Bard SH261, SH311 Installation Instructions Manual

INSTALLATION INSTRUCTIONS
WALL MOUNTED
PACKAGE HEAT PUMPS
Models
SH261 SH311
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
Since 1914...Moving ahead just as planned.
© Copyright 2003
Manual 2100-409C Page 1 of 25
CONTENTS
Getting Other Informations and Publications 3
Wall Mount General Information
Heat Pump Wall Mount Model Nomenclature.......... 4
Shipping Damage .................................................... 7
General ................................................................ 7
Duct Work ................................................................ 7
Filters ................................................................ 7
Fresh Air Intake ....................................................... 8
Condensate Drain .................................................... 8
Installation Instructions
Wall Mounting Information ....................................... 9
Mounting the Unit .................................................... 9
Wiring – Main Power ............................................. 14
Wiring – Low Voltage Wiring ................................. 14
Optional Outdoor Thermostat Applications ............ 15
Thermostat Indicators ............................................ 17
Low Voltage Connections ...................................... 17
Start Up
Important Installer Note ......................................... 18
High Pressure Switch ............................................ 18
Three Phase Scroll Compressor Start Up.............. 18
Phase Monitor ....................................................... 18
Service Hints ......................................................... 18
Sequence of Operation .................................. 18 & 19
Pressure Service Ports .......................................... 19
Defrost Cycle ......................................................... 19
Troubleshooting
Solid State Heat Pump Control
Troubleshooting Procedure ................................... 21
Checking Temperature Sensor Outside
Unit Circuit ............................................................. 22
Fan Blade Setting Dimensions .............................. 23
Removal of Fan Shroud ......................................... 23
Refrigerant Charge ................................................ 23
Pressure Tables ..................................................... 24
Optional Accessories ............................................. 25
Figures
Figure 1 Unit Dimensions ...................................... 5
Figure 2 Fresh Air Damper Assembly ................... 8
Figure 3 Mounting Instructions ............................ 10
Figure 4 Electric Heat Clearance ......................... 11
Figure 5 Wall Mounting Instructions.................... 12
Figure 6 Wall Mounting Instructions.................... 12
Figure 7 Common Wall Mounting Installations.... 13
Figure 8 Unit 24V Terminal Board ....................... 14
Figure 9 Compressor Cutoff and Outdoor
Thermostat Wiring ................................ 15
Figure 10 Compressor Cutoff and Outdoor
Thermostat Wiring ................................ 15
Figure 11 Electric Heat Hold-Off Wiring ................ 16
Figure 12 Electric Heat Hold-Off Wiring ................ 16
Figure 13 Defrost Control Board ........................... 20
Figure 14 Fan Blade Setting ................................. 23
Manual 2100-409C Page 2 of 25
Tables
Table 1 Electrical Specifications .......................... 6
Table 2 Thermostat Wire Size ........................... 14
Table 3 Wall Thermostat .................................... 17
Table 4 Troubleshooting .................................... 21
Table 5 Fan Blade Dimensions .......................... 23
Table 6 Refrigerant Charge ............................... 23
Table 7 Indoor Blower Performance .................. 23
Table 8 Recommended Operating Ranges ....... 23
Table 9 Pressure Table – Cooling ...................... 24
Table 10 Pressure Table – Heating...................... 24
Table 11 Optional Accessories ............................ 25
Getting Other Information and Publications
These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation .............. ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ...................... ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for ....................... ACCA Manual J or
Winter and Summer Air Conditioning Manual N
Low Pressure, Low Velocity Duct . ACCA Manual D or System Design for Winter and Manual Q Summer Air Conditioning
For more information, contact these publishers:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Avenue Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute
11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE
American Society of Heating Refrigerating, and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association
Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manual 2100-409C Page 3 of 25
WALL MOUNT GENERAL INFORMATION
HEAT PUMP WALL MOUNT MODEL NOMENCLATURE
SH 26 1 – A 08 X X X X X B
MODEL NUMBER
CAPACITY
26 – 2 Ton 31 – 2
½
To n
VENTILATION OPTIONS
X – Barometric Fresh Air Damper (Standard) B – Blank-off Plate M – Motorized Fresh Air Damper V – Commercial Room Ventilator - Motorized with Exhaust E – Economizer (Internal) - Fully Modulating with Exhaust R – Energy Recovery Ventilator - Motorized with Exhaust P – Commercial Room Ventilator - w/Exhaust Power Open & Close
NOTE: For 0KW and circuit breakers (230/208 V) or pull disconnects (460 V) applications, insert 0Z in the KW field of model number.
