Bard W24G3-B, W30G3-C, W24G3-C, W30G3-B, W36G3-A Installation Instructions Manual

...
INSTALLATION INSTRUCTIONS
WALL MOUNTED GAS/ELECTRIC
Models:
W24G3-A W24G3-B W24G3-C
W30G3-A W30G3-B W30G3-C
W36G3-A W36G3-B W36G3-C
W42G3-A W42G3-B W42G3-C
READ ALL INSTRUCTIONS CAREFULLY BEFORE BEGINNING THE INSTALLATION.
THE INSTALLATION MUST COMPLY WITH THESE INSTRUCTIONS AND THE REQUIREMENTS OF ALL GOVERNING CODES AND ORDINANCES FOR THE INSTALLATION LOCATION.
IT IS THE RESPONSIBILITY OF INSTALLER TO KNOW AND UNDERSTAND ALL OF THESE REQUIREMENTS.
W48G3-A W48G3-B W48G3-C
W60G3-A W60G3-B W60G3-C
FAILURE TO DO SO COULD CREATE A HAZARD RESULTING IN PROPERTY DAMAGE, BODILY INJURY, OR DEATH.
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
www.bardhvac.com
Manual No.: 2100-630A Supersedes: 2100-630 Date: 5-4-15
Page 1 of 49
CONTENTS
Page
Getting Other Information and Publications ... 4 Wall Mount Gas/Electric General Information
W**G Series Model Nomenclature ..................... 5
Ventilation Options .......................................... 5
Air Conditioning Module Options ....................... 6
1. Important ..................................................... 10
2. Application ................................................... 10
3. Duct Work ..................................................... 10
4. High Altitude Applications .............................. 11
5. Transportation Damage ................................... 11
6. General Information ....................................... 11
7. Wall Mounting Information ............................. 11
8. Mounting the Unit ......................................... 11
9. Clearances .................................................... 17
10. Vent Terminal and Combustion Inlet Hood ........ 18
11. Optional Vertical Venting ................................ 18
12. Vent Resizing Instructions .............................. 19
13. Fresh Air Intake ............................................. 19
14. Condensate Drain .......................................... 19
15. Wiring – Main Power ...................................... 20
16. Wiring – Low Voltage Wiring ............................ 21
17. Thermostats .................................................. 21
18. Gas Supply and Piping ................................... 26
.. 5
Page
19. Manifold Pressure Adjustment ........................ 27
20. Checking Gas Input Rate ................................ 27
21. Standard Orifice Sizing and High
Altitude Derate .............................................. 29
22. Conversion of Gas Input BTUH from High
to Low Rating ................................................ 32
23. Measuring Air Temperature Rise ...................... 32
24. Filters .......................................................... 33
25. Compressor Control Module ............................ 33
26. Phase Monitor ............................................... 34
27. Lighting and Shutdown Instructions ................ 35
28. Service Agency Procedures ............................. 36
29. Maintaining Unit in Good Working Order .. 36 & 37
30. Replacement Parts ........................................ 37
31. Sequence of Operation – Heating .................... 38
32. Sequence of Operation – Cooling..................... 38
33. Indoor Blower Operation ................................. 39
34. Pressure Service Ports ................................... 47
35. Refrigerant Charge ......................................... 48
36. Fan Blade Setting Dimensions ........................ 48
37. Low NOx Burner Assembly "N" Suffix
Models Only – U.S. Installations Only .............. 48
Index – Wiring Diagrams and Ladder Diagrams ....... 49
Manual 2100-630A Page 2 of 49
Page
FIGURES
Figure 1 Unit Dimensions .................................. 9
Figure 2 Mounting Instructions – W24-36G ....... 12
Figure 2A Mounting Instructions – W42-60G ....... 13
Figure 3 Combustible Clearance – W24-36G ..... 14
Figure 3A Combustible Clearance – W42-60G ...... 14
Figure 4 Wall Mounting Instructions .................. 15
