of the model number. 2 Insert “D” for dehumidification with hot gas reheat. Reference Form 7960-576 for complete details.
NOTE: Vent options X, B and M are without exhaust capability. May require separate field supplied barometric relief in building.
H - Heat Pump
SPECIALTY PRODUCTS 2
(Non-Standard)
VENTILATION OPTIONS
X - Barometric Fresh Air Damper (Standard) B - Blank-off Plate M - Motorized Fresh Air Damper V - Commercial Ventilator - Motorized with Exhaust E - Economizer (Internal) - Fully Modulating with Exhaust R - Energy Recovery Ventilator - Motorized with Exhaust
(See Spec. Sheet S3398)
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
REVISIONS
VOLTS & PHASE
A - 230/208/60/1 B - 230/208/60/3 C - 460/60/3
KW
1
COLOR OPTIONS
X - Beige (Standard) 1 - White 4 - Buckeye Gray 5 - Desert Brown 8 - Dark Bronze
FILTER OPTIONS
X - One Inch Throwaway (Standard) W - One Inch Washable P - Two Inch Pleated
OUTLET OPTIONS
X - Front (Standard) T - Top Outlet (W30H, W36H Only)
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
CONTROL MODULES
(See Spec. Sheet S3398)
COIL OPTIONS
X - Standard 1 - Phenolic Coated Evaporator 2 - Phenolic Coated Condenser 3 - Phenolic Coated Evaporator
and Condenser
While these instructions are intended as a general
GENERAL
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 3 for information on codes and standards.
Size of unit for a proposed installation should be based on heat loss/gain calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
Manual 2100-511F Page 4 of 27
DUCT WORK
All duct work, supply and return, must be properly sized for the design airflow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
Refer to Maximum ESP of operation Electric Heat Tables 7.
FILTERS
A 1-inch throwaway filter is standard with each unit. The filter slides into position making it easy to service. This filter can be serviced from the outside by removing the filter access panel. A 1-inch washable filter and 2­inch pleated filter are also available as optional accessories. The internal filter brackets are adjustable to accommodate the 2-inch filter by bending two (2) tabs down on each side of the filter support bracket.
Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
Models W18 & W24 are approved for zero inch clearance to the supply duct. For model series W30, W36, W42, W48 and W60 a 1/4 inch clearance to combustible material for the first three feet of duct attached to the outlet air frame is required. See Wall Mounting Instructions and Figures 3 and 4 for further details.
Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.
Some installations may not require any return air duct. A metallic return air grille is required with installations not requiring a return air duct. The spacing between louvers on the grille shall not be larger than 5/8 inch.
Any grille that meets with 5/8 inch louver criteria may be used. It is recommended that Bard Return Air Grille Kit RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used. Contact distributor or factory for ordering information. If using a return air filter grille, filters must be of sufficient size to allow a maximum velocity of 400 fpm.
FRESH AIR INTAKE
All units are built with fresh air inlet slots punched in the service door.
If the unit is equipped with a fresh air damper assembly, the assembly is shipped already attached to the unit. The damper blade is locked in the closed position. To allow the damper to operate, the maximum and minimum blade position stops must be installed. See Figure 1.
All capacity, efficiency and cost of operation information is based upon the fresh air blank-off plate in place and is recommended for maximum energy efficiency.
The blank-off plate is available upon request from the factory and is installed in place of the fresh air damper shipped with each unit.
CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.
NOTE: If no return air duct is used, applicable installation
codes may limit this cabinet to installation only in a single story structure.
FIGURE 1
FRESH AIR DAMPER
Manual 2100-511F Page 5 of 27
INSTALLATION INSTRUCTIONS
WALL MOUNTING INFORMATION
1. Two holes for the supply and return air openings must be cut through the wall as shown in Figure 3.
2. On wood frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration.
3. Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installed unit.
MOUNTING THE UNIT
1. These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides. A bottom mounting bracket, attached to skid for shipping, is provided for ease of installation, but is not required.
2. The unit itself is suitable for 0 inch clearance, but the supply air duct flange and the first 3 feet of supply air duct require a minimum of 1/4 inch clearance to combustible material for model series W30, W36, W42, W48 and W60. However, it is generally recommended that a 1-inch clearance is used for ease of installation and maintaining the required clearance to combustible material. See Figure 3 for details on opening sizes.
3. Locate and mark lag bolt locations and bottom mounting bracket location. See Figure 3.
WARNING
Failure to provide the 1/4 inch clearance between the supply duct and a combustible surface for the first 3 feet of duct can result in fire causing damage, injury or death.
6. Position unit in opening and secure with 5/16 lag bolts; use 7/8 inch diameter flat washers on the lag bolts.
7. Secure rain flashing to wall and caulk across entire length of top. See Figure 3.
8. For additional mounting rigidity, the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance if combustible wall.
9. On side-by-side installations, maintain a minimum of 20 inches clearance on right side to allow access to control panel and heat strips, and to allow proper airflow to the outdoor coil. Additional clearance may be required to meet local or national codes.
4. Mount bottom mounting bracket.
5. Hook top rain flashing, attached to front - right of supply flange for shipping, under back bend of top.
wolfriAresnednoCetauqedAdna
SLEDOM EDISTFEL EDISTHGIR
H63W,H03W,H42W,H81W "51 "02
H06W,H84W,H24W "02 "02
Manual 2100-511F Page 6 of 27
sseccAecivreSrofderiuqeRsecnaraelC
otderiuqeRsecnaraelCmuminiM
slairetaMelbitsubmoC
SLEDOM
H42W/H81W"0"0 H63W/H03W"4/1"0
H06W/H84W/H24W"4/1"0
TCUDRIAYLPPUS
TEEFEERHTTSRIF
TENIBAC
FIGURE 2
)lanimoN(stnemeriuqeRnoitallatsnIdnalarutcetihcrAroftinUcisaBfosnoisnemiD
HTDIW
LEDOM
)W(
1H81W 1H42W
1H03W 1H63W
1H24W 1H84W
1H06W570.24234.22578.4988.988.9288.5188.9288.3465.3166.1400.0386.2449.6396.4434.2473.300.3488.3300.0144.100.6188.1
HTPED
)D(
003.33521.71365.0788.788.9188.1188.9100.5305.8157.5265.0257.6260.8252.9200.7236.231.4360.2255.0100.500.2100.5
002.83521.71365.0788.788.7288.3188.7200.0405.8157.5239.7157.6257.8252.9200.7236.231.9357.2241.900.500.2100.5
570.24234.22578.4888.988.9288.5188.9288.3401.9166.1300.0386.2349.6296.4334.2373.300.3488.3200.0144.100.6188.1
THGIEH
)H(
All dimensions are in inches. Dimensional drawings are not to scale.
