Table 4 Thermistor Resistance Vs. Temperature Table.
.............................................88
2100-444-003A
Page vi
1.0 INTRODUCTION
1.1 Shipping Damage
Upon receipt of equipment, the carton should be checked for external signs of shipping damage.
If damage is found, the receiving party must contact the carrier immediately, preferably in writing,
requesting inspection by the carrier's agent.
1.2 Package Contents
1 - TCS22
1 - Outdoor Humidity Sensor
1 - Outdoor Temperature Sensor
1 - TCS22 Operations Manual
1 - TCS Software Package
1.3 Additional Requirements
This controller is suitable for use with 1 1/2 ton through 6 ton Bard WallMount airconditioners. The Bard WallMount must be equipped with the "V" control module for proper
operation of the TCS22. Air-conditioner model numbers used with the TCS22 should contain the letter
"V" in the 15th position of the model number.
The TCS22 can be used with or without economizers. If economizers are to be used the units
should be ordered with the “D” vent option. The air-conditioner with economizer used with the TCS22
should contain the letter "D" in the 10th position of the model number.
Additionally, to utilize the Power Failure Management portion of the controller an Inverter and
battery backup system should be installed in the shelter. This provides for ventilation of the structure in
case of utility power failure, alarming of the power failure condition, and acts as an uninterruptible
power supply for the TCS22. See Figure 6.
If the inverter and battery backup system is not used disregard the power failure management
sequence later in this manual.
The power transfer relays shown in Figure 3 are field supplied items and are needed if ventilation
of the structure is required during power outages. The field supplied power transfer relays should be
sized to handle the MCA of the unit being controlled. Single phase units will require a 4 pole contactor
with 2 normally open and 2 normally closed contacts. Three phase units will require either a six pole
contactor or two 3 pole relays with 3 normally closed and three normally open contacts. Square D, DLine or F-Line contactors or equivalent are recommended.
If ventilation of the structure is not required during power outages these may be omitted. The
TCS22 will still dial out and alarm the power failure condition although no ventilation will be provided.
1.4 Copyright Notice
All materials contained in this manual originated from and are the property of Bard
Manufacturing Co. Any reproduction of the text, drawings, or wiring diagrams contained in this manual
is forbidden without the written consent of Bard Manufacturing Co.
2100-444-003A
Page 1
All SOFTWARE supplied with this product is the property of Bard Manufacturing Co. You may
not modify, disassemble, de-compile, reverse engineer, or create derivative works from this
SOFTWARE. Bard Manufacturing Co. licenses the purchaser of this product to use two copies of this
SOFTWARE on two computer systems, one remote computer system and one on site computer system.
If installed on a network server, additional software licenses should be purchased for each
computer on the network using the SOFTWARE.
1.5 General
The Telcom Climate Watch System (TCS) is a building monitoring and control system used in
conjunction with one (1) Bard Wall-Mount air-conditioners. The system consists of a state of the art
direct digital controller, the TSC22, one (1) Bard Wall-Mount air-conditioners, and a special "V"
control module that is added to the Bard Wall-Mount air-conditioners. This system provides the
following features.