Figure 5 Wall Mounting Instructions .................. 15
Figure 6 Common Wall Mounting Installations .... 16
Figure 7 Location of Vent Terminal in Shipping ..17
Figure 8 Vent Terminal and Combustion
Air Intake ..........................................18
Figure 9 Fresh Air Damper ............................... 19
Figure 10 Installation of Flexible Conduit ............ 21
Figure 11 Low Voltage Wiring –
No Ventilation Package .......................22
Figure 12 Low Voltage Wiring – MFAD and Commercial Room Ventilator
Spring and Power ............................... 23
Figure 13 Low Voltage Wiring –
JIFM Economizer. ...............................24
Figure 14 Gas Pipe Connection ........................... 25
Figure 15 Proper Piping Practice ........................ 26
Figure 16 Access Internal Filter through
Upper Service Door .............................33
Figure 17 Lighting and Shutdown
Instruction Label ................................ 35
Figure 18 Top View of Gas Control ......................36
Figure 19 Sequence of Operation – Electronic
Blower Control ...................................38
Figure 20 Furnace Control Board and
Blower Control ...................................39
Figure 21 Fan Blade .......................................... 48
Figure 22 Low NOx Insert .................................. 48
Page
TABLES
Table 1 Specifications – W24-36G Models ........... 7
Table 1A Specifications – W42-60G Models ........... 8
Table 2 Minimum Installation Clearances ........... 17
Table 3 Thermostat Wire Size ............................21
Table 4 Wall Thermostat ................................... 21
Table 5 Length of Standard Pipe Threads ........... 26
Table 6 Gas Pipe Sizes – Natural Gas ................ 26
Table 7 Natural Gas Derate Capacities
for All Models ...................................... 29
Table 8 Natural Gas Orifice Tables – W24-36G ... 30
Table 8A Natural Gas Orifice Tables – W42-60G ...31
Table 9 Motor Speed Taps ................................ 39
Table 10 W24G Indoor Blower Performance .........40
Table 11 W30G Indoor Blower Performance .........41
Table 12 W36G Indoor Blower Performance .........42
Table 13 W42G Indoor Blower Performance ........43
Table 14 W48G Indoor Blower Performance .........44
Table 15 W60G Indoor Blower Performance .........45
Table 16 Integrated Furnace and Blower
Control Operation ................................. 46
Table 17A W24G3-W36G3 Cooling Pressure Table .. 47
Table 17B W42G3-W60G3 Cooling Pressure Table .. 47
Table 18 Fan Blade Dimension ...........................48
Manual 2100-630A Page 3 of 49
Getting Other Information and Publications
These publications can help when installing the furnace. They can usually be found at the local library or purchased directly from the publisher. Be sure to consult the current edition of each standard.
National Fuel Gas Code ....ANSI Z223.1 / NFPA 54
National Electrical Code .............. ANSI / NFPA 70
Standard for the Installation ..... ANSI / NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air .............. ANSI / NFPA 90B
Heating and Air Conditioning Systems
Standard for Chimneys, .......................NFPA 211
Fireplaces, Vents, and Solid Fuel Burning Appliances
Load Calculation for .....................ACCA Manual J
Residential Winter and Summer Air Conditioning
For more information, contact these publishers:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Avenue, NW Washington, DC 20009 Telephone: (202) 483-9370
ANSI American National Standards Institute 11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating Refrigerating, and Air Conditioning Engineers, Inc.
1791 Tullie Circle, NE. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association
Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Duct Design for Residential ........ ACCA Manual D
Winter and Winter Air Conditioning and Equipment Selection
Canadian Electrical Code .....................CSA C22.1
Canadian Installation Code
…………
CAN/CGA B149
BARD MANUFACTURING COMPANY, INC.