YLPPUSNRUTER
AB C B E F G I J K L MNO P QRST
W**H RIGHT UNIT
FRONT VIEW
SIDE VIEW
*Optional top outlet (factory installed only) for W30H and W36H models only.
BACK VIEW
Manual 2100-511F Page 7 of 27
FIGURE 3A
W18H1, W24H1
MOUNTING INSTRUCTIONS
Manual 2100-511F Page 8 of 27
FIGURE 3B
W30H1, W36H1
MOUNTING INSTRUCTIONS
Manual 2100-511F Page 9 of 27
FIGURE 3C
W42H1, W48H1, W60H1
MOUNTING INSTRUCTIONS
Manual 2100-511F Page 10 of 27
FIGURE 4
ELECTRIC HEAT CLEARANCE
W30H1, W36H1, W42H1, W48H1, W60H1
SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1/4 INCH CLEARANCE TO COMBUSTIBLE SURFACES.
WARNING
A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting.
It is important to insure that the 1/4 inch minimum spacing is maintained at all points.
Failure to do this could result in overheating the combustible material and may result in a fire causing damage, injury or death.
Manual 2100-511F Page 11 of 27
WALL MOUNTING INSTRUCTIONS
SEE FIGURE 3 – MOUNTING INSTRUCTIONS
FIGURE 5
FIGURE 6
WALL MOUNTING INSTRUCTIONS
IF REQUIRED
IF REQUIRED
SEE UNIT DIMENSIONS, FIGURE 2, FOR ACTUAL DIMENSIONS
Manual 2100-511F Page 12 of 27
FIGURE 7
COMMON WALL MOUNTING INSTALLATIONS
Manual 2100-511F Page 13 of 27
WIRING – MAIN POWER
Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75° C copper) for all models including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.
The unit rating plate lists a “Maximum Time Delay Relay Fuse” or “HACR” type circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.
WIRING – LOW VOLTAGE WIRING
230/208V, 1 phase and 3 phase equipment dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:
TAP RANGE
240 253 – 216 208 220 – 187
NOTE: The voltage should be measured at the field power
connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).
For wiring size and connections, refer to Wiring Manual 2100-516.
The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect. To convert for the locking capability, bend the tab located in the bottom left-hand corner of the disconnect opening under the disconnect access panel straight out. This tab will now line up with the slot in the door. When shut, a padlock may be placed through the hole in the tab preventing entry.
See “Start Up” section for important information on three phase scroll compressor start ups.
See Table 4 for Electrical Specifications.
Manual 2100-511F Page 14 of 27
START UP
THESE UNITS REQUIRE R-410A REFRIGERANT AND POLYOL ESTER OIL.
GENERAL:
1. Use separate service equipment to avoid cross contamination of oil and refrigerants.
2. Use recovery equipment rated for R-410A refrigerant.
3. Use manifold gauges rated for R-410A (800 psi/250 psi low).
4. R-410A is a binary blend of HFC-32 and HFC-125.
5. R-410A is nearly azeotropic - similar to R-22 and R-12. Although nearly azeotropic, charge with liquid refrigerant.
6. R-410A operates at 40-70% higher pressure than R-22, and systems designed for R-22 cannot withstand this higher pressure.
7. R-410A has an ozone depletion potential of zero, but must be reclaimed due to its global warming potential.
8. R-410A compressors use Polyol Ester oil.
9. Polyol Ester oil is hygroscopic; it will rapidly absorb moisture and strongly hold this moisture in the oil.
10. A liquid line dryer must be used - even a deep vacuum will not separate moisture from the oil.
11. Limit atmospheric exposure to 15 minutes.
12. If compressor removal is necessary, always plug compressor immediately after removal. Purge with small amount of nitrogen when inserting plugs.
TOPPING OFF SYSTEM CHARGE
If a leak has occurred in the system, Bard Manufacturing recommends reclaiming, evacuating (see criteria above), and charging to the nameplate charge. If done correctly, topping off the system charge can be done without problems.
With R-410A, there are no significant changes in the refrigerant composition during multiple leaks and recharges. R-410A refrigerant is close to being an azeotropic blend (it behaves like a pure compound or single component refrigerant). The remaining refrigerant charge, in the system, may be used after leaks have occurred and then “top-off” the charge by utilizing the pressure charts on the inner control panel cover as a guideline.
REMEMBER: When adding R-410A refrigerant, it must come out of the charging cylinder/tank as a liquid to avoid any fractionation, and to insure optimal system performance. Refer to instructions for the cylinder that is being utilized for proper method of liquid extraction.
WARNING
Failure to conform to these practices could lead to damage, injury or death.
SAFETY PRACTICES:
1. Never mix R-410A with other refrigerants.
2. Use gloves and safety glasses, Polyol Ester oils can be irritating to the skin, and liquid refrigerant will freeze the skin.
3. Never use air and R-410A to leak check; the mixture may become flammable.
4. Do not inhale R-410A – the vapor attacks the nervous system, creating dizziness, loss of coordination and slurred speech. Cardiac irregularities, unconsciousness and ultimate death can result from breathing this concentration.
5. Do not burn R-410A. This decomposition produces hazardous vapors. Evacuate the area if exposed.
6. Use only cylinders rated DOT4BA/4BW 400.
7. Never fill cylinders over 80% of total capacity.
8. Store cylinders in a cool area, out of direct sunlight.
9. Never heat cylinders above 125°F.
10. Never trap liquid R-410A in manifold sets, gauge lines or cylinders. R-410A expands significantly at warmer temperatures. Once a cylinder or line is full of liquid, any further rise in temperature will cause it to burst.
