Requirements: R-410A
Important Installer Note
Service Hints
High & Low Pressure Switch
Sequence of Operation
Compressor Control Module
Adjustments
Pressure Service Ports
Troubleshooting
Fan Blade Setting Dimension
Refrigerant Charge
Pressure Table
Optional Field Installed Accessories
Tables
Table 1 Electric Heat Table ..................................4
X - Standard Low Pressure Switch,
High Pressure Switch, Compressor
Control Module
E - X + Low Ambient Control
J - X + Low Ambient Control and
Alarm Relay
COIL OPTIONS
X - Standard Coils
1 - Phenolic Coated Evaporator
2 - Phenolic Coated Condenser
3 - Phenolic Coated Evaporator and
Condenser
OUTLET OPTIONS
X - Front
COLOR OPTIONS
X - Beige
1 - White
4 - Buckeye Gray
5 - Desert Brown
8 - Dark Bronze
FILTER OPTIONS
X - 1-Inch Throwaway
(Standard)
W - 1-Inch Washable
P - 2-Inch Pleated
VENTILATION OPTIONS
X - Barometric Fresh Air Damper (Standard)
B - Blank-off Plate
E - Economizer (Internal) - Fully Modulating with Exhaust
V - Commercial Ventilator - Motorized with Exhaust
NOTE: Maintain a minimum of 20 inches clearance on right side to allow access to control panel and allow proper airow to outdoor
condenser coil. Allow 15 inches on left side.
Manual 2100-618
Page 5 of 21
TABLE 2
ELECTRICAL HEAT SPECIFICATIONS
SINGLE CIRCUIT
Rated Volts
Models
W12AAAA0Z
A03
A05
W12AAAK00
K02
W12AAAD00
D03
j Maximum size of the time delay fuse or HACR type circuit breaker for protection of eld wiring conductors.
Based on 75°C copper wire. All wiring must conform to NEC and all local codes.
These “Minimum Circuit Ampacity” values are to be used for sizing the eld power conductors. Refer to the National
Electrical Code (latest revision), article 310 for power conductor sizing.
CAUTION: When more than one eld power conductor circuit is run through one conduit, the conductors must be
derated. Pay special attention to note 8 of table 310 regarding Ampacity
conductors are in a raceway.
and
Phase
230/208-1
115-1
240/220-1
No. Field
Power
Circuits
1
1
1
1
1
1
1
Minimum
Circuit
Ampacity
9
20
27
17
26
9
20
j
Maximum
External Fuse
or Circuit
Breaker
15
20
30
30
30
15
20
Adjustment Factors when more than 3
Field Power
Wire Size
14
12
10
10
10
14
12
Ground
Wire Size
14
12
10
10
10
14
12
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked
for external signs of shipping damage. If damage is
found, the receiving party must contact the last carrier
immediately, preferably in writing, requesting inspection
by the carrier’s agent.
GENERAL
The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.
The refrigerant system is completely assembled and
charged. All internal wiring is complete.
The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
air ducts.
These instructions explain the recommended method to
install the air cooled self-contained unit and the electrical
wiring connections to the unit.
These instructions and any instructions packaged with
any separate equipment required to make up the entire
air conditioning system should be carefully read before
beginning the installation. Note particularly “Starting
Procedure” and any tags and/or labels attached to the
equipment.
While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way. Authorities having
jurisdiction should be consulted before the installation
is made. See Page 3 for information on codes and
standards.
Size of unit for a proposed installation should be based
on heat loss/gain calculation made according to methods
of Air Conditioning Contractors of America (ACCA).
The air duct should be installed in accordance with the
Standards of the National Fire Protection Association
for the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA No.
90A, and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B. Where local
regulations are at a variance with instructions, installer
should adhere to local codes.
Manual 2100-618
Page 6 of 21
DUCT WORK
FRESH AIR INTAKE
All duct work, supply and return must be properly sized
for the design air ow requirement of the equipment.