REVISIONS
VOLTS & PHASE
A – 230/208/60-1 B – 230/208/60-3 C – 460/60-3
KW
COLOR OPTIONS
X – Beige (Standard) 1 – White 2 – Mesa Tan 4 – Buckeye Gray 5 – Desert Brown 8 – Dark Bronze
OUTLET OPTIONS
X – Front (Standard)
FILTER OPTIONS
X – 1-Inch Throwaway (Standard) W – 1-Inch Washable P – 2-Inch Pleated
COIL OPTIONS
X – Standard 1 – Phenolic Coated Evaporator 2 – Phenolic Coated Condenser 3 – Phenolic Coated Evaporator
CONTROL MODULES
and Condenser
Manual 2100-409C Page 4 of 25
FIGURE 1
UNIT DIMENSIONS
Manual 2100-409C Page 5 of 25
TABLE 1
2
2
1
3
2
2
eriWdnuorG
eziS
rewoPdleiF
eziSeriW
rekaerB.tkC
lanretxE
roesuF
mumixaM
yticapmA
muminiM
tiucriC
AtkCBtkCAtkCBtkCAtkCBtkCAtkCBtkC
dnuorG
eziS
eriW
rewoP
dleiF
eziS
eriW
lanretxE
rekaerB
roesuF
mumixaM
TIUCRICELGNIS TIUCRICLAUD
1
tiucriC
ELECTRICAL SPECIFICATIONS
yticapmA
muminiM
tiucriC
3
rewoP
.stkC
.oN
dleiF
esahP&
detaR
stloV
Z0A-162HS1-802/03212253801A/NA/NA/NA/NA/NA/NA/NA/N
ledoM
Z0B-162HS3-802/032171520101A/NA/NA/NA/NA/NA/NA/NA/N
01514141A/NA/NA/NA/NA/NA/NA/NA/N
Z0C-162HS3-0641
Z0A-113HS1-802/032162040101A/NA/NA/NA/NA/NA/NA/NA/N
11514141A/NA/NA/NA/NA/NA/NA/NA/N
Z0C-113HS3-0641
Z0B-113HS3-802/032102520101A/NA/NA/NA/NA/NA/NA/NA/N
1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
2 Based on 75° C copper wire. All wiring must conform to the National Electrical Code and all local codes.
3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest
attention to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three conductors are in a raceway.
revision), article 310 for power conductor sizing.
CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors must be derated. Pay special
Manual 2100-409C Page 6 of 25
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
GENERAL
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment required to make up the entire heat pump system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 3 for information on codes and standards.
Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
DUCT WORK
Any heat pump is more critical of proper operating charge and an adequate duct system than a straight air conditioning unit. All duct work, supply and return, must be properly sized for the design airflow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
Refer to Table 7 for maximum static pressure available for duct design.
Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
A 1/4 inch clearance to combustible material for the first three feet (3') of duct attached to the outlet air frame is required. See Wall Mounting Instructions and Figures 3, 5 and 6 for further details.
Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.
CAUTION
Some installations may not require any return air duct. A metallic return air grille is required with installations not requiring a return air duct. The spacing between louvers on the grille shall not be larger than 5/8 inches.
Any grille that meets the 5/8 inch louver criteria, may be used. It is recommended that Bard Return Air Grille Kit RG-2 through RG-5 or RFG-2 through RFG-5 be installed when no return duct is used. Contact distributor or factory for ordering information. If using a return air filter grille, filters must be of sufficient size to allow a maximum velocity of 400 fpm.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to installation only in a single story structure.
FILTERS
A 1-inch throwaway filter is supplied with each unit. The filter slides into position making it easy to service. This filter can be serviced from the outside by removing the service door. A 1-inch washable filter and 2-inch pleated filter are also available as optional accessories. The internal filter brackets are adjustable to accommodate the 2-inch filter by bending down the tabs to allow spacing for the 2-inch filters.
Manual 2100-409C Page 7 of 25
FRESH AIR INTAKE
All units are built with fresh air inlet slots punched in the service panel.
The blank-off plate is available upon request from the factory and is installed in place of the fresh air damper shipped with each unit.
If the unit is equipped with the fresh air damper assembly, the assembly is shipped already attached to the unit. The damper blade is locked in the closed position. To allow the damper to operate, the maximum and minium blade position stops must be installed. See Figure 2.
All capacity, efficiency and cost of operation information as required for Department of Energy “Energyguide” Fact Sheets is based upon the fresh air blank-off plate in place and is recommended for maximum energy efficiency.
BLOWER DAMPER ASSEMBLY
CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.
FIGURE 2
Manual 2100-409C Page 8 of 25
Loading...
+ 17 hidden pages