Bard T24H1, T30H1, T24H1D, T30H1D, T36H1 Installation Instructions Manual

...
INSTALLATION INSTRUCTIONS
WALL MOUNTED
PACKAGE HEAT PUMPS
Standard & Dehumidification
MODELS
T24H1 T24H1D T30H1 T30H1D T36H1 T36H1D T42H1 T42H1D T48H1 T48H1D T60H1 T60H1D
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
Since 1914...Moving ahead just as planned.
Manual 2100-541C Page 1 of 28
Contents
Getting Other Information and Publications 3
Wall Mount General Information
Wall Mount Model Nomenclature ............................ 4
Shipping Damage .................................................... 4
General ................................................................ 4
Duct Work ................................................................ 5
Filters ................................................................ 5
Fresh Air Intake ....................................................... 5
Condensate Drain .................................................... 5
Installation Instructions
Wall Mounting Information ....................................... 6
Mounting the Unit .................................................... 6
Placement ................................................................ 6
Clearances Required ............................................... 6
Minimum Clearances ............................................... 6
Wiring – Main Power ............................................. 13
Wiring – Low Voltage Wiring ................................. 13
Optional Outdoor T-Stat Applications ..................... 14
Figures
Figure 1 Fresh Air Damper Assembly ................... 5
Figure 2 Unit Dimensions ...................................... 7
Figure 3A Mounting Instructions T24 & 30 .............. 8
Figure 3B Mounting Instructions T36, 42, 48 ........... 9
Figure 4 Electric Heat Clearance ........................ 10
Figure 5 Wall Mounting Instructions.....................11
Figure 6 Wall Mounting Instructions.....................11
Figure 7 Common Wall Mounting Installations.... 12
Figure 8 Compressor Cutoff ................................ 14
Figure 9 Compressor Cutoff ................................ 14
Figure 10 Electric Heat Hold-Off Wiring ................ 15
Figure 11 Electric Heat Hold-Off Wiring ................ 15
Figure 12 Defrost Control Board ........................... 19
Figure 13 Fan Blade Setting ................................. 22
Figure 14 Control Disassembly ............................. 28
Figure 15 Winding Test ......................................... 28
Figure 16 Drip Loop .............................................. 28
Start Up
General .............................................................. 16
Topping Off System Charge ................................... 16
Safety Practices ..................................................... 16
Important Installer Note ......................................... 17
High & Low Pressure Switch ................................. 17
Three Phase Scroll Compressor............................ 17
Phase Monitor ....................................................... 17
Service Hints ......................................................... 17
Sequence of Operation .......................................... 18
Pressure Service Ports .......................................... 18
Defrost Cycle ......................................................... 18
Troubleshooting
Solid State Heat Pump Control .............................. 20
Checking Temperature Sensor .............................. 21
Fan Blade Setting Dimensions .............................. 22
Removal of Fan Shroud ......................................... 22
R-410A Refrigerant Charge ................................... 22
Troubleshooting GE ECM Motors .......................... 27
Troubleshooting GE ECM Motors .......................... 28
Tables
Table 1 Clearances Required .............................. 6
Table 2 Min. Clearances Required ...................... 6
Table 3 Troubleshooting .................................... 20
Table Temperature F vs. Resistance .............. 21
Table 4 Fan Blade Dimension............................ 22
Table 5A Cooling Pressure .................................. 23
Table 5B Heating Pressure .................................. 23
Table 6A Electrical Specifications T**H ................ 24
Table 6B Electrical Specifications T**H Dehum. .. 25
Table 7 Indoor Blower Performance .................. 26
Manual 2100-541C Page 2 of 28
GETTING OTHER INFORMATION AND PUBLICATIONS
These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation .............. ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ...................... ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for ............................ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for Residential .............. ACCA Manual D
Winter and Summer Air Conditioning and Equipment Selection
FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute
11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigeration
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association
Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manufactured under the following
U.S. Patent numbers: 5,485,878; 5,301,744
Manual 2100-541C Page 3 of 28
WALL MOUNT GENERAL INFORMATION
HEAT PUMP WALL MOUNT MODEL NOMENCLATURE
T 36 H 1– A 10 X X X X X X
MODEL
NUMBER
CAPACITY |
24 - 2 Ton 30 - 2½ Ton 36 - 3 Ton 42 - 3½ Ton 48 - 4 Ton 60 - 5 Ton
1 For 0 KW and circuit breakers (230/208 volt) or toggle disconnect (460V) applications, insert 0Z in the KW field of the model number. See Pages 24 & 25. 2 Insert “D” for dehumidification with hot gas reheat. Reference Form 7960-627 for complete details.