Manual 2100-511F Page 15 of 27
START UP (Continued)
IMPORTANT INSTALLER NOTE
For improved start up performance wash the indoor coil with a dish washing detergent.
HIGH & LOW PRESSURE SWITCH
All W**H wall mounted air conditioner series models are supplied with a remote reset for the high and low pressure switch. If tripped, this pressure switch may be reset by turning the thermostat off then back on again.
THREE PHASE SCROLL COMPRESSOR START UP INFORMATION
Scroll compressors, like several other types of compressors, will only compress in one rotational direction. Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction.
However, three phase compressors will rotate in either direction depending upon phasing of the power. Since there is a 50-50 chance of connecting power in such a way as to cause rotation in the reverse direction, verification of proper rotation must be made. Verification of proper rotation direction is made by observing that suction pressure drops and discharge pressure rises when the compressor is energized. Reverse rotation also results in an elevated sound level over that with correct rotation, as well as substantially reduced current draw compared to tabulated values.
Verification of proper rotation must be made at the time the equipment is put into service. If improper rotation is corrected at this time, there will be no negative impact on the durability of the compressor. However, reverse operation for over one hour may have a negative impact on the bearing due to oil pump out.
NOTE: If compressor is allowed to run in reverse rotation
for several minutes, the compressor’s internal protector will trip.
PHASE MONITOR
All units with three phase scroll compressors are equipped with a 3 phase line monitor to prevent compressor damage due to phase reversal.
The phase monitor in this unit is equipped with two LEDs. If the Y signal is present at the phase monitor and phases are correct the green LED will light.
If phases are reversed, the red fault LED will be lit and compressor operation is inhibited.
If a fault condition occurs, reverse two of the supply leads to the unit. Do not reverse any of the unit factory
wires as damage may occur.
CONDENSER FAN OPERATION
Applies to W42, W48 and W60 models only. The condenser fan motor on 230/208 volt, one and three phase, 60 HZ units is a two-speed motor that comes factory wired on high speed for peak performance. If ambient conditions permit, it can be reconnected to low speed (red wire) for lower sound level. See wiring diagram.
50 HZ models must have fan wired on low speed. These models are factory wired on low speed.
SERVICE HINTS
1. Caution owner/operator to maintain clean air filters at all times. Also, not to needlessly close off supply and return air registers. This reduces airflow through the system, which shortens equipment service life as well as increasing operating costs.
2. Check all power fuses or circuit breakers to be sure they are the correct rating.
3. Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential.
All three phase ZP compressors are wired identically internally. As a result, once the correct phasing is determined for a specific system or installation, connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction.
The direction of rotation of the compressor may be changed by reversing any two line connections to the unit.
Manual 2100-511F Page 16 of 27
SEQUENCE OF OPERATION
COOLING – Circuit R-Y makes at thermostat pulling in
compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation. HEATING – A 24V solenoid coil on reversing valve controls heating cycle operation. Two thermostat options, one allowing “Auto” changeover from cycle to cycle and the other constantly energizing solenoid coil during heating season, and thus eliminating pressure equalization noise except during defrost, are to be used. On “Auto” option a circuit is completed from R­W1 and R-Y on each heating “on” cycle, energizing reversing valve solenoid and pulling in compressor contactor starting compressor and outdoor motor. R-G also make starting indoor blower motor. Heat pump heating cycle now in operation. The second option has no “Auto” changeover position, but instead energizes the reversing valve solenoid constantly whenever the system switch on subbase is placed in “Heat” position, the “B” terminal being constantly energized from R. A Thermostat demand for heat completes R-Y circuit, pulling in compressor contactor starting compressor and outdoor motor. R-G also make starting indoor blower motor.
PRESSURE SERVICE PORTS
High and low pressure service ports are installed on all units so that the system operating pressures can be observed. Pressure tables can be found later in the manual covering all models. It is imperative to match the correct pressure table to the unit by model number. See Tables 3A & 3B.
DEFROST CYCLE
The defrost cycle is controlled by temperature and time on the solid state heat pump control. When the outdoor temperature is in the lower 40°F temperature range or colder, the outdoor coil temperature is 32°F or below. This coil temperature is sensed by the coil temperature sensor mounted near the bottom of the outdoor coil. Once coil temperature reaches 30°F or below, the coil temperature sensor sends a signal to the control logic of the heat pump control and the defrost timer will start accumulating run time. After 30, 60 or 90 minutes of heat pump operation at 30°F or below, the heat pump control will place the system in the defrost mode. During the defrost mode, the refrigerant cycle switches back to the cooling cycle, the outdoor motor stops, electric heaters are energized, and hot gas passing through the outdoor coil melts any accumulated frost. When the temperature rises to approximately 57°F, the coil temperature sensor will send a signal to the heat pump control which will return the system to heating operations automatically. If some abnormal or temporary condition such as a high wind causes the heat pump to have a prolonged defrost cycle, the heat pump control will restore the system to heating operation automatically after 8 minutes. The heat pump defrost control board has an option of 30, 60 or 90-minute setting. By default, this unit is shipped from the factory with the defrost time on the 60 minute pin. If circumstances require a change to another time, remove the
wire from the 60-minute terminal and reconnect to the desired terminal. Refer to Figure 8. There is a cycle speed up jumper on the control. This can be used for testing purposes to reduce the time between defrost cycle operation without waiting for time to elapse. Use a small screwdriver or other metallic object, or another ¼ inch QC, to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost. Be careful not to touch any other terminals with the instrument used to short the SPEEDUP terminals. It may take up to 10 seconds with the SPEEDUP terminals shorted for the speedup to be completed and the defrost cycle to start.