BRYAN, OHIO 43506 USA
CSA Canadian Standards Association
178 Rexdale Boulevard Rexdale, Ontario Canada. M9W 1R3 Telephone: (416) 447-4044
Manual 2100-630A Page 4 of 49
WALL MOUNT GAS/ELECTRIC GENERAL INFORMATION
MODEL NUMBER NOMENCLATURE
W 42 G 3 – A X C X X X X X X
MODEL
Wall Mount
COOLING CAPACITY
24 – 2 ton 30 – 2½ ton 36 – 3 ton 42 – 3½ ton 48 – 4 ton 60 – 5 ton
REVISION
GAS/ELECTRIC
FEATURE
(-) – Standard D – Dehumidification C – Canadian Approval
VENT
(See table
VOLTAGE
A230/208-60-1
230/208-60-3
B
460-60-3
C
EMISSIONS
X = Standard N = NOx Certified
HEATING INPUT 2 - 3 Ton 3.5 - 5 Ton
A – 45,000 B – 75,000 B – 67,500 C – 100,000 C – 90,000 D – 125,000*
*125,000 BTU input model is not NOx certified.
below)
FILTER
X – 2" Pleated (Standard) W – 1" Washable
Ventilation Options
COLOR
X – Beige (Standard) 4 – Gray
CONTROL OPTIONS
(See table page 6)
COIL OPTIONS
X – Standard 1 – Phenolic coated evaporator 2 – Phenolic coated condenser 3 – Phenolic coated both coils
OUTLET
X – Front (Standard) T – Top
Models
W24G, W30G, W36G W42G, W48G, W60G
Description
Factory Installed
Code No.
Field Installed
Part No.
Field Installed
Part No.
Barometric Fresh Air Damper X WGBFAD-3 WGBFAD-5
Blank-Off Plate B WGBOP-3 WGBOP-5
Motorized Fresh Air Damper M WGMFAD-3A WGMFAD-5A
Commercial Ventilator – Spring Return V WGCRVS-3A WGCRVS-5A
Commercial Ventilator – Power Return P WGCRVP-3A WGCRVP-5A
Economizer - Fully Modulating
E WGJIFM-3 WGJIFM-5
Energy Recovery Ventilator – 230 Volt R WGERV-A3B WGERV-A5B
Energy Recovery Ventilator – 460 Volt R WGERV-C3C WGERV-C5C
Low ambient control is required with economizer for low temperature compressor operation.
Manual 2100-630A Page 5 of 49
Air Conditioning Module Options
CCM
STD STD STD H CMA-29
STD – Standard equipment.
CCM Compressor control module has adjustable 30 second to 5 minute delay-on-break timer. On initial power up, or any
time the power is interrupted, the delay-on-make will be 2 minutes plus 10% of the delay-on-break setting. There is no delay-on-make during routine operation of the unit. The module also provides the lockout feature (with 1 retry) for high and/or low pressure controls, and a 2-minute timed bypass for low pressure control.
HPC High pressure control is auto reset. Always used with compressor control module (CCM) which is included. See Note
HPC
LPC
LAC
SK
Field Only SK111 or CMC-15
Factory Installed
Code
Field Installed
Part
.
LPC Low pressure control is auto reset. Always used with compressor control module (CCM) which is included. See Note
LAC Low ambient control permits cooling operation down to 0°F. (Includes fan cycling control + Freeze Stat)
SK CMC-15 is PTCR Start Kit can be used with all -A single phase models. Increases starting torque 2-3X. Not used for -B
or -C 3-phase models. Do not use if SK111 is used.
SK SK111 Start Capacitor and Potential Relay Start Kit can be used with all -A single phase models. Increases starting
torque 9x. Not used for -B or -C 3-phase models. Do not use if CMC-15 is used.
.