1.5.1 BUILDING POINTS TO BE MONITORED:
Space Temperature
Space Humidity
Outdoor Temperature
Outdoor Humidity
Occupancy Override Switch
Main Power to Building
Fire Alarm Circuit
Fire Trouble Circuit
Door Alarm Circuit
1.5.2 WALLMOUNT POINTS TO BE MONITORED FOR EACH UNIT:
Blower Airflow
Discharge Air Temperature
Valid Compressor Current Sensor
Compressor Lockout Relay
Dirty Filter Sensor
1.5.3 BUILDING POINTS TO BE CONTROLLED:
Power Transfer Relay
Shelter Alarm Circuit
Door Alarm
2100-444-003A
Page 2
1.5.4 SYSTEM POINTS TO BE CONTROLLED:
Modem Power
1.5.5 WALLMOUNT POINTS TO BE CONTROLLED:
Blower Unit #1
Economizer Unit #1
Compressor Unit #1
Heating Unit #1
Blower Unit #2
1.5.6 ALARM POINTS:
High Space Temperature
Low Space Temperature
High Space Humidity
Low Space Humidity
Blower Failure Unit #1
Compressor Lockout Unit #1
Compressor Current Failure Unit #1
Dirty Filter Unit #1
Main Power Failure
Fire Alarm
Fire Trouble
Door Alarm
2100-444-003A
Page 3
INPUTS
1 Indoor Temperature Sensor Required (Standard in TCS22)
2 Indoor Humidity Sensor Optional (Optional in TCS22)
3 -0 Unit #1 Blower Airflow Sensor Required (Standard in "V" Module)
-1 Unit #1 Compressor Lockout Relay Required (Standard in "V" Module)
-2 Unit #1 Dirty Filter Sensor Optional (Standard in "V" Module)
4 Unit #1 Discharge Air Sensor Optional (Standard in "V" Module)
5 Spare
6 Spare
7 Unit #1 Compressor Current Switch Required (Standard in "V" Module)
8 Spare
9 Fire Trouble Optional
10 Fire Alarm Optional
11 Spare
12 Door Alarm Optional
13 Main Power Sensor Optional
14 Occupied Override Switch Required (Standard in TCS22)
15 Outdoor Temperature Sensor Required (Standard in TCS22)
16 Outdoor Humidity Sensor Required (Standard in TCS22)
OUTPUTS
1 Spare
2 Cycle Power To Modem
3 Power Transfer Switch
4 Unit #1 Economizer (Y1)
5 Unit #1 Compressor (Y2)
6 Unit #1 Heater (W1)
7 Unit #1 Blower (G)
8 Spare
9 Spare
10 Spare
11 Spare
12 Shelter Alarm Circuit
13 Unit #1 is Lead Unit
14 Spare
15 Free Cooling
16 Power Failure
2100-444-003A
Page 4
1.6 Model Nomenclature
TCS2 2 - H D M - 001
BASIC MODEL SOFTWARE
REVISION NUMBER ---- REMOTE COMMUNICATIONS
SENSORS DISPLAY M - With
H- Humidity & Temperature D - With X - Without
T - Temperature Only X – Without E - Ethernet
Controller Analog Inputs 16
Resolution 8 bits/ 0.4% Full Scale
Voltage Range 0 Vdc to +10 Vdc
Current Rating 5.0 mA at +10 Vdc
Binary Relay Outputs 12
Type Form "A" Relay SPST N.O.
Contact Rating 24 VAC, 5 A Resistive
24 VAC, 2 A Inductive
2.2 Mechanical Specifications
Height 26.25 in., (667 mm.)
Width 17.00 in., (432 mm.)
Depth 5.50 in., (140 mm.)
Material 18 ga galvanized steel with Beige baked polyester enamel.
Mounting Vertical
Mounting Area Required 27 in. high by 18 in. wide, (686 mm. high by 457 mm. wide)
Weight 27 lb., (12.3 kilograms)
2.3 Environmental Specifications
Operating Temperature Range 32 to 130 o F (0 to 55o C)
Operating Humidity Range 10 to 95%, non condensing
Storage Temperature Range -35 to 180 o F (-37 to 82o C)
Storage Humidity Range 5 to 95%, non condensing
2100-444-003A
Page 5
2.4 Sensor Specifications
2.4.1 TEMPERATURE SENSORS
Indoor and Outdoor
Type Thermistor
Ohms 3000 Ω at 77o F (25o C)
Temperature Range -40 to 302
Interchangeability .2 Deg Celsius
Discharge
Type Thermistor
Ohms 10000 Ω at 77o F (25o C)
Temperature Range -40 to 302
Interchangeability .2 Deg Celsius
2.4.2 HUMIDITY SENSORS
Type Bulk Polymer
Output 0-5 Vdc
Supply Voltage 24 Vac, +/- 15%
Accuracy +/- 5%
Sensitivity 0.1% RH
Repeatability 0.5% RH
Long Term Stability Less than 1% per year
Interchangeability +/- 3%
Temperature Range -40 to 130 o F (-40 to 76o C)
Humidity Range 0 to 99%, non condensing
o
F (-40 to 150o C)
o
F (-40 to 150o C)
2.4.3 COMPRESSOR CURRENT SENSOR
Type Solid State DC Switch
Output Form "A" solid state DC switch
Supply Voltage Self Powered
Trip Current Range 1 to 175 Amps
Maximum Load 150 mA, at 30 VDC