H - Heat Pump
SPECIALTY PRODUCTS
(Non-Standard)
VENTILATION OPTIONS
X - Barometric Fresh Air Damper (Standard) B - Blank-off Plate M - Motorized Fresh Air Damper C - Commercial Ventilator - Mod. Spring Return w/Exhaust V - Commercial Ventilator - Spring Return w/Exhaust P - Commercial Ventilator - Power Return w/Exhaust E - Economizer (Internal) - Fully Modulating with Exhaust R - Energy Recovery Ventilator - Motorized with Exhaust
(See Spec. Sheet S3398)
REVISIONS
VOLTS & PHASE
A - 230/208/60/1 B - 230/208/60/3 C - 460/60/3
2
KW1
0Z - 0KW 04 - 4KW 05 - 5KW 06 - 6KW F8 - 8KW S8 - 8KW 09 - 9KW 10 -10KW 15 -15KW 20 -20KW
COLOR OPTIONS
X - Beige 1 - White 4 - Buckeye Gray 5 - Desert Brown 8 - Dark Bronze A - Aluminum S - Stainless Steel
FILTER OPTIONS
X - 1-Inch Fiberglass (MERV 2) M - 2-Inch Pleated (MERV 11) H - 2-Inch Pleated (MERV 8) P - 2-Inch Pleated (MERV 6) E - 24V 1"Electrostatic Air Cleaner
OUTLET OPTIONS
X - Front (Standard)
CONTROL MODULES
(See Spec. Sheet S3436)
COIL OPTIONS
X - Standard 1 - Phenolic Coated Evaporator 2 - Phenolic Coated Condenser 3 - Phenolic Coated Evaporator
and Condenser
NOTE: Vent options X, B and M are without exhaust capability. May require separate field supplied barometric relief in building.
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
While these instructions are intended as a general
GENERAL
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 3 for information on codes and standards.
Size of unit for a proposed installation should be based on heat loss/gain calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
Manual 2100-541C Page 4 of 28
DUCT WORK
All duct work, supply and return, must be properly sized for the design airflow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
A 1/4 inch clearance to combustible material for the first three feet of duct attached to the outlet air frame is required. See Wall Mounting Instructions and Figures 3A, 3B and 4 for further details.
Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.
Some installations may not require any return air duct. A metallic return air grille is required with installations not requiring a return air duct. The spacing between louvers on the grille shall not be larger than 5/8 inch.
Any grille that meets with 5/8 inch louver criteria may be used. It is recommended that Bard Return Air Grille Kit RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used. Contact distributor or factory for ordering information. If using a return air filter grille, filters must be of sufficient size to allow a maximum velocity of 400 fpm.
NOTE: If no return air duct is used, applicable installation
codes may limit this cabinet to installation only in a single story structure.
FILTERS
A 1-inch throwaway filter is standard with each unit. The filter slides into position making it easy to service. This filter can be serviced from the outside by removing the filter access panel. 2-inch pleated filters are also available as optional accessories. The internal filter brackets are adjustable to accommodate the 2-inch filter by bending two (2) tabs down on each side of the filter support bracket.
FRESH AIR INTAKE
All units are built with fresh air inlet slots punched in the service door.
If the unit is equipped with a fresh air damper assembly, the assembly is shipped already attached to the unit. The damper blade is locked in the closed position. To allow the damper to operate, the maximum and minimum blade position stops must be installed. See Figure 1.
All capacity, efficiency and cost of operation information is based upon the fresh air blank-off plate in place and is recommended for maximum energy efficiency.
The blank-off plate is available upon request from the factory and is installed in place of the fresh air damper shipped with each unit.
CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.
