THE WALL-MOUNT™ AIR CONDITIONERS (50HZ)

Models W24A to W70A and W24L to W70L

 

GREEN REFRIGERANT

 

21,200 Btuh (6.21 KW) – 59,000 Btuh (17.28 KW)

 

 

Right Side Control Panel

50Hz

 

R-410A

 

 

 

 

 

 

 

 

 

The Bard Wall-Mount Air Conditioner is a self contained energy efficient system, which is designed to offer maximum indoor comfort at a minimal cost without using valuable indoor floor space or outside ground space. This unit is the ideal product for versatile applications such as: new construction, modular offices, school modernization, telecommunication structures, portable structures or correctional facilities. Factory or field installed accessories are available to meet specific job requirements.

Engineered Features

Aluminum Finned Copper Coils:

Grooved tubing and enhanced louvered fin for maximum heat transfer and energy efficiency.

Twin Blowers:

Move air quietly. Most models feature multispeed blower motors providing airflow adjustment for high and low static operation. Motor overload protection is standard on all models.

Air Conditioner Compressor:

Scroll Compressors eliminate need for crankcase heater. Standard on all models.

R-410A Refrigerant:

Designed with R-410A (HFC) nonozone depleting refrigerant in compliance with the Montreal protocol and 2010 EPA requirements.

Phase Rotation Monitor:

Standard on all 3 phase scroll compressors. Protects against reverse rotation if power supply is not properly connected.

Galvanized 20 Gauge Zinc Coated Steel Cabinet:

Cleaned, rinsed, sealed and dried before the polyurethane primer is applied. The cabinet is handsomely finished with a baked on textured enamel, which allows it to withstand 1000 hours of salt spray tests per ASTM B117-03.

Foil Faced Insulation:

Standard on all units.

Full Length Mounting Brackets:

Built into cabinet for improved appearance and easy installation. NOTE: Bottom mounting bracket included to assist in installation.

Electrical Components:

Are easily accessible for routine inspection and maintenance through a right side, service panel opening. Features a lockable, hinged access cover to the circuit breaker or toggle disconnect switch.

Electric Heat Strips:

Features an automatic limit and thermal cut-off safety control. Heater packages can be factory or field installed for all 1½ through 6 ton models.

Filter Service Door:

Separate service door provides easy access for filter change.

One Inch, Disposable Air Filters:

Are standard equipment. Optional one inch washable filters available and filter racks permit the addition of 2" pleated filter. Factory or field installed.

Condenser Fan and Motor

Shroud Assembly:

Slides out for easy access.

Barometric Fresh Air Damper:

Standard on all units. Allows up to 25% outside fresh air. Optional ventilation packages available.

Built-in Circuit Breakers:

Standard on all electric heat versions of single (230/208 volt) and three phase (230/208 volt) equipment. Toggle disconnects are standard on all electric heat versions of three phase (460 volt) equipment.

Slope Top:

Standard feature for water run-off.

Top Rain Flashing:

Standard feature on all models.

Liquid Line Filter Drier:

Standard on all units. Protects system against moisture.

Compressor Control Module:

Standard on all units. Built-in off-delay timer adjustable from 30 seconds to 5 minutes. 2-minute on-delay if power interrupt. 120-second bypass for low pressure control, and both soft and manual lockouts for high and low pressure controls. Alarm output for alarm relay.

High & Low Pressure Switches are Auto-Reset:

Standard on all units. Built-in lockout circuit resets from the room thermostat. Provides commercial quality protection to the compressor.

Form No.

S3408-1011

Supersedes

S3408-710

Page

1 of 8

Capacity and Efficiency Ratings

MODELS

W24A1

W30A1

W36A1

W42A1

W48A1

W60A1

W70A1

W24L1

W36L1

W42L1

W48L1

W60L1

W70L1

 

 

Cooling Capacity Btuh

21,200

26,000

31,200

36,000

41,500

48,500

59,000

Cooling Capacity KW

6.21

7.62

9.14

10.54

12.15

14.20

17.28

EER

9.0

9.0

9.0

9.2

9.0

9.0

9.5

All capacity, efficiency and cost of operation information is based on high speed operation with fresh air cover plate. Cover plate must be ordered separately and is recommended for use to obtain maximum energy efficiency where fresh air is not required.