Temperature Range -58 to 149 o F (-50 to 65o C)
Dimensions 2.125 in. high, 3.25 in. wide, 1 in. deep
(54 mm. high, 83 mm. wide, 26 mm. deep)
2.4.4 DIRTY FILTER SENSOR
Type Mechanical Airflow Switch
Output Form "A" Contact
Supply Voltage Self Powered
Maximum Load 1.5A, at 24 VAC
Temperature Range 0 to 170 o F (-18 to 77o C)
Pressure Range 0.1 to 0.7 in. wc. Dimensions 3 1/4 in. high, 2 1/4 in. wide, 2 in. deep
(83 mm. high, 57 mm. wide, 51 mm. deep)
2100-444-003A
Page 6
2.4.5 BLOWER AIRFLOW SWITCH
Type Mechanical Airflow Switch
Output Form "C" Contact
Supply Voltage Self Powered
Maximum Load 300 VA, at 24 VAC
Temperature Range -40 to 180 o F (-40 to 82o C)
Pressure Range 0.07 to 0.12 in. wc
Dimensions 6.125 high, 4.125 wide, 3.188 deep
(156 mm. high, 105 mm. wide, 81 mm. deep)
2100-444-003A
Page 7
Figure 1 Front Cover
2100-444-003A
Page 8
Figure 2 Control Location
2100-444-003A
Page 9
Figure 3 Mounting Template
16.000
9.356
7.856
6.356
4.856
3.356
1.000
1.288
HIGH VOLTAGE
WIRING
22.288
MIS-866
2100-444-003A
Page 10
3.0 INSTALLATION
This section discusses mounting and wiring
of the TCS22 into the building. Also included is an
installation checklist to be completed by the
installing contractor. See installation instructions
supplied with the Bard Wall-Mount air
conditioners for information on installing the air
conditioners.
This controller should be installed and
serviced by a qualified service technician only.
3.1 Mounting
TCS22 should be mounted on a flat vertical
surface four (4) to six (6) feet from the floor of the
building. When choosing a suitable location take
into consideration that the electrical connections
can be made from the back or top of the TCS22.
See Figure 3 for rear electrical entrance locations.
The TCS22 is secured to the wall with
four (4) - 1/4 inch fasteners with flat washers.
Hollow wall anchors or lag bolts are suitable as
dictated by the wall construction. See Figure 3 for
a bolt pattern layout drawing.
! WARNING
_________________________________
•HAZARD OF ELECTRIC SHOCK.
•ELECTRIC SHOCK CAN RESULT IN
SERIOUS INJURY OR DEATH.
•DISCONNECT THE REMOTE ELECTRIC
POWER SUPPLIES BEFORE SERVICING.
3.2 Wiring
Electrical connections can be made from
the back or top of the TCS22. All wiring should
exit the TCS22 in conduit. Use the supplied wire
ties and cable holders to route unit low voltage,
communication, and sensor wiring neatly. Avoid
looping excess wire. See Figure 2 for suggested
conduit connections.
Never connect or disconnect wiring from the
controller with power connected to the controller
or to either of the Bard Wall-Mount air-
conditioners.
3.2.1 HIGH VOLTAGE WIRING
IMPORTANT: High voltage wiring must
not be run in the same conduit as low voltage
control or sensor wiring. Failure to comply with
this requirement will result in poor or no remote
communication and/or in inaccurate sensor
reading.
Supply power is 208/240 VAC, 50/60 Hz,
1 Phase at 3 amps minimum circuit ampacity. A 3
amp circuit breaker is supplied as part of the
TCS22. This circuit breaker is for internal circuit
protection only and cannot be used as a disconnect.
Supply wire size should be 18 ga. or larger. Use
Copper Conductors Only. All wiring must comply
with the applicable sections of the National
Electrical Code ( NEC) and any applicable local
codes.
The TCS22 is shipped for 240 VAC
operation . For 208 Volt operation change both
transformer primaries in the TCS22 to the 208 volt
tap. See Wiring Diagram. The acceptable operating
voltage ranges for the 240 and 208 volt taps are:
Tap Range
240 253-216
208 220-187
Connect the high voltage power supply to
Terminal Block TB2. Connect ground wire to the
ground connector provided. TCS22 must be
grounded for proper operation. Failure to ground
the controller may cause erratic controller
operation and inaccurate sensor operation. See
Figure 2 and the wiring diagram.
