Description of Standard Equipment
Optional CFM (Q36A2, Q42A2, Q48A2 & Q60A2 Only)
Important Installer Note
Phase Monitor
Three Phase Scroll Compressor Start Up
P - Commercial Ventilator - Motorized w/Exhaust Power Return
V - Commercial Ventilator - Motorized w/Exhaust Spring Return
R - Energy Recovery Ventilator w/Independent Intake & Exhaust Control
CAUTION: Whenmorethanoneeldpowerconductorcircuitisrunthroughoneconduit,theconductorsmustbederated. Pay special attention to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three
conductorsareinaraceway.
Single CircuitDual Circuit
j
Maximum
External
Fuse or
Ckt. Brkr.
30
30
60
20
25
35
15
15
20
35
35
60
25
25
35
45
15
15
20
25
45
45
60
90
30
30
35
60
15
15
20
30
50
50
60
90
35
35
35
60
15
15
20
30
50
50
60
90
40
40
40
60
20
20
20
30
60
60
90
45
45
60
20
20
30
Field
Power
Wire
Size
10
10
6
12
10
8
14
14
12
8
8
6
10
10
8
6
14
14
12
10
8
8
6
4
10
10
8
6
14
14
12
10
8
8
6
4
8
8
8
6
14
14
12
10
8
8
6
4
8
8
8
6
12
12
12
10
8
6
4
8
8
6
12
12
10
Minimum
Ground
Wire
10
10
10
12
10
10
14
14
12
10
10
10
10
10
10
10
14
14
12
10
10
10
8
8582560256101010
10
10
10
10
14
14
12
10
10
10
8
8582560256101010
10
10
10
10
14
14
12
10
10
10
10
8582560258101010
10
10
10
10
12
12
12
10
10
10
8592560258101010
10
10
10
12
12
10
Circuit
Ampacity
Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B
j Maximum
External Fuse
or Ckt. Breaker
Field Power
Wire Size
Ground
Wire Size
Manual 2100-600
Page 6 of 38
FIGURE 1
UNIT DIMENSIONS
Manual 2100-600
Page 7 of 38
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be
checked for external signs of shipping damage. The
skid must remain attached to the unit until the unit is
ready for installation. If damage is found, the receiving
party must contact the last carrier immediately,
preferably in writing, requesting inspection by the
carrier’s agent.
UNIT REMOVAL FROM SKID
WARNING
This unit is heavy and requires more than one
persontohandleandremovefromtheskid.
Check unit wheels to ensure that wheels are
lockedbeforeremovingfromskid.Extreme
caution must be taken to prevent injury to
personnelanddamagetotheunit.
It is recommended that the unit not be removed from
the skid with a forklift since the air seal under the unit
could be damaged. See Figure 2.
The shipping brackets on each side of the unit must be
removed and discarded. See Figure 3-A. The return air
grille panel can be removed to provide a place to hold
FIGURE 2
AIR SEAL UNDER QTec UNIT
Air Seal
the unit. The unit can be slid forward on the skid until
the front wheels hang over the edge of the skid. See
Figure 3-B. The unit can be tipped forward and slid
down the edge of the skid until the front wheels touch
the ground. See Figure 3-C. The wheels will not roll.
They are shipped from the factory locked so they will
not roll. The back of the skid will have to be held down
to keep it from tipping up. The skid can be slid out
from under the unit. The unit can then be set upright.
The unit will have to be turned sideways and removed
from the skid to t through a 36" doorway. If the door
height allows, the unit can be slid sideways through the
door.
If the unit can not be slid through the door, then the unit
will have to be put on a cart and tipped down to roll
through the door. It is recommended that an appliance
cart by used with a strap to hold the unit on the cart. The
wheels of the unit must be locked. If the wheels were
allowed to roll, the unit could roll off the cart. The unit should always be carted from the left side. This is the
side where the compressor is located. See Figure 4.
The blade of the appliance cart should be slid under
the wheels of the unit. The strap of the appliance cart
should be placed around the unit and strapped tightly.
Help will be required to tip the unit back onto the cart.
The unit can be leaned far enough back to be rolled
through the door. Be careful when setting the unit back
up to keep from damaging the unit.
GENERAL
The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians. A QWS-Series wall sleeve supplied as a
separate accessory must be ordered and installed with
Q-Tec unit.