Manual 2100-630A Page 6 of 49
ABLE 1 T
Specifications
W24G, W30G and W36G Models
Models W24G3-A W24G3-B W24G3-C W30G3-A W30G3-B W30G3-C W36G3-A W36G3-B W36G3-C
Minimum Circuit Ampacity 21 16 10 23 17 11 27 20 11
* Field Wire Size 10 12 14 10 12 14 8 10 14
Operating Voltage Range 197-253 187-253 414-506 197-253 187-253 414-506 197-253 187-253 414-506
Electrical Rating – 60 Hz 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3
Ground Wire Size 10 12 14 10 12 14 10 10 14
** Delay Fuse or Circuit Breaker Max. 30 25 15 35 25 15 40 25 15
Compressor
Voltage 230/208 230/208 460 230/208 230/208 460 230/208 230/208 460
Rated Load Amps 9.9/10.9 6.4/7.1 3.9 11.8/12.9 7.5/8.2 4.7 12.4/14.0 7.8/8.8 4.9
Branch Circuit Selection Current 12.8 8.3 5.1 14.1 9.0 5.6 16.7 10.5 5.8
Lock Rotor Amps 64/64 58/58 28 77/77 71/71 38 79/79 73/73 38
Compressor Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Fan Motor – Amps 1.5 1.5 0.8 1.5 1.5 0.8 1.5 1.5 0.8
Fan Motor – HP/RPM/SPD 1/5-1050-1 1/5-1050-1 1/5-1050-1 1/5-1050-1 1/5-1050-1 1/5-1050-1 1/5-1050-1 1/5-1050-1 1/5-1050-1
Fan Motor and Condenser
Blower Motor – HP/RPM/SPD 1/4-950-3 1/4-950-3 1/4-950-3 1/3-1075-3 1/3-1075-3 1/3-1075-3 1/3-1075-3 1/3-1075-3 1/3-1075-3
Blower Motor – Amps 1.8 1.8 .8 2.2 2.2 1.1 2.2 2.2 1.1
CFM Cooling and E.S.P. 800 - .15 800 - .15 800 - .15 1000 - .35 1000 - .35 1000 - .35 1100 - .25 1100 - .25 1100 - .25
Fan – DIA/CFM 20” - 2400 20” - 2400 20” - 2400 20” - 2400 20” - 2400 20” - 2400 20” - 2400 20” - 2400 20” - 2400
Blower Motor and Evaporator
Filter Size 20 x 25 x 2 20 x 25 x 2 20 x 25 x 2 20 x 25 x 2 20 x 25 x 2 20 x 25 x 2 20 x 25 x 2 20 x 25 x 2 20 x 25 x 2
Shipping Weight – LBS. 500 500 500 530 530 530 530 530 530
* 75° C Copper wire size
** Maximum time delay fuse or circuit breaker
Manual 2100-630A Page 7 of 49
TABLE 1A
Specifications
W42G, W48G and W60G Models
Models W42G3-A W42G3-B W42G3-C W48G3-A W48G3-B W48G3-C W60G3-A W60G3-B W60G3-C
Minimum Circuit Ampacity 33 25 12 36 26 12 41 27 14
* Field Wire Size 8 8 14 8 8 14 8 8 12
Operating Voltage Range 197-253 187-253 414-506 197-253 187-253 414-506 197-253 187-253 414-506
Electrical Rating – 60 Hz 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3
Ground Wire Size 10 10 14 10 10 14 10 10 12
** Delay Fuse or Circuit Breaker Max. 50 35 15 50 35 15 60 40 20
Manual 2100-630A Page 8 of 49
Voltage 230/208 230/208 460 230/208 230/208 460 230/208 230/208 460
Rated Load Amps 16/17.9 10.6/11.8 5.5 15.9/18.9 10.0/11.9 5.4 23.2/26.3 14.0/16.6 7.8
Compressor
Branch Circuit Selection Current 19.9 13.1 6.1 21.8 13.8 6.3 26.3 16.6 7.8
Lock Rotor Amps 109/109 83/83 41 117/117 83/83 41 134/134 110/110 52
Compressor Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Fan Motor – HP/RPM/SPD 1/3-825-2 1/3-825-2 1/3-825-1 1/3-825-2 1/3-825-2 1/3-825-1 1/3-825-2 1/3-825-2 1/3-825-1
Fan Motor – Amps 2.5 2.5 1.3 2.5 2.5 1.3 2.5 2.5 1.3
Fan Motor and Condenser