Air Conditioning Contractors of America (ACCA) is
an excellent guide to proper sizing. All duct work or
portions thereof not in the conditioned space should be
properly insulated in order to both conserve energy and
prevent condensation or moisture damage.
Refer to Table 8 for maximum static pressure available
for duct design.
Design the duct work according to methods given by
the Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of one inch of insulation.
Use insulation with a vapor barrier on the outside of the
insulation. Flexible joints should be used to connect the
duct work to the equipment in order to keep the noise
transmission to a minimum.
Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture entering the
wall cavity.
Some installations may not require any return air duct.
It is recommended that on this type of installation that
a lter grille be located in the wall. Filters must be of
sufcient size to allow a maximum velocity of 400 FPM.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to
installation only in a single story structure.
All units are built with fresh air inlet slots punched in the
service panel.
If the unit is equipped with a fresh air damper assembly,
the assembly is shipped already attached to the unit. The
damper blade is locked in the closed position. To allow
the damper to operate, the maximum and minimum blade
position stops must be installed. See Figure 2.
All capacity, efciency and cost of operation information
as required for Department of Energy “Energyguide”
Fact Sheets is based upon the fresh air blank-off plate
in place and is recommended for maximum energy
efciency.
The blank-off plate is available upon request from the
factory and is installed in place of the fresh air damper
shipped with each unit.
CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at the top
of the unit down to the unit base. There are openings in
the unit base for the drain hose to pass through. In the
event the drain hose is connected to a drain system of
some type, it must be an open or vented type system to
assure proper drainage.
FIGURE 2
FRESH AIR DAMPER
FILTERS
A one inch throwaway lter is supplied with each unit.
The lter slides into position making it easy to service.
This lter can be serviced from the outside by removing
the service door. A 2-inch pleated lter is also available
as an optional accessory. The internal lter brackets are
adjustable to accommodate the 2-inch lter by bending
the metal tabs holding the 1-inch lter down. There are
two tabs on each side of the lter.
Manual 2100-618
Page 7 of 21
INSTALLATION INSTRUCTIONS
WALL MOUNTING INFORMATION
1. These units are secured by wall mounting brackets
which secure the unit to the outside wall surface at
both sides.
2. On wood frame walls, the wall construction must be
strong and rigid enough to carry the weight of the
unit without transmitting any unit vibration.
3. Concrete block walls must be thoroughly inspected
to insure that they are capable of carrying the weight
of the installed unit.
MOUNTING THE UNIT
1. Two holes, for the supply and return air openings,
must be cut through the wall as shown in Figure 3.
2. Locate and mark lag bolt locations, if desired. See
Figure 3.
3. Hook top rain ashing under back bend of top. Top
rain ashing is shipped attached to the back of the
unit on the right side.
4. Position unit in opening and secure with 5/16 lag
bolts; use 7/8 inch diameter at washers on the lag
bolts.
5. Secure rain ashing to wall and caulk across entire
length of top. See Figure 3.
6. For additional mounting rigidity, the return air
and supply air frames or collars can be drilled
and screwed or welded to the structural wall itself
(depending upon wall construction). Be sure to
observe required clearance if combustible wall.
7. On side-by-side installations, maintain a minimum
of 20 inches clearance on right side to allow access
to control panel and allow proper airow to outdoor
coil. Additional clearance may be required to meet
local or national codes.
Manual 2100-618
Page 8 of 21
FIGURE 3
MOUNTING INSTRUCTIONS
2.500
19.719
19.719
7.031
17.000
17.0006.969
SEAL WITH BEAD OF CAULKING
ALONG ENTIRE LENGTH OF TOP.
TOP
WALL
7.031
5.000
10.000
5.000
RAIN FLASHING
SUPPLIED
FOAM AIR SEAL
WALL STRUCTURE
SUPPLY AIR DUCT
RETURN AIR
OPENING
WALL OPENING AND HOLE
LOCATION VIEW
NOTE:
IT IS RECOMMENDED THAT A BEAD OF SILI CONE
CAULKING BE PLACED BEHIND THE SIDE MOUNTI NG
FLANGES AND UNDER TOP FLASHING AT TIME OF
INSTALLATION.