The unit is designed for use with or without duct work.
For use without duct work, Plenum Box QPB42 is
recommended.
These instructions explain the recommended method
to install the air cooled self-contained unit and the
electrical wiring connections to the unit.
These instructions and any instructions packaged with
any separate equipment required to make up the entire
air conditioning system should be carefully read before
beginning the installation. Note particularly “Start
Procedure” and any tags and/or labels attached to the
equipment.
APPLIANCE
CART
COMPRESSOR
FIGURE 4
UNIT ON APPLIANCE CART
Q-Tec UNIT
(Right Side)
STRAP
While these instructions are intended as a general
recommended guide, they do not supersede any
national and/or local codes in any way. Authorities
having jurisdiction should be consulted before the
installation is made. See Page 3 for information on
codes and standards.
Size of unit for a proposed installation should be based
on heat loss calculation made according to methods
of Air Conditioning Contractors of America (ACCA).
The air duct should be installed in accordance
with the Standards of the National Fire Protection
Systems of Other Than Residence Type, NFPA No.
90A, and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B. Where local
regulations are at a variance with instructions, installer
should adhere to local codes.
MINIMUM INSTALLATION HEIGHT
The minimum installation height of the unit with a
Free Blow Plenum is 8 ft. 6 in. This provides enough
clearance for the plenum to be removed. See Figure 5.
The minimum installation height for ducted
applications is 8 ft. 4½ in. This provides enough
clearance to install the duct work. See Figure 6.
Manual 2100-600
Page 9 of 38
FIGURE 5
INSTALLATION WITH FREE BLOW PLENUM
FIGURE 6
DUCTED APPLICA TION
Manual 2100-600
Page 10 of 38
DUCT WORK
All duct work must be properly sized for the design
airow requirement of the equipment. Air Conditioning
Contractors of America (ACCA) is an excellent guide
to proper sizing. All duct work or portions thereof not
in the conditioned space should be properly insulated in
order to both conserve energy and prevent condensation
or moisture damage. When duct runs through unheated
spaces, it should be insulated with a minimum of one
inch of insulation. Use insulation with a vapor barrier
on the outside of the insulation. Flexible joints should
be used to connect the duct work to the equipment in
order to keep the noise transmission to a minimum.
The Q-Tec series unit has provision to attach a supply
air duct to the top of the unit. Duct connection size is
12 inches x 20 inches. The duct work is eld supplied
and must be attached in a manner to allow for ease of
removal when it becomes necessary to slide the unit out
from the wall for service. See Figure 7 for suggested
attachment method.
The Q-Tec series units are designed for use with free
return (non-ducted) and either free blow with the use of
QPB Plenum Box or a duct supply air system.
The QPB and QPBHW Plenum Box mounts on top
of the unit and has both vertically and horizontally
adjustable louvers on the front discharge grille.
For hot water coil option a QPBHWxx-F for free blow
or QPBHWxx-D for ducted airow is used.
When used with a ducted supply, a QCX Cabinet
Extension can be used to conceal the duct work above
the unit to the ceiling. This extends 20" above the
unit for a total height above the oor of 10'-7/8". The
unit is equipped with a variable speed indoor blower
motor which increases in speed with an increase in duct
static pressure. The unit will therefore deliver proper
rated airow up to the maximum ESP shown in Table
7. However, for quiet operation of the air system, the
duct static should be kept as low as practical, within the
guidelines of good duct design.
FILTERS
Two 1-inch throw away lters [(1) 16x16 and (1)
16x20] are supplied with each unit. The lters slide
into lter brackets. Refer to Figure 8.
The lters are serviced from the inside of the building
by opening the hinged door. This door is attached by a
screw and one locking latch.
The internal lter brackets are adjustable to
accommodate 2-inch lters. The tabs for the 1-inch
lters must be bent down to allow the 2-inch lters to
slide in place.
FIGURE 7
SUPPLY DUCT CONNECTIONS
SUPPLY DUCT
TO BE FIELD
SUPPLIED
ATTACHMENT
SCREWS TO
BE FIELD
SUPPLIED
ROOM SIDE OF
Q-T
ec UNIT
DUCT FLANGE
PROVIDED WITH
UNIT
NOTE: Unit cabinet, supply air duct and free blow
plenum are approved for “0” clearance to
combustible material.