As soon as the defrost cycle kicks in remove the shorting instrument from the SPEEDUP terminals. Otherwise the
timing will remain accelerated and run through the 1-minute minimum defrost length sequence in a matter of seconds and will automatically terminate the defrost sequence. There is an initiate defrost jumper (sen jump) on the control that can be used at any outdoor ambient during the heating cycle to simulate a 0° coil temperature. This can be used to check defrost operation of the unit without waiting for the outdoor ambient to fall into the defrost region. By placing a jumper across the SEN JMP terminals (a ¼ inch QC terminal works best) the defrost sensor mounted on the outdoor coil is shunted out & will activate the timing circuit. This permits the defrost cycle to be checked out in warmer weather conditions without the outdoor temperature having to fall into the defrost region. In order to terminate the defrost test the SEN JMP jumper must be removed. If left in place too long, the compressor could stop due to the high pressure control opening because of high pressure condition created by operating in the cooling mode with outdoor fan off. Pressure will rise fairly fast as there is likely no actual frost on the outdoor coil in this artificial test condition. There is also a 5-minute compressor time delay function built into the HPC. This is to protect the compressor from short cycling conditions. The board’s LED will have a fast blink rate when in the compressor time delay. In some instances, it is helpful to the service technician to override or speed up this timing period, and shorting out the SPEEDUP terminals for a few seconds can do this. Low Pressure Switch Bypass Operation - The control has a selectable (SW1) low pressure switch bypass set up to ignore the low pressure switch input during the first (30, 60, 120 or 180 seconds) of “Y” operation. After this period expires, the control will then monitor the low pressure switch input normally to make sure that the switch is closed during “Y” operation. High Pressure Switch Operation - The control has a built-in lockout system that allows the unit to have the high pressure switch trip up to two times in one hour and only encounter a “soft” lockout. A “soft” lockout shuts the compressor off and waits for the pressure switch to reset, which at that point then allows the compressor to be restarted as long as the 5-minute short cycle timer has run out. If the high pressure switch trips a third time within one hour, the unit is in “hard” lockout indicating something is certainly wrong and it will not restart itself.
Manual 2100-511F Page 17 of 27
FIGURE 8
DEFROST CONTROL BOARD
LOW PRESSURE BYPASS TIMER SWITCH *(FACTORY SETTING 120 SECONDS)
SW1SW
2 TIME (SEC)
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
ON
30 60
120*
180
Manual 2100-511F Page 18 of 27
ACCUMULATED DEFROST TIME TIMER (FACTORY SETTING 60 MIN.)
MIS-2668 A
TROUBLESHOOTING
SOLID STATE HEAT PUMP CONTROL TROUBLESHOOTING PROCEDURE
1. NOTE: A thorough understanding of the defrost
cycle sequence is essential. Review that section earlier in this manual prior to troubleshooting the control. Turn on AC power supply to unit.
2. Turn thermostat blower switch to “fan on” – the indoor blower should start. (If it doesn’t, troubleshoot indoor unit and correct problem.)
3. Turn thermostat blower to “auto” position. Indoor blower should stop. NOTE: Many models have a
1-minute blower time delay on “off” command; wait for this to time-out.
4. Set system switch to “heat” or “cool”. Adjust thermostat to call for heat or cool. The indoor blower, compressor and outdoor fan should start.
TROUBLESHOOTING
motpmySsesuaCelbissoP&kcehC,noitpircseD riapeR/kcehCotwoH&tahW
lliwrosserpmoC
gnitaeh(tratston
)gniloocro
.sedockcehC.4
?gniknilbsiedoctahW
.draobytluaF.31
rotomroodtuonaF
nurtonseod
gnitaehrognilooc(
gnirudtpecxe
)tsorfed
evlavgnisreveR
ezigrenetonseod
)ylnognitaeh(
ogtonlliwtinU
tsorfedotni
)ylnognitaeh(
emoctonlliwtinU tsorfedfotuo )ylnognitaeh(
evitcefedrotoM
.noitanimulliDELrofkcehC.1
?)gnihsalf(draobehtnodetanimulliDELnaerehtsI
.sedocrorrerofkcehC.2
?edoCagnihsalfDELehtsI
.draobtarewoprofkcehC.3
?CdnaRneewtebCAstlov42erehtsI
.evitcayaledrosserpmoC.5
.tluaferusserpwoL.6
.tluaferusserphgiH.7
.langistupnirosserpmoCrofkcehC.8
?CdnaYneewtebCAstlov42erehtsI
.draobotrewopoN.9
.langistuptuorosserpmoCrofkcehC.01
?C&CCneewtebCAstlov42erehtsI
.langistupnirosserpmoc"Y"oN.11 yllanifdna,)rotinoMesahPnonoitcesees(tinufoesahptcerrocni,gniriwtatsomrehtkcehC
.langistuptuorosserpmoc"CC"oN.21
evitcefedlortnocpmuptaeH
evitcefedroticapacrotoM
evitcefedlortnocpmuptaeH
evitcefedliocdionelosevlavgnisreveR
evitcefedlortnocpmuptaehrorosneserutarepmeT
evitcefedlortnocpmuptaehrorosneserutarepmeT
TABLE 1
."snippudeeps"s'draobpmujroyaledetunim5roftiaW
NOTE: If there was no power to 24 volt transformer,
the compressor and outdoor fan motor will not start for 5 minutes. This is because of the compressor short cycle protection.