2100-444-003A
Page 11
3.2.2 WIRING - LOW VOLTAGE
IMPORTANT: High voltage wiring must
not be run in the same conduit as low voltage
control or sensor wiring. Failure to comply with
this requirement will result in poor or no remote
communication and/or in inaccurate sensor
reading.
Sixteen (16) wires should be run from each
Bard Wall-Mount to the low voltage terminal
block in the TCS22. An eight pair shielded cable
with 20 gauge copper conductors, such as National
Wire & Cable Corporation NQP series cable or
equivalent, is recommended for distances up to 45
feet. See Table 1 for distances more than 45 feet.
The connection points are shown in Figure 5.
IMPORTANT: High voltage wiring must
not be run in the same conduit as low voltage
control or sensor wiring. Failure to comply with
this requirement will result in poor or no remote
communication and/or in inaccurate sensor
reading.
3.2.3.1 Outdoor Temperature Sensor (OTS)
The Outdoor Temperature Sensor (OTS) is
supplied as part of the TCS22 package. The
Outdoor Temperature Sensor (OTS) is a thermistor
type device. The sensor is mounted in a
weatherproof junction box suitable for connection
to conduit. This sensor is a two (2) wire device.
The Outdoor Temperature Sensor (OTS)
2100-444-003A
Page 12
should be mounted on the exterior of the structure
at a height above any expected accumulation of
snow. It is recommended that the box be mounted
securely to the outside wall of the structure and all
wiring to the sensor be made through conduit. A
one (1) pair shielded cable with 20 gauge copper
conductors, such as National Wire & Cable
Corporation NQP series cable or equivalent, is
recommended for connection to the sensor for
distances up to 45 feet. See Table 1 for distances
more than 45 feet.
Use wire nuts to connect the cable to the
blue and yellow sensor leads in the sensor housing.
Polarity is not critical with this sensor. The
connection points for the sensor inside the TCS22
are shown in Figure 4.
3.2.3.2 Outdoor Humidity Sensor (OHS)
The Outdoor Humidity Sensor (OHS) is
supplied as part of the TCS22 package. The
Outdoor Humidity Sensor (OHS) is a bulk polymer
type device. The sensor is mounted in a
weatherproof junction box suitable for connection
to conduit. This sensor is a four (4) wire device, 1
to 5 Vdc output.
The Outdoor Humidity Sensor (OHS)
should be mounted on the exterior of the structure
at a height above any expected accumulation of
snow. It is recommended that the box be mounted
securely to the outside wall of the structure and all
wiring to the sensor be made through conduit. A
two (2) pair shielded cable with 20 gauge copper
conductors, such as National Wire & Cable
Corporation NQP series cable or equivalent, is
recommended for connection to the sensor for
distances up to 45 feet. See Table 1 for distances
more than 45 feet.
Connect the cable to the terminal blocks in
the sensor housing. Polarity is critical with this
sensor. The connection points for the sensor inside
the TCS22 are shown in Figure 4.
3.2.3.3 Zone Temperature Sensor (ZTS)
The Zone Temperature Sensor (ZTS) is
supplied as part of the TCS22 package. The Zone
Temperature Sensor (ZTS) is a thermistor type
device. The sensor is premounted to the front door
of the TCS22. No wiring is required.
3.2.3.4 Zone Humidity Sensor (ZHS) (Optional)
The Zone Humidity Sensor (ZHS) is
supplied as part of the TCS22 package (Optional).
The Zone Humidity Sensor (ZHS) is a bulk
polymer type device. If so equipped, the sensor is
premounted to the front door of the TCS22. No
wiring is required.
3.2.4 WIRING – INPUTS & OUTPUTS
A shielded cable with 20 gauge copper conductors,
such as National Wire & Cable Corporation NQP
series cable or equivalent, is recommended for
connection to the inputs and outputs of the TCS22
for distances up to 45 feet. See Table 1 for
distances more than 45 feet.
3.2.4.1 Shelter Alarm Output
The Shelter Alarm Output (SA) is a
normally open set of contacts that closes whenever
an alarm condition exists as sensed by the TCS22
controller. See the alarm section of this manual for
an explanation of the various conditions that will
send a shelter alarm.