Specifications 21,200 Btuh (6.21 KW) — 31,200 Btuh (9.14 KW)

MODELS

W24A1-D

W24A1-F

W30A1-D

W30A1-F

W36A1-D

W36A1-E

W36A1-F

W24L1-F

W36L1-F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electrical Rating-50 Hz

240/220 - 1

415/380 - 31

240/220 - 1

415/380 - 31

240/220 - 1

220/200 - 3

415/380 - 31

Operating Voltage Range

198-254

342-456

198-254

342-456

198-254

180-242

342-456

 

 

 

 

 

 

 

 

Compressor--Circuit A

 

 

 

 

 

 

 

Voltage

240/220

415/380

240/220

415/380

240/220

220/200

415/380

Rated Load Amps

9.4/10.6

4.8/5.0

12.9/14.7

4.8/4.8

15.1/15.8

11.8/13.1

5.8/6.0

Branch Circuit Selection Current

10.9

5.2

14.7

4.8

16.0

13.3

6.0

Lock Rotor Amps

60/60

28/28

67/67

30/30

87/87

95/95

44/44

Compressor Type

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

 

 

 

 

 

 

 

 

Fan Motor & Condenser

 

 

 

 

 

 

 

Fan Motor--HP--RPM

1/5 - 950

1/5 - 950

1/5 - 950

1/5 - 950

1/5 - 950

1/5 - 950

1/5 - 950

Fan Motor--Amps

1.0

1.0

1.5

1.5

1.5

1.5

1.5

Fan--DIA m3/s

458/0.66

458/0.66

508/0.86

508/0.86

508/0.86

508/0.86

508/0.86

Blower Motor & Evaporator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blower Motor--HP-RPM-SPD

Blower Motor--Amps

m3/s Cooling & E.S.P. (pa)

w/Filter (Rated-Wet Coil)

Filter Sizes (mm) STD.

Shipping Weight -- Lbs. (Kg)

1/5-950-1

1/5-950-1

1/3-950-2

1/3-950-2

1/3-950-2

1/3-950-2

1/3-950-2

1.2

1.2

2.2

2.2

2.2

2.2

2.2

0.32/55

0.32/55

0.45/55

0.45/55

0.47/50

0.47/50

0.47/50

405x635x25

405x635x25

405x765x25

405x765x25

405x765x25

405x765x25

405x765x25

 

 

 

 

 

 

 

335 (152)

335 (152)

375 (170)

375 (170)

375 (170)

375 (170)

375 (170)

 

 

 

 

 

 

 

Specifications 36,000 Btuh (10.54 KW) — 59,000 Btuh (17.28 KW)

MODELS

W42A1-E

W42A1-F

W48A1-E

W48A1-F

W60A1-E

W60A1-F

W70A1-P

W42L1-F

W48L1-F

W60L1-F

W70L1-P

 

 

 

 

 

 

 

 

 

 

 

 

Electrical Rating--50 Hz

220/200-3

415/380-3 1

220/200-3

415/380-3 1

220/200-3

415/380-3 1

400/380-3 1

Operating Voltage Range

180-242

342-456

180-242

342-456

180-242

342-456

342-440

Compressor--Circuit A

 

 

 

 

 

 

 

Voltage

220/200

415/380

220/200

415/380

220/200

415/380

400/380

Rated Load Amps

11.0/12.5

5.8/5.8

13.9/15.2

7.1/7.1

13.5/15.2

7.4/7.6

12.2/14.1

Branch Circuit Selection Current

13.2

6.0

15.2

7.1

15.7

7.8

14.1

Lock Rotor Amps

83/83

44/44

98/98

48/48

110/110

52/52

75/75

Compressor Type

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Fan Motor & Condenser

 

 

 

 

 

 

 

Fan Motor--HP-RPM

1/3-825

1/3-825

1/3-825

1/3-825

1/3-825

1/3-825

1/3-950

Fan Motor--Amps

2.5

2.5

2.5

2.5

2.5

2.5

4.0

Fan--DIA. m3/s

610/1.01

610/1.01

610/1.01

610/1.01

610/1.01

610/1.01

610/1.01

Blower Motor & Evaporator

 

 

 

 

 

 

 

Blower Motor--HP-RPM-SPD

1/2-950-2

1/2-950-2

1/2-950-2

1/2-950-2

1/2-950-2

1/2-950-2

1/2-950-2

Blower Motor--Amps

3.3

3.3

3.3

3.3

3.3

3.3

3.3

m3/s Cooling & E.S.P. (pa)

0.55/75

0.55/75

0.60/50

0.60/50

0.66/75

0.66/75

0.70/50

w/Filter (Rated-Wet Coil)

 

 

 

 

 

 

 

Filter Sizes (mm) STD.

508x765x25

508x765x25

508x765x25

508x765x25

508x765x25

508x765x25

508x765x25

 

 

 

 

 

 

 

 

Shipping Weight -- Lbs. (Kg)

525 (238)

525 (238)

525 (238)

525 (238)

525 (238)

525 (238)

525 (238)

 

 

 

 

 

 

 

 

1 415/380-3 and 400/380-3 electrical ratings are 3-phase wye (star) systems requiring three (3) phase legs plus neutral and ground. NOTE: The indoor & outdoor motors, and 24V transformer primary are connected at 240V derived from one (1) phase leg to neutral.