LED BLINK CODES
BLINK FUNCTION
Slow Normal function (1.0 sec on/1.0 sec off) Fast ASCD timer active (0.1 sec on/0.1 sec off) 1 Low pressure switch failure 2 High pressure switch failure/“Soft” Lockout 3 Defrost mode active 4 High pressure switch failure/“Hard” Lockout
3#petSotog=oN;2#petSotog=seY
8#petSotog=oN;4#petSotog=seY
9#petSotog=oN;31#petSotog=seY
5#petSotog,knilBtsaF;7#petSotog,"2"edoC;6#petSotog,"1"edoC
.1#petSotkcabog,dedeenllitsfi;noitareporeporprofkcehC
.serusserptinudnatiucricgniriwkcehC .serusserptinudnatiucricgniriwkcehC
11#petSotog=oN;01#petSotog=seY
.tcerrocnisigniriwtinuehtrodabsiremrofsnarteht,egatlovtinuevahtonseodrehtietinuehT
31#petSotog=oN;21#petSotog=seY
.gniriwtinu
.rosserpmockcehcyllanifdnanoitareporeporprofrotcatnocrosserpmockcehC
.draobtsorfedecalpeR
)CN-moC(.lortnocpmuptaehnoyalernafssorcakcehC
.lortnocpmuptaehecalpeR
.rotomecalpeR.gnidniwrotomdetrohsroneporofkcehC
.roticapacecalpeR.roticapacdetrohsroneporofkcehC.gnitarroticapackcehC
.C-BdnaC-VRneewtebV42rofkcehC
.gniriwtiucriclortnockcehC.1
lortnocpmuptaehecalpeR.2
.liocdetrohsroneporofkcehC
.liocdionelosecalpeR
NES"dnaslanimret"PUDEEPS"ssorcarepmujdnadraobmorfrosneserutarepmettcennocsiD
.etunimenonihtiwelcyctsorfedahguorhtogottinuehtesuacdluohssihT.slanimret"PMJ
.rosneserutarepmetecalper,elcyctsorfedhguorhtseogtinufI.1
.lortnocpmuptaehecalper,elcyctsorfedhguorhtogtonseodtinufI.2
.lanimret"PUDEEPS"ssorcarepmuJ
.etunimenonihtiwtsorfedfotuoemocottinuehtesuacdluohssihT
.rosneserutarepmetecalper,elcyctsorfedfotuosemoctinufI.1
.lortnocpmuptaehecalper,elcyctsorfedfotuoemoctonseodtinufI.2
Manual 2100-511F Page 19 of 27
CHECKING TEMPERATURE SENSOR OUTSIDE UNIT CIRCUIT
1. Disconnect temperature sensor from board and from outdoor coil.
2. Use an ohmmeter and measure the resistance of the sensor. Also use ohmmeter to check for short or open.
3. Check resistance reading to chart of resistance. Use sensor ambient temperature. (Tolerance of part is ± 10%.)
4. If sensor resistance reads very low, then sensor is shorted and will not allow proper operation of the heat pump control.
5. If sensor is out of tolerance, shorted, open or reads very low ohms then it should be replaced.
TEMPERATURE F VS. RESISTANCE R OF TEMPERATURE SENSOR
FR FR FR FR
0.52-
0.42-
0.32-
0.22-
0.12-
0.02-
0.91-
0.81-
0.71-
0.61-
0.51-
0.41-
0.31-
0.21-
0.11-
0.01-
0.9-
0.8-
0.7-
0.6-
0.5-
0.4-
0.3-
0.2-
0.1-
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
0.01
0.11
0.21
178691 990091 585381 813771 982171 784561 409951 925451 553941 473441 675931 659431 605031 912621 980221 801811 272411 575011 010701 475301 062001 46079
18939 80019 93188
17358 99628
12108 23677 03257 01927 07607 70586 81466 99346 94426 56506 54785
0.31
0.41
0.51
0.61
0.71
0.81
0.91
0.02
0.12
0.22
0.32
0.42
0.52
0.62
0.72
0.82
0.92
0.03
0.13
0.23
0.33
0.43
0.53
0.63
0.73
0.83
0.93
0.04
0.14
0.24
0.34
0.44
0.54
0.64
0.74
0.84
0.94
0.05
58965 48255 04635
15025 41505 82094 09574 00264 55844 45534 59224 77014 89893 75783 25673 38563 84553 54543 47533 43623 32713 04803 68992 75192 55382 77572 32862 29062 38352 69642 03042 48332 85722 05122
16512 98902 53402 69891
0.35
0.25
0.35
0.45
0.55
0.65
0.75
0.85
0.95
0.06
0.16
0.26
0.36
0.46
0.56
0.66
0.76
0.86
0.96
0.07
0.17
0.27
0.37
0.47
0.57
0.67
0.77
0.87
0.97
0.08
0.18
0.28
0.38
0.48
0.58
0.68
0.78
0.88
47391 76881 57381 98971 43471 48961 74561 22161 01751 01351
12941 44541 77141 02831 47431 73131 01821 29421 38121 38811
19511 70311
13011 26701
10501 74201 00001 0679 6259 9929 7709 2688 3568 9448 0528 7508 9687 6867
0.98
0.09
0.19
0.29
0.39
0.49
0.59
0.69
0.79
0.89
0.99
0.001
0.101
0.201
0.301
0.401
0.501
0.601
0.701
0.801
0.901
0.011
0.111
0.211
0.311
0.411
0.511
0.611
0.711
0.811
0.911
0.021
0.121
0.221
0.321
0.421
7057 4337 5617 0007 0486 3866
1356 3836 9326 8906
1695 7285 7965 0755 6445 6235 8025 4905 2894 3784 7674 3664 2654 4644 7634 4724 2814 3904 6004
1293 8383 7573 8763
1063 6253 2543
Manual 2100-511F Page 20 of 27
TROUBLESHOOTING
FAN BLADE SETTING DIMENSIONS
Shown in Figure 9 is the correct fan blade setting for proper air delivery across the outdoor coil. Refer to Table 2 for unit specific dimension.
Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly.
FIGURE 9
FAN BLADE SETTING
AIRFLOW
"A"
MIS-1724
TABLE 2
FAN BLADE DIMENSION
ledoM
1H81W 1H42W
1H03W 1H63W
1H24W 1H84W 1H06W
noisnemiD
A
"00.1
"52.1
"57.1
REMOVAL OF FAN SHROUD
1. Disconnect all power to the unit.
2. Remove the screws holding both grilles, one on each side of unit, and remove grilles.
3. Remove screws holding fan shroud to condenser and bottom. Nine (9) screws.
4. Unwire condenser fan motor.
5. Slide complete motor, fan blade, and shroud assembly out the left side of the unit.
6. Service motor/fan as needed.
7. Reverse steps to reinstall.
R-410A
REFRIGERANT CHARGE
This unit was charged at the factory with the quantity of refrigerant listed on the serial plate. AHRI capacity and efficiency ratings were determined by testing with this refrigerant charge quantity.
The following pressure tables show nominal pressures for the units. Since many installation specific situations can affect the pressure readings, this information should only be used by certified technicians as a guide for evaluating proper system performance. They shall not be used to adjust charge. If charge is in doubt, reclaim, evacuate and recharge the unit to the serial plate charge.
