Bard W12AAA, W12AAAA, W12AAAD, W12AAAK Installation Instructions Manual

INSTALLATION INSTRUCTIONS
WALL MOUNTED
P ACKAGE AIR CONDITIONERS
Model:
W12AAA
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
Since 1914....Moving ahead just as planned.
Page 1 of 21
CONTENTS
Getting Other Informations and Publications .........3
Wall Mount General Information
Air Conditioner Wall Mount Model Nomenclature Shipping Damage General Duct Work Filters Fresh Air Intake Condensate Drain
Installation Instructions
Wall Mounting Information Mounting the Unit Wiring – Main Power Wiring – Low Voltage Wiring
Figures
Figure 1 Unit Dimensions ......................................5
Figure 2 Fresh Air Damper ....................................7
Figure 3 Mounting Instructions ..............................9
Figure 4 Wall Mounting Instructions ....................10
Figure 5 Wall Mounting Instructions ....................10
Figure 6 Common Wall Mounting Installations ....11
Figure 7 Low Voltage Wiring – Basic A/C with Optional Electric Heat No Economizer or Ventilation
Packages ..............................................13
Figure 8 Low Voltage Wiring –
A/C with Programmable Thermostat .....14
Figure 9 Low Voltage Wiring – A/C with Non-Programmable
Thermostat ............................................15
Figure 10 Low Voltage Wiring – 1-Stage A/C with Optional Electric Heat with ECONWM Style
Economizer ...........................................16
Figure 11 Fan Blade Setting Dimensions ..............20
.....................................................................6
.................................................................7
........................................................................7
.....................................................6
.........................................................7
.....................................................7
........................................8
......................................................8
...............................................12
...................................12
.....4
Start Up
Requirements: R-410A Important Installer Note Service Hints High & Low Pressure Switch Sequence of Operation Compressor Control Module Adjustments Pressure Service Ports
Troubleshooting
Fan Blade Setting Dimension Refrigerant Charge Pressure Table Optional Field Installed Accessories
Tables
Table 1 Electric Heat Table ..................................4
Table 2 Electrical Heat Specications ..................6
Table 3 Wall Thermostat ....................................12
Table 4 Thermostat Wire Size ...........................12
Table 5 Fan Blade Dimensions ..........................20
Table 6 Indoor Blower Performance ..................20
Table 7 Rated CFM and ESP Recommended
Airow Range ........................................20
Table 8 Maximum ESP of Operation
Electric Heat Only .................................20
Table 9 Pressure Table - Cooling .......................21
T able 10 Optional Accessories ............................21
...........................................................18
............................................................19
........................................................21
............................................17
...........................................18
...................................18
...........................................18
...................................18
...........................................19
.................................20
.................................................20
.......................21
Manual 2100-618 Page 2 of 21
GETTING OTHER INFORMATION and PUBLICATIONS
These publications can help you install the air
conditioner or heat pump. You can usually nd these
at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code .......................ANSI/NFPA 70
Standard for the Installation of .......... ANSI/NFPA 90A
Air Conditioning and Ventilating Systems
Standard for Warm Air Heating .........ANSI/NFPA 90B
and Air Conditioning Systems
Load Calculation for .......................... ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for .................................ACCA Manual D
Residential Winter and Summer Air Conditioning and Equipment Selection
For more information, contact these publishers:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Avenue NW Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute 11 West Street, 13th Floor
New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigerating
1791 Tullie Circle, NE
Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association Batterymarch Park
P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-355 Fax: (617) 984-7057
and Air Conditioning Engineers, Inc.