The Form "A" contacts are SPST N.O.
rated at 24 VAC, 5 A Resistive, or 24 VAC, 2 A
Inductive. These rating should not be exceeded
under any conditions.
These contacts may be used to trigger an
alarm in the shelter or a remote alarm.
3.2.4.2 Power Transfer Switch Output (PTS)
The Power Transfer Switch Output is a
normally open set of contacts that closes two (2)
minutes after a power failure is sensed by the
TCS22 controller. See the alarm section of this
manual for an explanation of the power failure
alarm.
The Form "A" contacts are SPST N.O.
rated at 24 VAC, 5 A Resistive, or 24 VAC, 2 A
Inductive. These rating should not be exceeded
under any conditions.
These contacts can be used to energize a power
transfer switch when used in conjunction with an
inverter to provide emergency ventilation of the
shelter during power failures. Consult the power
failure management sequence, section 4.2.10 and
section 1.3, for more details.
3.2.4.3 Power Failure Sense Input
The Power Failure Sense is an input into
the Controller. A normally open set of contacts is
connected across these inputs. When power is lost
to the shelter these contacts should close indicating
that the building has lost normal utility power.
These contacts can be used in conjunction with an
inverter and power transfer switch to provide
emergency ventilation of the shelter during power
failures. Consult the power failure management
sequence, section 4.2.10 and section 1.3, of this
manual for more details..
This is a dry contact input only. Do not
connect any voltage source to these terminals. Do
not connect utility power to these terminals.
3.2.4.4 Fire Alarm Input
The Fire Alarm is an input into the
Controller. A set of normally open contacts is
connected across these inputs. These contacts
should close when fire alarm system has sensed a
fire.
This is a dry contact input only. Do not
connect any voltage source to these terminals. Do
not connect utility power to these terminals.
3.2.4.5 Fire Trouble Input
The Fire Trouble is an input into the
Controller. A set of normally open contacts is
connected across these inputs. These contacts
should close when the fire alarm system senses a
problem with the fire alarm system.
This is a dry contact input only. Do not connect
any voltage source to these terminals. Do not
connect utility power to these terminals.
3.2.4.6 Door Alarm Input
The Door Alarm is an input into the
Controller. A set of normally open contacts is
connected across these inputs. These contacts
2100-444-003A
Page 13
should close when door is closed. If a door switch
is not used a jumper should be placed across
this input.
This is a dry contact input only. Do not
connect any voltage source to these terminals. Do
not connect utility power to these terminals.
3.2.5 WIRING - TELEPHONE LINE
When the TCS22 is equipped with a
modem, an analog phone line should be connected
to the back of the modem in the jack labeled LINE.
This jack accepts a standard a RJ-11 six (6)
position modular phone plug.
3.2.6 WIRING - ETHERNET
When the TCS22 is equipped with an
Etherlink communications module, The
LAN/WAN should be connected to the back of the
module in the jack labeled Ethernet. This jack
accepts a standard a RJ-11 eight (8) position
modular phone plug.
The Etherlink communications module
requires a dedicated IP address. This must be
programmed by the end user via a computer and
RS232 cable at the time of connection to the
network. The cable is provided with the TCS22.
Specific configuration information is
provided with the EtherLink Module in a separate
document.
2100-444-003A
Page 14
Figure 4
External Wiring
2100-444-003A
Page 15
Figure 5
Internal Wiring
Figure 6
Power
2100-444-003A
Page 16
Backup System
2100-444-003A
Page 17
3.3 Installation Check List
TCS22 securely mounted to wall and all conduit connections tight.
Main power wiring is NOT in same conduit as low voltage or sensor wiring
Main power wires are copper conductors
TCS22 is grounded.
Check supply voltage. Change both transformer taps if necessary. See Sec. 3.21
Carefully recheck all low voltage wiring for correct connection points .
Carefully recheck all sensor connections for correct connection points.
Recheck analog telephone wire connection to modem if so equipped
Make sure modem power switch is on if so equipped.
Connect jumper between terminals DA if a door switch is not used.
.