Manual 2100-511F Page 21 of 27
TABLE 3A
COOLING PRESSURE TABLE
ledoM
1H81W
1H42W
1H03W
1H63W
1H24W
1H84W
1H06W
Low side pressure ± 4 PSIG High side pressure ± 10 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate charge weight.
NOTE: Pressure table based on high speed condenser fan operation. If condensing pressures appear elevated check condenser fan wiring. See “Condenser Fan Operation”.
riAnruteR
erutarepmeTerusserP5708580959001501011511021
BD.ged57 BW.ged26
BD.ged08 BW.ged76
BD.ged58 BW.ged27
BD.ged57 BW.ged26
BD.ged08 BW.ged76
BD.ged58 BW.ged27
BD.ged57 BW.ged26
BD.ged08 BW.ged76
BD.ged58 BW.ged27
BD.ged57 BW.ged26
BD.ged08 BW.ged76
BD.ged58 BW.ged27
BD.ged57 BW.ged26
BD.ged08 BW.ged76
BD.ged58 BW.ged27
BD.ged57 BW.ged26
BD.ged08 BW.ged76
BD.ged58 BW.ged27
BD.ged57 BW.ged26
BD.ged08 BW.ged76
BD.ged58 BW.ged27
ediSwoL
231
431
731
831
ediShgiH
292
113
233
ediSwoL
ediSwoL
ediSwoL
ediSwoL
ediSwoL
ediSwoL
ediSwoL
ediSwoL
ediSwoL
ediSwoL
ediSwoL
ediSwoL
ediSwoL
ediSwoL
ediSwoL
ediSwoL
ediSwoL
ediSwoL
ediSwoL
ediSwoL ediShgiH
141
341
ediShgiH
992 641
ediShgiH
903 421
ediShgiH
923 331
ediShgiH
733 831
ediShgiH
943 521
ediShgiH
623 431
ediShgiH
433 931
ediShgiH
643 221
ediShgiH
923
131
ediShgiH
733 631
ediShgiH
943 721
ediShgiH
453 631
ediShgiH
363
141
ediShgiH
673 921
ediShgiH
253 831
ediShgiH
163
341
ediShgiH
473 621
ediShgiH
233 531
ediShgiH
143
041 353
641
913
043
841
151
033
253
621
821
153
373
531
731
063
383
041
241
373
693
821
131
053
373
731
041
953
383
241
541
273
693
421
621
153
573
331
531
063
583
831
041
373
893
031
231
273
293
931
141
283
204
441
641
593
614
231
431
473
893
141
341
483
804
641
841
793
224
821
131
253
373
731
041
163
383
241
541
473
693
041
353
673
841
051
263
683
351
551
573
004
131
331
893
324
041
241
804
434
541
741
224
944
331
631
893
324
241
441
804
834
741
051
224
944
821
031
993
424
731
731
904
444
241
441
324
054
431
531
314
734
341
341
424
254
841
941
934
464
631
731
224
944
541
741
334
064
051
251
844
674
331
531
793
124
241
341
704
434
741
941
124
744
Air Temperature Entering Outdoor Coil °F
241
441
641
841
004
424
054
251
451
014 751
424
531 944
441 064
941 674
731 844
741 954
251 574
231 944
141 164
641 774
631
164
541 374
051 094
931 674
941 884
451 505
731 844
741 954
251 574
651
534
264
951
161
054
874
731
831
574
305
641
841
784
615
151
351
405
435
931
141
274
694
941
151
484
905
451
651
105
725
531
731
674
305
441
641
884
615
941
151
505
435
731
731
884
615
641
641
005
925
151
151
815
845
141
341
505
535
151
351
815
945
651
851
635
865
931
141
674
505
941
151
884
815
451
651
505
635
051
774
505
851
061
984
815
461
661
605
635
041
241
135
165
051
251
545
575
551
751
465
595
341
541
225
745
351
551
535
165
851
061
455
185
831
141
035
955
841
151
445
375
351
651
365
395
731
631
645
875
641
541
065
395
151
051
085
416
541
641
665
006
551
651
185
516
061
161
106
736
341
541
635
865
351
551
055
385
851
061
965
306
TABLE 3B
HEATING PRESSURES – (ALL TEMPERATURES °F)
ledoM
H81W.ged07
H42W.ged07
H03W.ged07
H63W.ged07
H24W.ged07
H84W.ged07
H06W.ged07
riAnruteR
erutarepmeTerusserP050151025203530454055506
ediSwoL
84
25
65
16
66
27
97
78
59
401
411
ediShgiH
092
582
282
282
582
092
792
703
913
433
ediSwoL
75
55
55
75
95
46
07
77
68
ediShgiH
292
692
103
703
413
323
233
243
ediSwoL
35
35
55
85
16
66
27
ediShgiH
452
662
872
092
103
213
ediSwoL
74
94
15
55
95
ediShgiH
182
282
382
782
ediSwoL
05
05
25
ediShgiH
992
003
ediSwoL
24
ediShgiH
ediSwoL
ediShgiH
54
862
072
93
34
492
692
45
303
803
94
45
472
872
74
25
003
503
46
292
003
85
26
413
223
95
46
482
192
85
36
113
913
08
223
233
07
77
803
913
86
57
133
243
07
77
892
703
07
67
823
833
69
453
763
88
79
243
153
58
39
133
543
48
39
553
073
48
29
713
723
48
29
943
263
421
253
273
801
121
083
593
801
911
063
963
301
311
163
973
401
511
683
404
001
901
933
253
001
901
673
193
531 493
531
114
231 773
421 893
821 324
811 663
811 804
Manual 2100-511F Page 22 of 27
TABLE 4
Electrical Specifications — W**H Series
tiucriCelgniS tiucriClauD
42W1HZ0B,00B-
42W1HZ0C,00C-
3 80A
3 80A
3 *01A
3 *90B
3 *90C
3 *01A 5 51A