Manual 2100-618 Page 3 of 21
WALL MOUNT GENERAL INFORMATION
AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE
W 12 A A A A 00 X X X X X J
MODEL
NUMBER
CAPACITY
12 - 1 Ton
AIR CONDITIONER
1 STAGE
REVISIONS
EFFICIENCY
A - 10 EER
VOLTS & PHASE
A - 230/208/60/1 D - 240/220/50/1 K - 115/60/1
KW
00 - No KW 02 - 2.2 KW 03 - 3.6 KW 05 - 5.0 KW 0Z - Circuit Breaker Only
CONTROL MODULES
X - Standard Low Pressure Switch, High Pressure Switch, Compressor Control Module E - X + Low Ambient Control J - X + Low Ambient Control and Alarm Relay
COIL OPTIONS
X - Standard Coils 1 - Phenolic Coated Evaporator 2 - Phenolic Coated Condenser 3 - Phenolic Coated Evaporator and Condenser
OUTLET OPTIONS
X - Front
COLOR OPTIONS
X - Beige 1 - White 4 - Buckeye Gray 5 - Desert Brown 8 - Dark Bronze
FILTER OPTIONS
X - 1-Inch Throwaway (Standard) W - 1-Inch Washable P - 2-Inch Pleated
VENTILATION OPTIONS
X - Barometric Fresh Air Damper (Standard) B - Blank-off Plate E - Economizer (Internal) - Fully Modulating with Exhaust V - Commercial Ventilator - Motorized with Exhaust
TABLE 1
ELECTRIC HEAT TABLE
Models
KW
A
02 18.3 7,985 03 15.0 12,760 13.0 9,705 15.0 12,760 13.8 10,735 05 20.8 17,540 18.1 13,275
j With blower watts included
W12AAAA W12AAAK W12AAAD
240V 208V 120V 240V 220V
j
BTU
A
j
BTU
A
j
BTU
A
j
BTU
A
j
BTU
Manual 2100-618 Page 4 of 21
ENTRANCE
LOW VOLTAGE
ENTRANCE
ELECTRICAL
BUILT-IN RAIN
HOOD 2° PITCH
21.88
1.50
48.00
14.63
ACCESS
HEATER & FILTER
VENTILATION AIR
CONDENSER AIRFLOW IS BLOW THRU
19.72
19.72
3.88
31.06
20.43
ELECTRICAL ENTRANCE
SHIPPING LOCATION
OPTIONAL
TOP RAIN FLASHING
DRAIN HOSE
10.00
5.00
30.13
17.00
5.00
32.00
22.25
25.750
2.50
MIS-3599
FRONT VIEW
BACK VIEW
RIGHT SIDE VIEW
FIGURE 1
UNIT DIMENSIONS
NOTE: Maintain a minimum of 20 inches clearance on right side to allow access to control panel and allow proper airow to outdoor
condenser coil. Allow 15 inches on left side.
Manual 2100-618 Page 5 of 21
TABLE 2
ELECTRICAL HEAT SPECIFICATIONS
SINGLE CIRCUIT
Rated Volts
Models
W12AAAA0Z
A03 A05
W12AAAK00
K02
W12AAAD00
D03
j Maximum size of the time delay fuse or HACR type circuit breaker for protection of eld wiring conductors.
Based on 75°C copper wire. All wiring must conform to NEC and all local codes.
These “Minimum Circuit Ampacity” values are to be used for sizing the eld power conductors. Refer to the National

Electrical Code (latest revision), article 310 for power conductor sizing.
CAUTION: When more than one eld power conductor circuit is run through one conduit, the conductors must be
derated. Pay special attention to note 8 of table 310 regarding Ampacity conductors are in a raceway.
and
Phase
230/208-1
115-1
240/220-1
No. Field
Power
Circuits
1 1 1
1 1
1 1
Minimum
Circuit
Ampacity
9 20 27
17 26
9 20
j
Maximum
External Fuse
or Circuit
Breaker
15 20 30
30 30
15 20
Adjustment Factors when more than 3
Field Power
Wire Size
14 12 10
10 10
14 12
Ground
Wire Size
14 12 10
10 10
14 12
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
GENERAL
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return air ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 3 for information on codes and standards.
Size of unit for a proposed installation should be based on heat loss/gain calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
Manual 2100-618 Page 6 of 21
DUCT WORK
FRESH AIR INTAKE
All duct work, supply and return must be properly sized
for the design air ow requirement of the equipment.
Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
Refer to Table 8 for maximum static pressure available for duct design.
Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.
Some installations may not require any return air duct. It is recommended that on this type of installation that
a lter grille be located in the wall. Filters must be of sufcient size to allow a maximum velocity of 400 FPM.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to installation only in a single story structure.
All units are built with fresh air inlet slots punched in the service panel.
If the unit is equipped with a fresh air damper assembly, the assembly is shipped already attached to the unit. The damper blade is locked in the closed position. To allow the damper to operate, the maximum and minimum blade position stops must be installed. See Figure 2.
All capacity, efciency and cost of operation information
as required for Department of Energy “Energyguide” Fact Sheets is based upon the fresh air blank-off plate in place and is recommended for maximum energy
efciency.
The blank-off plate is available upon request from the factory and is installed in place of the fresh air damper shipped with each unit.
CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.
FIGURE 2
FRESH AIR DAMPER
FILTERS
A one inch throwaway lter is supplied with each unit. The lter slides into position making it easy to service. This lter can be serviced from the outside by removing the service door. A 2-inch pleated lter is also available as an optional accessory. The internal lter brackets are adjustable to accommodate the 2-inch lter by bending the metal tabs holding the 1-inch lter down. There are two tabs on each side of the lter.
Manual 2100-618 Page 7 of 21
Loading...
+ 14 hidden pages