This is internally connected and no field wiring required.

Form No.

S3408-1011

Supersedes

S3408-710

Page

2 of 8

Ventilation System Packages

Bard Wall-Mounts are designed to provide optional ventilation packages to meet all of your ventilation and indoor air quality requirements. Standard on all units is the barometric fresh air damper. All packages can be ordered built-in at the factory or can be easily field-installed at the time of installation of the Wall-Mount, or can be retrofitted at a later date.

BAROMETRIC FRESH AIR DAMPER - BFAD

STANDARD

The barometric fresh air damper is a standard feature on all models. It is installed on the inside of the service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed with the conditioned air. The damper opens during blower operation and closes when the blower is off. Adjustable blade stops allow different amounts of outside air to be introduced into the building and can be easily locked closed if required.

BAROMETRIC FRESH AIR DAMPER BLANK OFF PLATE - BOP OPTIONAL

A blank off plate is installed on the inside of the service door. It covers the air inlet openings, which restricts any outside air from entering the unit. The blank off plate should be utilized in applications where outside air is not required to be mixed with the conditioned air.

MOTORIZED FRESH AIR DAMPER

COMMERCIALROOMVENTILATOR

MOTORIZED FRESH AIR DAMPER - MFAD

OPTIONAL

The motorized fresh air damper is internally mounted behind the service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed with the conditioned air. The two position damper can be fully open or closed. The damper blade is powered open by a 24VAC motor with spring return on power loss. The damper can be controlled by indoor blower operation or can be field connected to be managed based on building occupancy.

NOTE: The above vent systems are intake only without built-in exhaust capability. Building will likely require separate field installed barometric relief or mechanical exhaust elsewhere within the conditioned space. Balancing dampers in the return air grille may be required to achieve specified amount of outdoor air intake.

COMMERCIAL ROOM VENTILATOR - CRV

OPTIONAL

The built-in commercial room ventilator is internally mounted behind the service door and allows outside ventilation air, up to 50% of the total airflow rating of the unit, to be introduced through the air inlet openings. It includes a built-in exhaust air damper.

The commercial room ventilator (CRV) is a simple and innovative approach to improving the indoor air quality by providing fresh air intake and exhaust capability through the CRV. The damper can be easily adjusted to control the amount of fresh air supplied into the building. The CRV can be controlled by indoor blower operation or field controlled based on room occupancy. The CRV is power open - spring return on power loss. Complies with ASHRAE Standard 62.1 “Ventilation for Acceptable Indoor Air Quality.”

ECONOMIZER - EIFM

OPTIONAL

The built-in economizer system is internally mounted behind the service door and allows outdoor air to be introduced through the air inlet openings. The amount of outdoor air varies in response to the system controls and settings defined by the end user. It includes a built-in exhaust air damper. The economizer is designed to provide “free cooling” when outside air conditions are cool and dry enough to satisfy cooling requirements without running the compressor. This in turn provides lower operating costs, while extending the life of the compressor.

 

Standard Features:

ECONOMIZER

 

One Piece Construction - Easy to install with no mechanical linkage adjustment required.

Exhaust Air Damper - Built in with positive closed position. Provides exhaust air capability to prevent pressurization of tight buildings.

Actuator Motor - 24 volt, power open, spring return with built in torque limiting switch.Proportioning Type Control - for maximum “free cooling” economy and comfort.

Moisture Eliminator & Prefilter - permanent, washable aluminum construction.Enthalpy Control - adjustable to monitor outdoor temperature and humidity.

Minimum Position Potentiometer - adjustable to control minimum damper blade position for ventilation purposes.

Mixed Air Sensor - to monitor outside and return air to automatically modulate damper position.

Form No.

S3408-1011

Supersedes

S3408-710

Page

3 of 8

Clearances - Inches (mm) Required for Service Access and Adequate Condenser Airflow

MODELS

LEFT SIDE

RIGHT SIDE

W24A, W30A, W36A

15 (380)

20 (510)

W24L, W36L

 

 

W42A, W48A, W60A, W70A

20 (510)

20 (510)

W42L, W48L, W60L, W70L

 

 

Minimum Clearances - Inches (mm) Required to Combustible Materials

MODELS 1

SUPPLY AIR DUCT

 

FIRST 3 FEET (1m)

CABINET

W24A, W24L

0

0

 

 

 

W30A, W36A, W36L

.25 (6.35)

0

 

 

 

W42A, W48A, W60A, W70A

.25 (6.35)

0

W42L, W48L, W60L, W70L

 

 