FIGURE 1
FRESH AIR DAMPER
Manual 2100-541C Page 5 of 28
s
C a
M
E
T T
T
T T
INSTALLATION INSTRUCTIONS
WALL MOUNTING INFORMATION
1. Two holes for the supply and return air openings must be cut through the wall as shown in Figure 3.
WARNING
2. On wood frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration.
3. Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installed unit.
MOUNTING THE UNIT
1. These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides. A bottom mounting bracket, attached to skid for shipping, is provided for ease of installation, but is not required.
2. The unit itself is suitable for 0 inch clearance, but the supply air duct flange and the first 3 feet of supply air duct require a minimum of 1/4 inch clearance to combustible material. However, it is generally recommended that a 1-inch clearance is used for ease of installation and maintaining the required clearance to combustible material. See Figure 3 for details on opening sizes.
3. Locate and mark lag bolt locations and bottom mounting bracket location. See Figures 3A & 3B.
4. Mount bottom mounting bracket.
5. Hook top rain flashing, attached to front - right of supply flange for shipping, under back bend of top.
Failure to provide the 1/4 inch clearance between the supply duct and a combustible surface for the first 3 feet of duct can result in fire causing damage, injury or death.
PLACEMENT
1. On side-by-side installations, maintain a minimum of 20 inches clearance on right side to allow access to control panel and heat strips, and to allow proper airflow to the outdoor coil. Additional clearance may be required to meet local or national codes.
2. Care should be taken to ensure that the recirculation and obstruction of condenser discharge air does not occur. Recirculation of condenser discharge air can be from either a single unit or multiple units. Any object such as shrubbery, a building or a large object can cause obstructions to the condenser discharge air. Recirculation or reduced airflow caused by obstructions will result in reduced capacity, possible unit pressure safety lockouts and reduced unit service life.
Units with a blow through condenser, such as the T**H 10 EER units, it is recommended there be a minimum distance of 15 feet between the front of the unit and any barrier or 20 feet between the fronts of two opposing (facing) units.
6. Position unit in opening and secure with 5/16 lag bolts; use 7/8 inch diameter flat washers on the lag bolts.
7. Secure rain flashing to wall and caulk across entire length of top. See Figures 3A & 3B.
8. For additional mounting rigidity, the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance if combustible wall.
SLEDO
H03T,H42
H06T,H84T,H24T,H63
Manual 2100-541C Page 6 of 28
wolfriAresnednoCetauqedAdn
EDISTFEL
"51 "02 "02 "02
seccAecivreSrofderiuqeRsecnarael
otderiuqeRsecnaraelCmuminiM
slairetaMelbitsubmoC
DISTHGIR
SLEDOM
H03T,H42
H06T,H84T,H24T,H63
TCUDRIAYLPPUS
TEEFEERHTTSRIF
"4/1"0 "4/1"0
ENIBAC
Panel
Door
Vent Option
Filter Access
Ventilation Air
Front View
5.75
F
W
G
Condenser
Air Outlet
1
1
MIS-2729 A
Electrical
Low Voltage
Entrance
High Voltage
Electrical Entrance
4° Pitch
Rain Hood
Built In
Access
Panel
(Lockable)
Heater
Electric
Heat
C. Breaker/ Disconnect
Access Panel
Drain
Side View
HC
K
J
I
D
2.13 A
Cond.
Air
Inlet
Electrical
Entrances
Optional
Side Wall
Mounting
Brackets
(Built In)
Location
Shipping
Return Air Opening
Supply Air Opening
Top Rain
Flashing
Bottom Installation Bracket
Back View
M
L
O
E
R
S
S
S
S
S
T
.44
N
Q
P
B
FIGURE 2
M
0
8
0
HTDIW
HTPED
LEDO
)W(
)D(
H42T H03T
H63T H24T
H84T H06T
002.83521.71365.0788.788.7288.3188.7200.0488.0157.5239.7157.6257.8252.9200.7236.231.9357.2241.900.500.21
570.24234.22578.4888.988.9288.5188.9288.3465.3166.1300.0386.2349.6296.4334.2373.300.3488.3200.0144.100.61
570.24234.22000.3988.988.9288.5188.9288.3465.3100.7300.0318.0460.5318.2465.0473.300.3400.1300.0144.100.61
THGIEH
)H(
All dimensions are in inches. Dimensional drawings are not to scale.