CFM Cooling and E.S.P. 1300 - .35 1300 - .35 1300 - .35 1550 -.38 1550 -.38 1550 -.38 1650 - .30 1650 - .30 1650 - .30
Blower Motor – Amps 3.4 3.4 1.5 3.4 3.4 1.5 3.4 3.4 1.5
Blower Motor – HP/RPM/SPD 1/2-1050-3 1/2-1050-3 1/2-1050-3 1/2-1050-3 1/2-1050-3 1/2-1050-3 1/2-1050-3 1/2-1050-3 1/2-1050-3
Fan – DIA/CFM 24” - 3050 24” - 3050 24” - 3050 24” - 3050 24” - 3050 24” - 3050 24” - 3050 24” - 3050 24” - 3050
Blower Motor and Evaporator
Filter Size 20 x 30 x 2 20 x 30 x 2 20 x 30 x 2 20 x 30 x 2 20 x 30 x 2 20 x 30 x 2 20 x 30 x 2 20 x 30 x 2 20 x 30 x 2
Shipping Weight – LBS. 700 700 700 710 710 710 725 725 725
* 75° C Copper wire size
** Maximum time delay fuse or circuit breaker
F
G
N
P
D
DD
FF
GG
HH
A
M
I
C
KJ
L
H
R
S
S
S
S
S
T
V
Y
AA
X
U
Z
CC
BB
B
EE
O
E
B
II
Q
W
COMBUSTION
AIR INTAKE
CONTROL
RIGHT SIDE
ENTRANCES
GAS
RETURN OPENING
4 DEG. PITCH IN TOP
PANEL DOOR
DOOR
LOW VOLTAGE
SUPPLY OPENING
PANEL
BACK
DISCONNECT ACCESS
VESTIBULE
PANEL (LOCKABLE)
CONDENSER
AIR INLETS
CONDENSER
VENT OPTION
AIR OUTLET
AIR EXHAUST
COMBUSTION
ENTRANCES
FRONT
CIRCUIT BREAKER/
MIS-3239
HIGH VOLTAGE
ENTRANCES
FRONT DOOR
FILTER
SERVICE
DOOR
UNIT A B C D E F G H I J K L M N O P QR
W24G-W30G-W36G 7.88 27.88 13.88 24.25 40 25.63 81.63 27.38 27.5 39.25 5.88
W42G-W48G-W60G
29.88
15.88
27.25
87.5
3.75
UNIT S T U V W X Y Z AA B B CC DD EE FF GG HH II
W24G-W30G-W36G 12 - 7 HOLES 2.88 22.9 38 17.84 4.44 11.44 9 36.25 2 0.38
W42G-W48G-W60G
42
10
2.75
0.44
1.257.25 1.133.75 2.25 3.25
15.31 4.5 2.514.88 30 14.12 15.44
FIGURE 1
Unit Dimensions
Manual 2100-630A Page 9 of 49
CAUTION
During the initial ring of the burners there will probably be some amount of smoke issued to the circulating air stream as the result of residual oil burning off of the heat exchanger tubes. This oil is required during the forming process of the stainless steel heat exchanger tubes to facilitate the bending. OSHA or the National Toxicology Program does not list the oil as a carcinogen. In vapor form this may be irritating to the eyes or could cause headaches. This is a one-time occurrence, and ventilation of the space may be required depending upon the space being conditioned.
1. IMPORTANT
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
2. APPLICATION
This is a fan-assisted forced air gas furnace with electric air conditioning for outdoor installation. A fan-assisted furnace is equipped with an integral mechanical means to draw products of combustion through the combustion chamber and heat exchanger. The furnace installation must conform with local building codes and ordinances or, in their absence, with the National Fuel Gas Code ANSI Z223.1 or CAN/CGA-B149.1, latest edition, and the National Electrical Code ANSI/NFPA-7 or CSA C22.1, latest edition. It is the personal responsibility and obligation of the purchaser to contact a qualified installer to assure that installation is adequate and is in conformance with governing codes and ordinances.