1 Refer to the installation manual for more detailed information.

Dimensions of Basic Unit for Architectural and Installation Requirements - Inches (mm)

MODEL

WIDTH

DEPTH

HEIGHT

SUPPLY

RETURN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(W)

(D)

(H)

A

B

C

B

E

F

G

I

J

K

L

M

N

O

P

Q

R

S1

S2

T

 

 

 

 

 

W24A, W24L

33.300

17.125

70.563

7.88

19.88

11.88

19.88

35.00

10.88

25.75

20.56

26.75

28.06

29.25

27.00

2.63

34.13

22.06

10.55

4.19

12.00

12.00

5.00

(845)

(435)

(1792)

(200)

(505)

(302)

(505)

(889)

(276)

(654)

(522)

(680)

(713)

(743)

(686)

(67)

(867)

(560)

(268)

(106)

(305)

(305)

(127)

W30A

38.200

17.125

70.563

7.88

27.88

13.88

27.88

40.00

10.88

25.75

17.93

26.75

28.75

29.25

27.00

2.75

39.19

22.75

9.14

4.19

12.00

12.00

5.00

W36A, W36L

(970)

(435)

(1792)

(200)

(708)

(353)

(708)

(1016)

(276)

(654)

(455)

(680)

(730)

(743)

(686)

(70)

(996)

(578)

(232)

(106)

(305)

(305)

(127)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W42A, W42L

42.075

22.432

84.875

9.88

29.88

15.88

29.88

43.88

13.56

31.66

30.00

32.68

26.94

34.69

32.43

3.37

42.88

23.88

10.00

2.00

16.00

16.00

1.88

W48A, W48L

W60A, W60L

(1069)

(570)

(2156)

(251)

(759)

(403)

(759)

(1115)

(344)

(804)

(762)

(830)

(684)

(881)

(824)

(86)

(1089)

(607)

(254)

(51)

(406)

(406)

(48)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W70A, W70L

42.075

22.432

94.875

9.88

29.88

15.88

29.88

43.88

13.56

41.66

30.00

42.68

36.94

44.69

42.43

3.37

42.88

33.88

10.00

2.00

16.00

21.00

1.88

 

(1069)

(570)

(2410)

(251)

(759)

(403)

(759)

(1115)

(344)

(1056)

(762)

(1084)

(939)

(1135)

(1078)

(86)

(1089)

(861)

(254)

(51)

(406)

(533)

(48)

 

 

Built In

 

W

Rain Hood

 

4° Pitch

 

 

Heater

 

 

Access

 

 

Panel

 

 

Electric

 

 

Heat

 

 

C. Breaker/

 

 

Disconnect

 

 

Access Panel

 

 

(Lockable)

 

 

Filter Access

 

 

Panel

5.75

 

Vent Option

 

 

 

 

Door

F

 

Ventilation

 

Air

 

 

 

 

Low Voltage

 

 

Electrical

 

 

Entrance

G

Condenser

High Voltage

 

Electrical

 

Air Outlet

 

Entrance

Front View

E

D

O

 

 

 

 

 

.44

 

 

2.13

 

 

 

 

R

 

 

 

Side Wall

 

 

 

A

 

Supply Air Opening

 

 

 

Mounting

 

 

 

 

 

 

 

 

 

Brackets

 

 

 

 

 

 

(Built In)

 

 

S1

 

 

 

 

B

 

 

 

 

 

 

 

 

I

 

 

 

 

 

 

 

 

Top Rain

 

 

 

 

 

 

Flashing

 

 

S1

 

 

 

Shipping

 

 

 

 

 

 

 

 

 

 

 

Location

 

 

 

 

C

H

Optional

Return Air Opening

 

 

Electrical

S1

 

 

 

Entrances

 

 

 

 

 

 

 

 

 

S2

Cond.

K

 

 

 

 

 

J

 

L

 

 

 

Air

 

M

 

 

 

 

 

 

 

S2

Inlet

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

T

Side View

Drain

 

N

Back View

Bottom Installation

 

 

 

 

 

Q

 

Bracket

MIS-2762

 

 

 

 

 

Form No.