3 *90B 5 51B
3 *90C
3 01A
5 51A
3 90B
5 51B
3 90C
5 51C
3 01A 5 51A 5 02A
3 90B 5 51B 5 81B
3 90C
5 51C
3 01A 5 51A 5 02A
3 90B 5 51B 5 81B
3 90C 5 51C
ledoM
Z0A,00A-1H81W
40A
Z0A,00A-1H42W
40A
60B
60C
*Z0A,00A-1H03W
*50A
*Z0B,00B-1H03W
60B
*Z0C,00C-1H03W
60C 51C
*Z0A,00A-1H63W
50A
*Z0B,00B-1H63W
60B
*Z0C,00C-1H63W
60C 51C
Z0A,00A-1H24W
50A
Z0B,00B-1H24W
60B
Z0C,00C-1H24W
60C
Z0A,00A-1H84W 40A 50A
Z0B,00B-1H84W 60B
Z0C,00C-1H84W
Z0A,00A-1H06W 50A
Z0B,00B-1H06W
Z0C,00C-1H06W
detaR
stloV
esahPdna
1-802/032
1-802/032
3-802/032
3-064
1-802/032
3-802/032
3-064
1-802/032
3-802/032
3-064
1-802/032
3-802/032
3-064
1-802/032
3-802/032
3-064
1-802/032
3-802/032
3-064
4 muminiM
dleiF.oN rewoP stiucriC
1 1 1 1 1 1 1 1 1 1 1 1
2ro1 1 1 1 1 1 1 1 1 1
2ro1
2ro1 1 1 1 1 1 1 1 1 1 1
2ro1
2ro1 1 1 1 1 1 1 1 1 1 1
2ro1
2ro1
2ro1
2ro1 1 1 1 1
2ro1 1
1 1
1
2ro1
2ro1
2ro1
2ro1 1 1 1 1 1 1 1
1 mumixaM
tiucriC
yticapmA
61 73 85 42 44 56 71 53
11
12 42 05 67 81 63 54
11 02 52 62 92 55
18 48 32 14 05
15 21
12 52 62 63 26 88 88 62 44 35 35 31 22 62 62 73 85 36 98 98
111 92 74 65 65 26 41 72 72 14 76 39 39
111 82 55 55 26 61 82 82
2 dleiF esuFlanretxE .rkrB.tkCro
02 04 06 52 05 07 02 04 51 52 53 05 08 52 04 54 51 02 52 03 04 06 09 09 03 54 05 06 51 52 52 03 05 07 09 09 53 05 06 06 51 52 03 03 05 06 07 09 09
521 53 05 06 06 07 02 03 03 06 08
001
001
521 04 06 06 07 02 03 03
2 dnuorG
rewoP
eziSeriW
21 8 6
01 8 6
21 8
41
01 8 8 4
01 8 8
41
21
01
01 8 6 4 4
01 8 8 8
41
01
01
01 8 6 3 3 8 8 6 6
41
01
01
01 8 6 6 3 3 2 8 8 6 6 6
21
01
01 8
4 3 3 2 8 6 6 6
21
01
01
1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes. 3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article
310 for power conductor sizing. Caution: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310
regarding Ampacity Adjustment Factors when more than three (3) current carrying conductors are in a raceway. * Top outlet supply option is available only factory installed and only on the selected models. IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in
accordance with the National Electrical Code and all local codes.
4 muminiM
eriW
21 01 01 01 01
8
21 01 41 01 01 01
8056205038 010101
01 01 01 41 21 01 01 01
01 8 8
01
01
01
01
41
01
01
01
01 8 8 8
01
01
01
01
41
01
01
01
01
01 8 8 8 6
01
01
01
01 8
21
01
01
01 8 8 8 6
01
01
01
01438204038010101
21
01
01
A.tkC B.tkC A.tkC B.tkC A.tkC B.tkC A.tkC B.tkC
44 12 54 52 8 01 01 01
55 55
63 63 63
73 73 73 95
43 82 04 03 8 01 01 01
14 14 14 95
1 mumixaM
tiucriC
yticapmA
62
06
25
06
62
05
25
05
25
05
62
05
25
05
25
05
25
06
62
06
25
06
25
06
25
06
2 dleiF
esuFlanretxE
rekaerB.tkCro
03
6
06
6
03
8
06
8
06
8
03
8
06
8
06
8
06
6
03
8
06
8
06
8
06
6
2 dnuorG
rewoP
eziSeriW
01
01
6
01
01
01
6
01
6
01
01
01
6
01
6
01
6
01
01
01
6
01
6
01
6
01
Manual 2100-511F Page 23 of 27
eziSeriW
01 01
01 01 01
01 01 01 01
01 01 01 01
TABLE 5
RECOMMENDED AIRFLOW
detaR
ledoM
*MFC
H81W006 1 03.527-575hgiH H42W00802.059-007hgiH H03W000104.0031-039hgiH H63W001103.0531-039hgiH H24W004103.0511-0061hgiH H84W055102.5821-0571hgiH H06W056103.5731-0591hgiH
* Rated CFM and ESP on high speed tap. 1 Rated CFM and ESP on low speed tap.
detaR
*PSE
dednemmoceR
egnaRwolfriA
deepSyrotcaF
noitcennoC
TABLE 6
INDOOR BLOWER PERFORMANCE
H42W,H81WH81WH63W,H03WH84W,H24WH06W
.P.S.E
nI
O
H
2
0.
1.
2.
3.
4.
5.
yrD
069 568 028 537 516
deepShgiHdeepSwoLdeepShgiHdeepSwoLdeepShgiHdeepSwoLdeepShgiHdeepSwoL teW
lioC
0201
yrD
lioC
579
057
509
537
008
017
537
066
056
506
535
045
teW
lioC
yrD
lioC
007 576 056 006 055
094
teW
lioC
5931 0431 5821 5021 0111 5001
yrD
lioC
5131 0721 0911 0011 0001
078
teW
lioC
059 039 019 558 008
yrD
lioC
539 519 588 038 557
teW
lioC
5881 0771 5361 0051 0731 0521
yrD
lioC
0081 5661 0451 0041 5821
0511
teW
lioC
lioC
0561
0061
0551
0051
0541
0041
0531
0031
0031
5711
yrD
teW
lioC
0022 0012 0002 5781 5771 0561
yrD
lioC
0002 0091 0081
0071
0061
5741
teW
lioC
lioC
0061
0541
5251
5731 — — — —
Manual 2100-511F Page 24 of 27
ledoMPSE
1H81W 1H42W
1H42W
1H42W
TABLES 7
MAXIMUM ESP OF OPERATION
ELECTRIC HEAT ONLY
00A 40A 80A
00B 60B
00C 60C
05.