FIGURE 8
FILTER LOCATION
FILTERS
RETURN AIR
GRILLE
Manual 2100-600
Page 11 of 38
FRESH AIR INTAKE
This unit is equipped with a fresh air damper assembly.
The damper blade is locked in the closed position
when the unit is shipped from the factory. To allow
the damper to operate remove the two plastic locking
pins, one on each end of the blade. This will allow for
maximum fresh airow. The damper blade will now
open when the indoor blower is operating. If less than
maximum fresh airow is required, reinsert the plastic
pins to limit damper blade opening to desired level.
Two extra pins are provided (taped to the inside of the
assembly) which may be used to hold the blade in some
position other than minimum or maximum position.
This fresh air assembly is located in the rear of the unit
and to gain access to make these adjustments remove
the air lter service door.
All capacity, efciency and cost of operation
information as required for Department of Energy
“Energyguide” Fact Sheets are based upon the fresh
air blank-off plate in place and is recommended for
maximum energy efciency.
The blank-off plate is available upon request from the
factory and is installed in place of the fresh air damper
shipped with each unit.
For details on energy recovery ventilation see separate
section.
SERVICE LIGHT
The unit is equipped with a service light, which signals
the user that service is required. The light is located
in the upper control panel and is visible only when the
hinged service/lter access door is open.
The Service Unit light indicates that the unit has
been shut off by a high or low pressure device. This
indicates that the unit needs to be serviced.
CONDENSATE DRAIN
There are two drain connections on the unit. The rear
drain is the primary drain, and is located on the right
lower rear panel of the unit. The optional side drain is
located on the bottom right side of the unit. The side
drain is shipped with a plug installed.
The side drain requires a water trap for proper
drainage. See Figure 9. The drain can be routed
through the oor or through the wall. If the drain is to
be routed through an unconditioned space, it must be
protected from freezing. The drain line must be able
to be removed from the unit if it is necessary to remove
the unit from the wall. When the side drain is used, the
plug must be removed and installed in the rear drain
outlet.
The rear drain can be used with wall thickness of up to
10 inches where a water trap can be installed between
the unit and the interior wall. See Figure 10. The trap
cannot extend beyond the edge of the unit or it will
interfere with the wall mounting bracket. The drain can
be routed through the oor or through the wall. If the
drain is routed through the wall, the drain line must be
positioned such that it will not interfere with the sleeve
ange or the grille. See Figure 11. If the drain is to
be routed through an unconditioned space, it must be
protected from freezing.
OPTIONAL REAR DRAIN KITS
Optional Rear Drain Kit, Bard Model QCDS48A,
is also available for these products. The optional
rear drain kit offers multiple benets that include the
following:
• Allows unit to be rolled away from the sleeve
without having to disconnect any hard plumbing
connections.
• Allows indoor coil condensate to be easily
connected to Rear Drain Box while bypassing the
outdoor coil drain pan. This aids in minimizing the
potential for biological growth to occur by
minimizing the standing water and exposing it to
warm temperatures.
See Figures 12A, 12B, 12C and 12D.
The drain box permanently mounts onto the wall sleeve
and is then either piped directly outdoors, or can be
piped vertically. The Q-Tec unit is then equipped with
ttings on the rear of the unit that slide into the drain
box as it is wheeled towards the wall sleeve.
NOTE: On models equipped with a refrigerant
subcooler in the lower drain pan may experience a
2-3% decrease in cooling performance and efciency
when the indoor condensate is routed around the
outdoor coil drain pan/subcooler assembly. Unit
rated performance and efciency are with the indoor
condensate routed to the outdoor coil pan.
There is also a heated version of the rear drain box
available (Model #QCDS48H) for installation in
northern climates where freezing may occur.
SEPARATE EVAPORATOR DRAIN
CONNECTION (OPTIONAL)
A knockout is provided in the back right corner of the
units for use when draining the evaporator drain pan
separately from the condenser. This knockout is 5
inches above the back condenser drain opening. To
utilize a separate evaporator drain connection remove the
knockout and route the existing evaporator drain hose
out this knockout and then to an appropriate drain line.
Manual 2100-600
Page 12 of 38
Loading...
+ 26 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.