S3408-1011

Supersedes

S3408-710

Page

4 of 8

Electrical Specifications

 

 

Rated

Operating

No. Field

2 Minimum

1 Maximum

 

Model

Volts

Voltage

Power

Circuit

External Fuse

 

 

 

and Phase

Range

Circuits

Amps

or Circuit Breaker

 

W24A1

- D0Z

 

 

1

16

20

 

 

D05

240/220-1

198-254

1

28

30

 

 

D08

 

 

1

44

45

 

 

 

 

 

 

 

 

 

W24A1

- F0Z

415/380-3 3

342-456

1

9

15

 

W24L1

F05

1

11

15

 

 

 

 

 

 

 

 

 

 

 

 

W30A1

- D0Z

 

 

1

23

35

 

 

D05

240/220-1

198-254

1

29

35

 

 

D10

 

 

1

55

60

 

W30A1

- F0Z

 

 

1

9

15

 

 

F07

415/380-3 3

342-456

1

15

15

 

 

F12

 

 

1

24

25

 

W36A1

- D0Z

 

 

1

24

35

 

 

D05

240/220-1

198-254

1

29

35

 

 

D10

 

 

1

55

60

 

 

 

 

 

 

 

 

W36A1 - E0Z

 

 

1

20

25

 

 

E06

220/200-3

180-242

1

24

30

 

 

E12

 

 

1

40

40

 

 

 

 

 

 

 

 

 

W36A1

- F0Z

 

 

1

11

15

 

W36L1

F07

415/380-3 3

342-456

1

16

20

 

 

F12

 

 

1

25

25

 

 

 

 

 

 

 

 

 

W42A1

- E0Z

 

 

1

25

35

 

 

E09

220/200-3

180-242

1

32

35

 

 

E15

 

 

1

53

60

 

W42A1

- F0Z

 

 

1

14

20

 

W42L1

F07

415/380-3 3

342-456

1

17

20

 

 

F14

 

 

1

31

35

 

W48A1 - E0Z

 

 

1

27

35

 

 

E09

220/200-3

180-242

1

34

35

 

 

E15

 

 

1

53

50

 

 

 

 

 

 

 

 

 

W48A1

- F0Z

 

 

1

15

20

 

W48L1

F07

415/380-3 3

342-456

1

17

20

 

 

F14

 

 

1

31

35

 

W60A1

- E0Z

 

 

1

28

40

 

 

E09

220/200-3

180-242

1

34

40

 

 

E15

 

 

1

53

60

 

W60A1

- F0Z

 

 

1

16

20

 

W60L1

F07

415/380-3 3

342-456

1

17

20

 

 

F14

 

 

1

31

35

 

W70A1

- P0Z

 

 

1

25

35

 

W70L1

P07

400/380-3 3

342/440

1

25

35

 

 

P14

 

 

1

32

35

 

1 Maximum size of the time delay fuse or "D" rated circuit breaker for protection of field wiring conductors. 2 These "Minimum Circuit Amps" values are to be used for sizing the field power conductors.

3415/380-3 and 400/380-3 electrical ratings are 3-phase wye (star) systems requiring three (3) phase legs plus neutral and ground. NOTE: The indoor and outdoor motors and 24V transformer primary are connected at 240V derived from one (1) phase leg to neutral. This is internally connected and no field wiring required.

NOTE: All wiring must conform to NIC/EIC latest edition.

IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses & conductor wires in accordance with the National Electrical Code & all local codes.

Form No.

S3408-1011

Supersedes

S3408-710

Page

5 of 8

Indoor Blower Performance - CFM (m3/s) at 220 Volts

ESP

W24A, W24L

 

W30A

 

 

W42A, W42L

W60A, W60L

 

W36A, W36L

 

 

W48A, W48L

W70A, W70L

in Inches

 

 

 

 

 

H2O

Single Speed

High Speed

Low Speed

High Speed

Low Speed

High Speed

Low Speed

(Pa)

Dry / Wet Coil

Dry / Wet Coil

Dry / Wet Coil

Dry / Wet Coil

Dry / Wet Coil

Dry / Wet Coil

Dry / Wet Coil

 

.00

800

/ 845

1160

/ 1095

790

/ 780

1565 / 1500

1370 / 1330

1825 / 1660

1330 / 1200

(0)

(0.38

/ 0.40)

(0.55

/ 0.52)

(0.37

/ 0.37)

(0.74

/ 0.71)

(0.65 / 0.63)

(0.86 / 0.78)

(0.63 / 0.57)

.10

830

/ 780

1115 / 1060

775

/ 760

1470 / 1380

1285 / 1240

1740 / 1570

- / -

(25)

(0.39

/ 0.37)

(0.53

/ 0.50)

(0.36

/ 0.35)

(0.69

/ 0.65)

(0.61 / 0.59)

(0.82 / 0.74)

 

.20

780

/ 720

1070 / 1000

760

/ 740

1360 / 1285

1200 / 1160

1660 / 1500

- / -

(50)

(0.37

/ 0.34)

(0.50

/ 0.47)

(0.35

/ 0.35)

(0.64

/ 0.61)

(0.57 / 0.55)

(0.78 / 0.71)

 

 

 

 

 

 

 

 

 

 

 

.30

710

/ 640

1000 / 915

- / -

1250 / 1160

1120 / 1080

1550 / 1400

- / -

(75)

(0.33

/ 0.30)

(0.47

/ 0.43)

(0.59

/ 0.55)

(0.53 / 0.51)

(0.73 / 0.66)

 

 

 

.40

640

/ 560

925

/ 830

- / -

1140

/ 1065

- / -

1470 / 1330

- / -

(100)

(0.30

/ 0.26)

(0.44

/ 0.39)

(0.54

/ 0.50)

(0.69 / 0.63)

 

 

 

 

Above data is with 1" (25mm) standard disposable filter and 1" (25mm) washable filter.