2100-444-003A
Page 18
3.4 System Startup
3.4.1 WALLMOUNT STARTUP CHECKLIST
Operation Procedure
Bypassing TCS22
Controller
Apply power to both
Wall-mounts
Compressor Test Connect jumper wire on A/C unit low voltage terminals from R to Y
Blower Test Connect a jumper wire on A/C unit low voltage terminals R to G and
Economizer Test Connect a jumper wire on A/C unit low voltage terminals R to G and
Heater Test Connect a jumper wire on A/C unit low voltage terminals R to W1.
Disconnect Power to
WallMount AirConditioners
Disconnect power to the TCS22. Unplug the plug in connectors J4 and
J5 from the controller
Follow recommended startup procedure in the WallMount installation
instructions. Compressor damage could occur if startup procedures are
not followed.
and observe Compressor operation (There will be a Time delay
between the installation of the jumper and the starting of the
Compressor. The Compressor Time Delay relay will determine the
time delay period.). After the Compressor starts, the jumper wire can
be removed.
observe Blower operation (The Blower will continue to run for One (1)
minute after the jumper is removed).
observe Blower operation. After Blower operation is confirmed, the
Economizer can be tested. Leave the jumper in place from the previous
step. Connect a separate jumper on the A/C unit low voltage terminals
from E to F and observe the Economizer operation (Never connect
power to terminals E or F).
The Heating contactor will engage when the jumper is connected. The
Blower will also operate while this jumper is in place. To check the
operation of the Heater, you will have to check the Discharge Air
temperature of the A/C unit.
Disconnect power to WallMount air conditioners. Reconnect plug-in
connectors J4 and J5 to the controller. Go to TCS22 Startup Checklist
2100-444-003A
Page 19
3.4.2 TCS22 STARTUP CHECKLIST
Apply power to
WallMount airConditioners
Apply power to TCS22 Apply power to TCS22 and monitor LEDs on the front of the
Connect to Controller Use the DAK or Laptop PC to connect to controller to change
Apply power to WallMount air-Conditioners. Wait two minutes for
wallmount time delays to expire.
controller. The controller performs a self test on startup. Upon
application of power, 9 LEDs will light.
System Power led will light and stay lit
Unit #1 is Lead Unit, Unit #2 is Lead Unit, Free Cooling, Power
Failure LEDs will light for 5 seconds and then resume normal
operation
System Rx and Tx and Local Rx and Tx will all flash on, flash off,
flash on and then flash off during this five seconds and will then
resume normal operation .
This completes the self test and controller will now start controlling
per the sequence of operation.
setpoints.
See Section 5.0 for DAK operation procedures.
See Section 6.0 for direct connect PC operation.
2100-444-003A
Page 20
4.0 OPERATION
This section describes the sequence of operation of the controller. The tools available for
monitoring and controlling the air-conditioners for both on-site and remote operations are explained. The
remote trending, alarming, and site setup software are detailed.
4.1 General
This section will describe the sequence of operation of the controller. Cooling , heating,
dehumidification, and alarm sequences are explained.
4.2 Sequence of Operation
This sequence of operation is for the TCS22-002 software package. Different software packages
have different sequences of operation. Check the last three numbers of the TCS22 model number on the
serial plate to verify that the sequence installed is "002"
4.2.1 COOLING SEQUENCE WITH ECONOMIZERS
Free cooling setpoint, that is, the outdoor conditions at which cooling is handled by the
economizer, can be configured to use either enthalpy or dry bulb temperature.
Outdoor Enthalpy or Temperature is calculated from Outdoor Temperature and/or Outdoor
Humidity sensors. If the outdoor enthalpy or temperature is below the free cooling setpoint, free cooling
is enabled and Output #15, Free Cooling is lit.
Active Cooling Setpoint is compared to Space Temperature . If Space temperature is above
Active Cooling Setpoint, stage 1 cooling is enabled. If Free Cooling is enabled, Economizer and Blower
of the Unit are energized. If Free Cooling is inhibited, Compressor and Blower of the Unit are
energized.
If the Space Temperature is above Active Cooling Setpoint plus 2 deg Fo, stage 2 cooling is
enabled. If Free Cooling is enabled, Compressor and Blower of the Unit are energized.
4.2.2 HEATING SEQUENCE
Active Heating Setpoint is compared to Space Temperature. If Space temperature is below
Active Heating Setpoint , Stage 1 heating is enabled. Heater and Blower of the Unit are energized.