3. DUCT WORK
The unit is designed for use with or without duct work (see WARNING). Flanges are provided for attaching the supply and return ducts. These instructions explain the recommended method to install the air cooled self-contained electric air conditioning and gas heating unit and the electrical wiring connections and gas piping to the unit. The refrigerant system is completely assembled and charged. All internal wiring is complete.
These instructions and any instructions packaged with any separate equipment required to make up the entire heating/cooling system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
All duct work, supply and return, must be properly sized for the design airflow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing.
Refer to Tables 10, 11, 12, 13, 14 and 15 for maximum static pressure available for duct design.
WARNING
In all cases, there must be a metal duct
connection made to the supply air ange, and a 1"
clearance to combustibles must be maintained to this duct connection.
For free blow applications, a metal sleeve must be
used in the wall opening itself, again maintaining a 1" clearance to combustibles.
Failure to use the sheet metal can cause re resulting in property damage, injury, or death.
See Figure 3 and clearance information in Section 9 and Table 2 for additional information.
Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of one-inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
A 1" clearance to combustible material for the first 3' of duct attached to the outlet air frame is required. See Wall Mounting Instructions and Figures 2, 2A, 3 and 3A for further details.
Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.
Some installations may not require any return air duct. A metallic return air grille is required with installations not requiring a return air duct. The spacing between louvers on the grille shall not be larger than 5/8".
Any grille that meets with the 5/8" louver criteria may be used. It is recommended that Bard Return Air Grille or Return Filter Grille be installed when no return duct is used. Contact distributor or factory for ordering information. If using a return air filter grille, filters must be of sufficient size to allow a maximum velocity of 400 fpm.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to installation only in a single story structure.
Manual 2100-630A Page 10 of 49
4. HIGH ALTITUDE APPLICATIONS
8. MOUNTING THE UNIT
Ratings of gas utilization equipment are based on sea level operation and need not be changed for operation at elevations up to 6,000'. For operation at elevations above 6,000' and in the absence of specific recommendations from the local authority having jurisdiction, equipment ratings shall be reduced as specified in Section 21.
5. TRANSPORTATION DAMAGE
All units are packed securely in shipping containers. All units should be carefully inspected upon arrival for damage. In the event of damage, the consignee should:
1.
Note on delivery receipt of any damage to container.
2. Notify carrier promptly, and request an inspection.
3. In case of concealed damage, the carrier must be notified as soon as possible within 15 days after delivery.
4. Claims for any damage, apparent or concealed, should be filed with the carrier, using the following supporting documents:
A. Original Bill of Lading, certified copy or
indemnity bond.
B. Original paid freight bill of indemnity in lieu
thereof.
C.
D. Copy of the inspection report issued by
Original invoice or certified copy thereof showing trade and other discounts or deductions.
carrier’s representative at the time damage is reported to carrier.
6. GENERAL INFORMATION
1. These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides. A bottom mounting bracket is provided for ease of installation but is not required.
CAUTION
If the bottom bracket is used, be certain the bracket is secured to the outside wall surface in a way sufcient to support the entire weight of the unit during installation until side mounting brackets are secured.
The W42G, W48G and W60G models are suitable
2. for 0 clearance on the installation mounting wall and to the top. For all models the supply air duct flange and the first 3’ of supply air duct require a minimum of 1” clearance to combustible material. The W24G, W30G and W36G models are suitable for 0 clearance on the installation mounting wall, but require 1” clearance to the top if combustible material overhang projects above the unit (see Figures 3 and 3A). If a combustible wall, use a minimum of Figure 1 “A” dimension plus 2” and “B” dimension plus 2”. See Figures 4 and 5 for details.