MIS-3600
Manual 2100-618
Page 9 of 21
FIGURE 4
WALL MOUNTING INSTRUCTIONS
SEE FIGURE 3 - MOUNTING INSTRUCTIONS
FIGURE 5
WALL MOUNTING INSTRUCTIONS
SEE UNIT DIMENSIONS, FIGURE 1,
FOR ACTUAL DIMENSIONS
Manual 2100-618
Page 10 of 21
FIGURE 6
COMMON WALL MOUNTING INSTALLATIONS
Manual 2100-618
Page 11 of 21
WIRING – MAIN POWER
WIRING – LOW VOLTAGE WIRING
Refer to the unit rating plate for wire sizing information
and maximum fuse or “HACR” type circuit breaker size.
Each outdoor unit is marked with a “Minimum Circuit
Ampacity”. This means that the eld wiring used must
be sized to carry that amount of current. Depending
on the installed KW of electric heat, there may be two
eld power circuits required. If this is the case, the unit
serial plate will so indicate. All models are suitable
only for connection with copper wire. Each unit and/or
wiring diagram will be marked “Use Copper Conductors
Only”. These instructions must be adhered to. Refer to
the National Electrical Code (NEC) for complete current
carrying capacity data on the various insulation grades of
wiring material. All wiring must conform to NEC and all
local codes.
The electrical data lists fuse and wire sizes (75°C copper)
for all models, including the most commonly used heater
sizes. Also shown are the number of eld power circuits
required for the various models with heaters.
The unit rating plate lists a “Maximum Time Delay Relay
Fuse” of “HACR” type circuit breaker that is to be used
with the equipment. The correct size must be used for
proper circuit protection and also to assure that there
will be no nuisance tripping due to the momentary high
starting current of the compressor motor.
See Table 2 for electrical specications.
230/208, 1 phase equipment use dual primary voltage
transformers. All equipment leaves the factory wired on
240V tap. For 208V operation, reconnect from 240V to
208V tap. The acceptable operating voltage range for the
240 and 208V taps are:
TapRange
240253 - 216
208220 - 187
NOTE: The voltage should be measured at the eld
power connection point in the unit and while the
unit is operating at full load (maximum amperage
operating condition).
An 18 gauge copper, color-coded thermostat cable is
recommended. The connection points are shown in this
Manual. See Table below.
TABLE 3
WALL THERMOSTAT
Part NumberPredominate Features
8403-057
(TH3110D1040)
8403-058
(TH5220D1151)
8403-060
(1120-445)
1 stage Cool, 1 stage Heat
Electronic Non-Programmable
Auto or Manual changeover
2 stage Cool, 2 stage Heat
Electronic Non-Programmable
HP or Conventional
Auto or Manual changeover
3 stage Cool; 3 stage Heat
Programmable/
Non-Programmable Electronic
HP or Conventional
Auto or Manual changeover
Dehumidication Output
Manual 2100-618
Page 12 of 21
Transformer
VA
552.3
TABLE 4
THERMOSTAT WIRE SIZE
FLAWire Gauge
20 gauge
18 gauge
16 gauge
14 gauge
12 gauge
Maximum
Distance
In Feet
45
60
100
160
250
Low Voltage Connection
These units use a 24-volt AC low voltage circuit. The “R” terminal is the hot terminal and the “C” terminal is grounded.
“G” terminal is the fan input.
“Y” terminal is the compressor input for cooling 1-Stage units only or 2-Stage units with ECONWM*
“Pink Wire” is 2nd Stage cooling 2-Stage units only with ECONWM*
“Y1” terminal is the 1st Stage compressor input for cooling 2-Stage units only — No ECONWM*
“Y2” terminal is the 2nd Stage compressor input for cooling 2-Stage units only — No ECONWM*
“W1” terminal is the 1st stage electric heat.
“W2” terminal is the 2nd stage heat (if equipped).
“A”, “E”, “F” terminals are the ventilation inputs. See Figures 8-10 for detailed diagrams.