4.2.3 FAN SEQUENCE
The Evaporator Fan is programmed for continuous operation. Operator can change continuous
operation to cycle on demand. Lag unit fan will cycle on demand.
2100-444-003A
Page 21
4.2.4 OCCUPIED / UNOCCUPIED MODE SEQUENCE
In heating mode, activation of the Occupancy Override Button will change the Active Heating
Setpoint from Unoccupied Heating Setpoint to Occupied Heating Setpoint for a period of two hours. In
cooling mode, activation of the Occupancy Override Button will change the Active Cooling Setpoint
from Unoccupied Cooling Setpoint to Occupied Cooling Setpoint for two hours.
4.2.5 ALARM SEQUENCE
The controller will alarm on the following failures. Modem dial-out is initiated when any of the
following alarms occur.
High Space Temperature
When Space Temperature is above High Temperature Alarm Setpoint a critical alarm is logged
in the Event List and Output 12, Shelter Alarm, is energized. This is a self clearing alarm.
Low Space Temperature
When Space Temperature is below Low Temperature Alarm Setpoint a critical alarm is logged in
the Event List and Output 12, Shelter Alarm, is energized. This is a self clearing alarm.
High Space Humidity
When Space Humidity is above High Humidity Alarm Setpoint a critical alarm is logged in the
Event List and Output 12, Shelter Alarm, is energized. This is a self clearing alarm.
Low Space Humidity
When Space Humidity is below Low Humidity Alarm Setpoint a critical alarm is logged in the
Event List and Output 12, Shelter Alarm, is energized. This is a self clearing alarm.
Blower Failure Unit #1
If Blower operation is called for the blower airflow sensor is checked. If the airflow sensor does
not confirm that there is airflow, Output 7, Unit #1 Blower, is de-energized. After 30 seconds the
blower is energized again. If airflow is not sensed, Output 7, Unit #1 Blower, is de-energized.
After another 30 seconds the blower is energized again. If airflow is not sensed, Output 7, Unit
#1 Blower, is de-energized and locked out. A critical alarm is logged in the Event List and
Output 12, Shelter Alarm, is energized. Lead unit switches to lag unit. The Output Alarm must be
cleared to resume operation.
2100-444-003A
Page 22
Compressor Lockout Failure Unit #1
If Compressor operation is not verified because the High or Low Pressure Lockout Relay has
been energized, Output 5, Unit #1 Compressor, is de-energized and locked out. A critical alarm
is logged in the Event List and Output 12, Shelter Alarm, is energized. Lead unit switches to lag
unit .The Output Alarm must be cleared to resume operation. Verify is tried 3 times before the
output is locked out. Compressor Operation is verified by Unit #1 Compressor Lockout Relay
and Unit #1 Compressor Current Switch.
Compressor Current Failure Unit #1
If Unit #1 Compressor is on and Unit #1 Compressor Current Switch is not valid , a
critical alarm is logged in the Event List and Output 12, Shelter Alarm, is energized. Lead unit
switches to lag unit. The Output Alarm must be cleared to resume operation. Verify is tried 3
times before the output is locked out. Compressor Operation is verified by Unit #1 Compressor
Lockout Relay and Unit #1 Compressor Current Switch.
Dirty Filter Unit #1
If Unit #1 Dirty Filter Switch is closed, a low priority alarm is logged in the Event List and
Output 12, Shelter Alarm, is energized. This alarm must be reset at the unit.
Utility Power Failure
If Input #13, Power Sense, is closed indicating a utility power failure, a critical priority alarm is
logged in the Event list and Output 12, Shelter Alarm, is energized. All unit outputs are de-
energized. Two minutes after the alarm, Output #3, Power Transfer Switch, is energized . Three
minutes after the alarm, Lead Unit Blower and Lead Unit Economizer are energized
continuously until Utility Power Failure Alarm is cleared. This is a self clearing alarm.
Fire Trouble
If Input #9, Fire Trouble, is closed indicating a problem with the Fire Alarm System, a medium
priority alarm is logged in the Event list and Output 12, Shelter Alarm, is energized.
Fire Alarm
If Input #10, Fire Alarm, is closed indicating a fire in the Zone, a critical priority alarm is logged
in the Event list and Output 12, Shelter Alarm, is energized. All unit outputs are de-energized.
2100-444-003A
Page 23
Loading...
+ 66 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.