For optional 2" (51mm) pleated filter - reduce ESP by .15” (37.33Pa).

Speeds marked “bold” above

See installation instructions for maximum ESP information on various KW application.

are Factory Connected.

Electric Heat Table - Refer to Electrical Specifications for Availability by Unit Model

 

 

 

 

 

 

 

 

 

W30A1-F

W42A1-E

W42A1-F, W42L1-F

 

 

 

W24A1-F

W30A1-D

 

 

W48A1-F, W48L1-F

Model

W24A1-D

W36A1-E

W36A1-F

W48A1-E

W24L1-F

W36A1-D

W60A1-F, W60L1-F

 

 

 

 

 

W36L1-F

W60A1-E

 

 

 

 

 

 

 

 

 

W70A1-P, W70L1-P

 

 

 

 

 

 

 

 

 

 

 

 

 

KW

240V-1

220V-1

415V-3

380V-3

240V-1

220V-1

220V-3

200V-3

415V-3

380V-3

220V-3

200V-3

415V-3

380V-3

WATTS

WATTS

WATTS

WATTS

WATTS

WATTS

WATTS

WATTS

WATTS

WATTS

WATTS

WATTS

WATTS

WATTS

 

5.0

5011

4220

4484

3751

5011

4220

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8.0

8011

6721

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10.0

 

 

 

 

9994

8411

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6.0

 

 

 

 

 

 

5041

4161

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.0

 

 

 

 

 

 

 

 

6740

5656

 

 

6740

5660

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9.0

 

 

 

 

 

 

 

 

 

 

7562

6213

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12.0

 

 

 

 

 

 

10082

8323

11178

9408

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14.0

 

 

 

 

 

 

 

 

 

 

 

 

13450

11280

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15.0

 

 

 

 

 

 

 

 

 

 

12603

10345

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Form No.

S3408-1011

Supersedes

S3408-710

Page

6 of 8

Cooling Application Data - Outdoor Temperature 1

Model

DB/WB2

Cooling

 

 

OUTDOOR TEMPERATURE 1

 

 

Capacity

75°F (23.9°C)

85°F (29.4°C)

95°F (35.0°C)

105°F (40.6°C)

115°F (46.1°C)

125°F (51.7°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75/62°F

Total

22,900 (6.71)

20,600 (6.03)

18,400 (5.39)

16,900 (4.95)

15,500 (4.54)

14,700 (4.30)

W24A

(23.9/16.7°C)

Sensible

17,700 (5.18)

16,900 (4.95)

16,200 (4.74)

15,400 (4.51)

14,500 (4.25)

13,500 (3.95)

 

 

 

 

 

 

 

 

W24L

80/67°F

Total

24,400 (7.14)

22,800 (6.68)

21,200 (6.21)

19,800 (5.80)

18,700 (5.48)

17,800 (5.21)

 

 

(26.7/19.4°C)

Sensible

17,200 (5.04)

16,800 (4.92)

16,300 (4.77)

15,700 (4.60)

15,000 (4.39)

14,200 (4.16)

 

75/62°F

Total

27,600 (8.08)

25,000 (7.32)

22,600 (6.62)

20,700 (6.06)

19,100 (5.59)

17,900 (5.24)

W30A

(23.9/16.7°C)

Sensible

21,600 (6.33)

20,700 (6.06)

19,800 (5.80)

18,800 (5.51)

17,700 (5.18)

16,700 (4.89)

80/67°F

Total

29,400 (8.61)

27,700 (8.11)

26,000 (7.61)

24,400 (7.14)

23,000 (6.73)

21,800 (6.38)

 

 

(26.7/19.4°C)

Sensible

20,900 (6.12)

20,500 (6.00)

19,900 (5.83)

19,200 (5.62)

18,400 (5.39)

17,600 (5.15)

 

75/62°F

Total

33,600 (9.84)

30,100 (8.81)

27,200 (7.96)

25,200 (7.38)

23,700 (6.94)

22,900 (6.71)

W36A

(23.9/16.7°C)

Sensible

25,100 (7.35)

23,900 (7.00)

22,800 (6.68)

21,800 (6.38)

20,900 (6.12)

20,100 (5.89)