NOTE: On models with “J” Control Module, Terminals 1, 2 and 3 are used for the alarm relay.
FIGURE 7
LOW VOLTAGE WIRING
BASIC A/C WITH OPTIONAL ELECTRIC HEAT
NO ECONOMIZER OR VENTILATION PACKAGES
Manual 2100-618
Page 13 of 21
4
8403-060
THERMOSTAT
FIGURE 8
LOW VOLTAGE WIRING
A/C WITH PROGRAMMABLE THERMOSTAT
LOWVOLTAGEWIRING
ACWITHPROGRAMMABLETHERMOSTAT
C
GRY1W2
W1/E
YO/D
Y2
LO/B
ELECTRONIC
A
PROGRAMABLE
UNIT 24V
TERMINAL BLOCK
RED
BLACK
2
1
345
3
CRG123
YW1W2Y1
Y2
1
CRV
BROWN/WHITE
OPTIONAL
VENT PACKAGE
REMOVE JUMPER FOR 2 STAGE ELECTRIC HEAT ON UNITS
1
WITH 15 OR MORE KW
YELLOW/RED
OPTIONAL 8403-067
6
CO2 CONTROLLER
FE
MIS-3597
2
A
Manual 2100-618
Page 14 of 21
DO NOT CONNECT "A" FROM 8403-060 IF OPTIONAL CO2
2
CONTROLLER IS USED
ADD JUMPER FROM "G" TO "E" ONLY IF OPTIONAL CO2 CONTROLLER IS INSTALLED
3
CHANGE MODEL CONFIGURATION FROM HEAT PUMP TO HEAT/COOL.
4
MUST BE CONFIGURED TO PROGRAMMABLE AND FAN SET TO PROGRAMMED
FAN FOR THE "A" OUTPUT TO FUNCTION DURING SCHEDULED OCCUPIED PERIODS.
MIS-3597
LOW VOLTAGEWIRING
ACWITHNON-PROGRAMMABLETHERMOSTAT
FIGURE 9
LOW VOLTAGE WIRING
A/C WITH NON-PROGRAMMABLE THERMOSTAT
8403-057
(TH3110D1040)
4
8403-058
(TH5220D1151)
UNIT 24V
TERMINAL BLOCK
RED
BLACK
Rc
2
Rc
RGY
GY
R
RG
CRV
C
C
2
C
W
O
W2Y2
W
YW1W2Y1Y2
OPTIONAL
VENT PACKAGE
REMOVE JUMPERFOR 2 STAGEELECTRIC HEAT ON UNITS
1
WITH 15OR MORE KW
1 STAGE COOL
B
1 STAGE HEAT
THERMOSTAT
2 STAGE COOL
2 STAGE HEAT
THERMOSTAT
YELLOW/RED
123EF
31
BROWN/WHITE
2
1
3456
5
A
OPTIONAL 8403-067
CO2 CONTROLLER
FACTORY INSTALLED JUMPER
2
ADD JUMPER IFOPTIONAL CO2 CONTROLLER IS NOT USED,
3
VENT WILLRUN WHILE BLOWER IS ENERGIZED.DO NOT
INSTALL JUMPER IF OPTIONALCO2 CONTROLLER INSTALLED,
AND SEENOTE 6.
CHANGE "SYSTEMTYPE", SET UP FUNCTION 1, FROM 5 (2 HEAT/ 1 COOL HEATPUMP)
4
TO 6 (2HEAT/ 2 COOLCONVENTIONAL).
5
ADD JUMPERFROM "G" TO"E" ONLY IF
OPTIONAL CO2CONTROLLER IS I NSTALLED
MIS-3598
Manual 2100-618
Page 15 of 21
LowVoltage Wiring Diagram
4
8403-058
(TH5220D1151)
5
Thermostat
part #8403-060
LOW VOLTAGE WIRING
1-STAGE A/C WITH OPTIONAL ELECTRIC HEAT
WITH ECONWM STYLE ECONOMIZER
3
Y
C
RRC
GW2
Y2
Y2
YO/D
RGC
Y1
FIGURE 10
W
W1/E
W2
2
A
O/B
L
A/C UNIT
24V TERMINALS
CGR
BLACK
Economizer
Wiring Harness
Must be energized to enable minimum position. NOTE: Economizer Control Default Setting
2
is 10V (100%). Depending upon application may require setting to lower value.