YLPPUSNRUTER
ABCBE F G I J K L MNO P QRST
T**H
RIGHT UNIT
)lanimoN(stnemeriuqeRnoitallatsnIdnalarutcetihcrAroftinUcisaBfosnoisnemiD
0.5
8.1
0.01
Manual 2100-541C Page 7 of 28
1/4" CLEARANCE ON ALL
FOUR SIDES OF SUPPLY
MIS-311 C
MATERIALS
AIR DUCT IS REQUIRED
FROM COMBUSTABLE
FOAM AIR SEAL
RAIN FLASHING
SUPPLIED
FIGURE 3A
T24H1, T30H1
SEAL WITH BEAD
OF CAULKING ALONG
ENTIRE LENGTH OF TOP.
MOUNTING INSTRUCTIONS
EDCBA
TOP
17 5/83 13/165 1/48 1/228 1/2
WALL STRUCTURE
WALL
SUPPLY AIR
DUCT
PANEL
HEATER ACCESS
RETURN AIR
OPENING
NOTES:
IT IS RECOMMENDED THAT A BEAD OF
SILICONE CAULKING BE PLACED BEHIND
THE SIDE MOUNTING FLANGES AND UNDER
TOP FLASHING AT TIME OF INSTALLATION.
W*R UNIT SHOWN, W*L UNIT
CONTROLS AND HEATER ACCESS
IS ON OPPOSITE (LEFT) SIDE.
16 7/84 9/164 1/21030
B
E
14"
1"
"
1
2
"
1
8
3
4"
Typ.
4
COMBUSTIBLE MATERIALS
1/4" MIN. CLEARANCE FROM
REQUIRED DIMENSIONS TO MAINTAIN
COMBUSTIBLE MATERIALS
RECOMMENDED 1" CLEARANCE FROM
REQUIRED DIMENSIONS TO MAINTAIN
Manual 2100-541C Page 8 of 28
28"
Supply Opening
Return Opening
C CA
D
12"
12"
12"
12"
1"
4"
3"
"
7
8
12"
Typ.
"
1
2
4
Wall Opening and Hole Location View Right Side View
5"
RAIN FLASHING
SUPPLIED
FOAM AIR SEAL
FOUR SIDES OF SUPPLY
AIR DUCT IS REQUIRED
1/4" CLEARANCE ON ALL
WALL STRUCTURE
FROM COMBUSTABLE
MATERIALS
PANEL
SUPPLY AIR
DUCT
RETURN AIR
OPENING
NOTES:
THE SIDE MOUNTING FLANGES AND UNDER
TOP FLASHING AT TIME OF INSTALLATION.
IT IS RECOMMENDED THAT A BEAD OF
SILICONE CAULKING BE PLA CE D BEHI ND
MIS-416 E
Right Side View
TOP.
FIGURE 3B
TOP
SEAL WITH BEAD
ENTIRE LENGTH OF
OF CAULKING ALONG
MOUNTING INSTRUCTIONS
T36H1, T42H1, T48H1, T60H1
6 1/4 1 1/4 29 3/4
10 1/2
ABCDE
30 1/2
29
2
32 12 5 1/2
WALL
HEATER ACCESS
A CC
Typ.
3
"
1
8
2
"
1
2
"
7
B
E
16"
8
"
8
1
3
4"
30"
3"
1"
4"
Typ.
"
2
6
1
16"
" 6
1
2
6
Dimension is 21" on 95" tall units.
Dimension is 10" on T48H1 & T60H1.
Dimension is 6" on T48H1 & T60H1.
2
3
1
"
7
8
1
2
Wall Opening and Hole Location View
16"
Return Opening
1
1
16"
Supply Opening
D
16"
16"
REQUIRED DIMENSIONS TO MAINTAIN
1/4" MIN. CLEARANCE FROM
COMBUSTIBLE MATERIALS
RECOMMENDED 1" CLEARANCE FROM
REQUIRED DIMENSIONS TO MAINTAI N
COMBUSTIBLE MATERIALS
Manual 2100-541C Page 9 of 28
Loading...