 

 

 

 

 

 

 

 

W36L

80/67°F

Total

35,800 (10.48)

33,300 (9.75)

31,200 (9.14)

29,700 (8.70)

28,600 (8.37)

27,900 (8.17)

 

 

(26.7/19.4°C)

Sensible

24,300 (7.12)

23,600 (6.91)

22,900 (6.71)

22,300 (6.53)

21,700 (6.35)

21,200 (6.21)

 

75/62°F

Total

38,400 (11.24)

34,900 (10.22)

31,500 (9.22)

28,300 (8.29)

25,300 (7.41)

23,500 (6.88)

W42A

(23.9/16.7°C)

Sensible

31,300 (9.17)

29,600 (8.67)

28,000 (8.20)

26,500 (7.76)

25,000 (7.32)

23,500 (6.88)

W42L

80/67°F

Total

41,00 (12.01)

38,700 (11.33)

36,000 (10.54)

33,400 (9.78)

30,400 (8.90)

27,200 (7.96)

 

 

(26.7/19.4°C)

Sensible

30,300 (8.87)

29,400 (8.61)

28,300 (8.29)

27,200 (7.96)

26,000 (7.61)

24,700 (7.23)

 

75/62°F

Total

43,700 (12.80)

39,700 (11.63)

36,000 (10.54)

32,700 (9.58)

29,400 (8.61)

27,100 (7.94)

W48A

(23.9/16.7°C)

Sensible

35,200 (10.31)

33,700 (9.87)

32,100 (9.40)

30,400 (8.90)

28,800 (8.43)

27,100 (7.94)

 

 

 

 

 

 

 

 

W48L

80/67°F

Total

46,600 (13.65)

44,100 (12.91)

41,500 (12.12)

38,500 (11.27)

35,200 (10.31)

31,800 (9.31)

 

 

(26.7/19.4°C)

Sensible

34,100 (9.99)

33,300 (9.75)

32,300 (9.46)

31,200 (9.14)

30,000 (8.78)

28,500 (8.35)

 

 

 

 

 

 

 

 

 

 

75/62°F

Total

52,100( 15.26)

47,000 (13.76)

42,200 (12.36)

38,000 (11.13)

34,000 (9.96)

30,500 (8.93)

W60A

(23.9/16.7°C)

Sensible

39,800 (11.65)

37,300 (10.92)

35,000 (10.25)

32,900 (9.63)

30,800 (9.02)

29,000 (8.49)

W60L

80/67°F

Total

55,700 (16.31)

52,100 (15.26)

48,500 (14.17)

44,800 (13.12)

41,000 (12.00)

37,100 (10.86)

 

 

(26.7/19.4°C)

Sensible

38,600 (11.30)

36,900 (10.81)

35,300 (10.34)

33,800 (9.90)

32,100 (9.40)

30,500 (8.93)

 

75/62°F

Total

65,300 (19.12)

58,300 (17.07)

52,100 (15.26)

46,800 (13.70)

42,200 (12.36)

38,200 (11.19)

W70A

(23.9/16.7°C)

Sensible

46,700 (13.67)

44,000 (12.88)

41,100 (12.04)

38,400 (11.24)

35,700 (10.45)

32,900 (9.63)

 

 

 

 

 

 

 

 

W70L

80/67°F

Total

69,700 (20.41)

64,700 (18.95)

59,000 (17.28)

55,200 (16.16)

50,700 (14.85)

46,400 (13.59)

 

 

(26.7/19.4°C)

Sensible

45,300 (13.27)

43,500 (12.74)

41,500 (12.15)

39,400 (11.54)

37,100 (10.86)

34,600 (10.13)

 

 

 

 

 

 

 

 

 

1 Below 65°F (18.3C), unit requires a factory or field installed low ambient control. 2 Return air temperature.

Form No.

S3408-1011

Supersedes

S3408-710

Page

7 of 8

Air Conditioning Wall-Mount Model Nomenclature

W 36 A 1

D

10 X

X X

X

X

X

SERIES |

REVISION

KW

NOMINAL

CAPACITY |

24 - 2 Ton

30 - 2½ Ton

36 - 3 Ton

42 - 3½ Ton

48 - 4 Ton

60 - 5 Ton

70 - 6 Ton

VOLTS & PHASE |

D - 240/220/50/1 E - 220/200/50/3 F - 415/380/50/3 1 P - 400/380/50/3 1

TYPE

A = Compressor & Controls - Right Side

L = Compressor & Controls - Left Side

1 See Electrical Specifications (Page 5).

VENTILATION OPTIONS

X - Barometric Fresh Air Damper (Standard) B - Blank-off Plate

M - Motorized Fresh Air Damper

V - Commercial Room Ventilator-Motorized w/Exhaust E - Economizer (Internal) - Fully Modulating w/Exhaust