Factory Jumper Installed.
3
Change "system type", set up function 1, from 5 (2 heat/ 1 cool heat pump)
4
to 6 (2 heat/ 2 cool conventional).
Change model configuration from heat pump to heat/cool, and must be configured for
5
economizer for YO/D output to be active as first stage cooling.
RED
Y
YELLOW
Y1
PURPLE
Y2
W1
PINK
BLUE
BROWN/WHITE
W2
3
2
1
EA
F
2
YELLOW/RED
Manual 2100-618
Page 16 of 21
MIS-3593
START UP
THESE UNITS REQUIRE R-410A
REFRIGERANT AND POL YOL
ESTER OIL.
GENERAL:
1. Use separate service equipment to avoid cross
contamination of oil and refrigerants.
2. Use recovery equipment rated for R-410A
refrigerant.
3. Use manifold gauges rated for R-410A (800 psi/250
psi low).
4. R-410A is a binary blend of HFC-32 and HFC-125.
5. R-410A is nearly azeotropic - similar to R-22 and
R-12. Although nearly azeotropic, charge with
liquid refrigerant.
6. R-410A operates at 40-70% higher pressure than
R-22, and systems designed for R-22 cannot withstand this higher pressure.
7. R-410A has an ozone depletion potential of zero,
but must be reclaimed due to its global warming
potential.
8. R-410A compressors use Polyol Ester oil.
9. Polyol Ester oil is hygroscopic; it will rapidly absorb
moisture and strongly hold this moisture in the oil.
10. A liquid line dryer must be used - even a deep
vacuum will not separate moisture from the oil.
11. Limit atmospheric exposure to 15 minutes.
12. If compressor removal is necessary, always plug
compressor immediately after removal. Purge with
small amount of nitrogen when inserting plugs.
TOPPING OFF SYSTEM CHARGE
If a leak has occurred in the system, Bard Manufacturing
recommends reclaiming, evacuating (see criteria above),
and charging to the nameplate charge. If done correctly,
topping off the system charge can be done without
problems.
With R-410A, there are no signicant changes in the
refrigerant composition during multiple leaks and
recharges. R-410A refrigerant is close to being an
azeotropic blend (it behaves like a pure compound
or single component refrigerant). The remaining
refrigerant charge, in the system, may be used after leaks
have occurred and then “top-off” the charge by utilizing
the pressure charts on the inner control panel cover as a
guideline.
REMEMBER: When adding R-410A refrigerant, it must
come out of the charging cylinder/tank as a liquid to
avoid any fractionation, and to insure optimal system
performance. Refer to instructions for the cylinder that
is being utilized for proper method of liquid extraction.
WARNING
Failure to conform to these practices
could lead to damage, injury or death.
SAFETY PRACTICES:
1. Never mix R-410A with other refrigerants.
2. Use gloves and safety glasses, Polyol Ester oils can
be irritating to the skin, and liquid refrigerant will
freeze the skin.
3. Never use air and R-410A to leak check; the
mixture may become ammable.
4. Do not inhale R-410A – the vapor attacks the nervous system, creating dizziness, loss of coordination and slurred speech. Cardiac irregularities, unconsciousness and ultimate death
can result from breathing this concentration.
5. Do not burn R-410A. This decomposition produces hazardous vapors. Evacuate the area if
exposed.
6. Use only cylinders rated DOT4BA/4BW 400.
7. Never ll cylinders over 80% of total capacity.
8. Store cylinders in a cool area, out of direct
sunlight.
9. Never heat cylinders above 125°F.
10. Never trap liquid R-410A in manifold sets, gauge
lines or cylinders. R-410A expands signicantly at
warmer temperatures. Once a cylinder or line is full
of liquid, any further rise in temperature will cause it to burst.