WARNING
Failure to provide the one inch clearance between the supply duct and a combustible
surface for the rst three feet of duct can result in re causing damage, injury or death.
Size of unit for proposed installation should be based on heat loss/heat gain calculations made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
7. WALL MOUNTING INFORMATION
1.
Two holes for the supply and return air openings must be cut through the wall as detailed in Figure 4.
2. On wood-frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration.
3. Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installed unit.
3. Locate and mark lag bolt locations and bottom mounting bracket location.
4. Mount bottom mounting bracket.
5. Hook top rain flashing under back bend of top. Top rain flashing is shipped secured to the right side of the back.
6. Position unit in opening and secure with 5/16 lag bolts; use 7/8” diameter flat washers on the lag bolts. Use lag bolts long enough to support the unit’s weight when mounted to the structure. This length may be dependant on the type of construction.
7. Secure rain flashing to wall and caulk across entire length of top (see Figure 3).
8.
On side-by-side installations, maintain a minimum of 20” clearance on right side to allow access to control panel and burner compartment, and to allow proper airflow to the outdoor coil. Additional clearance may be required to meet local or national codes.
Manual 2100-630A Page 11 of 49
39 3/16"
29 3/4"
4 11/16"
12"
12"
12"
12"
12"
12"
2"
2 1/4"
10"
28 5/16"
15"
27"
17 15/16"
11 5/16"
8 5/8"
2 15/16"
2 1/4"
30"
29"
5 1/16"
7/16"
5 9/16"
4 9/16"
4 1/2"
2 15/16"
18 15/16"
4 9/16"
SUPPLY
AIR DUCT
RETURN
AIR DUCT
Ø2 3/4" GAS
OPENING
(OPTIONAL)
Ø2 3/4" HIGH
VOLTAGE
(OPTIONAL)
Ø2" LOW VOLTAGE
(OPTIONAL)
(12) FLANGE
SCREWS
UNIT SUPPORT
1" MIN.
NECCESSARY
NO CLEARANCE
SUPPLY
AIR DUCT
RETURN
AIR DUCT
CONTROL
PANEL
VESTIBULE
DOOR
WALL
STRUCTURE
(OUTSIDE)
1" CLEARANCE ON ALL
FOUR SIDES OF SUPPLY
AIR DUCT IS REQUIRED FROM
COMBUSTABLE MATERIALS
NOTE: IT IS RECOMMENDED THAT A BEAD
OF SILICONE CAULKING BE PLACED BEHIND
THE SIDE MOUNTING FLANGES AND UNDER
TOP FLASHING AT TIME OF INSTALLATION
RIGHT SIDE
VIEW WITH UNIT
OUTSIDE WALL WITH
UNIT REMOVED
RAIN FLASHING
SUPPLIED
SEAL WITH BEAD OF CAULKING
ALONG ENTIRE LENGTH OF TOP
TOP
FOAM AIR SEAL
WALL
MIS-1681
FIGURE 2
Mounting Instructions
for W24G, W30G and W36G
Manual 2100-630A Page 12 of 49
FIGURE 2A
Mounting Instructions
for W42G, W48G and W60G
Manual 2100-630A Page 13 of 49
FIGURE 3
Combustible Clearance
for W24G, W30G and W36G Models
FIGURE 3A
Combustible Clearance
for W42G, W48G and W60G Models
WARNING
A minimum of one (1) inch clearance must be maintained between the supply air duct and combustible materials.
This is required for the rst three (3) feet of ducting.
It is important to insure that the one (1) inch minimum spacing is maintained at all points.
Failure to do this could result in overheating the combustible material and may result in a re causing damage, injury or death.
Manual 2100-630A Page 14 of 49
FIGURE 4
Wall Mounting Instructions
FIGURE 5
Wall Mounting Instructions
Manual 2100-630A Page 15 of 49
Loading...
+ 34 hidden pages