05.
04.
1H03W 1H63W
05.
05.
05.
1H03W 1H63W
05.
1H03W 1H63W
teltuOtnorFteltuOpoT
ledoM
00A 50A 01A 51A
00B 60B 90B 51B
00C 60C 90C 51C
deepS
05.
04.
53.
53.
05.
04.
53.
53.
05.
05.
03.
03.
woL
hgiH
deepS
05.
05.
04.
04.
05.
05.
54.
54.
05.
05.
04.
04.
woL
deepS
05.
04.
52.
AN
05.
AN
03.
AN
05.
AN
53.
AN
hgiH
deepS
05.
05.
04.
AN
05.
AN
04.
AN
05.
AN
54.
AN
ledoM
WKdeepS
00A­40A­50A­01A­51A­02A-
00B­90B­51B­81B-
00C­90C­51C-
05.
-----
05.
05.
05.
-----
05.
05.
05.
-----
05.
05.
05.
1H24W1H84W1H06W
deepShgiHdeepSwoLdeepShgiHdeepSwoLdeepShgiHdeepSwoL
05.
-----
05.
54.
54.
-----
05.
54.
54.
-----
05.
04.
04.
05.
05.
05.
05.
05.
05.
05.
05.
05.
05.
05.
05.
05.
05.
05.
05.
54.
54.
54.
05.
54.
54.
54.
05.
04.
04.
05.
-----
05.
05.
05.
05.
05.
05.
05.
05.
05.
05.
05.
TABLE 8
ELECTRIC HEAT
sledoM1-V0421-V8023-V0423-V8023-V064
WKspmAHUTBspmAHUTBspmAHUTBspmAHUTBspmAHUTB
47.61056314.4104201
04.
-----
52.
52.
52.
52.
04.
03.
03.
03.
04.
53.
53.
58.02560711.8100821
64.41005025.21063512.700502
83.33003728.8257402
97.12006037.81030328.0100703
016.14031432.6300652 21 4.4105904
515.26052150.45004832.63002152.13004830.8100215
813.34034165.7300164
022.38062861.2700215
Manual 2100-511F Page 25 of 27
OPTIONAL ACCESSORIES
rebmuNtraP
W18H1-A
W24H1-A
W24H1-B
40A-A20HWHEX
80A-A20HWHEX 40A-H42WHEX 80A-H42WHEX 60B-H42WHEX 50A-03HWHEX 01A-03HWHEX 50A-63HWHEX 01A-63HWHEX 51A-63HWHEX 60B-30HWHEX 60B-H63WHEX 90B-30HWHEX 51B-H03WHEX
60C-A30CWHEXX
HEATER KITS
PULL DISCONNECT (WMPD)
CIRCUIT BREAKER (WMCB) &
50A-24HWHE XX 01A-24HWHE XX 51A-24HWHE XX
02A-40-HWHE XX 60B-50HWHE XX 90B-50HWHE XXX 51B-50HWHE XXX 60C-24HWHE X
90C-A50HWHE XXX
51C-A50HWHE XXX 51A-40HWHE X 01A-40HWHE X 81B-H50WHE XX
A20-BCMWX B20-BCMWX A30-BCMWX B30-BCMWX A60-BCMWXX B50-BCMW XX B70-BCMW X A80-BCMW XX A90-BCMW X C10-DPMW XXXXXX
TABLE 9
W24H1-C
W30H1-A
W30H1-B
W30H1-C
W36H1-A
W36H1-B
W36H1-C
W42H1-A
W42H1-B
W42H1-C
W48H1-A
W48H1-B
X
X
W48H1-C
W60H1-A
W60H1-B
W60H1-C
Manual 2100-511F Page 26 of 27
TABLE 10
VENT & CONTROL OPTIONS
rebmuNtraPnoitpircseD
W18, W24
W30, W36
W42, W48, W60
41-CMCTDO XXX 51-CMC)ylnoesahP-1V032(tiKtratS 1 XXX
111KS)ylnoesahP-1V032(tiKtratS 2 XXX
82-CMCCAL XXX
2-DAFBdradnatS-repmaDriAhserFcirtemoraBX
2-POBetalPffOknalBX
2-DAFMrepmaDriAhserFdezirotoMX
2-VRCnruteRgnirpS-rotalitneVlaicremmoCX
B2-MFIErezimonocEX
2A-FVREtloV032-rotalitneVyrevoceRygrenEX
3-DAFBdradnatS-repmaDriAhserFcirtemoraBX
3-POBetalPffOknalBX
3-DAFMrepmaDriAhserFdezirotoMX 3-SVRCnruteRgnirpS-rotalitneVlaicremmoCX 3-PVRCnruteRrewoP-rotalitneVlaicremmoCX
C3-MFIErezimonocEX
3A-FVREtloV032-rotalitneVyrevoceRygrenEX 3C-FVREtloV064-rotalitneVyrevoceRygrenEX
5-DAFBdradnatS-repmaDriAhserFcirtemoraBX
5-POBetalPffOknalBX
5-DAFMrepmaDriAhserFdezirotoMX 5-SVRCnruteRgnirpS-rotalitneVlaicremmoCX 5-PVRCnruteRrewoP-rotalitneVlaicremmoCX
C5-MFIErezimonocEX
5A-FVREtloV032-rotalitneVyrevoceRygrenEX 5C-FVREtloV064-rotalitneVyrevoceRygrenEX
1 PTCR Start Kit can be used with all -A single phase models. Increases starting torque 2-3x. Not used for -B or -C three phase
models. Do not use if SK111 is used.
2 Start Capacitor and potential relay start kit can be used with all -A single phase models. Increases starting torque 9x. Not used
for -B or -C three phase models. Do not use if CMC-15 is used.
Manual 2100-511F Page 27 of 27
Loading...