Manual 2100-618
Page 17 of 21
START UP
IMPORTANT INSTALLER NOTE
For improved start up performance, wash the indoor coil
with a dishwasher detergent.
SERVICE HINTS
1. Caution owner to maintain clean air lters at all
times. Also not to needlessly close off supply and
return air registers. This reduces airow through the
system which shortens equipment service life as well
as increasing operation costs.
2. The unit is equipped with a high pressure cut out
switch.
3. Check all power fuses or circuit breakers to be sure
they are the correct rating.
4. Periodic cleaning of the outdoor coil to permit full
and unrestricted airow circulation is essential.
HIGH and LOW PRESSURE SWITCH
The W12AAA models are supplied with a remote reset
high and low pressure switch. If tripped, this pressure
switch may be reset by turning the thermostat off then
back on again.
SEQUENCE OF OPERATION
HEATING – Circuit R-Y makes at thermostat pulling
in compressor contactor, starting the compressor
and outdoor motor. The G (indoor motor) circuit
is automatically completed on any call for cooling
operation or can be energized by manual fan switch
on subbase for constant air circulation. On a call for
heating, circuit R-W1 make at the thermostat pulling in
heat contact for the strip heat and blower operation.
COMPRESSOR CONTROL MODULE
The compressor control is an anti-short cycle/lockout
timer with high and low pressure switch monitoring and
alarm relay output.
During routine operation of the unit with no power
interruptions the compressor will operate on demand
with no delay.
High Pressure Switch and Lockout Sequence
If the high pressure switch opens, the compressor
contactor will de-energize immediately. The lockout
timer will go into a soft lockout and stay in soft lockout
until the high pressure switch closes and the delay on
break time has expired. If the high pressure switch opens
again in this same operating cycle the unit will go into
manual lockout condition and the alarm relay circuit
will energize. Recycling the wall thermostat resets the
manual lockout.
Low Pressure Switch, Bypass and Lockout
Sequence
If the low pressure switch opens for more than 120
seconds, the compressor contactor will de-energize
and go into a soft lockout. Regardless the state of the
low pressure switch, the contactor will reenergize after
the delay on make time delay has expired. If the low
pressure switch remains open, or opens again for longer
that 120 seconds, the unit will go into manual lockout
condition and the alarm relay circuit will energize.
Recycling the wall thermostat resets the manual lockout.
Alarm Relay Output
Alarm terminal is output connection for applications
where alarm relay is employed. This terminal is powered
whenever compressor is locked out due to HPC or LPC
sequences as described.
NOTE: Both high and low pressure switch controls
are inherently automatic reset devices. The
high pressure switch and low pressure switch
cut out and cut in settings are xed by specic
air conditioner or heat pump unit model. The
lockout features, both soft and manual, are a
function of the Compressor Control Module.
Adjustable Delay on Make and Break Timer
On initial power up or any time power is interrupted to
the unit the delay on make period begins, which will be
2 minutes plus 10% of the delay on break setting. When
the delay on make is complete and the high pressure
switch (and low pressure switch if employed) is closed,
the compressor contactor is energized. Upon shutdown
the delay on break time starts and prevents restart until
the delay on break and delay on make periods have
expired.
Manual 2100-618
Page 18 of 21
ADJUSTMENTS
PRESSURE SERVICE PORTS
Adjustable Delay on Make and Delay on Break
Timer
The potentiometer is used to select Delay on Break time
from 30 seconds to 5 minutes. Delay of Make (DOM)
timing on power up and after power interruptions is equal
to 2 minutes plus 10% of Delay of Break (DOB) setting:
0.5 minute (30 seconds) DOB = 123 second DOM
1.0 minute (60 seconds) DOB = 126 second DOM
2.0 minute (120 seconds) DOB = 132 second DOM
3.0 minute (180 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM
During routine operation of the unit with no power
interruptions the compressor will operate on demand
with no delay.
Typical Settings for Dual Unit Installation:
Unit No. 1: DOB set at 2 minutes, and DOM is 132
seconds.