FILTER OPTIONS

X - 1-Inch (25mm) Disposable (Standard)

W - 1-Inch (25mm) Washable

P - 2-Inch (51mm) Pleated

 

 

| CONTROL MODULES

 

 

(See Chart Below)

 

 

| COIL OPTIONS

 

 

X - Standard

COLOR OPTIONS

1 - Phenolic Coated Evaporator

X - Beige (Standard)

2 - Phenolic Coated Condenser

1 - White

3 - Phenolic Coated Evaporator

4 - Buckeye Gray

and Condenser

5 - Desert Brown

 

8 - Dark Bronze

| OUTLET OPTIONS

A - Aluminum

X - Front (Standard)

S - Stainless Steel

 

Ventilation Options

Models

W24A1

W30A1

W42A1, W48A1, W60A1, W70A1

W24L1

W36A1, W36L1

W42L1, W48L1, W60L1, W70L1

 

Description

Factory Installed

Field Installed

Factory Installed

Field Installed

Factory Installed

Field Installed

Code No.

Part No.

Code No.

Part No.

Code No.

Part No.

 

Barometric Fresh Air Damper

X

BFAD-2

X

BFAD-3

X

BFAD-5

 

 

 

 

 

 

 

Blank-Off Plate

B

BOP-2

B

BOP-3

B

BOP-5

 

 

 

 

 

 

 

Motorized Fresh Air Damper

M

MFAD-2

M

MFAD-3

M

MFAD-5

 

 

 

 

 

 

 

Commercial Ventilator - Motorized

V

CRV-2

V

CRV-3

V

CRV-5

 

 

 

 

 

 

 

Economizer (Internal) - Fully Modulating 1

E

EIFM-2B

E

EIFM-3C

E

EIFM-5C

 

 

 

 

 

 

 

1 Low ambient control is required with economizer for low temperature compressor operation.

 

 

 

Air Conditioning Control Modules

 

 

 

All Models Except As Noted

HPC 1

LPC 2

CCM 3

LAC 4

ALR 5

SK 6

SK 7

DDC 9

Factory Installed Code

Field Installed Part

STD

STD

STD

 

 

 

 

 

X

N/A

STD

STD

STD

 

 

 

 

 

E

CMA-28

 

 

 

 

 

STD

STD

STD

 

 

 

 

 

J

Factory Only

 

 

 

 

 

STD

STD

STD

 

 

 

 

 

K

CMC-15 and CMA-28

 

 

 

 

 

STD

STD

STD

 

 

 

 

 

M

Factory Only

 

 

 

 

 

STD

STD

STD

 

 

 

 

 

Field Installed Only

CMC-15

 

 

 

 

 

STD

STD

STD

 

 

 

 

 

V 9

Factory Only

 

 

 

 

 

STD

STD

STD

 

 

 

 

 

Field Installed Only

CMA-23 for W18-36A

 

 

 

 

CMA-24 for W42-70A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

STD

STD

 

 

 

 

 

Field Installed Only

SK111

 

 

 

 

 

STD = Standard equipment all models.

1 HPC. High pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note 3. 2 LPC. Low pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note 3.

3 CCM. Compressor control module has adjustable 30-second to 5-minute delay-on-break timer. On initial power-up, or any time the power is interrupted, the delay-on-make will be 2 minutes plus 10% of the delay-on-break setting. There is no delay-on-make during routine operation of the unit. The module also provides the lockout feature (with 1 retry) for high and/or low-pressure controls, and a 2-minute timed bypass for low-pressure control.

4 LAC. Low ambient control permits cooling operation down to 0°F (-17.7°C)

5 ALR. The alarm relay has a set of normally open and normally closed dry contacts to provide the ability to signal a condition of shutdown on either high or low pressure controls.

6 SK.

PTCR start kit can be used with all -A single phase models. Increases starting torque 2-3x. Not used for -E, -F or -P three phase models. Do not use if SK111 is used.

7 SK.

Start capacitor and potential relay start kit can be used with all -A single phase models. Increases starting torque 9x. Not used for -E, -F or -P three phase models. Do not

use if CMC-15 is used.

8 DDC. Incorporates 4 additional sensors: discharge air temperature, indoor blower airflow, compressor current, and dirty filter. These sensing devices function to input analog data such as temperature, as well as digital data such as airflow, compressor status or filter status.

9 “V” control module should be ordered in conjunction with direct digital controller (DDC) model TCS24. Refer to DDC specification sheet S3280 for more information.

Bard Manufacturing Company, Inc.

Bryan, Ohio 43506

www.bardhvac.com

Since 1914 . . . Moving ahead, just as planned.