Unit No. 2: DOB set at 4 minutes, and DOM is 144
seconds.
High and low pressure service ports are installed on
all units so that the system operating pressures can be
observed. Pressure chart can be found later in the manual
covering all models. It is imperative to match the correct
pressure chart to the unit by model number.
Manual 2100-618
Page 19 of 21
TROUBLESHOOTING
FAN BLADE SETTING DIMENSIONS
Shown in Figure 7 is the correct fan blade setting
dimension for proper air delivery across the outdoor coil.
Any service work requiring removal or adjustment in
the fan and/or motor area will require that the dimension
below be checked and blade adjusted in or out on the
motor shaft accordingly.
FIGURE 11
FAN BLADE SETTING DIMENSION
AIRFLOW
"A"
MIS-1724
TABLE 6
INDOOR BLOWER PERFORMANCE
E.S.P.
in
H2O
.0
.1
.2
.3
.4
RECOMMENDED AIRFLOW RANGE
Model
W12AAA400.10475 - 300
230V/115V-60Hz240V-50Hz
Dry / WetDry / Wet
475 / 450
425 / 400
375 / 360
315 / 300
270 / 250
TABLE 7
RATED CFM AND ESP
Rated
CFM
Rated
ESP
W12AAA
395 / 375
355 / 330
310 / 300
260 / 250
225 / 210
Recommended
Airow Range
TABLE 5
FAN BLADE DIMENSION
ModelDimension A
W12AAA2.25"
R-410A
REFRIGERANT CHARGE
This unit was charged at the factory with the quantity of
refrigerant listed on the serial plate. AHRI capacity and
efciency ratings were determined by testing with this
refrigerant charge quantity.
The following pressure tables show nominal pressures for
the units. Since many installation specic situations can
affect the pressure readings, this information should only
be used by certied technicians as a guide for evaluating
proper system performance. They shall not be used to
adjust charge. If charge is in doubt, reclaim, evacuate
and recharge the unit to the serial plate charge.
TABLE 8
MAXIMUM ESP OF OPERATION
ELECTRIC HEAT ONLY
ModelESP
W12AAAA00
A03
A05
W12AAAK00
K02
W12AAAD00
D03
Values shown are for units equipped with
STD 1" throwaway lters. Derate ESP
by .15 for 2" pleated lters.
.35
.35
.35
.35
.35
.35
.35
Manual 2100-618
Page 20 of 21
TABLE 9
PRESSURE TABLE
COOLING
Model
Return Air
Temperature
75 deg. DB
62 deg. WB
W12AAAA
W12AAAK
80 deg. DB
67 deg. WB
85 deg. DB
72 deg. WB
75 deg. DB
62 deg. WB
W12AAAD
80 deg. DB
67 deg. WB
85 deg. DB
72 deg. WB
Low Side Pressure +4 PSIG
High Side Pressure +10 PSIG
Air Temperature Entering Outdoor Coil °F
Pressure75° 80°85°90°95°100°105°100°115°120°
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
125
296
134
304
139
315
125
314
134
322
139
333
129
316
138
324
143
335
129
334
138
343
143
355
132
336
141
345
146
357
132
357
141
366
146
379
134
359
143
368
148
381
134
380
143
390
148
404
137
381
146
391
151
405
137
404
146
414
151
428
139
405
149
415
154
430
139
429
149
440
154
455
141
429
151
440
156
455
141
454
151
466
156
482
144
454
154
466
159
482
144
482
154
494
159
511
146
481
156
493
161
510
146
510
156
523
161
541
148
508
158
521
164
539
148
538
158
552
164
571
TABLE 10
OPTIONAL FIELD INSTALLED ACCESSORIES
ModelDescription
BOP-1ABlank Off PlateX
BFAD-1Barometric Fresh Air DamperX
JIFM-1AEconomizer with ExhaustX
CMA-28Low Ambient ControlX
CRVS-1ACommercial Ventilator - Spring ReturnX
W12AAA
Manual 2100-618
Page 21 of 21
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.